UNIVERSAL–XR Unit of Measure Change Instructions
Install the new Universal-XR per the installation instructions included with the controller.
THEN WITHIN 1 MINUTE COMPLETE STEPS 3, 4 AND 5.
Press the “SET” and “DOWN” key for 3 seconds and the controller will automatically recognise and
adjust itself to the type of probes connected. (The display briefly shows tPd followed by ntC or PtC).
Press the “AUX/tC” key for 3 seconds and the setting of parameter tC is displayed. Use the UP or
DOWN keys to adjust to required setting then confirm by pressing SET (see table 1 below).
Press SET for 3 seconds until the °C or °F icon starts to flash, then adjust the SET POINT using the UP
or DOWN keys, then press SET again to confirm.
1. GENERAL DESCRIPTION
Model Universal-XR is a 71x29 mm format microprocessor based controller, it is available in 12/24Vac/dc, 120Vac or
230Vac,and is suitable for applications on high, medium or low temperature refrigeration units. It is provided with three relay
outputs to control compressor, defrost - which can be both electrical or hot gas - and evaporator fans. It can work with PTC
or NTC probes. Where defrost is being terminated by time, it can operate with just one thermostat probe. Where defrost is
being terminated by temperature, it has an input for an evaporator probe(s).
The Universal-XR is equipped with a flashing visual alarm and buzzer.
Each instrument is fully configurable through special parameters that can be easily programmed through the keypad.
2. QUICK START UP PROCEDURE – Up and running in 5 easy steps
This Quick Start Up section is designed to get you up and running with the minimum of fuss. Just follow these 5 simple steps.
Notes:
1. All probes must be of the same type, either PTC or NTC.
2. Probes must be at between --58 to 140°F for auto recognition to work;
3. If 1 minute expires before you have completed quick set up, either cycle the power OFF then ON to start the set up again or
enter Pr2 as per the instructions and adjust your parameter settings manually (see Section 9).
Universal-XR 1/15 UXR10012015_REV1.4mm
Table 1: parameter “tC” settings
12/24Vac/dc use Terminals 4 & 5 for power supply
TC=2 Cooling, Off Cycle Defrost, Time Ended
12/24Vac/dc use Terminals 4 & 5 for power supply
TC=3 Cooling, Off Cycle Defrost, Temperature Ended
12/24Vac/dc use Terminals 4 & 5 for power supply
TC=4 Cooling, Off Cycle Defrost, Temperature Ended, Alarm Relay
12/24Vac/dc use Terminals 4 & 5 for power supply
TC=5 Cooling, Electric or Hot Gas Defrost Temperature Ended
12/24Vac/dc use Terminals 4 & 5 for power supply
TC6= Low Temp, Elec. Or Hot Gas Defrost, Temp. Ended, Fan
Control
12/24Vac/dc use Terminals 4 & 5 for power supply
TC7= Open Map to be Configured for any application
12/24Vac/dc use Terminals 4 & 5 for power supply
Actual Label on The Control in the Box.
Load1 is always Comp, or Heat.
Load2 is OAA and Load3 is OAb.
On / Off thermostat – Heating
XR110C, XR01CX, XR10C, XR10CX
Off cycle defrost (timed)
XR120C, XR02CX, XR20C, XR20CX
Off Cycle defrost time initiated / temperature terminated
Off Cycle defrost time initiated / temperature terminated, Alarm
Relay
Electrical / Hot Gas defrost, time initiated / temperature terminated
Electrical / Hot Gas defrost, time initiated / temperature terminated
+ evap. Fan delay and control
Full open map of parameters configure your own control
Note: As you change parameter tC, defaults change and should be approximately correct for that application but we strongly recommend you check
all parameter default values listed in these instructions to ensure they suit your particular application and make further adjustments if necessary. Read
the following sections for information about programming.
3. TYPICAL CONNECTIONS - FOR GENERAL GUIDANCE ONLY
Table 2: typical connections
Universal-XR 2/15 UXR10012015_REV1.4mm
4. PARAMETER TABLE and factory default settings
WARNING!!
Always switch the power OFF and then ON at the end of programming to update any parameter changes.
Make sure you connect the correct number of probes to suit the setting of parameter tC. Failure to do this will cause probe alarms
Room + Evaporator 1 + Display or AUX
Any probe alarms can be cleared by turning off / on the power
Type (category) of controller
4 = Time / temp defrost + alarm
6 = Time / temp defrost + fan delay
7 = Full Open Map Configurable
Second compressor start delay
Temperature alarm configuration
rE (0)= Relative to Set Point;
0 to 50C (Rel); ALL to 150C (Abs);
0 to 90F (Rel); ALL to 302C (Abs)
0 to 50C (Rel); -55C to ALU (Abs);
0 to 90C (Rel); -67C to ALU (Abs)
Delay of temperature alarm at start up
Outputs activation delay at start up
Set point for continuous cycle
-55 to 150°C;
-67 to 302°F
Defrost delay after thermostat override
Interval between defrosts
4 6 6 6 4 4 Delay start of defrost
0 0 0 0 0 0 Maximum duration of defrost
Defrost termination temperature
Maximum duration of defrost
(second evaporator)
Defrost termination temperature (second
evaporator)
IMPORTANT: Always set parameter “tC” first. As you move “tC” between settings 1 to 7, all non-relevant parameters will be masked. After setting
“tC”, it will be possible to modify all the other relevant parameters.
