dixell iCHiLL IC200CX Series, iCHiLL IC206CX, iCHiLL IC208CX Quick Reference Manual

F
IC200CX Series
Quick reference guide
INDEX
1 GENERAL ADVICE 6
2 IC200 CX TABLE OF THE FEATURES 7
3 USER INTERFACE 8
3.1 DISPLAY CONFIGURATION 8
3.2 Icons Meaning 8
3.3 Meaning / Functionning of the bottom display led 10
4 DISPLAY LAYOUT 10
4.1 How to read the measurement list 10
4.2 Read Probe values of circuit 1 or 2 10
5 DISPLAY INFORMATION 11
5.1 Read the Set Point value 11
5.2 Modify the Set Point 11
5.3 Read the active SetPoint during Energy Saving or Dynamic Setpoint 11
5.4 KEY FUNCTION 12
5.5 KEY COMBINANTION 13
6 REMOTE TERMINAL 13
7 FIRST INSTALLING 14
7.1 On Board Clock (Optional) 14
7.2 RTC Setup 14
8 ANALOG AND DIGITAL OUTPUT CONFIGURATION 15
8.1 Analog input Pb1 - Pb2 – Pb5 – Pb6 15
8.2 Analog input Configuration Pb3 - Pb4 15
8.3 Digital Input Configuration Id1 – Id18 16
8.4 Digital Output (relay) Configuration RL1- RL8 17
8.5 Analog output configuration 0 ÷ 10 Volt (OUT1 e OUT2) 18
8.6 Configurazione N° 2 Uscite Analogiche 0 ÷ 10 Volt / Taglio di Fase (OUT3 e OUT4) 18
9 PROGRAMMING WITH THE “HOT KEY 64” 18
9.1 Download: how to program an instrument with a programmed “Hot Key” 18
9.2 Upload: How to program a “Hot Key” with the parameters of the instrument 19
10 PROGRAMMING USING THE KEYBOARD 19
10.1 Password default values 19
10.2 Enter the Pr1 - Pr2 - Pr3 programming levels 19
10.3 How to change a parameter value 20
10.4 Change the Password value 20
10.5 Enter the programming level Pr1 21
10.6 Enter the programming level Pr2 21
10.7 Enter the programming level Pr3 22
11 FUNCTION MENU “ M” KEY 23
11.1 Alarm list: show and reset 23
11.2 Compressor overload alarm reset 24
11.3 Compressor overload password. 24
11.4 Alarm log list 24
11.5 Erase the Alarm log list 25
11.6 Password value of the alarm list 25
11.7 Disable – enable a single circuit 25
12 TABLE OF THE OUTPUT STATUS IN ALARM CONDITION 26
12.1 ALARM: “A” type and status of the loads in case of alarm 26
12.2 ALARM: “b” type and status of the loads in case of alarm 28
12.3 ALARM: “C” type and status of the loads in case of alarm 29
13 TABLE OF THE PARAMETERS 30
14 BLACK-OUT 53
15 WIRING CONNECTIONS 54
15.1 Hardware Resources for IC206CX model 54
15.2 Hardware Resources for 208CX Models 54
16 INSTALLING AND MOUNTING 55
16.1 Panel cut- out 55
16.2 Vertical boards Vi620CX panel cut-out 55
17 ELECTRICAL CONNECTIONS 56
18 TECHNICAL DATA 57
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Pag. 6/58
1 GENERAL ADVICE
PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick reference.
The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device.
Check the application limits before proceeding.
SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding
sudden temperature changes with high atmospheric humidity to prevent formation of condensation
Warning: disconnect all electrical connections before any kind of maintenance.
The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell s.r.l.”
(see address) with a detailed description of the fault.
Consider the maximum current which can be applied to each relay (see thechnical Data).
Ensure that the wires for probes, loads and the power supply are separated and far enough from
each other, without crossing or intertwining.
Fit the probe where it is not accessible by the end user.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel
with inductive loads could be useful.
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
2 IC200 CX TABLE OF THE FEATURES
CHARACTERISTICS IC206CX IC208CX
N° KEYS
6
n n
RELAYS
6
n
8
n
DIGITAL INPUTS
11 Config Config
ANALOG INPUTS
4 NTC – PTC 2 NTC - PTC - 4÷20mA - 0 ÷ 5Volt
Config Config
PROPORTIONAL OUTPUTS
2 configurables (signal 0÷10V) Config Config
2 configurables (signal 0÷10V, PWM) Config Config
SERIAL OUTPUTS
TTL with Mod-BusRtu protocol
n n
Remote Keyboard VICX620 (up to 2 remote keyboards with probe on board)
n n
POWER SUPPLY
12 Vac/dc (+15%;-10%)
n n
24 Vac/dc (± 10%) Opt Opt
MAIN DISPLAY (UPPER DISPLAY)
± 4 digits with decimal point
n n
SECONDARY DISPLAY (LOWER DISPLAY)
± 4 digits with decimal point
n n
OTHER
Clock on board Opt Opt
Buzzer Opt Opt
configurable = configurable through parameter  opt = optional
n = default
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Pag. 8/58
3 USER INTERFACE
3.1 DISPLAY CONFIGURATION
3.2 ICONS MEANING
ICON MEANING / FUNCTIONNING
°C -°F
BAR-PSI
Lighted when the display shows a temperature or pressure
Lighted when a compressor is activated Blinking = when the delay of activation is running
Alarm: blinking in case of alarm
Lighted if anti freeze heaters/ integration heating / boiler are activated
Flow alarm/ (differential) pressure switch / supply fan thermal (air / air unit): is blinking if the configuration of the digital input is active
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Lighted when the bottom display shows the RTC Lighted during the programming parameters if it is time based Lighted in function menu when the display shows the defrost delay
Water pump: lighted if at least one pump is activated
Condenser fan: lighted if at least one fan is active
Lighted if Dynamic set point or Energy saving are active
Lighted during menu navigation
Lighted if auxiliary ouput is active
Lighted when the controller is ON
Lighted when the display shows probes values of circuit 1 or circuit 2
Lighted when the defrost is activated Blinking during the counting of the interval between defrost
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Pag. 10/58
3.3 MEANING / FUNCTIONNING OF THE BOTTOM DISPLAY LED
Led # 1 – 2 (With RTC)
If the bottom display shows the RTC the leds are both blinking.
Led # 1 – 2 In function Menu
During the time counting to the next defrost for one or both circuits the leds are both blinking.
LED during parameters programming
In Pr2 level: led #3 indicates the visibility of the parameter; the led #1 and #2 show if the parameter can be modified or not. In Pr3 level: led #3 and #4 indicate the visibility of the parameter; the led #1 and #2 show if the parameter can be modified or not.
4 DISPLAY LAYOUT
4.1 HOW TO READ THE MEASUREMENT LIST
With the icon Cir1 on, push UP or Down keys to display the labels of the information of the circuit 1. With the icon Cir2 on, push UP or Down keys to display the labels of the information of the circuit 2. Each measurement is defined by a label that indicates which if it is a pressure a temperature or a time.
4.2 READ PROBE VALUES OF CIRCUIT 1 OR 2
To swap between the information of the two circuits use the UP and DOWN key to select a label then push SET, check the led.
Example in fig.1 Icon Cir1 is on: the top display shows the value of the output evaporator temperature (12.8°C) of the
circuit 1; the bottom display shows Out 1 (outlet temperature evaporator 1). Push SET key to swap to the circuit 2. Fig2 Icon Cir2 is on: the top display shows the value of the output evaporator temperature (11.7°C) of the circuit 2, the bottom display shows Out 2.
Fig.1
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Fig.2
5 DISPLAY INFORMATION
5.1 READ THE SET POINT VALUE
Push and release the SET key, the set value is displayed. In stand-by the bottom display shows SetC (set chiller), by pushing SET again the next label is SetH (set heat pump). If the unit is running the only set displayed is related to the running mode.
5.2 MODIFY THE SET POINT
1) Push SET key for at least 3 seconds
2) Use the UP or DOWN key to modify the setpoint. In chiller it is possible to modify the chiller set
point, in heat pump it is possible to modify the heat pump set point, in std-by it is possible to modify both the set point.
3) Push SET to confirm or wait the timeout (15seconds).
5.3 READ THE ACTIVE SETPOINT DURING ENERGY SAVING OR DYNAMIC SETPOINT
If the unit is running in chiller or heat pump, the Energy Saving or the Dinamic Setpoint activity is signalled by the blinking of the Vset icon.
Chiller mode: push SET one time, the bottom display shows the SEtC (set chiller) while the top display shows the set value. Only if the Energy saving or the Dynamic Setpoint are active, pushing another time the SET key, the bottom display shows “SEtr” (real setpoint), and the top display shows the setpoint that the unit is really using for the thermoregulation. Heat pump mode: push SET one time, the bottom display shows the SEtH (set Heat pump) while the top display shows the set value. Only if the Energy saving or the Dynamic Setpoint are active, pushing
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Pag. 12/58
another time the SET key, the bottom display shows “SEtr” (real setpoint), and the top diplay shows the setpoint that the unit is really using for the thermoregulation.
