dixell xc440c Instruction Manual

Electronic Controller for
Compressor Racks
XC440C
Instructions Manual
g
Operating instructions cod. 1592001300

INDEX

1. GENERAL WARNING 4
LEASE READ BEFORE USING THIS MANUAL
P
AFETY PRECAUTIONS
S
2. GENERAL DESCRIPTION 4
4 4
3. FIRST INSTALLATION 5
3.1 H
3.2 H
3.3 H
OW TO SET THE KIND OF GAS OW TO SET THE RANGE OF THE PRESSURE PROBES OW TO SET THE KIND OF DISPLAY: RELATIVE OR ABSOLUTE PRESSURE
4. USER INTERFACE 7
4.1 D
4.2 K
4.3 THE ICONS 8
ISPLAYING EYBOARD
5. HOW TO SEE AND MODIFY THE SET POINT 8
5.1 H
5.2 H
OW TO SEE THE SET POINT OF COMPRESSORS OR FANS OW TO MODIFY THE SET POINT OF COMPRESSORS OR FANS
6. PARAMETERS PROGRAMMING 9
6.1 H
6.2 H
6.3 H
OW TO ENTER THE “PR OW TO ENTER IN PARAMETERS LIST “PR OW TO CHANGE PARAMETER VALUES
PARAMETER LIST
1”
2” 9
7. HOW TO DISABLED AN OUTPUT 10
7.1 H
7.2 O
7.3 R
OW TO DISABLED AN OUTPUT DURING A MAINTENANCE SESSION UTPUT DISABLED SIGNALLING EGULATION WITH SOME OUTPUTS DISABLED
.10
.10
.10
8. RUNNING HOURS OF LOADS 10
8.1 H
8.2 H
OW TO DISPLAY THE RUNNING HOURS OF A LOAD OW TO RESET THE RUNNING HOURS OF A LOAD
.10
.11
5 5 6
7 7
8 8
9 9
9. ALARM MENU 11
9.1 H
OW TO SEE THE ALARMS
10. USE OF THE PROGRAMMING “HOT KEY “ 12
10.1 H
10.2 H
OW TO PROGRAM A HOT KEY FROM THE INSTRUMENT OW TO PROGRAM AN INSTRUMENT USING A HOT KEY
(UPLOAD) 12
(DOWNLOAD) 12
11. KEYBOARD LOCKING 12
11.1 H
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
OW TO LOCK THE KEYBOARD
e
11
12
2 / 28
g
Operating instructions cod. 1592001300
11.2 T
O UNLOCK THE KEYBOARD
12
12. LIST OF PARAMETERS 13
12.1 P
12.2 P
12.3 O
12.4 D
12.5 C
12.6 F
12.7 A
12.8 A
12.9 O
LANT DIMENSIONING AND TYPE OF REGULATION ROBES CONFIGURATION
THERS INPUTS CONFIGURATION ISPLAY AND MEASUREMENT UNIT
OMPRESSORS REGULATION ANS REGULATION LARMS – COMPRESSOR SECTION LARMS – FANS SECTION
THER
.13
14 14 15 15 16 16 16 17
13. TYPE OF REGULATION 18
13.1 D
13.2 P
EAD BAND ROPORTIONAL BAND – FOR COMPRESSORS OR FANS
NLY FOR COMPRESSORS
– O
18 19
14. MOUNTING & INSTALLATION 20
15. ELECTRICAL CONNECTIONS 21
15.1 P
ROBES CONNECTION
21
16. RS485 SERIAL LINK 21
17. TECHNICAL FEATURES 22
18. ALARM LIST 22
18.1 T
18.2 A
18.3 A
YPES OF ALARMS AND SIGNALLING MANAGED LARM MUTING LARM CONDITIONS – SUMMARY TABLE
22 24 24
19. WIRING CONNECTIONS 25
20. DEFAULT VALUE 26
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
e
3 / 28
g
Operating instructions cod. 1592001300

1. General warning

1.1 Please read before using this manual
This manual is part of t he product and should be kept near the i nstrument for easy and
quick reference.
The inst rument shall not be used for purposes dif ferent from thos e described hereunder. It
cannot be used as a safety devic e.
Check the application li mits before proceeding.
1.2
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits
avoiding sudden temperature changes with high atm ospheric hum idity to prevent formati on of condensation
Warning: disconnect all electrical c onnections before any kind of mai nt enance.
The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to
“DIXELL s.r.l.” (see address) with a det ai l ed description of the fault.
Consider the maximum current which can be applied to each relay (see Techni c al Data).
Ensure that the wires for probes, loads and the power supply are s eparated and f ar enough
from each other, without c ros sing or intertwining.
Fit the probe where it is not acces sible by the end user.
In case of applications in industrial environments, t he use of m ains f ilters (our mod. FT1) in
parallel with inductive loads coul d be useful.
Safety Precautions

2. General description

The XC440C is designed to manage compressors or fans in a c ondensing system such as a pack. The compressors can be s i mple, multist age or with di fferent capacities. Control is by means of a neutral zone or proportional band and is based on the pres sure or temperature sensed in the LP suction (compressors) or HP (condenser) circuits. A special algorithm balances the run hours of the compressors to distribute the work load uniformly. The controllers can convert pres sure and display it as temperat ure. The front panel offers com plete information on the system’ s status by displaying the suction and condenser pressure (temperatures), the status of the loads, possible alarms or maintenance conditions. Each load has its own alarm input that is able to stop it when act i vat ed. By means of the HOT KEY the controller can be eas y programmed at power on. The controller can be connected to the XJ500, controlling and monitoring system , thank s to the serial TTL output, using the standard ModBus RTU protocol.
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
4 / 28
e
g
Operating instructions cod. 1592001300

3. First installation

At first inst al l at i on, it’s necessary the fol l owing:
1. Select the kind of gas.
2. Set the range of the pressure probes.
In the following paragraph a short cut f or t he above operations. Chapters operations.
6 Parameters programming
12 List of parameters
and
will explain in detail these

3.1 How t o set t he kind of gas

The controller has mem ori sed the relation between temperature and press ure for some gases.
The pre-set gases is: r404.
If another gas is used, act as in the following:
R507
Set
; 134=
1. Enter the Programmi ng mode by pressing the
2. Select the “
3. Select the
4. Press the “
5. Use “UP” or “ following:
6. Press “
To exit
: Press
NOTE
: the set value is st ored even when the procedure is exited by waiting the tim e-out to
expire.
Pr2
” parameter. Then enter the pass word 3 –2 1.
FtyP, kind of gas,
SET
” key: the value of the parameter will start blinking.
DOWN
r22=
SET
” to store the new value and move to the f ol l owing parameter.
SET + UP
” to change the gas amount t he following: . S elect t he gas am ong the
; r404=
R22
or wait 30s without pressing a key.
parameter.
R404A
; 507=
and
134
DOWN
; r717=
key for 3s.
ammonia.

