1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
Pg.26/105
26. Water pump overload of evaporator 1
27. Water support pump overload of evaporator
28. Water pump overload of condenser 1
29. Water support pump overload of condenser
30. Recovery request for circuit 1
31. Recovery request for circuit 2
32. Defrost end of circuit 1
33. Defrost end of circuit 2
34. Energy Saving
35. Pressure switch / compressor 1 oil
36. Pressure switch / compressor 2 oil
37. Pressure switch / compressor 3 oil
38. Pressure switch / compressor 4 oil
39. Pressure switch / compressor 5 oil
40. Pressure switch / compressor 6 oil
41. Pump down pressure switch of circuit 1
42. Pump down pressure switch of circuit 2
43. Generic alarm from digital input with stop regulation
44. Digital input of thermoregulation request (motocondensing unit)
45. Digital input of cooling request (motocondensing unit)
46. Digital input of heating request (motocondensing unit)
47. Request / partialization 1 of compressor 1 (motocondensing unit)
48. Request / partialization 2 of compressor 1 (motocondensing unit)
49. Request / partialization 3 of compressor 1 (motocondensing unit)
50. Request compressor #2
51. Request / partialization 1 of compressor 2 (motocondensing unit)
52. Request / partialization 2 of compressor 2 (motocondensing unit)
53. Request / partialization 3 of compressor 2 (motocondensing unit)
54. Request compressor #3
55. Request / partialization 1 of compressor 3 (motocondensing unit)
56. Request / partialization 2 of compressor 3 (motocondensing unit)
57. Request / partialization 3 of compressor 3 (motocondensing unit)
58. Request compressor #4
59. Request / partialization 1 of compressor 4 (motocondensing unit)
60. Request / partialization 2 of compressor 4 (motocondensing unit)
61. Request / partialization 3 of compressor 4 (motocondensing unit)
62. Request compressor #5 (motocondensing unit)
63. Request compressor #6(motocondensing unit)
8.4 DIGITAL OUTPUT (RELAY) CONFIGURATION RL1- RL14
Parameter involved:
CF54= Configuration RL1…CF67= Configuration RL14
0. Not enabled
1. Alarm
2. Evaporator water pump / Supply fan
3. Support water pump of the evaporator
4. Anti-freeze heater / integration heating / boiler circuit #1
5. Anti-freeze heater / integration heating / boiler circuit #2
6. Water pump of the condenser recovery circuit
7. Support water pump of the condenser recovery circuit
8. 4-way valve for chiller / heat pump inversion of the circuit #1
9. 4-way valve for chiller / heat pump inversion of the circuit #2
10. 1° condenser fan step ON/OFF control of the circuit #1
11. 2° condenser fan step ON/OFF control of the circuit #1
12. 3° condenser fan step ON/OFF control of the circuit #1
13. 4° condenser fan step ON/OFF control of the circuit #1
14. 1° condenser fan step ON/OFF control of the circuit #2
15. 2° condenser fan step ON/OFF control of the circuit #2
16. 3° condenser fan step ON/OFF control of the circuit #2
17. 4° condenser fan step ON/OFF control of the circuit #2
18. Solenoid valve of the pump-down circuit #1
19. Solenoid valve of the pump-down circuit #2
20. Recovery valve circuit #1
21. Recovery valve circuit #2
22. Free cooling ON/OFF valve
23. Auxiliary output circuit #1
24. Auxiliary output circuit #2
25. Solenoid valve Intermittent for screw compressor #1
26. Solenoid valve Intermittent for screw compressor #2
27. Solenoid valve of the liquid injection for compressor #1
28. Solenoid valve of the liquid injection for compressor #2
29. Direct start-up : compressor #1 relay
PW start: relay PW #1 of the compressor #1
Star-delta start: relay line #1 of the compressor #1
30. PW start: relay PW #2 of the compressor #1