5.4 KEY FUNCTION
KEY ACTION FUNCTION
Push and release
Show chiller set point SetC and heat pump SetH
Push once again
In chiller or heat pump if the Energy saving or the Dynamic setpoint are enabled it shows the real
setpoint Setr, the led is blinking. Push for 3 seconds Set point modification During the programming: push once
To enter parameter modification or confirm a
value Push when an alarm is showed in menù ALrM
To reset the alarm
Push once with probe label showed on the bottom display (press up or down starting from default visualization)
To read probes values of circuit 1 or circuit 2
Push once To read probes value
Pushing once during the programming
To change the group of parameters, to change
the parameter, to change the value of the
parameter Push for 1 second during the programming when the display visualize Pr1 or Pr2
1 time shows the Pr2 programming level
2 times shows the Pr3 programming level
Push once To read probes value
Pushing once during the programming
To change the group of parameters, to change
the parameter, to change the value of the
parameter
Push once
To turn ON or turn OFF the controller (in chiller or
heat pump depending from CF51 parameter)
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Push once
To turn ON or turn OFF the controller (in chiller or
heat pump depending from CF51 parameter)
Push once To enter the function Menu Push for 3 seconds To set the clock (controller with clock on board)
Pushing once during the programming
To exit from a group of parameter
5.5 KEY COMBINANTION
KEY ACTION FUNCTION
Push for 3 seconds together Enter the programming parameters
Only in Pr3 level: push SET and DOWN key
Select the parameter level visibility Pr1 / Pr2 / Pr3
Push once together Exit the programming parameters
Push 5 seconds in heat pump mode
Manual defrost
Only in Pr3 programming level: push SET and then the MENU key
In Pr3 defines if the parameter can be modified or not in the other levels.
6 REMOTE TERMINAL
The iCHILL can be connected to a remote keyboard (max 2 remote keyboards). The remote keyboard with probe on board can be used for the regulation of the machine. The maximum length of the cable is 150mt (shielded cable is recommended). Use the connection cable CAB/CJ30 (2x0.2 mm2) to interface the ichill connector to the shielded wire. In case of communication problems (hardware problems or bad connection) the upper display shows “noL” (no link).
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Pag. 14/58
7 FIRST INSTALLING
7.1 ON BOARD CLOCK (OPTIONAL)
Giving power supply the bottom display shows “rtC” alternated to a temperature or pressure value: It is necessary to set the RTC (Real time clock). ATTENTION The RTC function is an option and it is not possible to update the instrument It is necessary to order the instrument already complete of this features.
With a prolunged power failure (several days) it is necessary to setup the clock again.
7.2 RTC SETUP
1. Push Menu key for 3 seconds until the bottom display shows “Hour” and the top display shows its value.
2. Push SET one time: the value is blinking.
3. Use the Up and Down keys to adjust it. Push SET one time to confirm.
4. Push up or down keys and repeat the operations 2. 3. and 4. for all the RTC parameters:
- Min: minutes (0÷60)
- UdAy: day of the week (Sun = Sunday, Mon =Monday, tuE =Tuesday, UEd = Wednesday, tHu = Thursday, Fri =Friday, SAt =Saturday)
- dAy: day of the month (0÷31)
- MntH: month (1÷12)
- yEAr: year (00÷99)
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
8 ANALOG AND DIGITAL OUTPUT CONFIGURATION
8.1 ANALOG INPUT PB1 - PB2 PB5 PB6
Parameters involved: CF08 = Configuration PB1 CF09 = Configuration PB2 CF12 = Configuration PB5 CF13 = Configuration PB6
0. Not enabled
1. Temperature probe PTC for compressor #1 discharge
2. Temperature probe NTC for evaporator inlet
3. Temperature probe NTC for evaporator #1 outlet
4. Temperature probe NTC for evaporator #2 outlet
5. Temperature probe NTC for common evaporator outlet
6. Temperature probe NTC for common hot water condenser inlet
7. Temperature probe NTC for hot water of the condenser circuit #1 inlet
8. Temperature probe NTC for hot water of the condenser circuit #2 inlet
9. Temperature probe NTC for hot water of the condenser circuit #1 outlet
10. Temperature probe NTC for hot water of the condenser circuit #2 outlet
11. Temperature probe NTC for hot water of the condenser common outlet
12. Temperature probe NTC (external temperature) for dynamic setpoint / boiler / change over
13. Temperature probe NTC for combined defrost circuit #1
14. Temperature probe NTC for combined defrost circuit #2
15. Temperature probe NTC for auxiliary output #1
16. Temperature probe NTC for auxiliary output #2
17. Temperature probe NTC for condensing circuit #1
18. Temperature probe NTC for condensing circuit #2
Every analogue input can be configured as digital input; after the number 18, the values o 1c38 allow the configuration of the analogue input as digital inputs with the same meaning (o 1= remote ON/OFF, o 2= Remote chiller / heat pump, …..).
8.2 ANALOG INPUT CONFIGURATION PB3 - PB4
Parameter involved: CF10 = Configuration PB3 CF11 = Configuration PB4
0 Not enabled 1 Temperature probe PTC for compressor #1 discharge 2 Temperature probe NTC for evaporator inlet 3 Temperature probe NTC for evaporator #1 outlet 4 Temperature probe NTC for evaporator #2 outlet 5 Temperature probe NTC for common evaporator outlet 6 Temperature probe NTC for common hot water condenser inlet 7 Temperature probe NTC for hot water of the condenser circuit #1 inlet 8 Temperature probe NTC for hot water of the condenser circuit #2 inlet 9 Temperature probe NTC for hot water of the condenser circuit #1 outlet 10 Temperature probe NTC for hot water of the condenser circuit #2 outlet 11 Temperature probe NTC for hot water of the condenser common outlet
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Pag. 16/58
12 Temperature probe NTC (external temperature) for dynamic setpoint / boiler / change over 13 Temperature probe NTC for combined defrost circuit #1 14 Temperature probe NTC for combined defrost circuit #2 15 Temperature probe NTC for auxiliary output #1 16 Temperature probe NTC for auxiliary output #2 17 Condenser probe circuit 1 ( temperature NTC / pressure 4÷20 mA / ratio-metric 0÷ 5Volt ) 18 Condenser probe circuit 2 ( temperature NTC / pressure 4÷20 mA / ratio-metric 0÷ 5Volt ) 19 Evaporator pressure probe circuit 1 (pressure 4÷20 mA / ratio-metric 0÷ 5Volt ) 20 Evaporator pressure probe circuit 1 (pressure 4÷20 mA / ratio-metric 0÷ 5Volt ) 21 Auxiliary output 1 pressure probe control (4÷20 mA / ratio-metric 0÷ 5Volt). 22 Auxiliary output 2 pressure probe control (4÷20 mA / ratio-metric 0÷ 5Volt). 23 Dynamic setpoint pressure probe (4÷20 mA) Every analogue input can be configured as digital input; after the number 18, the values o 1c38 allow the configuration of the analogue input as digital inputs with the same meaning (o 1= remote ON/OFF, o 2= Remote chiller / heat pump, …..).