Once the program is completed you may want to save the parameter map to a Hot Key. If the “tC” is changed after final programming the
parameters will be changed back to the default listed below.
Table 3: default controller parameters
Universal-XR 3/15 UXR10012015_REV1.4mm
it (1) = Temp. at defrost start
sEt (2) = Set Point
dEF (3) = “DEF” label
dEG (4) = “DEG” label
First defrost after power on
N (1) = After normal interval
Evaporator fan operating mode
C_n (0) =On with Comp, off with defrost
O_n (1) =On regardless of comp, off w/
defrost
C_y (2) =On with comp, on with defrost
O_y (3) =Always on
Evaporator fan stop temperature
Evaporator fan delay after defrost
Thermostat probe calibration
Evaporator probe presence
N (0) = evaporator probe not present
Y (1) = evaporator probe present
Evaporator probe calibration
n (0) = third probe not present,
Y (1) = third probe present.
Y (0) = With decimal point in C only
Temperature measurement unit (°C/°F)
P1 (0)= Thermostat probe
P2 (1) = Evaporator probe
P3 (2) = Third probe
sEt (3) = SET-POINT
0 to 20min0sec, res. 10sec
Compressor ON time with faulty probe
Compressor OFF time with faulty probe
Alarm muting configuration for
buzzer & relay
Y (1) = Mute buzzer & relay
Second Digital input configuration
dor (1)= Door switch
AUS (2) = Auxiliary relay
ES (3) = Energy saving
onF (4) = Remote On/OFF
EAl (5) = Generic alarm
bAl (6) = Serious alarm
Second Digital input polarity
Door open – compressor / fan status
FAn (1) = Fan off
CPr (2) = Compressor off
F_C (3) = Compressor & Fan off
Defrost relay configuration
db (1) = Dead Band;
AUS (2) = Auxiliary;
CP2 (3) = Second compressor output;
liG (4) = Light output;
dF2 (5) = Second defrost output.
dEF (6) =1st Defrost output
Fan (7) =Fan output
Universal-XR 4/15 UXR10012015_REV1.4mm
Auxiliary relay configuration
db (1) = Dead Band;
AUS (2) = Auxiliary;
CP2 (3) = Second compressor output;
liG (4) = Light output;
dF2 (5) = Second defrost output.
dEF (6) =1st Defrost output
Fan (7) =Fan output
Cl (0)= [11 -12] closed with alarm
oP (1) = [11 -12] open with alarm
Exclude temperature alarm - door open
Restart regulation with door open alarm
Probe selection for Condenser Alarm
nP (0) =No Probe selected
P1 (1) =Probe 1
P2 (2) =Probe 2
P3 (3) =Probe3
Low temperature alarm of condenser
High temperature alarm of condenser
Differential for temperature condenser
alarm recovery
Condenser temperature alarm delay
Condenser temperature alarm exclusion at
start up
Compressor off with low temperature alarm
of condenser
Compressor off with high temperature
alarm of condenser
Temperature deviation from normal
Set Point during Energy Saving
nU (0) = Disabled
OFF(1) = Enabled
n (0) = Disabled
Y (1) = Enabled
Evaporator probe temperature
READ ON IF YOU NEED MORE DETAIL
Type of Controller: tells the Universal-XR which type of controller it will be operating as.
1 = on/off Heating thermostat – 1 relay & 1 probe;
2 = Combined thermostat with off cycle defrost timer – 1 relay & 1 probe;
3 = Combined thermostat with time initiated & time terminated defrost – 2 relays & 2 probe;
4 = Combined thermostat with time initiated & temperature terminated defrost – 2 relays & 2 probes; alarm
5 = Combined thermostat with time initiated, temperature terminated defrost + 2 relays & 2 probes; defrost
6 = Combined thermostat with time initiated, temperatures terminated defrost + evaporator fans control with delay after defrost – 3 relays & 3 probes;
7 = Combined thermostat with time initiated, temperatures terminated defrost + evaporator fans control with delay after defrost – 3 relays & 3 probes. Fully open map
Probe Type: configures the controller to work with PTC or NTC probes.
0= ptC = PTC,
1= ntC = NTC.
Differential: (1 to 50) sets the degrees above Set Point at which the compressor cuts in.
Note: when tC = 1 (heating applications) the tC value is automatically set below the Set Point. If the temperature decreases and reaches set point minus differential the regulation output is activated and
then turned off when the temperature reaches the set point value again.
Minimum set point limit: (-55°C to SET or -67°F to SET) sets the lower limit of set point adjustment.
Maximum set point limit: (SET to 150°C or SET to 302°F) sets the upper limit of set point adjustment.
Anti-short cycle delay: (0 to 50min) minimum interval between the compressor stop and the next possible restart.
5. PARAMETERS – THEIR FUNCTIONS IN DETAIL
Table 4: controller parameters in detail
Universal-XR 5/15 UXR10012015_REV1.4mm