WING
XW10L – XW10V
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
• This manual is part of the product and should be kept near the instrument for easy and quick
reference.
• The instrument shall not be used for purposes different from those described hereunder. It cannot
be used as a safety device.
• Check the application limits before proceeding.
4. KEYBOARD
1.2
• Check the supply voltage is correct before connecting the instrument.
• Do not expose to water or moisture: use the controller only within the operating limits avoiding
• Warning: disconnect all electrical connections before any kind of maintenance.
• Fit the probe where it is not accessible by the End User. The instrument must not be opened.
• In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.”
• Consider the maximum current which can be applied to each relay (see Technical Data).
• Ensure that the wires for probes, loads and the power supply are separated and far enough from
• In case of applications in industrial environments, the use of mains filters (our mod. FT1) in
SAFETY PRECAUTIONS
sudden temperature changes with high atmospheric humidity to prevent formation of
condensation
(see address) with a detailed description of the fault.
each other, without crossing or intertwining.
parallel with inductive loads could be useful.
2. GENERAL DESCRIPTION
Model XW10L, 38x185 mm format, and model XW10V, 100x64 format, are microprocessor based
controllers suitable for applications in the field of refrigeration or heating. They are provided with 2 relay
outputs one for the regulation and other one for the lights. They are also provided with 1 NTC or PTC
probe input for temperature control. There is 1 digital input (free contact) configurable by parameter.
An output allows the user to programme the parameter list with the “Hot Key”.
3. CONTROLLING LOADS
3.1 THE REGULATION OUTPUT
The regulation is performed according to the temperature measured by the probe.
The instruments are provided with the CH programmable parameter which enables the user to set the
regulation both for heating or cooling applications:
· CH = CL: cooling applications
· CH = Ht: heating applications
3.2 CH = CL: COOLING APPLICATIONS.
The Hy value is automatically set above the Set Point. If the temperature increases and reaches set
point plus differential the compressor is started and then turned off when the temperature reaches the
set point value again.
In case of fault in the thermostat probe the start and stop of the compressor are timed through
parameters “COn” and “COF”.
3.3 CH = HT: HEATING APPLICATION.
The Hy value is automatically set under the Set Point. If the temperature decreases and reaches set
point minus differential the regulation output is activated and then turned off when the temperature
reaches the set point value again.
3.4 FAST COOLING
It can be activated the keypad by holding the o key pressed for about 3 seconds. The compressor
operates in continuous mode for the time set through the “CCt” parameter. The cycle can be terminated
before the end of the set time using the same activation key, o for about 3 seconds.
KEY COMBINATIONS
4.1 USE OF LEDS
Each LED function is described in the following table.
4.2 HOW TO SEE THE MIN TEMPERATURE
To display and modify target set point; in programming mode it selects a parameter or
confirm an operation.
By holding it pressed for 3s when max or min temperature is displayed it will be erased.
To see the max. stored temperature; in programming mode it browses the parameter
codes or increases the displayed value. By holding it pressed for 3s the fast freezing cycle
is started.
To see the min stored temperature; in programming mode it browses the parameter codes
or decreases the displayed value.
Not used
Switch ON and OFF the light of the cold-room
Switch ON and OFF the instrument.
+
+
+
LED MODE Function
ON The compressor is running
FLASHING
FLASHING
ON The Fast cooling cycle is enabled
ON - ALARM signal
ON The light is on
To lock and unlock the keyboard.
To enter the programming mode.
To exit the programming mode.
- Programming Phase (flashing with LED
- Anti-short cycle delay enabled
Programming Phase (flashing with LED
- In “Pr2” indicates that the parameter is also present in “Pr1”
1. Press and release the n key.
2. The “Lo” message will be displayed followed by the minimum temperature recorded.
3. By pressing the n key or waiting for 5s the normal display will be restored.
4.3 HOW TO SEE THE MAX TEMPERATURE
1. Press and release the o key.
2. The “Hi” message will be displayed followed by the maximum temperature recorded.
3. By pressing the o key or waiting for 5s the normal display will be restored.
4.4 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
To reset the stored temperature, when max or min temperature is displayed :
1. Press SET key unt il “rST” label starts blinking.
N.B. After the installation RESET the temperature stored .