8.3 DIGITAL INPUT CONFIGURATION ID1 ID18
Parameters involved: CF24 = Configuration ID1…CF34 = Configuration ID18
0. Not enabled
1. Remote ON / OFF
2. Remote chiller / heat pump
3. Flow switch evaporator pump / supply fan overload
4. Flow switch condenser pump
5. Antifreeze heater circuit 1
6. Antifreeze heater circuit 2
7. High pressure switch circuit 1
8. High pressure switch circuit 2
9. Low pressure switch circuit 1
10. Low pressure switch circuit 2
11. Compressor 1 high pressure
12. Compressor 2 high pressure
13. Compressor 1 overload
14. Compressor 2 overload
15. Condenser fan overload of circuit 1
16. Condenser fan overload of circuit 2
17. Condenser fan overload of circuit 1 and 2 (common condenser)
18. Evaporator water pump overload
19. Support evaporator water pump overload
20. Condenser water pump overload
21. Support condenser water pump overload
22. End defrost of circuit 1
23. End defrost of circuit 2
24. Energy Saving
25. Pressure switch / compressor 1 oil
26. Pressure switch / compressor 2 oil
27. Pump down pressure switch of circuit 1
28. Pump down pressure switch of circuit 2
29. Generic alarm n°1
30. Generic alarm n°2
31. RTC disabled
32. Supplay fan enabled (the unit works only with the supplay fan)
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
33. Thermoregulation request (motocondensing unit)
34. Cooling request (motocondensing unit)
35. Heating request (motocondensing unit)
36. Request step 2 (motocondensing unit)
37. Request step 3 (motocondensing unit)
38. Request step 4 (motocondensing unit)
8.4 DIGITAL OUTPUT (RELAY) CONFIGURATION RL1- RL8
Parameter involved: CF35= Configuration RL1…CF42= Configuration RL8
0. Not enabled
1. Alarm
2. Evaporator water pump / Supply fan
3. Evaporator support water pump
4. Anti-freeze heater / integration heating / boiler circuit 1
5. Anti-freeze heater / integration heating / boiler circuit 2
6. Condenser water pump
7. Condenser support water pump
8. 4-way valve for chiller / heat pump inversion of the circuit 1
9. 4-way valve for chiller / heat pump inversion of the circuit 2
10. 1° condenser fan step ON/OFF control of the circuit 1
11. 2° condenser fan step ON/OFF control of the circuit 1
12. 3° condenser fan step ON/OFF control of the circuit 1
13. 1° condenser fan step ON/OFF control of the circuit 2
14. 2° condenser fan step ON/OFF control of the circuit 2
15. 3° condenser fan step ON/OFF control of the circuit 2
16. Solenoid valve of the pump-down circuit 1
17. Solenoid valve of the pump-down circuit 2
18. Auxiliary output circuit 1
19. Auxiliary output circuit 2
20. Solenoid valve Intermittent for screw compressor 1
21. Solenoid valve of the liquid injection for compressor 1
22. Soleniod valve water side for chiller and heat pump circuit 1
23. Soleniod valve water side for heat pump circuit 1
24. Soleniod valve water side for chiller and heat pump circuit 2
25. Soleniod valve water side for heat pump circuit 2
26. Valve for geothermal function
27. Direct start-up : compressor 1 relay Part Winding 1 of the compressor 1
28. Part Winding 2 of the compressor 1
29. Capacity step valve 1 compressor 1
30. Capacity step valve 2 compressor 1
31. Capacity step valve 3 compressor 1
32. By-pass gas valve compressor 1start
33. Direct start: compressor 2 start Part Winding 1 of the compressor 2
34. Part Winding 2 of the compressor 2
35. Capacity step valve 1 compressor 2
36. By-pass gas valve compressor 2 start
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Pag. 18/58
8.5 ANALOG OUTPUT CONFIGURATION 0 ÷ 10 VOLT (OUT1 E OUT2)
Parametri: CF43 = Analog output OUT1 configuration CF44 = Analog output OUT2 configuration
0 = output disabled 1 = 0..10V output for compressor 1 inverter controlled 2 = 0..10V output for compressor 2 inverter controlled 3 = 0..10V output for auxiliary output 1 4 = 0..10V output for auxiliary output 2 5 = 0..10V output for geothermal function 6 = 0..10V output for condenser fan circuit 1 7 = 0..10V output for condenser fan circuit 2 8 = 0..10V output for modulating evaporator pump 9 = 0..10V output for modulating condenser pump o1..c26 = ON / OFF output for external relay management (same meaning of relays configuration)
8.6 CONFIGURAZIONE 2 USCITE ANALOGICHE 0 ÷ 10 VOLT / TAGLIO
DI FASE (OUT3 E OUT4)
Parametri: CF45 = Configurazione uscita analogica n° 3 CF46 = Configurazione uscita analogica n° 4
0 = output disabled 1 = 0..10V output for compressor 1 inverter controlled 2 = 0..10V output for compressor 2 inverter controlled 3 = 0..10V output for auxiliary output 1 4 = 0..10V output for auxiliary output 2 5 = 0..10V output for geothermal function 6 = 0..10V output for condenser fan circuit 1 7 = 0..10V output for condenser fan circuit 2 8 = PWM output for condenser fan circuit 1 9 = PWM output for condenser fan circuit 2 o1..c26 = OFF output for external relay management (same meaning of relays configuration)
9 PROGRAMMING WITH THE “HOT KEY 64”
9.1 DOWNLOAD: HOW TO PROGRAM AN INSTRUMENT WITH A
PROGRAMMED “HOT KEY
1. Turn off the instrument supply
2. Insert the hot key.
3. Turn on the power supply.
4. Immediately the parameters are downloaded.
During the download the regulation is locked and the top display shows the “doL” blinking label. At the end of the download will appear:
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
“End” if the programming procedure is completely OK, after 30seconds the regulation starts automatically. “Err” if the programming procedure has found an error and the parameter have not been transferred. In this case turn off and then on the instrument supply to repeat the operation or remove the hot key, with power supply off, to restart the regulation.
9.2 UPLOAD: HOW TO PROGRAM A “HOT KEY WITH THE
PARAMETERS OF THE INSTRUMENT
1. Turn on the power supply.
2. Insert the hot key.
3. Enter the function Menu.
4. Select the UPL function (on the bottom display).
5. Push SET key and immediately the instrument starts transfer the parameters into the Hot key.
During the upload the regulation is locked and the top display shows the “UPL” blinking label. At the end of the UPLOAD will appear: “End” if the programming procedure is completely OK, after 30seconds the regulation starts automatically. “Err” if the programming procedure has found an error and the parameter have not been transferred. Repeat the procedure. To exit the UPL function push the MENU key or wait the time-out.
10 PROGRAMMING USING THE KEYBOARD
Through the instrument keyboard it is possible to enter the programming. In all the three accessible levels the user can show and modify both value and visibility of the parameters. To ensure an easy navigation through the different levels the common parameters have been named and grouped under a family name. The three levels of programming:
Pr1 User level
Pr2 Maintenance level
Pr3 OEM level
10.1 PASSWORD DEFAULT VALUES
Password level Pr1 = 1
Password level Pr2 = 2
Password level Pr3 = 3
Each password can be changed, the range is from 0 to 999.
10.2 ENTER THE PR1 - PR2 - PR3 PROGRAMMING LEVELS
Pr1 LEVEL:
Push SET + DOWN together for 3 seconds, the top display shows the PAS label and the bottom display shows the Pr1 label. The leds Cir1 and Cir2 are blinking to inform that you now are in PR1 programming level.
Pr2 LEVEL:
Starting from Pr1 level push the UP key for 2 seconds and the bottom display will show Pr2. The top display still shows PAS. Push the SET key and the top display will show the 0 blinking value; set the password level using the UP and DOWN keys then confirm with SET key.
Pr3 LEVEL:
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Pag. 20/58
Starting from the Pr2 level push the UP key for 2 seconds and the bottom display will show Pr3. The top display still shows PAS. After selecting the level push the SET key and the top display will show the 0 blinking value where to insert the password. Set the password level using the UP and DOWN keys then confirm with SET key. Dependening on the password value there will be the different level access, if the password is wrong the instrument shows the password value again.
ATTENTION: For all the programming levels Pr1, 2, 3: the CF family (or configuration parameters) can not be changed if the unit is running in chiller or heat pump. To change this parameters is necessary to set the unit in stand-by and then enter the programming again. During the defrost the dF family can’t be programmed.
10.3 HOW TO CHANGE A PARAMETER VALUE
Enter the programming
1. Push the SET + DOWN keys together for 3 seconds;
2. Select the parameter label with up and down keys;
3. Push SET to enter the parameter value;
4. Change the value with UP or DOWN keys;
5. Push “SET” to confirm, after some seconds the display shows the next parameter;
6. Exit: Push SET + UP together when a parameter label is displayed or wait 15seconds without pushing a key.
NOTE: a new parameter value is confirmed also after the 15 seconds of timeout is expired (without pushing SET key to confirm).
10.4 CHANGE THE PASSWORD VALUE
Pr1 LEVEL
Remember that it is necessary to know the old password value.
1) Enter the Pr1 level
2) Select a parameter family.
3) Select “Pr1” on the bottom display; the current password value is on the top display. Push the SET key to change the value that now is blinking.
4) Use the UP or DOWN key to insert the NEW PASSWORD value, then push SET to confirm the new value.
5) The top display blinks for some seconds and then shows the next parameter.
6) Exit the programming pushing SET + UP together or wait the timeout.
Pr2 LEVEL
Remember that it is necessary to know the old password value.
1. Enter the Pr2 level
2. Select a parameter family.
3. Select the “Pr2” on the bottom display; the current password value on the top display. Push the SET key to change the value that now is blinking.
4. Use the UP or DOWN key to insert the NEW PASSWORD value, then push SET to confirm the new value.
5. The top display blinks for some seconds and then shows the next parameter
6. Exit the programming pushing SET + UP together or wait the timeout.
Inside the Pr2 level it is possible to change also the Pr1 password.
Pr3 LEVEL
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Remember that it is necessary to know the old password value.
1. Enter the Pr3 level
2. Select a parameter family.
3. Select the “Pr3” on the bottom display; the current password value on the top display. Push the SET key to change the value that now is blinking.
4. Use the UP or DOWN key to insert the NEW PASSWORD value, then push SET to confirm the new value.
5. The top display blinks for some seconds and then shows the next parameter
6. Exit the programming pushing SET + UP together or wait the timeout.
Inside the Pr3 level it is possible to change also the Pr1 and Pr2 passwords.
10.5 ENTER THE PROGRAMMING LEVEL PR1
Enter the Pr1 “User level ”:
1. Push the SET + DOWN keys together for 3 seconds. The top display shows PAS while the bottom display shows Pr1 labels.
2. Push SET key and the top display shows a blinking 0, with UP or DOWN insert the Pr1 password. Push SET and, if the value is correct, the top display will show the first family of parameters “ALL”. Otherwise set the password again.