3.2 How t o set t he range of the pressure probes

According to the part number a controller is pre-set to work with the f ol l owing pressure probes:
XC440C – xxxxA XC440C – xxxxB:
XC440C – xxxxE
, or
PP30: 0÷30 bar (0÷435PSI) - relative pressure
: PP11: -0.5÷11 bar (-7÷160 PSI) - relative pressure;
If the probes you’re using have a different range act as in the following: To set the pressure range of the
PA04: Adjustment of read out corresponding to 4mA PA20
Adjustment of read out corresponding to 20mA
:
Practically these parameters has to be set with the s t art and end scale of the probe range.
WARNING:
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
set a value correspondent to
E.I. PP11 PP30
relative pressure transducer, range -0.5÷11.0 bar. PA04=0.50; PA20=12.00.
relative pressure transducer, range: 0÷30bar. PA04=1.00; PA20=31.00.
Probe
use the parameters:
absolute pressure
.
5 / 28
e
g
How to do:
1. Enter the Programmi ng mode by pressing the
2. Select the “
3. Select the
4. Press the “
5. Set the lower value of the probe range (lower value +1 if the probe detects relative pressure).
6. Push the
corresponding to 20mA
7. Set the higher value of the range (higher value +1 if the probe detects relative press ure).
8. Push the
Pr2
” parameter. Then enter the pass word 3 –2 1.
PA04, adjustment of read out corresponding to 4mA,
SET
” key: the value of the parameter will start blinking.
SET
key to confirm the value. The
SET
key to confirm the value. Next parameter will be displayed.
Operating instructions cod. 1592001300
Set
parameter will be displayed.
DOWN
and
PA20: adjustment of read out
key for 3s.
parameter.
Do the same things for the Probe 2,
FA04, FA20
parameters
.

3.3 How t o set t he kind of display: relative or absolute pressure

After setting the probe range by m eans of the PA04, PA20 param eters, it ’s pos sible to select if the absolute or relative pressure has to be displayed.
The controller is pre-set for RELATIVE PRESSURE displaying.
absolute pressure
If the
9. Enter the Programmi ng mode by pressing the
10. Select the “
1. Select by pushing the
2. Push the
3. Set the
To exit
: Press
Pr2
SET
AbS
SET + UP
has to be displayed, act as i n the following:
Set
” parameter. Then enter the pass word 3 –2 - 1.
UP
to modify the value.
value and push the
key the
or wait 30s without pressing a key.
rELP
parameter.
SET
key to confirm it.
and
DOWN
key for 3s.
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
6 / 28
e
g

4. User interface

4.1 Displaying

Operating instructions cod. 1592001300
UPPER DISPLAY LOWER DISP LAY ICONS
Temperature Pressure
-
Working loads
-
Measurement unit
-
Alarm or status Icons

4.2 Keyboard

SET
To see or modify the set point. in program ming m ode it sel ects a param eter or confirm an operation.
Alarm menu:
9
(UP) To enter the Alarm menu.
9
In programming mode: it browses the parameter codes or increases the displayed value. With Hot key inserted: it starts t he Hot key programming procedure.
8
(DOWN) In programming mode: it browses the parameter codes or decreases the
8
displayed value. Manual restart of loads: By holding i t pressed for 3s, it switches on agai n l oads previous locked by a safety digi tal input alarm.
/
CLOCK To display the loads running hours.
By holding it pressed for 3s t he Maintaining menu is entered.
KEY COMBINATIONS
+
9
8
9
SET + SET +
To lock and unlock the keyboard.
8
8
To enter the programming mode.
8 9
To exit the programming mode.
9
By holding it pressed for
3s,
the current alarm is eras ed.
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
7 / 28
e
g
Operating instructions cod. 1592001300

4.3 THE ICONS

LED FUNCTION MEANING
ON Celsius degrees ON Fahrenheit degrees ON bar displaying
bar
ON PSI displaying
PSI
ON Load 1 on Flashing Load 1 is waiting to start (1HZ). or digital input alarm for Load 1 (2Hz).
ON Load 2 on Flashing Load 2 is waiting to start (1HZ). or digital input alarm for Load 2 (2Hz).
ON Load 3 on Flashing Load 3 is waiting to start (1HZ). or digital input alarm for Load 3 (2Hz).
ON Load 4 on Flashing Load 4 is waiting to start (1HZ). or digital input alarm for Load 4 (2Hz).
ON The Maintenance menu has been entered Flashing One or more loads have been placed in maintenance stat us ON Alarm is happening ON All the stored alarms have been seen
Flashing A new alarm has happened.
o Load 1 in maintenance status (2Hz).
o Load 2 in maintenance status (2Hz).
o Load 3 in maintenance status (2Hz).
o Load 4 in maintenance status (2Hz).

5. How to see and modify the set point

5.1 How t o see t he set point of compressors or fans

If the controller can m anage compressors or fans, the set point are displayed in sequence, otherwise only the set point of the enabled sect ion will be displayed.
1) Push and rel ease the
2) The Lower display will show the
SET
key;
“SEtC”
label for compress or/
“SEtF”
for fans, will the Upper display will show its value.
To exit:
push the
SET key
or wait for 30 without pressing any keys .

5.2 How t o modi f y the set point of compressors or fans

WARNING: before setting the target set points for the first time, check and, if necessary, modify the type of freon (par. FtyP) and the default unit of measurement (par. dEU) for compressors and fans
PROCEDURE
1. Set the kind of freon by means of the FtyP parameter (see 3.1
)
gas
2. Set the measurem ent uni t (dEU par.).
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
How to set the kind of
label
8 / 28
e
g
3. Check and if necessary modify the set point limits (LSE and HSE par.).
Operating instructions cod. 1592001300
1. Push the
2. The Lower display will show the for fans, will the Upper display will show its value flashing.
3. To change the Set value push the
4. To memorise the new value and pass to the normal display push the SET key.
To exit: push the SET key or wait for 30 without pressing any keys.
SET
key for more than 2 sec onds;
“SEtC”
9
or
9
label for compress or/
8
within 30s.
8
“SEtF”
label

6. Parameters programming

6.1 How to ent er t he “Pr1” paramet er l i st

To enter the “Pr1” parameter lis t , user accessible, operate as follows:
1. Hold pressed the SET and DOWN key for 3s.
2. The controller displays the name of the parameter in the Lower display, its
value on the Upper display.
3. Press the “SET” key: the value of the parameter will start blinking.
4. Use “UP” or “DOWN” to change the value.
5. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 30s without pressing a key.
NOTE: the set value is st ored even when the procedure is exited by waiting the tim e-out to
expire.

6.2 How to ent er i n paramet ers l i st “Pr2”

The “Pr2” parameter list is protected by a security code (Password).
SECURITY CODE is 321
To access parameters i n “ Pr2”:
1. E nter the “Pr1” level.
2. S el ec t “Pr2” parameter and press the “SET” key.
3. The flashing value “0 --” is displayed.
4. Use
5. Repeat operat i ons 2 and 3 for the other digits.
NOTE: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing “SET” +
9
or
8
to input the security code and confirm the figure by pressi ng “SET” key.
9
8
8
. When a paramet er i s present also in “Pr1” decim al poi nt of the lower display is on.
8

6.3 How t o change paramet er values

1. Enter the Programming mode.
2. Select the required parameter with
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
9
9
or
8
8
.
e
9 / 28
g
y
Operating instructions cod. 1592001300
3. Press the “
4. Use
5. Press “
To exit
NOTE
out.
SET
” key the value start blinking.
9
8
9
8
or
to change its value.
SET
” to store the new value and move to the f ol l owing parameter.
SET + UP
: Press
: the new programming is st ored even when the procedure is exited by waiting the t ime-
or wait 15s without pressing a key.

7. How to disabled an output

To disabled an output during a maintenance session means to exclude t he output from the regulation.

7.1 How t o di sabled an output during a maintenance session.

1. Push the
2. The LED’s of the first output is switched on, the Lower displa shows the “
if the first output i s enabled, or the
section. With compres sor with more steps all the LED’s linked to the c ompressor and the valves are switched on..
3. Select the output by pressing the UP or
To modify the status of the output
4. flashing, then push the UP or DOWN to pass from “On” to “
5. Push the
To exit:
SET
push the
key to confirm the status and pass to the next output. .
CLOCK
key or wait 30 sec
CLOCK
key for 3s.
StA
” label, while the Upper display shows the “On” label
“oFF”
label if the output is dis abled f or a m aint enance
DOWN
key.
: push the
SET
key, the status of the output starts
OFF
” and viceversa.

7.2 Output disabled signalling.

If an output is disabled i ts led blinks (2 Hz)

7.3 Regulation with some outputs disabled.

If some outputs are disabled they don’t take part to the regulat ion, so the regulation goes on with the other outputs.

8. Running hours of loads

8.1 How t o di splay the running hours of a load.

The controller memori s es the running hours of each load.
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
To see how long a load has been working follow this procedure:
1. Press and release the “CLOCK” k e y.
2. The led of the first output is switched on, the
“HUr”
the running hours of the first out put .
label, while the
Lower Display
Upper Display
shows the shows the
shows
10 / 28
e
g
Operating instructions cod. 1592001300
3. To see the running hours of the following load pres s the UP key .
To exit:
push the
CLOCK
key or wait 30 sec

8.2 How t o reset t he running hours of a load.

1. Display the running hour according to t he above procedure.
2. Select the load by press i ng the UP key.
3. Push the
4. Hold pushed the key for some seconds till the
display shows zero.
To exit:
NOTE:
the selected loads..
SET
push the
SET
if the
key (immediat el y on the lower display the
CLOCK
key is released within 2s, the controller reverts to display the running hours of
key or wait 30 sec
rSt
“rSt”
label is displayed).
label starts flashi ng and the Lower

9. Alarm Menu

The controller memori s es the last 20 alarms happened, together with their duration.. To see the alarm codes see par.

9.1 How t o see t he al arms

1. Push the
2. The last alarm happened is s howed on the Upper display, while
3. Push again the
4. To see the alarm
5. By pushing again the
duration
par. 18 Alarm list
9
.
9
key the lower display shows its number. from the most recent.
and push the
or SET
9
9
9
9
key and the other alarm are displayed starting
SET
key.
key the next alarm is dis pl a yed.
Alarms erasing.
Enter the Alarm Menu.
1.
To erase the displayed alarm pus h the “
2.
Lower Display,
the running alarms cannot be eras ed..
NOTE
To erase the whole Alarm Menu, hold pressed t he “
3.
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
” key till the “rSt” label will be displayed in the
SET
” key for 10s.
SET
11 / 28
e
g
y
g
y
Operating instructions cod. 1592001300

10. Use of the programming “HOT KEY “

10.1 How t o program a hot key from the instrument (UPLOAD)

1. Program one controller with the f ront keypad.
2. When the controller is ON, insert the “ appears followed a by flashing
3. Push “
4. Turn OFF the instrument rem ove t he
SET”
key and the
“End”
End
will stop flashing.
Hot key
“Hot Key”,
9
” and push
then turn it ON again.
9
key; the
"uPL"
message
NOTE
you want to restart the upload again or remove the “
: the “
Err
” message is displ ayed for f ailed program m ing. In t his cas e push again
Hot key
” to abort the operation.
9
9
key if
10.2 How t o program an i nst rument using a hot key
(DOWNLOAD)
1. Turn OFF the instrument.
2. Ins ert a ON.
3. Automatically the parameter list of the memory, the “
4. After 10 seconds the instrument will restart working with the new parameters.
5. Remove the
NOTE
then on if you want to restart the download again or remove the “ operation. The unit can UPLOAD or DOWNLOAD the parameter list f rom its own E2 internal mem ory to
“Hot Key”
the
programmed “Hot Key” into the 5 PIN receptacle
doL
“Hot Key”.
the message “
and vice-versa.
” message is blink i ng f ol l owed a by flashing
.
Err
” is displayed for failed program ming. I n this cas e turn the unit off and
“Hot Key”
and then turn the Controller
is downloaded into the Controller
“End”.
Hot key
” to abort the

11. Keyboard locking

11.1 How t o l ock t he keyboard

9
1. Keep the and
2. The “POF” messa
this point it is onl menu.
8
8
keys.
9
and
8
8
s pressed together for more than 3 s the
ke
e will be displayed and the keyboard is locked. At
possible to view the set point or enter t he HACCP
9
9

11.2 To unlock the keyboard

9
8
9
Keep the appears.
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
and
8
keys pressed together for more t han 3s till the “
POn”
flashing message
12 / 28
e
g
Operating instructions cod. 1592001300

12. List of parameters

12.1 Plant dimensioni ng and t ype of regulati on.

oA1, oA2, oA3, oA4 Outputs 1- 4 configuration
be dimensioned according to the number and type of compressors or fans and the number of steps for eac h one.
Each relay according to the c onfiguration of the oA(i) parameter can work as:
Compressor
-
Step:
-
Fan:
-
-
-
oAi = FAn
Alarm: Not used: NOTE:
According to the oA1÷oA4 configurat i on, 2 kinds of plant can be defined:
Rack with compressors only: Rack with fans only:
: oAi = cPr,
oAi = StP
oAi = ALr
oAi = nu
also the “Lin” value is present. This val ue
all the oAi different from FAn
all the oAi different f rom CPr of StP
: by means of these param eters t he plant c an
must not
be used..
WARNING: It’s not allowed to configure a plant with both compressors and fans
COMPRESSORS CONFIGURATION
step compressors
With step.
ES. C
ompressor with 3 steps:
the output of compressor has to be set before the output of the
oA1 = cPr, oA2= StP, oA2 = StP.
If an oAi set as step without any previous oAi set as cPr the configuration alarm “CStP” will be activated.
If compressor with different capacities are used configured as
cPr
(compressor) otherwise the
(CtyP=dPo)
, all the oAi must to be
configuration alarm “CStP” will be
activated.
RACK WITH FANS ONLY
If the controller is used for fans, all the oAi must be set as FAn or “nu” not used
CtyP:Compressor type
not.
dPo = compressor with different capacities StP
homogeneous
=
Scr = don’t set it
StP: valve outputs polarity:
of the relays associated with the c apacity valves (only for homogeneous and stepped­capacity compressors):
oP
=valve enabled with open contact;
PC1 ..PC4 Power of compressor 1...4
only if CtyP=dPo. The power is identified by a value (range 1÷255) proportional to the capacity of single compressor.
: it selects if the compress ors have the s ame power (homogeneous ) or
: in this case the regulation is neutral zone.
: the regulation can be neutral zone or proporti onal band.
polarity of the outputs for capacity valves. It determ ines the st ate
cL
= valve enabled with closed contact.
: for setting the power of single compress ors. Avail able
.
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
13 / 28
e
g
E.I.
3 compressors with foll owing capaci ty: 10, 20, 40 HP. The param et ers have t o be s et
in these way: PC1=10, PC2=20, PC3=40.
FtyP:Freon Type
r22
= R22;
rty:Type of regulation (see par. 13 Type of regulation)
db
= neutral zone,
Sty Compressor rotation
YES
ensure even run times.
no
= fixed sequence: the compres sors are enabled and disabl ed in fixed sequence: first ,
second etc.
rot Fans rotation
YES
ensure even run times.
no
= fixed sequence: the compres sors are enabled and disabl ed in fixed sequence: first ,
second etc.
: set the kind of freon used in the plant
r404
= R404A ;
= rotation: this algorit hm distributes the working time between the various loads to
= rotation: this algorit hm distributes the working time between the various loads to
Operating instructions cod. 1592001300
507
= R507;
Pb
= proportional band.
134
=134;
r717
=r717 (ammonia)

12.2 Probes configuration

12.2.1 Probe configuration
Pbc: Probe 1 setting. Cur = PA04: Adjustment of read out for the Probe 1
input signal, given by the suc tion probe (0 ÷31 bar or 0÷450 PSI or 0÷3100KPA)
Warning:
relative pressure increase the range of 1 bar. See also par.
E.I. PP11
PA20=12.0 (11+1).
PP30
PA20
Adjustment of read out for the Probe 1
:
the suction probe (0 ÷ 31.0 bar or 0÷450 PSI or 0÷3100KPA))
PA04
CAL: Probe 1 calibration
set a value correspondent to absol ute pressure. If the transducer m easures
3.2 How to set the range of the pressure probes
relative pressure transducer, range -0.5÷12.0 bar. PA04=0.5 (-0.5+1);
relative pressure transducer, range: 0÷30bar. PA04=1; PA20=31.
.
4 ÷ 20 mA probe;
(-12.0÷12.0 bar; -12.0÷12.0°C or -20÷20 PSI/°F)
ntc =
NTC probe,
(used only if Pbc=Cur). c orrespondi ng to
corresponding to
Ptc =
20mA
SEE THE WARNING FOR
NTC probe.
4mA
input signal, given by

12.3 Others inputs configuration

i1c Configurable digital input polarity
oP:
the digital input is activated by opening the contact;
CL:
the digital input is activated by closing the contac t.
i1F Configurable digital input polarity functions
ES = E
did Configurable digital input delay: ( ALIP: Alarm input for compressors and fans polarity
oP: CL:
ALMr Manual reset of alarms for compressors and fans.
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
nergy saving;
the digital input is activated by opening the contact; the digital input is activated by closing the contac t.
oFF
= instrument shut down;
(terminals 3-4)
enabled only if i1F=LL) 0÷255min
:
(terminals 3 - 4)
LLi =
liquid level alarm
14 / 28
e
g
no
= automatic recover of alarm: regulation res tart when the corres pondent digit al input is
disabled
yES =
manual recover for the alarm s of compressors and fans See also par
Operating instructions cod. 1592001300
.

12.4 Display and Measurement unit

dEU:Default measurement unit for displaying (bar
NOTE1: T
following parameters:
LAF, HAF. NOTE2:
parameters
HAF
in the measurement unit set in dEU parameter. In any case after modifying this parameter it’s better check and modify if necessary the set point and the above parameters.
rES Resolution for °C and bar (in = rELP Pressure displaying: AbS
rEL
= relative pressure.
NOTE:
LSE HSE, LSF and HSF are automatically decreased by 1.0 bar or 14 PS I
dEU
he
parameter sets the m easurement unit also for the
.
The controller automatically converts values of set point and following
CAL, FCAL, Pbd, ESC, LSE, HSE, Pb, ESF, LSF, HSF, LAL, HA, LAF,
In this case the press ure displayed, the set point and the following paramet ers
CAL, FCAL, Pbd, ESC, LSE, HSE, Pb, ESF, LSF, HSF, LAL, HA,
integer;
= absolute pressure;
dE =
decimal point)
=bar; °C=°C,
PSI
=PSI; °F=°F)
set point
and the

12.5 Compressors regulation

Pbd:Proportional band or neutral zone width
The band (or zone) is symmetrical compared to the target set point, with extremes: set+Pbd/2 ... set-Pbd/2. The measurement unit depends on the dEU par.
ESC Energy saving value for compressors:
compressor set point.
onon: Minimum time between 2 following switching ON of the same compressor
(0÷255 min).
oFon: Minimum time between the switching off of a compressor and the following
switching on
don: Time delay between the insertion of two different compressors doF: Time delay between switching off of two different compressors
10s)
donF: Minimum time a stage stays switched ON FdLy: “don” delay enabled also for the first call.
delayed for a “don” value, respect to the call. (no = “don” not enabled; enabled)
FdLF“doF” delay enabled also for the first switching off
between the request of a release and the act ual s witching off. (no = “doF” not enabled;
odo: Regulation delay on start-up:
after the time delay imposed in this parameter.
. (0÷255min).
Note: usually onon is greater than oFon.
yES
=”doF” enabled)
(0÷255s) on switching ON the instrument s tarts working
(0.10÷5.00bar/0.5÷30°C or 1÷80PSI/1÷50°F)
(-20÷20bar; -50÷50°C) this value is add to the
(0÷99.5min; res. 10s).
(0÷99.5 min; res.
(0÷99.5 min; res. 10s)
If enabled, the triggering of the step is
. It enables the “doF” delay
yES
=”don”
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
15 / 28
e
g
Operating instructions cod. 1592001300
LSE: Minimum set point
minimum value that can be used for the set point, to prevent the end user from setting incorrect values.
HSE: Maximum set point
maximum accept abl e val ue for set point.
: The measurement unit depends on dEU parameter. It sets the
: The measurement unit depends on dEU parameter. It sets the

12.6 Fans regulation

Pb Proportional band zone width
Set the dEU par. and the target set point for fans before setting this parameter.
band is symmetrical compared to the target set point, with extremes: set+Pb/2 ... set­Pb/2. The measurem ent unit depends on the dEU par.
ESF Energy saving value for fans:
point.
Fon: Time delay between the insertion of two different fans FoF: Time delay between switching off of two different compressors LSF: Minimum set point for fans
the minimum value that can be used for the set point, to prevent the end user from setting incorrect values.
HSF: Maximum set point for fans
the maximum acc eptable value for set point.
(00.10÷5.00bar/0.5÷30°C or 1÷80PSI/1÷50°F).
(-20÷20bar; -50÷50°C) this value is add to the fans set
(0÷255sec).
(0÷255 sec)
: The measurement unit depends on dEU param eter. It s ets
: The measurement unit depends on dEU param eter. I t sets

12.7 Alarms – compressor section

PAo: Alarm probe exclusion at power on.
before an alarm probe is signall ed. (0÷255 min). During this time if the pressure is out of range all the compressor are s witched on.
LAL: Low pressure (temperature) alarm – compressor section
depends on dEU parameter. It’ s al ways subtrac ted t o the s et point . When the value
LAL
is reached the A03C alarm is enabled, (possibly after the
HAL:High pressure (temperature) alarm– compressor section
depends on dEU parameter. It’s always added to the set point. When the value SET+HAL is reached the A04C al arm is enabled, (possibly after the
tAo:Low and High pressure (temperature) alarms delay– compressor section
min) time interval bet ween the detection of a pres sure (temperat ure) alarm condi tion and alarm signalling.
Ser: Service request:
maintenance call is generated.
SPr: number of steps engaged with faulty probe PoPr capacity engaged with faulty probe
(1÷9990 hours, res. 10h) number of running hours aft er that the “A14”
it is the period starti ng from ins trument s witch on,
: The measurement unit
tAo
delay time).
: The measurement unit
tAo
delay time).
. (0÷#compr).
(0÷100%) It’s used only if CtyP =dPo.
The
SET-
: (0÷255

12.8 Alarms – fans section

LAF: Low pressure alarm – fans section
parameter. It’s al ways referred to fan s et point When the value SETF-LAF is reached the LA2 alarm is enabled, (possibly after the
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
: The measurement unit depends on the dEU
AFd
delay time).
16 / 28
e
g
Operating instructions cod. 1592001300
HAF:High pressure alarm – fans section
parameter. It’s al ways referred to the set point. W hen the value SETF+HA F is reached the HA2 alarm is enabled, (possibly after the
AFd:Low and High pressure alarms delay – fans section
between the detection of a pressure alarm condition in the fans section and alarm signalling.
FPr: Number of fans engaged with faulty probe
: The measurement unit depends on the dEU
AFd
delay time).
: (0÷255 min) time interval
. (0÷#fans).

12.9 Other

tbA Alarm relay silencing:
yES=
oFF Switching ON/OFF enabling from keyboard: (no
Ad1: Compressors address Ad2: Fans address rEL Software release Ptb Parameter table code Pr2 Access to security code protected menu
alarm relay is switc hed off by pushing any keys.
the switching ON/OFF of the ins trument by pressing the SET key for more than 4s.
(1 –247) It is used in monitoring system.
by pushing one of the keypad buttons. no= alarm relay stays on;
= disabled;
(1 –247) It is used in monitoring system.
for internal use.
: readable only.
yES
= enabled) It permits
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
17 / 28
e
g
Compressor inserction area
neutral zone
y
g
Compressor disconnection area
Operating instructions cod. 1592001300

13. Type of regulation

13.1 Dead band – Only for compressors

This kind of regulation is available onl y for c om press ors. The neut ral zone (Pbd) is s ym m etric al compared to the target set point, with extremes: set+Pbd/2 ... set-Pbd/2. If the pressure (temperature) is inside this zone the controller maintains the same number of l oads switched on and off, without changing anything. When the pressure (temperature) go out from the zone, regul ation starts. If the pres sure is greater than SET+Pbd/2, the l oads are switching on with tim ing given by param eters: don and doF. A load is turned on only if the his safety times Regulation stops when the pressure (temperature) come back int o the neutral zone.
In the following a simpli fy exemplum that explains the regulation i n neut ral zone f or c om pres sor homogeneous with 1 step for each c ompressors. The safety ti mes onon, oFon and donF are not considered. In the real regulation the a load is entered or turned off only if t hese times are over.
Ex. Dead band control, compressors with same capacities, 1 step for each com p ressor. In this example:
oA1 = cPr; oA2 = cPr; oA3 = cPr; oA4 =nu; CtyP = SPo rty = db Sty = yES FdLy = no dLF = no
Set + (Pbd/2)
Se t - (Pbd/2 )
Compressor
Dela
functionin
homogeneous compressors;
dead band regulation
rotation “don” delay not enabled at first calling after an equilibrium condition.
“doF” delay not enabled at first calling after an equilibrium condition.
Pressure
Set
Status
2Q
&
2Q
&
2Q
&
GRQ
GR)
don
onon, oFon, donF
don
are over.
number of compress ors
doF
doF
7LPH
7LPH
7LPH
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
18 / 28
e
g
ALL LOADS ON
ALL LOADS OFF
Operating instructions cod. 1592001300

13.2 Proportional Band – for compressors or fans

The regulation band (Pbd) is divided into as many parts as there are stages according to the following formula:
# step = oAi = CPr or StP (number of compressors or steps).
The numbers of stages s witched ON is proportional to the value of the input signal: when thi s distances itself from the target set point and enters the various bands, the com pressors are switched ON, to be then turned OFF when the signal bri ngs near the set point.
In this way if the pressure is greater than regulation band, all the compress ors are on, if the pressure (temperature) is l ower than t he regul ation band all the compressors are off. Naturally also for this regulat ions all the delays (don and doF) saf ety times (onon, oFon and donF) are valid.
Regulation according to the running hours
The algorithm switch on and off the loads according to the runni ng hours of each load. In this way the running hours are balanced.
Example
oA1 = cPr; oA2 = cPr; oA3 = cPr; oA4 = cPr: 4 CtyP = SPo rty = Pb Sty = yES FdLy = no dLF= no
homogeneous compressors.
proportional band regulation rotation “don” delay at first call not enabl ed. “doF” delay at first call not enabl ed.
compressors
Set+Pbd/2 Set+Pbd/4
Set-Pbd/4 Set-Pbd/2
This draw highlights the doF tim e: the loads are in fact turned off only when the doF time is over.
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
6(7
GRQ
GR)
=,&
&
&
&
&
19 / 28
e
g
Operating instructions cod. 1592001300

14. Mounting & installation

The instruments are suitabl e only for internal us e. Instrum ents shal l be mounted on panel, in a 29x71 mm hole, and fixed using the special brackets supplied. To obtain an IP65 protection grade use the front panel rubber gask et (mod. RG-C) as shown in figure. The ambient operating temperature range is between 0÷60°C. Avoid locations subject to heavy vibration, corrosive gas es or excessive dirt . The same appli es to the probes. Ensure ventil at i on around the instrument.
Figure 1
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
20 / 28
e
g
Operating instructions cod. 1592001300

15. Electrical connections

The controller is provided with screw term inal blocks for wires having section not bigger than
2
2.5 mm
:
Check power supply data before connection wires.
Keep the probe and the digital input wires separate from the power cable.
Do not exceed the maximum rating current for each relay, check technical data and if the load is bigger, use filtered c ontactors. Before connecting cables make sure the power supply complies with the instrument’s requirements. Separate the input connection c ables from the power supply cables, from the outputs and the power connect ions.
relay
, in case of heavier loads use a suitable external relay.
Do not exceed the maximum current allowed on each

15.1 Probes connection

Pressure probe (4 - 20 mA)
bear parts which could cause short circuiting or introduce noise disturbance at high frequencies. To minimise the induced disturbances use shielded cables with the shield connected to earth.
Temperature probe:
streams to correc tly measure the temperature.
: respect the polarity. If using terminal ends be sure there are no
it is recomm ended to place the temperature probe away from direct air

16. RS485 serial link

All models can be int egrated into the m onitoring and al arm s ystem XJ500 using t he TTL seri al port. They use the standard ModBus RTU prot ocol, s o they c an be fitt ed in a sys tem integrat or using this protocol.
The controller has 2 serial addresses first one Ad1 for compressor section, second one Ad2 for fan section. To completely monitor both sections the values of the 2 addresses have to be different. If the Ad2 parameters have the same value the status of the fans is not monitored.
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
21 / 28
e
g
Operating instructions cod. 1592001300

17. Technical features

Housing: Case: Mounting : Protection: Frontal protection: Connections: Power supply: Power absorption: Display: Inputs: Digital inputs Relay outputs: Serial output : Communication protocol: Data storing: Kind of action: Operating temperature: Relative humidity: Measuring range: NTC probe: Resolution:
Self extinguishing ABS.
Front panel 32x74 mm, depth 60m m (“C” format);
“C” format panel mounti ng i n a 29x71 m m panel cut-out
IP65.
IP65 with frontal gasket mod RG-C model.
screw terminal block,
12Vac/dc
3 digits red led and 4 digit orange led.
1 NTC probe, or 1 PTC probe or 1 4÷20mA transducer.
: 5 free voltage
5 relay SPST 8(3)A, 250Vac
TTL standard
on the non-volatile memory (EEPROM).
1B;
0,1 °C or 1°C;
±
10%, 24Vac/dc ± 10%, 50-60Hz.
5VA max.
ModBus – RTU
Pollution grade:
0÷60 °C.;
÷
20
85% (no condensing)
Accuracy (ambient temp. 25°C)
normal;
Storage temperature:
-40÷110°C.
Software class:

18. Alarm list

Usually alarm conditions are signalled by means of:
1. Activation of alarm output relay
2. Buzzer activation
3. Message on proper display
4. Log of alarm: code and duration.
A.
-25÷60 °C.
: ±0,7 °C ±1 digit
The table at paragraph 18.3

18.1 Types of alarms and signalling managed

18.1.1 A12: Configuration alarm
The following configuration paramet ers are checked after each modi fication.:
OA1 ÷ OA4
CtyP
When these param eters are set in wrong way an alarm message is generated: the label A12 is shown on the upper display, while the lower displ ay signal s what wrong sett ing has created the error: The following table contains the displayed messages:
Mess. Errata Corrige
nLod
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
Outputs 1- 4 configuration Compressor type
Number of loads higher than loads available in the
Check number of oAi set as load, this
number has to be lower of equal to the
e
22 / 28
g
cStP
FAP2
CSP2
controller number of relay of the control l er. Load (step) configuration error
P2 probe not available for fan regulation
P2 probe not available for screw compressor
Operating instructions cod. 1592001300
A relay oA(i) has been set as compressor
without a previous relay oA(i-1) has been set as compressor. E I oA1 = StP
Some relays have been set as compressors
(oAi = CPr) some others have been set as fans (oAi = FAn). Set all t he oA i as compressors or fans.
Check CtyP and set i t different from Scr.
18.1.2 EA1÷EA4: Compressors or fans safeties alarm.
Terminals WARNING: THESE TERMINALS REQUIRE A FREE OF VOLTAGE CONNECTION.
The terminals (6-11, 7-11, 8-11, 9-11) really used depends on the number of loads. The protections regarding the compressors and fans are connected to thes e inputs. If one of these protections is enabling (E.I. for lack of oil or overheating, etc,) the corresponding load is turn off.
Parameters ALIP:
It establishes if the input is activated by c losing (ALIP = cL) or by opening (ALI P = oP)
the terminals.
Actions
Every time one input is ac tivated the corresponding output is turned off.
Recovery
Recovery depends on
ALMr
With disabled. With key for 3s.
= no The instrument restart the standard operating mode when the input is
ALMr
yES
=
ALMr
parameter:
manual recover for the alarm s of compressors and fans. Push the
DOWN
18.1.3 P1: probe failure alarm
It is generated by failure in t he probe P 1.
Parameters
According to the confi gurat i on of the controller one of the following parameters is used:
SPr: number of steps engaged with faulty probe PoPr: capacity engaged with faulty probe FPr
Number of fans engaged with faulty probe
:
Recovery
Automatic as soon as probe restarts working.
. (0÷# oAi = cPr or StP).
(0÷255) It’s used only if CtyP=dPo .
. (0÷# oAi = FAn)
18.1.4 HA, LA, HA2, LA2High and low pressure (temperature) alarms
This alarm signals that the pressure (tem perature) is out of limits est ablished by parameters LAL and HAL for compress ors and LAF –HAF for fans.
tAo
The
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
and
AFd
parameters set the delay between alarm c ondition and alarm signalling.
e
23 / 28
g
Code
Automatically
Action
The alarm is signalled with s tandard action. The outputs are unchanged.
Operating instructions cod. 1592001300

18.2 Alarm muting

Press any buttons to si l ence the buzzer during an alarm condition. Hold pressed for more than 3 seconds switch off the alarm rel ay duri ng an al arm condition

18.3 Alarm conditions – summary table

P1 P1 probe failure
EA1 EA2 EA3 EA4
LA Minimum
LA2 Minimum
HA Maximum
HA2 Maximum
A5 Liquid level
A14 Load
Description Cause Action Reset
alarm
Load safeties alarm
pressure (temperature) alarm for compressors
pressure (temperature) alarm for fans
pressure (temperature) alarm for compressors
pressure (temperature) alarm for fans
alarm
maintenance alarm
Probe failure or out of range
Safeties compressor/f an input activation. NOTE: with step compressors 1 input for each compressor has to be used. Suction pressur e or temperature lower than SET_C-LAL value
Condensing pressure or temperature lower than SET_F-LAL value Suction pressur e or temperature higher than SET_C+HAL value
Condensing pressure or temperature higher than SET_F+HAL value Input enabled signalling only
A load has worked for the hour set in the SEr parameter
The compressors are activated according to the SPr or PoPr parameters. the corresponding load is turned off. (with step compressors all relays referred to the input are disabled). signalling only
signalling only
signalling only
signalling only
signalling only
Automatically
working.
Recovery depends on With standard operating mode when the input is disabled. With alarms of compressors and fans. Push the
DOWN Automatically:
temperature reaches the (Set_C-LAL+ differential) value. (differential = 0.3bar or 1°C)
Automatically:
temperature reaches the (Set_F-LAL+ differential) value. (differential = 0.3bar or 1°C)
Automatically:
temperature reaches the (Set_C + HAL ­differential) value. (differential = 0.3bar or 1°C)
Automatically:
temperature reaches the (Set_F + HAL ­differential) value. (differential = 0.3bar or 1°C)
Manually:
compressor (see par. 8 Running hours of loads)
as soon as the probe restarts
= no The instrument restart the
ALMr
=
ALMr
key for 3s.
reset the running hour of the
ALMr
manual recover for the
yES
as soon as the pressure or
as soon as the pressure or
as soon as the pressure or
as soon as the pressure or
as soon as the input i s disabled
parameter:
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
24 / 28
e
g
LOAD4
LOAD3
LOAD2
LOAD1
ALARM
Input
4÷ 20 mA
Operating instructions cod. 1592001300

19. Wiring connections




Probe: PP11 / PP30: Brown (5), White (4) PTC/NTC: 3-4




8(3)A250V8(3)A8(3)A8(3)A8(3)A


Hot Key

1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
25 / 28
e
g
Level

20. Default value

Operating instructions cod. 1592001300
Name
°C °F bar PSI
SEtC SEtF OA1
OA2
OA3
OA4
CtyP StP PC1 PC2 PC3 PC4 FtyP rty Sty rot PbC PA04
PA20
CAL
i1C i1F
did ALIP
ALMr
dEU
rES rELP Pdb
ESC
OnOn
OFOn
0
-18,0 35,0
CPr CPr CPr CPr Pr2 Outputs 1 configuration CPr(0) - FAn(1) - StP(2) - ALr(3) - LIn(4) ­CPr CPr CPr CPr Pr2 Outputs 2 configuration CPr(0) - FAn(1) - StP(2) - ALr(3) - LIn(4) ­CPr CPr CPr CPr Pr2 Outputs 3 configuration CPr(0) - FAn(1) - StP(2) - ALr(3) - LIn(4) ­CPr CPr CPr CPr Pr2 Outputs 4 configuration CPr(0) - FAn(1) - StP(2) - ALr(3) - LIn(4) -
SPo SPo SPo SPo Pr2 Compressor type SPo(0) - dPo(1) - Scr (2)
CL CL CL CL Pr2 Valve outputs polarity OP(0) - CL(1)
25 25 25 25 Pr2 Power of compressor 1 0 ÷ 255 25 25 25 25 Pr2 Power of compressor 2 0 ÷ 255 25 25 25 25 Pr2 Power of compressor 3 0 ÷ 255 25 25 25 25 Pr2 Power of compressor 4 0 ÷ 255
404 404 404 404 Pr2 Freon Type r22(0) - 404(1) - 507(2) - 134(3) - 717( 4)
db db db db Pr2 Type of regulation db(0) - Pb(1) yES yES yES yES Pr2 Compressor rotation no(0) - yES(1) yES yES yES yES Pr2 Fans rotation no(0) - yES(1)
Cur Cur Cur Cur Pr2 Probe 1 setting Cur(0) - Ptc(1) - nt c( 2)
0,5 7 0,5 7 Pr2 Adjustment of read out for the Probe
12,0 174 12,0 174 Pr2 Adjustment of read out for the Probe
0 0 0 0 Pr2 Probe calibration (dEU=bar o °C) -12.0 ÷ 12.0 (dEU=PSI
cL cL cL cL Pr2 Configurable digital input polarity OP(0) - CL(1)
ES ES ES ES Pr2 Configurable digital input polarity
0 0 0 0 Pr2 Configurable digital input del ay 0 ÷ 255 (min.)
CL CL CL CL Pr2 Alarm input for compressors and fans
no no no no Pr2 Manual reset of alarms for
°C °F bar PSI Pr2 Default measurement unit for dE in dE in Pr2 Resolution for °C and bar in(0) - dE(1)
rEL rEL rEL rEL Pr2 Pressure displaying rEL(0) - AbS(1)
4 8 0.5 7 Pr2 Proportional band or neutral zone 0 0 0 0 Pr2 Energy saving value for compressors (BAR) -20.0÷20.0 (°C) -50.0÷50.0 5 5 5 5 Pr2 Minimum time between 2 following 2 2 2 2 Pr2 Minimum time between the switching
2,3 33 -- Set point for compressors LSE÷HSE
95
15,1 220 -- Set point for fans LSF÷HSF
Description Range
nu(5) nu(5) nu(5) nu(5)
at 4mA at 20mA
functions
polarity compressors and fans displaying
width
switching ON of the same compressor off of a compressor and the following
switching on
(0.0 ÷ PA20)BAR (0 ÷ PA20)PSI
(PA04 ÷ 51.0)BAR (PA04 ÷ 750)PSI
o °F) -20 ÷ 20
ES(0) - OFF(1) - LL(2)
OP(0) - CL(1)
no(0) - yES(1)
Bar(0) - °C(1) - PSI(2) - °F(3)
(BAR) 0.1÷10.0 (°C) 0.1÷30.0
(PSI) 1÷80 (°F) 1÷50
(PSI) -300÷300 (°F) -90÷90
0 ÷ 255 (min.) 0 ÷ 255 (min.)
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
26 / 28
e
g
Level
Operating instructions cod. 1592001300
Name
°C °F bar PSI
don
0,3 0,3 0,3 0,3 Pr2 Time delay between the insertion of
doF
0,1 0,1 0,1 0,1 Pr2 Time delay between switching off of
donF
0,3 0,3 0,3 0,3 Pr2 Minimum time a stage stays switched
FdLy
no no no no Pr2 “don” delay enabled also for the first
FdLF
no no no no Pr2 doF” delay enabled also for the first
odo
20 20 20 20 Pr2 Regulation delay on start-up 0 ÷ 255 (sec.)
LSE
-40 -40 0,3 5 Pr2 Minimum set point) BAR: (PA04÷HSE)abs; ((PA04-
HSE
10 50 7,2 100 Pr2 Maximum set point BAR :(LSE÷PA20)abs o (LSE÷(PA20-
Pb
ESF
Fon
FoF
LSF
HSF
PAO LAL
HAL
tAo
SEr SPr
PoPr LAF
HAF
AFd
4 8 2.0 24 Pr2 Proportional band zone width (BAR) 0.1÷10.0 (°C) 0.1÷30.0 0 0 0 0 Pr2 Energy saving value for fans (BAR) -20.0÷20.0 (°C) -50.0÷50.0
15 15 15 15 Pr2 Time delay between the insertion of
5 5 5 5 Pr2 Time delay between switching off of
10 50 7,2 100 Pr2 Lower set for fans BAR :(FA04 ÷ HSF)abs ((FA04 - 1.013) ÷
60 140 27,8 404 Pr2 Higher set for fans BAR : (LSF ÷ F20)abs (LSF ÷ (F20-
30 30 30 30 Pr2 Alarm probe exclusion at power on 0 ÷ 255 (min.) 15,0 30 1,5 21 Pr1 Low pressure (temperature) alarm –
20.0 40 2,5 46 Pr1 High pressure (temperature) alarm–
15 15 15 15 Pr1 Low and High pressure (temperature)
999 999 999 999 Pr2 Service request 1 ÷ 999 (0= ESCLUSO) (10 ore)
2 2 2 2 Pr2 number of steps engaged with faulty
50 50 50 50 Pr2 capacity engaged with faulty probe 0 ÷ 100 (%)
20 40 6,7 96 Pr1 Low pressure alarm – fans section (0.1 ÷ 30.0)BAR (0.1 ÷ 100.0)°C (1 ÷
20 40 9,8 141 Pr1 High pressure alarm – fans section (0.1 ÷ 30.0)BAR (0.1 ÷ 100.0)°C (1 ÷
15 15 15 15 Pr2 Low and High pressure alarms delay
Description Range
two different compressors two different compressors ON call switching off
(PA04÷HSE)abs o ((PA04-14)÷HSE)rel; °F:
two different fans two different fans
1.013))rel; °C:LSF ÷ 150.0; PSI: (LSF ÷ FA20)abs o (LSF÷ (FA20 - 14))rel; ° F: LSF ÷ 302
compressor section compressor section alarms delay– compressor section
probe
– fans section
0 ÷ 99.5 (min.10sec) 0 ÷ 99.5 (min.10sec) 0 ÷ 99.5 (min.10sec)
no(0) - yES(1) no(0) - yES(1)
1.013)÷HSE)rel; °C: -50.0÷HSE; PSI:
-58.0÷HSE
1.013))rel; °C:LSE ÷ 150.0; PSI:(LSE ÷
PA20)abs o (LSE÷(PA20-14))rel; °F: LSE
÷ 302
(PSI) 1÷80 (°F) 1÷50.0
(PSI) -300÷300 (°F) -90÷90
0 ÷ 255 (sec) 0 ÷ 255 (sec)
HSF)rel; °C:-50.0 ÷ HSF; PSI: (FA04 ÷
HSF)abs o ((FA04-14) ÷ HSF)rel; °F: -58.0
÷ HSF
(0.1 ÷ 30.0)BAR (0.1 ÷ 100.0)°C (1 ÷
430)PSI (1 ÷ 200.0)°F
(0.1 ÷ 30.0)BAR (0.1 ÷ 100.0)°C (1 ÷
430)PSI (1 ÷ 200.0)°F 0 ÷ 255 (min.)
0 ÷ (nCPR)
430)PSI (1 ÷ 200.0)°F
430)PSI (1 ÷ 200.0)°F
0 ÷ 255 (min)
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
27 / 28
e
g
Level
Operating instructions cod. 1592001300
Name
°C °F bar PSI
FPr
tbA oFF
Ad1 Ad2 rEL Ptb Pr2
2 2 2 2 Pr2 Number of fans engaged with faulty
yES yES yES yES Pr2 Alarm relay silencing no(0) - yES(1)
no no no no Pr2 Switching ON/OFF enabling from
1 1 1 1 Pr2 Compressors address 1 ÷ 247 1 1 1 1 Pr2 Fans address 1 ÷ 247
Description Range
probe
keyboard
Pr1 Software release read only Pr1 Parameter table code read only Pr1 Protected parameter menu read only
Fans parameters Compressor parameters Common parameters
0 ÷ (nFAN)
no(0) - yES(1)
Dixell s.r.l.
Z.I. Via dell’Industria, 27 - 32010 Pieve d’Alpago (BL) ITALY tel. +39 - 0437 - 98 33 - f ax +39 - 0437 - 98 93 13 http://www.dixell.com E-mail: dixell@dixell.com
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0