)
)
1592009211 XW10L-V GB r1.0 30.05.2011 XW10L – XW10V 1/4

4.5 HOW TO SEE AND MODIFY THE SET POINT
1. Push and immediately release the SET key: the display will show the Set point value;
2. The SET LED start blinking;
3. To change the Set value push the o or n arrows within 10s.
4. To memorise the new set point value push the SET key again or wait 10s.
4.6 TO ENTER IN PARAMETERS LIST “PR1”
To enter the parameter list “Pr1” (user accessible parameters) operate as follows:
1. Enter the Programming mode by pressing the Set and DOWN key for few
seconds (
2. The instrument will show the first parameter present in “Pr1”
and
start blinking).
4.7 TO ENTER IN PARAMETERS LIST “PR2”
To access parameters in “Pr2”:
1. Enter the “Pr1” level.
2. Select “Pr2” parameter and press the “SET” key.
3. The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero.
4. Use o or n to input the security code in the flashing digit; confirm the figure by pressing “SET”.
The security code is “321“.
5. If the security code is correct the access to “Pr2” is enabled by pressing “SET” on the last digit.
Another possibility is the following: after switching ON the instrument the user can push Set and DOWN
keys within 30 seconds.
NOTE: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing “SET” + n.
When a parameter is present in “Pr1” LED
is on.
ALC= Ab, ALL
when this temperature is reached and after the ALd delay time the HA alarm is enabled.
ALL Low temperature alarm setting:
ALC = rE , 0
ALC = Ab , - 50°C or -58°F
when this temperature is reached and after the ALd delay time, the LA alarm is enabled,.
AFH Temperature alarm differential: (0,1÷25,5°C; 1÷45°F) Int ervention differential for temperature
alarm set point, always positive.
ALd Temperature alarm delay: (0÷255 min) time interval between t he detection of an alarm condition
and the corresponding alarm signalling.
dAO Delay of temperature alarm at start-up: (0min÷23h 50min) time interval between the detection
of the temperature alarm condition after the instrument power on and the alarm signalling.
dot Delay of temperature alarm after closing the door : (0
temperature alarm condition after closing the door.
doA Open door alarm delay:(0÷255 min) delay between the detection of the open door condition and
its alarm signalling: the flashing message “dA” is displayed.
nPS Pressure switch number: (0
interval, before signalling the alarm event (I2F= PAL).
If the nPS activations in the did time are reached, switch off and on the instrument to
restart normal regulation.
PROBE INPUTS
Ot Thermostat probe calibration: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible offset of the
thermostat probe.
HES Temperature increase during the En ergy Saving cycle : (-30,0°C
the increasing value of the set point during the Energy Saving cycle.
DIGITAL INPUTS
odc Compressor status when open door:
no, Fan = normal; CPr, F_C = Compressor OFF.
I2P Configurable digital input polarity:
÷ 110°C or 230°F
÷ 50 °C or 90°F
÷ ALU
÷255 min) Time delay to signal the
÷15) Number of activation of the pressure switch, during the “did”
÷ 30,0°C / -22÷86°F) sets
CL : the digital input is activated by closing the contact;
4.8 HOW TO CHANGE THE PARAMETER VALUE
1. Enter the Programming mode.
2. Select the required parameter with o or n.
3. Press the “SET” key to display its value (
and LED st arts blinking).
4. Use o or n to change its value.
5. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15s without pressing a key.
NOTE: the new programming is stored even when the procedure is exited by waiting the time-out.
4.9 HOW TO LOCK THE KEYBOARD
1. Keep the o and n keys pressed together for more than 3 s the o and n keys.
2. The “POF” message will be displayed and the keyboard is locked. At this point it is
only possible the viewing of the set point or the MAX o Min temperature stored and
to switch ON and OFF the light, the auxiliary output and the instrument.
TO UNLOCK THE KEYBOARD
Keep the o and n keys pressed together for more than 3s.
4.10 ON/OFF FUNCTION
By pushing the ON/OFF key, the instrument shows “OFF” for 5 sec. and the ON/OFF
LED is switched ON.
During the OFF status, all the relays are switched OFF and the regulations are stopped;
N.B. During the OFF status the Light button is active.
5. PARAMETER LIST
REGULATION
Hy Differential: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point.
Cooling: Compressor Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the
temperature reaches the set point.
Heating: Compressor Cut I N is Set Point minus Differential (Hy). Compressor Cut OUT is when
the temperature reaches the set point.
LS Minimum set point limit: (-50,0°C
the set point.
US Maximum set point limit: (SET
point.
OdS Outputs activati on delay at start up: (0÷255 min) This funct ion is enabled at the initial start up
of the instrument and inhibits any output activation for the period of time set in the parameter.
(Light can work)
AC Anti-short cycle delay: (0÷30 min) interval between the compressor stop and the following
restart.
CCt Thermostat override: (0min ÷23h 50min) allows to set the length of the continuous cycle. Can
be used, for instance, when the room is filled with new products.
Con Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is active
in case of faulty thermostat probe. With COn=0 compressor is always OFF.
COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is off
in case of faulty thermostat probe. With COF=0 compressor is always active.
CH Type of action: CL = cooling; Ht = heating.
DISPLAY
CF Temperature measurement unit: °C = Celsius; °F = F ahrenheit. When the measurement unit is
changed the SET point and the values of some parameters have to be modified.
rES Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display.
dE = 0,1°C; in = 1 °C
ALARMS
ALC Temperature alarm configuration
rE = High and Low alarms related to Set Point
Ab = High and low alarms related to the absolute temperature.
÷SET; -58°F÷SET) Sets the minimum acceptable value for
÷110°C; SET÷230°F) Set the maximum acceptable value for set
OP : the digital input is activated by opening the contact
I2F Digital input operating mode: configure the digital input function:
EAL = generic alarm;
bAL = serious alarm mode;
PAL = Pressure switch;
dFr = Not used;
AUS = Not used;
Es = Energy Saving;
onF = remote On/OFF.
dor = door switch
did Time interval/delay for digital input alarm:(0
÷255 min.) Time interval to calculate the number of
the pressure switch activation when I2F=PAL. If I2F=EAL or bAL (external alarms), “did”
parameter defines the time delay between the detection and the successive signalling of the
alarm.
OTHER
PbC Type of probe: it allows to set the kind of probe used by the instrument:
PbC = PBC probe, ntC = NTC probe.
rEL Release software: (read only) Software version of the microprocessor.
Ptb Parameter table: (read only) it shows t he original code of the dIXEL parameter map.
Prd Probes display: (read only) display the temperature.
Pr2 Access to the protected parameter list (read only).
6. DIGITAL INPUTS
The XW10L has 1 free contact digital input. It is programmable in six different configurations by the
“I2F” parameter.
6.1 DOOR SWITCH INPUT (I2F = dor)
It signals the door status and the corresponding relay output status through the “odc” parameter:
no, Fan = normal (any change);
CPr, F_C = Compressor OFF;
Since the door is opened, after the delay time set through parameter “dOA”, the alarm output is
enabled and the display shows the message “dA”. The alarm stops as soon as the external digital input
is disabled again. During this time and then for the delay “dot” after closing the door, t he high and low
temperature alarms are disabled.
6.2 GENERIC ALARM (I2F = EAL)
As soon as the digital input is activated the unit will wait for “did” time delay before signalling the “EAL”
alarm message. The outputs status don’t change. The alarm stops just after the digital input is deactivated.
6.3 SERIOUS ALARM MODE (I2F = BAL)
When the digital input is activated, the unit will wait for “did” delay before signalling the “BAL” alarm
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is deactivated.
6.4 PRESSURE SWITCH (I2F = PAL)
If during the interval time set by “did” parameter, the pressure switch has reached the number of
activation of the “nPS” parameter, the “PAL” pressure alarm message will be displayed. The
compressor and the regulation are stopped. When the digital input is ON the compressor is always
OFF.
If the nPS activation in the did time are reached, switch off and on the instrument to restart
normal regulation.
6.5 ENERGY SAVING (I2F = ES)
The Energy Saving function allows to change the set point value as t he result of the SET+ HES
(parmeter) sum. This function is enabled until the digital input is activated.
6.6 REMOTE ON/OFF (I2F = ONF)
This function allows to switch ON and OFF the instrument.
ALU High temperature alarm setting:
ALC= rE, 0
÷ 50°C or 90°F
1592009211 XW10L-V GB r1.0 30.05.2011 XW10L – XW10V 2/4