3. Select a parameter family with DOWN or UP keys.
4. Push SET to enter, the bottom display shows the first available parameter label while the top display shows its value.
The user can shows and modify all the parameters belonging to this family.
Parameter status, leds and bottom display in Pr1
If the selected parameter can not be changed the leds 1 and 2 are blinking.
In Pr1 level the user can not see and change any parameter of Pr2 and Pr3.
The MENU key allows to exit from a family to reselect another without exit the Pr1 level.
To exit completely the programming push SET + UP.
10.6 ENTER THE PROGRAMMING LEVEL PR2
Enter the Pr2 “maintenance level ”:
1. Push the SET + DOWN keys together for 3 seconds. The top display shows PAS while the bottom display shows Pr1 labels.
2. Push UP key for 2 seconds and the top display will show Pr2.
3. Push SET key and the top display shows a blinking 0, with UP or DOWN insert the Pr2 password. Push SET and, if the value is correct, top display will show the first family of parameters “ALL”. Otherwise set the password again.
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Pag. 22/58
4. Select a parameter family with DOWN or UP keys.
5. Push SET to enter, the bottom display shows the first available parameter label while the top display shows its value.
The user can shows and modify all the paramters belonging to this family. Parameter status, leds and bottom display in Pr2
Leds 1 / 2 are blinking: the parameter can not be changed.
All the leds are off: the parameter ca not be seen in Pr1 level.
Led 3 is on: the parameter can be seen in Pr1 level.
Led 3 blinking: the parameter can be showed and changed in Pr2, showed but not changed in
Pr1.
Leds 1 / 2 / 3 are blinking: the parameter can’t be showed and changed in Pr2 and in Pr1.
In Pr2 level the user can not see and change any parameter of Pr3 level.
The MENU key allows to exit from a family to reselect another without exit the Pr2 level.
The MENU key allows to pass to Pr1 starting from a family label.
To exit completely the programming push SET + UP.
10.7 ENTER THE PROGRAMMING LEVEL PR3
Enter the Pr3 “OEM level ”:
1. Push the SET + DOWN keys together for 3 seconds. The top display shows PAS while the bottom display shows Pr1 labels.
2. Push UP key for 2 seconds and the top display will show Pr2.
1. Push UP key again for 2 seconds and the top display will show Pr3
3. Push SET key and the top display shows a blinking 0, with UP or DOWN insert the Pr3 password. Push SET and, if the value is correct, top display will show the first family of parameters “ALL”. Otherwise set the password again.
4. Select a parameter family with DOWN or UP keys.
5. Push SET to enter, the bottom display shows the first available parameter label while the top display shows its value.
The user can shows and modify all the paramters belonging to this family.
Parameter status, leds and bottom display in Pr3
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Leds 1 / 2 are blinking: the parameter can not be changed in Pr1 and Pr2 level.
All the leds are off: the parameter is available only in Pr3.
Led 4 on: the parameter can be changed also in Pr2.
Led 4 blinking: the parameter is visible but not modifiable in Pr2.
Leds 3 / 4 on: the parameter is visible and modifiable in Pr2 and in Pr1.
Leds 3 / 4 blinking: the parameter is visible but not modifiable in Pr1 and in Pr2.
The MENU key allows to exit from a family to reselect another without exit the Pr2 level.
The MENU key allows to pass to Pr1 starting from a family label.
To exit completely the programming push SET + UP.
11 FUNCTION MENU “ M” KEY
The function Menu is composed of the following items:
1) Show and reset the alarms ALrM
2) Compressor overload alarm reset COtr
3) Show and reset the alarm log ALOG
4) Upload the parameter into the Hot Key UPL
5) Enable – disable one or the two circuits CrEn
6) Enable – disable one of the compressors COEn
7) Enable – disable one of the pumps POEn
8) Display the compressor discharge temperature COdt
9) Show and reset the number of compressor running hour Hour
10) Show and reset the number of compressor starts-up COSn
11) Show the condensing fan speed percentage of the proportional output Cond
12) Show the percentage of the proportional output 0 ÷ 10 Vdc Pout
13) Time counting to next defrost cycle, under heat pump mode, dF
14) Show the probe temperatures that enabled to control the auxiliary output uS
15) Show the probe the temperature of the remote panels trEM
MENU FUNCTION ACCESS: Push and release the M key.
11.1 ALARM LIST: SHOW AND RESET
ALrM FUNCTION
Enter the function MENU pushing M key one time
1) Use the UP or DOWN to select the AlrM label
2) Push SET key (Nothing happens if there are no active alarm events)
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Pag. 24/58
3) Bottom display: alarm label code. Top display: label rSt to reset or NO if it is not possible.
4) Use the UP or DOWN to scroll the alarm list.
5) Pushing SET when the rSt label is displayed the corresponding alarm will be reset, then the display shows next alarm in the list, pushing SET again the alarm is reset and the display shows next alarm etc. Nothing happens by pushing SET when the label NO is displayed, in this case push UP or DOWN to move to another alarm label.
6) To exit the ALrM reset function push MENU one time or wait the timeout.
11.2 COMPRESSOR OVERLOAD ALARM RESET
COtr function resets the compressor overload alarm event.
Within the COtr function all the active compressor overload alarms are displayed in a list. Labels involved in COtr: CO1r = compressor 1 overload reset … CO2r = compressor 2 overload
reset. Labels CO1r – CO2r are available if the digital inputs have been previously configured.
ATTENTION
The COtr menù is displayed only if the compressor overload alarm is at manual reset (after AL25 alarm events per hour the alarm is at manual reset).
MANUAL ALARM RESET PROCEDURE Enter Menu function
1. Use UP or DOWN key and select the COtr on the bottom display.
2. Push SET one time, if there are active alarms the bottom display shows the alarm label eg. CO1r (for compressor 1) while the top display shows the label rSt to reset the alarm or NO if the alarm can not be reset. Use the UP or DOWN keys to scroll all the alrm list.
3. Nothing happens by pushing SET when the label NO is displayed.
4. Pushing SET when the rSt label is displayed the corresponding alarm will be reset after the password: bottom display = ArSt while the top display = PAS.
5. Push SET and the top display blinks 0 while the bottom shows PAS. Insert the password using UP or DOWN key (see AL60 parameter). If the password is OK the ArSt blinks for per 3seconds, if the password value is not correct the top display blinks 0 while the bottom shows PAS. If within 5 seconds no value is inserted the display label come back to CO1r function.
6. To exit the COtr function push MENU or wait the timeout.
11.3 COMPRESSOR OVERLOAD PASSWORD.
The default value is 0; to change this value enter Pr3 level, search AL60 parameter and modify its value.
11.4 ALARM LOG LIST
ALOG FUNCTION TO SEE THE ALARM LOG
The function and the alarm codes are visible only if there are alarm events. If many events are active at the same time the list displayed by increasing order. Enter the function Menu
1. Select ALOG
2. Push SET one time. Nothing happens if there are no active alarm events.
3. The bottom display shows the alarm label, the top display shows a number in the range 00 to 99.
4. Use the UP or DOWN keys to scroll the list.
5. To exit the ALOG function push MENU or wait the timeout.
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
11.5 ERASE THE ALARM LOG LIST
ALOG FUNCTION TO ERASE THE LOG LIST
1. Enter the function Menu.
2. Use the UP or DOWN keys to select ALOG on the bottom display.
3. Push the SET key.
4. Push UP or DOWN keys and search the ArSt label on the bottom display; the top display shows PAS.
5. Push SET: the bottom display shows PAS and the top display shows 0 value blinking.
6. Insert the password
7. If the password is OK the label ArST blinks for 5 seconds then the display returns to normal condition read-out (probes).
8. If the password is not correct the display shows PAS again. in any case is possible to scroll the list with UP or DOWN
9. To exit push the M key one time or wait the timeout.
11.6 PASSWORD VALUE OF THE ALARM LIST
The default value is 0 to change this value enter Pr3 level under the AL parameter family.
THE ALARM LIST CONTAINS 100 EVENTS IN A FIFO STRUCTURE. WHEN THE MEMORY IS FULL ANY NEW ALARM WILL ERASE THE OLDEST.
11.7 DISABLE ENABLE A SINGLE CIRCUIT
Through the instruments keyboard is possible to completely disable a single circuit for maintenance or to use just a cooling part of of the unit.
CrEn FUNCTION enables – disables a circuit from keyboard. Label involved with CrEn function: Cr1E = circuit 1, Cr2E = circuit 2
HOW TO DISABLE A CIRCUIT
Enter the function Menu
1. Use UP or DOWN keys to select CrEn on the bottom display
2. Push SET key: the bottom display = Cr1E, top display = En.
3. Select the circuit 1 or 2 with UP or DOWN key (Cr1E or Cr2E).
4. Push SET key for 3 seconds when; the top display shows the En blinking label. Using UP or DOWN key, choose the label diS (Disabled) or En (Enabled), then push SET key to confirm the new selection. The display shows next circuit status.
5. To exit the CrEn function push MENU key or wait the timeout.
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Pag. 26/58
Pg.26/58
12 TABLE OF THE OUTPUT STATUS IN ALARM CONDITION
The alarm codes are made of letters and numbers to define the different typologies:.
12.1 ALARM: “A” TYPE AND STATUS OF THE LOADS IN CASE OF ALARM
Alarm Code Alarm description Compressor Anti
freeze
heaters
Boiler
Support
heaters
Evap.
Pump.
Supply
fan
Condenser
Pump
Ventilaz.
cond.
Cir1 Cir2
Auxiliary
relay
ALti
Low air temperature of the evaporator inlet (air / air unit) Alarm
AEFL
Evaporator flow alarm
Yes
Yes
(boiler)
Yes (3)
Yes
ACFL
Condenser flow alarm Yes
Yes (3)
Yes
AtSF
Fan supply overload alarm Yes Yes Yes
Yes
AEUn
Unloading signalling from high temp of. evaporator water
AELt
Low temperature of the evaporator inlet in Heat Pump mode
Yes
Aedt
Differential temperature alarm (between temperature inlet and outlet)
Yes
AtE1
Water pump overload alarm evaporator 1
Yes (4)
Yes
(boiler)
(5)
Yes
Yes
AtE2
Water pump overload alarm support evaporator 2
Yes (4)
Yes
(boiler)
Yes
Yes
1592022750 Quick reference guide IC200CX Rel. 1.1 25/05/2009
(5)
AtC1
Water pump overload alarm condenser 1
Yes (4)
Yes Yes
AtC2
Water pump overload alarm support condenser 2
Yes (4)
Yes Yes
AEP1
Water pump maintenance evaporator 1
AEP2
Water pump maintenance support evaporator 2
ACP1
Water pump maintenance condenser 1
ACP2
Water pump maintenance support condenser 2
ArtC
Clock alarm
Atr1
Remote terminal n° 1 configured but not connected
Atr2
Remote terminal n° 2 configured but not connected
ArtF
clock failure
ALc1
Generic alarm n°1 Yes Yes Yes Yes Yes
ALc2
Generic alarm n°2 and AL56=0
ALc2
Generic alarm n°2 and AL56=1 Yes Yes Yes Yes Yes
AEE
Eeprom alarm Yes Yes Yes Yes Yes
AFr
Power supply frequency alarm (if CF54=2,
4)
Yes Yes Yes Yes Yes
ACF1
Configuration alarm Yes Yes Yes Yes Yes
ACF2
Configuration alarm Yes Yes Yes Yes Yes
ACF3
Configuration alarm Yes Yes Yes Yes Yes
ACF4
Configuration alarm Yes Yes Yes Yes Yes
ACF5
Configuration alarm Yes Yes Yes Yes Yes
ACF6
Configuration alarm Yes Yes Yes Yes Yes
ACF7
Configuration alarm Yes Yes Yes Yes Yes
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Pag. 28/58
Pg.28/58
ACF8
Configuration alarm Yes
Yes Yes Yes Yes
ACF9
Configuration alarm Yes
Yes Yes Yes Yes
AC10
Configuration alarm Yes
Yes Yes Yes Yes
AC11
Configuration alarm Yes
Yes Yes Yes Yes
AEht
High water temperature inlat evaporator Yes
(1) = with probe configured as anti-freeze / boiler control and Ar10 = 0 (2) = with probe configured as auxiliary relay control (3) = with manual alarm procedure (4) = Off compressors spenti with only 1 water pump configured or with 2 pumps but both in alarm from the corresponding digital inputs. (5) = Boiler heaters off with only 1 water pump configured or with 2 pumps but both in alarm from the corresponding digital inputs (in this case the
boiler heaters are on only with thermoregulation anti-freeze setpoint as evaporator protection function)
12.2 ALARM: B TYPE AND STATUS OF THE LOADS IN CASE OF ALARM
Alarm
Code
Alarm description
Compressors
of the circuit
(n)
Compressors
of the other
circuit
Fan condensing of
the circuit (n)
Fan
condensing of
the other
circuit
b(n)HP
High pressure switch of the circuit (n)
Yes
Yes after 60 seconds
b(n)LP
Low pressure switch of the circuit (n)
Yes
Yes
b(n)AC
Anti-freeze in chiller of the circuit (n)
Yes Yes
b(n)AH
Anti-freeze in heat pump of the circuit (n)
Yes Yes
b(n)hP
High condensing pressure of the circuit (n)
Yes
Yes after 60 seconds
b(n)hP
High condensing temperature from NTC of the circuit (n)
Yes
Yes after 60 seconds
b(n)LP
Low condensing pressure - (evaporating with low pressure transducer) with transducer of the circuit of the (n)
Yes Yes
1592022750 Quick reference guide IC200CX Rel. 1.1 25/05/2009
b(n)lP Low condensing temperature NTC circuit (n)
Yes Yes
b(n)tF
Fan overload circuit (n)
Yes Yes
b(n)PH
Pump down alarm in stop regulation of the circuit (n)
Yes
Yes
b(n)PL
Pump down in regulation start-up of the circuit (n)
Yes
Yes
b(n)dF Bad defrost circuit (n)
b(n)Cu Unloading from condenser high temp/press of the circuit (n) b(n)Cu
Unloading from evaporator low temp/press of the circuit (n)
Yes
Yes
b(n)rC
Recovery function disabled in circuit (n)
b(n)ds
Circuit (n) disabled from keyboard
Yes
Yes
b(n)Ac
Anti-freeze circuit (n) message in chiller
b(n)Ah
Anti-freeze circuit (n) message in heat pump
(n) identifies the circuit 1 or 2
12.3 ALARM: “C” TYPE AND STATUS OF THE LOADS IN CASE OF ALARM
Alarm Code
Alarm description Compressor
(n)
Compressors not involved
C(n)HP
Compressor(n) high pressure switch Yes
C(n)oP
Compressor(n) oil pressure switch / Oil level switch Yes
C(n)tr
Compressor(n) overload Yes
C(n)dt
Compressor high discharge temperature Yes
C(n)dS
Compressor (n) disabled from keyboard Yes
C(n)Mn
Compressor(n) maintenance
(n) identifies the compressor 1, 2 , 3 , 4 , 5 , 6
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
13 TABLE OF THE PARAMETERS
Thermoregulation
Par Description min max u.m.
Resol ution
ST 1
Chiller Setpoint Allow to modify the setpoint of the unit in chiller mode
ST02 ST03 °C/°F dec/int
ST 2
Chiller minimum Setpoint Minimum setpoint limit for ST 1
-50.0
-58
ST01
°C °F
dec/int
ST 3
Chiller maximum Setpoint Maximum setpoint limit for ST 1
ST01
70.0 158
°C °F
dec/int
ST 4
Heat pump setpoint Allow to modify the setpoint of the unit in heat pump mode
ST05 ST06 °C/°F dec/int
ST 5
Heat pump minimum Setpoint Minimum setpoint limit for ST 4
-50.0
-58
ST04
°C °F
Dec
int
ST 6
Heat pump maximum Setpoint Maximum setpoint limit for ST 4
ST04
70.0 158
°C °F
Dec
int
ST 7
Regulation band in chiller mode 0.0 0 25.0
45
°C °F
Dec
int
ST 8
Regulation band in heat pump mode 0.0 0 25.0
45
°C °F
Dec
int
ST 9
Thermoregulation probe selection in chiller 0= Temperature probe NTC for evaporator inlet 1= Temperature probe NTC for evaporator outlet 1 2= Temperature probe NTC for evaporator outlet 2 3= Temperature probe NTC for common evaporator outlet 4= Temperature NTC probe from remote keyboard 1 5= Temperature NTC probe from remote keyboard 2
0 5
ST 10
Thermoregulation probe selection in heat pump 0= Temperature probe NTC for evaporator inlet 1= Temperature probe NTC for evaporator outlet 1 2= Temperature probe NTC for evaporator outlet 2 3= Temperature probe NTC for common evaporator outlet 4= Temperature NTC probe from remote keyboard 1 5= Temperature NTC probe from remote keyboard 2 6= Temperature probe for water common inlet of the condenser 7= Temperature probe for water inlet of the circuit # 1 condenser 8= Temperature probe for water inlet of the circuit # 2 condenser 9= Temperature probe for water outlet of the circuit # 1 condenser 10= Temperature probe for water outlet of the circuit # 2 condenser 11= Temperature probe for water common outlet of the condenser ATTENTION To have the same thermoregulation for chiller and heat pump mode, set the parameters ST09 and ST10 with the same value
0 11
ST 11
Type of thermoregulation 0= Proportional 1= Neutral zone
0 1
ST 12
Set point for change over function -50.0
-58
70.0 158
°C °F
Dec
Int
ST 13
Differential for change over function 0.1 1 25.0
45
°C °F
Dec
Int
Pr1
Password 0 999
Pr2
Password 0 999
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Pr3
Password 0 999
Display read-out
Param eter
Description min max M. u. Resolu
tion
dP 1
Default read-out of the top display 0 15
dP 2
Default read-out of the bottom display 0 18
dP 3
Default display read-out configuration top / bottom 0= Configurable (parameters dP1 and dP2) 1= Top display: Evaporator IN, Bottom display: Evaporator OUT 2= Top display: Condenser IN, Bottom display: Condenser OUT 3=Top display: temperature/Condensing pressure, Bottom Display: evaporating pressure
0 3
dP 4
Display visualization in stand by mode 0= the display visualizes “Stby” 1= the display visualizes what defined by parameters dP1 and dP2 2= the display visualizes “OFF”
0 2
Display read-out of the remote keyboards
dP 5
Display default read-out of the remote keyboard 1 0= the read-out depends on the paremeters dP01 – dP02 – dP03 1= the read-out shows the NTC probe of the remote panel
0 1
dP 6
Display default read-out of the remote keyboard 2 0= the read-out depends on the paremeters dP01 – dP02 – dP03 1= the read-out shows the NTC probe of the remote panel.
0 1
dP 7
Display visualization of the remote keyboard 1 in stand by mode 0= the display visualizes “Stby” 1= the display visualizes what defined by parameters dP1 and dP2 2= the display visualizes “OFF”
0 2
dP 8
Display visualization of the remote keyboard 2 in stand by mode 0= the display visualizes “Stby” 1= the display visualizes what defined by parameters dP1 and dP2 2= the display visualizes “OFF”
0 2
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
Configuration
Param eter
Description min max M. u. Resolu
tion
Unit Model
CF 1
Type of unit 0= Air / air Chiller 1= Air / water Chiller 2= Water / water Chiller
0 2
CF 2
Selection type rof unit 1= only chiller 2= only heat pump 3= chiller and heat pump
0 3
CF 3
Motocondensing unit 0= no 1= si
0 1
Compressors
CF 4
Number of compressors circuit 1 1= 1 2= 2
1 2
CF 5
Number of compressors circuit 2 0= 0 1= 1
0 1
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
CF 6
Number of capacity steps 0= none 1= 1 2= 2 3= 3
0 3
Analog Inputs
CF 7
Pressure or temperature analogue input functioning 0 = Temperature / pressure NTC – 4÷20 mA : The condensing temperature is controlled with NTC probe while for the evaporating pressures of the circuits 1 and 2 and the pressure probe configured as auxiliary output 1 and 2 are controlled with 4÷20mA transducers. 1 = Pressure control with 4÷20 mA: To control the evaporating and condensing pressures it is necessary a 4÷20mA transducer. 2 = Temperature / pressure NTC – 0÷5Vdc: The condensing temperature is controlled with NTC probe while for the evaporating pressures of the circuits 1 and 2 and the pressure probe configured as auxiliary output 1 and 2 are controlled with 0÷5Vdc transducers. 3 = Pressure control with 0÷5Vdc: To control the evaporating and condensing pressures it is necessary a ratiometric 0÷5Vdc transducer.
0 3
CF 8
PB1 Configuration If configured as digital input
0
o 1
18
C38
CF 9
PB2 Configuration If configured as digital input
0
o 1
18
C38
CF 10
PB3 Configuration If configured as digital input
0
o 1
23
C38
CF 11
PB4 Configuration If configured as digital input
0
o 1
23
C38
CF 12
PB5 Configuration If configured as digital input
0
o 1
18
C38
CF 13
PB6 Configuration If configured as digital input
0
o 1
18
C38
Probe Offset
CF 14
PB1 Offset -12.0
21
12.0
21
°C °F
Dec
int
CF 15
PB2 Offset -12.0
21
12.0
21
°C °F
Dec
int
CF 16
PB3 Offset -12.0
-21
-5.0
-72
12.0
21
5.0 72
°C °F
bar
psi
Dec
int
dec
int
CF 17
PB4 Offset -12.0
-21
-5.0
-72
12.0 21
5.0 72
°C °F
bar
psi
Dec
int
dec
int
CF 18
PB5 Offset
-12.0 21
12.0 21
°C °F
Dec
int
CF 19
PB6 Offset -12.0
21
12.0 21
°C °F
Dec
int
CF 20
Pressure value at 4mA or 0.5 Vdc of the PB3 transducer 0
-14
50.0
725
Bar
psi
Dec
int
CF 21
Pressure value at 20mA or 5 Vdc of the PB3 transducer 0
-14
50.0
725
Bar
psi
Dec
int
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
CF 22
Pressure value at 4mA or 0.5 Vdc of the PB4 transducer 0
-14
50.0
725
Bar
psi
Dec
int
CF 23
Pressure value at 20mA or 5 Vdc of the PB4 transducer 0
-14
50.0
725
Bar
psi
Dec
int
Digital Inputs
CF 24
Configuration of ID1 0 C38
CF 25
Configuration of ID2 0 C38
CF 26
Configuration of ID3 0 C38
CF 27
Configuration of ID4 0 C38
CF 28
Configuration of ID5 0 C38
CF 29
Configuration of ID6 0 C38
CF 30
Configuration of ID7 0 C38
CF 31
Configuration of ID8 0 C38
CF 32
Configuration of ID9 0 C38
CF 33
Configuration of ID10 0 C38
CF 34
Configuration of ID11 0 C38
Relay Outputs
CF 35
Configuration of RL1 0 C36
CF 36
Configuration of RL2 0 C36
CF 37
Configuration of RL3 0 C36
CF 38
Configuration of RL4 0 C36
CF 39
Configuration of RL5 0 C36
CF 40
Configuration of RL6 0 C36
CF 41
Configuration of RL7 0 C36
CF 42
Configuration of RL8 0 C36
Proportional output
CF 43
OUT 1 configuration 0= Not enabled 1= 0..10V signal for compressor 1 inverter controlled 2= 0..10V signal for compressor 2 inverter controlled 3= 0..10V signal for auxiliary output 1 4= 0..10V signal for auxiliary output 1 5= 0..10V signal for geothermal function 6= 0..10V signal for condenser fan circuit 1 7= 0..10V signal for condenser fan circuit 2 8= 0..10V signal for modulating evaporator pump 9= 0..10V signal for modulating condenser pump o1 .. c26 signal to drive external relay
0
o 1
9
c26
CF 44
OUT 2 configuration 0= Not enabled 1= 0..10V signal for compressor 1 inverter controlled 2= 0..10V signal for compressor 2 inverter controlled 3= 0..10V signal for auxiliary output 1 4= 0..10V signal for auxiliary output 1 5= 0..10V signal for geothermal function 6= 0..10V signal for condenser fan circuit 1 7= 0..10V signal for condenser fan circuit 2 8= 0..10V signal for modulating evaporator pump 9= 0..10V signal for modulating condenser pump o1 .. c26 signal to drive external relay
0
o 1
9
c26
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
CF 45
OUT 3 configuration 0= Not enabled 1= 0..10V signal for compressor 1 inverter controlled 2= 0..10V signal for compressor 2 inverter controlled 3= 0..10V signal for auxiliary output 1 4= 0..10V signal for auxiliary output 1 5= 0..10V signal for geothermal function 6= 0..10V signal for condenser fan circuit 1 7= 0..10V signal for condenser fan circuit 2 8= PWM signal for condenser fan circuit 1 9= PWM signal for condenser fan circuit 2 o1 .. c26 signal to drive external relay
0
o 1
9
c26
CF 46
OUT 4 configuration 0= Not enabled 1= 0..10V signal for compressor 1 inverter controlled 2= 0..10V signal for compressor 2 inverter controlled 3= 0..10V signal for auxiliary output 1 4= 0..10V signal for auxiliary output 1 5= 0..10V signal for geothermal function 6= 0..10V signal for condenser fan circuit 1 7= 0..10V signal for condenser fan circuit 2 8= PWM signal for condenser fan circuit 1 9= PWM signal for condenser fan circuit 2 o1 .. c26 signal to drive external relay
0
o 1
9
c26
Remote keyboard
CF 47
Remote keyboard 1 configuration 0= Not enabled 1= with NTC temperature sensor on board 2= without NTC temperature sensor on board
0 2
CF 48
Remote keyboard 2 configuration 0= Not enabled 1= with NTC temperature sensor on board 2= without NTC temperature sensor on board
0 2
CF 49
Offset of the probe mounted on the remote keyboard 1 -12.0
-21
12.0 21
°C °F
Dec int
CF 50
Offset of probe mounted on the remote keyboard 2 -12.0
-21
12.0 21
°C °F
Dec int
Icon function
CF 51
Icon and keys for chiller and heat pump
0= chiller / heat pump
1= chiller / heat pump
0 1
Chiller / heat pump selection mode
CF 52
Chiller / heat pump selection 0= selection by keys on the keyboard 1= selection by digital input 2= selection by probe
0 2
Unit of measurement
CF 53
Unit of measurement 0= °C / °BAR 1= °F / °psi
0 1
Voltage frequency
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
CF 54
Power supply frequency 0= disabled 1= Frequency 50 Hz and only signalling alarm 2= Frequency 50 Hz and alarm (all output OFF in case of alarm) 3= Frequency 60 Hz and only signalling alarm 4= Frequency 60 Hz and alarm (all output OFF in case of alarm) (ATTENTION: if the condenser fan is not controlled by cut of phase signal (PWM) the parameter CF54 can be configured at 0 value and the frequency alarm is not enabled)
0 4
Serial Address
CF 55
Serial address 1 247
CF 56
Firmware Release (this parameter is only in reading)
CF 57
Eeprom parameter map (this parameter is only in reading)
Enabling compressors
CF 58
Enabling compressors 0= chiller and heat pump 1= only chiller 2= only heat pump
0 2
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
Dynamic Setpoint
Param eters
Description min max M. u. Resolu
tion
Sd 1
Maximum offset for dynamic setpoint function in chiller -30.0
-54
30.0 54
°C °F
Dec
int
Sd 2
Maximum offset for dynamic setpoint function in heat pump -30.0
-54
30.0 54
°C °F
Dec
int
Sd 3
Setpoint of outside temperature for dynamic setpoint function in chiller -50.0
-58
70.0
158
°C °F
Dec
int
Sd 4
Setpoint of outside temperature for dynamic setpoint function in heat pump
-50.0
-58
70.0
158
°C °F
Dec
int
Sd 5
Differential of outside temperature for dynamic setpoint function in chiller
-30.0
-54
30.0 54
°C °F
Dec
int
Sd 6
Differential of outside temperature for dynamic setpoint function in heat pump
-30.0
-54
30.0 54
°C °F
Dec
int
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
Energy saving
Param eters
Description min max udm Risolu
zione
ES 1
Start of the Time band 1 (0÷24) 0 24.00 Hr 10 Min
ES 2
End of the Time Band 1 (0÷24) 0 24.00 Hr 10 Min
ES 3
Start of the Time band 2 (0÷24) 0 24.00 Hr 10 Min
ES 4
End of the Time Band 2 (0÷24) 0 24.00 Hr 10 Min
ES 5
Start of the Time band 3 (0÷24) 0 24.00 Hr 10 Min
ES 6
End of the Time Band 3 (0÷24) 0 24.00 Hr 10 Min
ES 7
Monday: energy saving activated Automatic unit on-off
0 - 0 7 - 7
ES 8
Tuesday energy saving activated Automatic unit on-off
0 - 0 7 - 7
ES 9
Wednesday energy saving activated Automatic unit on-off
0 - 0 7 - 7
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
ES 10
Thursday energy saving activated Automatic unit on-off
0 - 0 7 - 7
ES 11
Friday energy saving activated Automatic unit on-off
0 - 0 7 - 7
ES 12
Saturday energy saving activated Automatic unit on-off
0 - 0 7 - 7
ES 13
Sunday energy saving activated Automatic unit on-off
0 - 0 7 - 7
ES 14
Offset for Energy Saving function in chiller mode -30.0
-54
30.0 54
°C °F
Dec
int
ES 15
Differential for Energy Saving function in chiller 0.1 1 25.0
45
°C °F
Dec
int
ES 16
Offeset for Energy Saving function in heat pump -30.0
-54
30.0 54
°C °F
Dec
int
ES 17
Differential for Energy Saving in heat pump 0.1 1 25.0
45
°C °F
Dec
int
ES 18
Maximum working time of the unit when switched on from keyboard (and the unit is OFF by Energy saving) 0= Not enabled
0 250 Min 10 Min
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
Compressors
Param eters
Description min max udm Risolu
zione
CO 1
Minimum compressor ON time after the start-up 0 250 10 sec 10 sec
CO 2
Minimum compressor OFF time after the switching off 0 250 10 sec 10 sec
CO 3
ON delay time between two compressors or compressor and valve.
1 250 Sec
CO 4
OFF delay time between two compressors or compressor and valve 0 250 Sec
CO 5
Delay time to activate the thermoregulation starting from the power on 0 250 10 Sec 10 sec
Partialization (Capacity Control)
CO 6
Functioning (see Capacity Control) 0= On/off steps 1= Continuous insertion of the steps and direct action 2= Continuous insertion of the steps and reverse action 3= Continuous insertion of the steps
0 3
CO 7
Start-up with minimum compressor power / automatic start-unloading valve 0 = Only at the compressor start-up (Minimum power automatic start­unloading valve off) 1= At the compressor start-up and during the termoregulation (Minimum power / automatic start-unloading valve off) 2 = Only at the screw compressor start-up (Minimum power automatic start-unloading valve off) 3= At the compressor start-up and during the termoregulation (Minimum power / Unloading valve ON with compressor off)
0 3
CO 8
ON time of the intermittent solenoid valve for screw compressor 0= the function is not enabled
0 250 Sec
CO 9
OFF time of the inetrmittent solenoid valve for screw compressor 0 250 Sec
Compressor start-up
CO 10
Compressor start-up selection 0= Direct 1= Part - winding
0 1
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
CO 11
Part - winding start-up time. To change the time delay between the activation of two contactors of the two compressor circuits
0 100 Sec/10 0.1 sec
CO 12
By-pass gas valve start-up time / automatic start-unloading valve (capacity step control)
0 250 sec
Rotating – Balancing – Compressors Thermoregulation
CO 13
Compressor rotation (See compressor rotation) 0 = Sequential 1 = Compressors rotation based on time running hours 2 = Compressors rotation based on number of starts-up
0 2
CO 14
Circuit balancing (See Circuit balancing) 0= Circuit saturation 1= Circuit balancing
0 1
Evaporator water pump / supply fan
CO 15
Operative mode of the evaporator pump / supply fan 0= Not enabled (evaporator pump or supply fan). 1= ON/OFF: continuous operation type 1 When the unit is running in Chiller or Heat Pump the pump or the supply fan is running. In std-by or remote OFF mode, the pump is OFF. 2= ON/OFF: on if called by compressor When a compressor is running, the pump or the supply fan is running. 3= ON/OFF: continuous operation type 2 When the unit is running in Chiller or Heat Pump or in STD-By or in OFF, the pump or the supply fan is running. 4= Modulation: continuous operation type 1 When the unit is running in Chiller or Heat Pump the pump or the supply fan is running. In std-by or remote OFF mode, the pump is OFF. 5= Modulation: on if called by compressor When a compressor is running, the pump or the supply fan is running. 6= Modulation: continuous operation type 2 When the unit is running in Chiller or Heat Pump or in STD-By or in OFF, the pump or the supply fan is running.
0 6
CO 16
ON compressor delay after water pump / supply fan start-up 1 250 10 sec 10 sec
CO 17
OFF delay evaporator water pump / supply fan after compressor switching OFF. This delay is also active when the unit is turned in stand-by
0 250 Min
CO 18
Number of running hours for evaporator pump rotation 0 999 10Hr 10Hr
CO 19
Contemporary working time of the pumps during rotation 0 250 Sec
Condenser water pump
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
CO 20
Operative mode of the condenser pump 0= Not enabled 1= ON/OFF: continuous operation type 1 When the unit is running in Chiller or Heat Pump the pump is running. In std-by or remote OFF mode, the pump is OFF. 2= ON/OFF: on if called by compressor When a compressor is running, the pump is running. 3= ON/OFF: continuous operation type 2 When the unit is running in Chiller or Heat Pump or in STD-By or in OFF, the pump is running. 4= Modulation: continuous operation type 1 When the unit is running in Chiller or Heat Pump the pump is running. In std-by or remote OFF mode, the pump is OFF. 5= Modulation: on if called by compressor When a compressor is running, the pump is running. 6= Modulation: continuous operation type 2 When the unit is running in Chiller or Heat Pump or in STD-By or in OFF, the pump is running.
0 6
CO 21
Delay time to switch off the pump starting from compressor deactivation or when the unit is placed in std-by
0 250 Min
CO 22
Number of running hours for condenser pump rotation 0 999 10Hr 10Hr
CO 23
Contemporary working time of the pumps during rotation 0 250 Sec
Load maintenance
CO 24
Compressor 1: number of working hour to signalling maintenance warning
0 999 10 Hr 10 Hr
CO 25
Compressor 2: number of working hour to signalling maintenance warning
0 999 10 Hr 10 Hr
CO 26
Evaporator pump / supply fan: number of working hour to signalling maintenance warning
0 999 10 Hr 10 Hr
CO 27
Support evaporator pump / supply fan: number of working hour to signalling maintenance warning
0 999 10 Hr 10 Hr
CO 28
Condenser pump: number of working hour to signalling maintenance warning
0 999 10 Hr 10 Hr
CO 29
Support condenser pump: number of working hour to signalling maintenance warning
0 999 10 Hr 10 Hr
Pump down
CO 30
Pump down operating mode (See pump down ON/OFF function) 0= Not enabled 1= Pump down enabled only during the switching off 2= Pump down enabled during the switching off and switching on 3= in Chiller mode pump down enabled only during the switching off 4= in Chiller mode pump down enabled during the switching off and switching on
0 4
CO 31
Pump–down pressure setpoint (See pump down ON/OFF function) 0 0 50.0
725
Bar
psi
Dec
int
CO 32
Pump-down pressure differential (See pump down ON/OFF function) 0 0 14.0
203
Bar
psi
Dec
int
CO 33
Maximum pump–down time duration at start-up and stop (See pump down ON/OFF function)
0 250 Sec
Evaporator Unloading
CO 34
Unloading compressor setpoint in chiller to prevent high temperature of the evaporator water inlet (See unloading function).
-50
-58
70.0
158
°C °F
Dec
int
CO 35
Unloading Differential. From high temperature of the evaporator water inlet (See unloading function).
0.1 1 25.0 45
°C °F
Dec
int
CO 36
Delay time to engage the Unloading function from high temperature of the evaporator water inlet (See unloading function).
0 250 Sec 10sec
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
CO 37
Maximum unloading duration time to keep activated the Unloading function from high temperature of the evaporator water inlet (See unloading function).
0 250 Min
CO 38
Unloading compressor setpoint in chiller to prevent low temperature of the evaporator water inlet (See unloading function).
-50
-58
70.0 158
°C °F
Dec
int
CO 39
Unloading Differential to prevent low temperature of the evaporator water inlet (See unloading function).
0.1 1 25.0 45
°C °F
Dec
int
CO 40
Maximum unloading duration time to keep activated the Unloading function from low temperature of the evaporator water inlet (See unloading function).
0 250 Min
Condenser Unloading
CO 41
Unloading compressor setpoint. From temperature / pressure in chiller mode (See unloading function).
0 0 50.0
725
Bar
psi
Dec
int
CO 42
Unloading Differential. From temperature / pressure in chiller mode (See unloading function).
0.0 0 14.0
203
Bar
Psi
Dec
int
CO 43
Unloading compressor setpoint. From temperature / pressure in HP mode (See unloading function).
0 0 50.0
725
Bar
psi
Dec
int
CO 44
Unloading Differential. From temperature / pressure in HP mode (See unloading function).
0.0 0 14.0
203
Bar
Psi
Dec
int
CO 45
Maximum unloading duration time from temperature/pressure control. 0 250 Min
CO 46
Number of steps for circuit with active unloading 1= 1st step 2= 2nd step 3= 3rd step
1 3
CO 47
Minimum ON time of the capacity step after the unloading function start (only for capacity compressor)
0 250 Sec
Compressor liquid injection
CO 48
Setpoint of the solenoid valve (on) of the liquid injection
0
32
150 302
°C °F
Dec /
int int
CO 49
Setpoint of the solenoid valve (off) of the liquid injection 0.1 1 25.0
45
°C °F
Dec
int
Load management in neutral zone
CO 50
Maximum working time in neutral zone without steps insertion 0 250 Min 10 Min
CO 51
Maximum working time in neutral zone without steps rotation 0 999 Hr 1Hr
Pump down to time
CO 52
Maximum time for the activation of the pump-down during the switching off CO58 = 0 Not enabled
0 250 Sec
CO 53
Maximum time for the activation of the pump-down during the switching on CO59 = 0 Not enabled
0 250 Sec
Compressor inverter controlled
CO 54
Time at maximum speed during compressor start up
0 250 sec
CO 55
Minimum value of the proportional output at compressor start up
0 100 %
CO 56
Minimum interval time of the capacity variation at compressor start up 1 250 sec
CO 57
Value under wich starts counting time CO58 0 100 %
CO 58
Maximum working time of the compressor with percentage lower than CO57
0 250 Min 10 Min
CO 59
Time of forcing the compressor digital scroll to the maximum power
0 250 sec 10sec
CO 60
Maximum working time for compressors rotation
0 999 Hr 1Hr
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
CO 61
Minimum value of the proportional output digital scroll 0÷10V compressor 1
0 CO62 %
CO 62
Maximum value of the proportional output digital scroll 0÷10V compressor 1
CO61 100 %
CO 63
Minimum value of the proportional output digital scroll 0÷10V compressor 2
0 CO64 %
CO 64
Maximum value of the proportional output digital scroll 0÷10V compressor 2
CO63 100 %
CO 65
Minimum interval time of the capacity variation
1 250 sec
Tandem function
CO 66
Maximum working time for compressors rotation 0 250 Min
Solenoid valve water side
CO 67
Delay time for compressor activation starting from solenoid valve activation
0 250 Min
CO 68
Delay time for solenoid valve deactivation starting from compressor deactivation
0 250 Min
Unbalanced compressors
CO 69
Compressor 1 weight 0 100 %
CO 70
Compressor 2 weight 0 100 %
CO 71
Maximum numbers of start up per hour 0= function disabled
0 60
Modulating evaporator water pump
CO 72
Probe selection (Pb1..Pb6) for modulating evaporator water pump in chiller
0 6
CO 73
Probe selection (Pb1..Pb6) for modulating evaporator water pump in heat pump
0 6
CO 74
Set point for modulating evaporator water pump in chiller -50.0
-58
0 0
70.0 158
50.0 725
°C
°F
Bar
Psi
Dec
Int
Dec
int
CO 75
Proportional band for modulating evaporator water pump in chiller 0.1
1
0.1 1
25.0 45
14.0
203
°C
°F
Bar
Psi
Dec
Int
Dec
int
CO 76
Set point for modulating evaporator water pump in heat pump -50.0
-58 0 0
70.0 158
50.0 725
°C
°F
Bar
Psi
Dec
Int
Dec
int
CO 77
Proportional band for modulating evaporator water pump in heat pump
0.1 1
0.1 1
25.0 45
14.0
203
°C
°F
Bar
Psi
Dec
Int
Dec
int
CO 78
Minimun value of the signal for the modulation of the pump
0
CO
79
%
CO 79
Maximun value of the signal for the modulation of the pump CO
78
100 %
CO 80
Time at maximum speed when the pump is activated 0 250 sec
CO 81
Value of the signal when the compressor is OFF or when the unit is in STD-BY or remote OFF
0 100 %
CO 82
Time at maximum speed during the switching off of the pump 0 250 sec
Modulating condenser water pump
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
CO 83
Probe selection (Pb1..Pb6) for modulating condenser water pump in chiller
0 6
CO 84
Probe selection (Pb1..Pb6) for modulating condenser water pump in heat pump
0 6
CO 85
Set point for modulating condenser water pump in chiller -50.0
-58 0 0
70.0 158
50.0 725
°C Int
Dec
int
CO 86
Proportional band for modulating condenser water pump in chiller 0.1
1
0.1 1
25.0 45
14.0
203
°C Int
Dec
int
CO 87
Set point for modulating condenser water pump in heat pump -50.0
-58 0 0
70.0 158
50.0 725
°C Int
Dec
int
CO 88
Proportional band for modulating condenser water pump in heat pump
0.1 1
0.1 1
25.0 45
14.0
203
°C Int
Dec
int
CO 89
Minimun value of the signal for the modulation of the pump 0 CO90 %
CO 90
Maximun value of the signal for the modulation of the pump CO89 100 %
CO 91
Time at maximum speed when the pump is activated 0 250 sec
CO 92
Value of the signal when the compressor is OFF or when the unit is in STD-BY or remote OFF
0 100 %
CO 93
Time at maximum speed during the switching off of the pump 0 250 sec
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
Auxiliary relay
Param eters
Description min max M. U. Resolu
tion
Auxiliary relay of the circuit 1
US 1
Auxiliary relay 1 operating mode 0= Not enabled 1= Always available with direct action 2= Available only when the unit is on with direct action 3= Always available with reverse action 4= Available only when the unit is on with reverse action
0 4
US 2
Probe selection for auxiliary relay 1 control. Allows to select which probe Pb1..Pb6 controls the relay
1 6
US 3
Auxiliary relay 1 setpoint
-50.0
-58
0.0 0
70.0 158
50.0 725
°C °F
Bar
Psi
Dec
int
Dec
int
US 4
Auxiliary relay 1 differential
0.1 1
0.0 0
25.0 45
14.0
203
°C °F
Bar
Psi
Dec
int
Dec
int
Auxiliary relay circuit 2
US 5
Auxiliary relay 2 operating mode 0= Not enabled 1= Always available with direct action 2= Available only when the unit is on with direct action 3= Always available with reverse action 4= Available only when the unit is on with reverse action
0 4
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
US 6
Probe selection for for auxiliary relay 2 control. Allows to select which probe value Pb1..Pb6 controls the relay
1 6
US 7
Auxiliary relay 2 setpoint
-50.0
-58
0.0 0
70.0 158
50.0 725
°C °F
Bar
Psi
Dec
int
Dec
int
US 8
Auxiliary relay 2 differential
0.1 1
0.0 0
25.0 45
14.0
203
°C °F
Bar
Psi
Dec
int
Dec
int
Auxiliary proportional output n° 1
US 9
Auxiliary proportional output n° 1 operating mode 0= Not enabled 1= Always available with direct action 2= Available only when the unit is on with direct action 3= Always available with reverse action 4= