2SHUDWLQJLQVWUXFWLRQV
1592002711 XH260L-V GB r1.0 12.01.04.doc
;+/ ;+9
3/4
ALH Temperature alarm recovery differential: (0,1÷25,5°C; 1÷45°F) Intervention differential for
recovery of temperature alarm.
ALd Temperature alarm delay: (0÷255 min) ti me inter val between the detecti on of an alarm condi tion
and the corresponding alarm signalling.
dAO Delay of temperature alarm at start-up: (0min÷23h 50min) time interval between the detection of
the temperature alarm condition after the instrument power on and the alarm signalling.
EdA Alarm delay at the end of defrost: (0
÷
255 min) Time interv al between the detection of the
temperature alarm condition at the end of defrost and the alarm signalling.
dot Delay of temperature alarm after closing the door : (0
÷
255 min) Time delay to signal the
temperature alarm condition after closing the door.
HUMIDITY ALARMS
AHC Humidity alarm configuration: rE = High and Low alarms related to humidity Set Point
Ab = High and low alarms related to the “absolute” humidity.
AHL Low humidity alarm setting: (with AHC = rE: 0 ÷ 50. With AHC = Ab: Lci ÷ AHu)
when this humidity is reached and after the AHd delay time, the HLA alarm is enabled,.
AHu High humidity alarm setting: (with AHC = rE: 0÷50°C. with AHC = Ab: AHL ÷ uci
when this humidity is reached and after the AHd delay time the HHA alarm is enabled.
AHH Humidity alarm recovery differ ential: (0.5÷20.0) Interventi on differenti al for recov ery of humi dity
alarm.
AHd Humidity alarm delay: (0÷ 255 mi n) time interval between the detection of an alar m conditi on and
the corresponding alarm signalling.
dHo Delay of humidity alarm at start-up: (0min÷23h 50min) time interval between the detection of the
humidity alarm condition after the instrument power on and the alarm signalling.
doH Alarm delay at the end of defrost: (0
÷
255 min) Time interv al between the detection of the
humidity alarm condition at the end of defrost and the alarm signalling.
doA Open door alarm delay:(0÷ 255 min) delay between the detection of the open door condition and
its alarm signalling: the flashing message “dA” is displayed.
nPS Pressure switch number: (0
÷
15) Number of activation of the pres sure switch, during the “did”
interval, before signalling the alarm event (I2F= PAL).
If the nPS activation in t he “ did ” t ime is r eached , swit ch o ff an d on the instr u ment t o r est ar t
normal regulation.
PROBE INPUTS
Ot Thermostat probe calibration: (-12.0÷12.0°C/ -21÷21°F) al lows to adjust possible offs et of the
thermostat probe.
OE Evaporator probe calibration: (-12.0
÷
12.0°C/ -21÷21°F) al lows to adjust possi ble offsets of the
evaporator probe.
O3 Humidity probe calibration: (-10÷10 RH) allows to adjust possible offsets of the humidity probe.
P2P Evaporator probe presence: n= not present: the defrost stops only by ti me; y= present: the
defrost stops by temperature and time.
P3P Humidity probe presence: n= not present; y= present.
LCI Readout with 4 mA : (-999 ÷ 999). Adjustment of read out corresponding to 4mA signal.
UCI Readout with 20 mA : (-999 ÷ 999). Adjustment of read out corresponding to 20mA signal.
DIGITAL INPUTS
i1P Digital input polarity: CL : the digital input is activated by closing the contact; OP : the digital input
is activated by opening the contact
i1F Digital input operating mode: configure the digital input function: EAL = generic alarm; bAL =
serious alarm mode; PAL = Pressure switch; Ht = heating relay safety; dor = door switch
odc Outputs status when open door: on = normal; Fan = Fan OFF; oFF = all the loads off
rrd Outputs r estar ting after doA alar m: no = outputs not affec ted by the doA al arm; yES = outputs
restart with the doA alarm;
did Time interval/delay for digital input alarm:(0
÷
255 min.) Time interv al to calc ulate the number of
the pressure switch acti v ati on when I1F= P A L. If I1F= E A L or bA L (ex ter nal alarms), “di d” par am eter
defines the time delay between the detection and the successive signalling of alarms.
OTHER
oA1 Light relay configuration (XH260L terminals 3-4, XH260V termin als. 11- 12): ALr = alar m; dEH
= dehumidifier; onF = on/off r elay: close wi th instrument on, open with instr ument off; Lig = light,
ESt, dEF not select
Adr RS485 serial address (0÷247) identifies the instrument within a control or supervising system.
Ptb Parameter table: (read only) it shows the original code of the
parameter map.
rEL Software release: (read only) Software version of the microprocessor.
Prd Probes display: (read only) display the temperature values of the evaporator probe Pb2.
Pr2 Access to the protected parameter list (read only).
8. DIGITAL INPUT
One digital input is present configurable by user by means of the i1F parameter according to the following
descriptions.
8.1 DOOR SWITCH (I1F = dor)
It signals the door status and the corresponding rel ay output status through the “odc” parameter: no =
normal (any change); Fan = Fan OFF; oFF = all the loads are switched off.
Since the door is opened, after the delay tim e set through par ameter “dOA”, the alar m output is enabl ed
and the display shows the message “dA”.
The status of loads depends on the “rrd” parameter:
with rrd=no outputs are not affected by the doA alarm;
with rrd=yES = outputs restart with the doA alarm;
The alarm stops as soon as the external digi tal i nput is di sabl ed again. Duri ng thi s tim e and then for the
delay “dot” and “doH” after closing the door, the temperature and humidity alarms are disabled.
8.2 GENERIC ALARM (I1F = EAL)
As soon as the digital input is ac tivated the unit w ill wait for “did” time delay before signalling the “EAL”
alarm message. The outputs s tatus don’t change. The alarm stops just after the digi tal input is deactivated.
8.3 SERIOUS ALARM MODE (I1F = BAL)
When the digital input is ac tivated, the unit will wait for “did” delay before signalling the “bAL” alarm
message. The relay outputs ar e switched OFF. The al arm will stop as soon as the digital input is deactivated.
8.4 PRESSURE SWITCH (I1F = PAL )
If during the interval time set by “did” param eter, the pressure switch has reached the number of
activation of the “nPS” parameter, the “PAL” pressure alarm message will be displayed. The compresso r
and the regulation are stopped. When the digital input is ON the compressor is always OFF.
If the nPS activation in t he d id t ime is reached, switch off and on t he in st r umen t to r est ar t n or mal
regulation.
8.5 HEATING RELAY SAFETY (i1F=Ht)
With i1F=Ht as soon as the digital input is activated for “did” time heating relay is disabled.
The alarm will stop as soon as the digital input is de-activated.
8.6 DIGITAL INPUTS POLARITY
The digital input polarity depends on the “i1P” parameters.
CL : the digital input is activated by closing the contact.
OP : the digital input is activated by opening the contact
9. INSTALLATION AND MOUNTING
Instruments XW240L shall be mounted on vertical panel, in a 150x31 m m hole, and fixed using two
screws
∅
3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L).
Instrument XH260V s hal l be m ounted on v er t i c al panel , i n a 72x 56 m m hole, and fixed using sc r ews
∅
3
x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-V).
The temperature range allowed for correct operation is 0 - 60 °C. Avoid places subject to strong
vibrations, corros ive gas es, exc essi ve di rt or hum idi ty. T he same r ecomm endations apply to probes. Let
the air circulate by the cooling holes.
9.1 XH260V: CUT OUT
10. ELECTRICAL CONNECTIONS
The instruments are provi ded with s crew ter mi nal bl ock to c onnect cables wi th a cr oss sec tion up to 2,5
mm
2
for the digital and analogue inputs . Relays and power suppl y have a Faston connec tion (6,3mm ).
Heat-resistant cables hav e to be used. Before connec ting cabl es make s ure the power supply com plies
with the instrument’s r equirements. Separate the pr obe cables from the power s upply cables , from the
outputs and the power connections. Do not exceed the m axim um c urrent al lowed on each relay , i n c ase
of heavier loads use a suitable external relay.
N.B. Maximum current allowed for all the loads is 20A.
10.1 PROBE CONNECTIONS
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It
is recommended to place the thermostat probe away from ai r stream s to corr ectly m easure the aver age
room temperature.
11. HOW TO USE THE HOT KEY
11.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1. Program one controller with the front keypad.
2. When the controller is ON, ins ert the “Hot key” and push
9
9
key; the "uPL" message appears
followed a by flashing “End”
3. Push “SET” key and the End will stop flashing.
4. Turn OFF the instrument remove the “Hot Key”, then turn it ON again.
NOTE: the “Err” message is displayed for failed programming. In this case push again
9
9
key if you want
to restart the upload again or remove the “Hot key” to abort the operation.
11.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD)
1. Turn OFF the instrument.
2. Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON.
3. Automatically the param eter li st of the “Hot Key” is downloaded into the Control ler mem ory, the
“doL” message is blinking followed a by flashing “End”.
4. After 10 seconds the instrument will restart working wit h the new pa r ameters.
5. Remove the “Hot Key”..
NOTE the message “Err” is displ ayed for fai led pr ogramm ing. In thi s c ase turn the uni t off and then on if
you want to restart the download again or remove the “Hot key” to abort the operation.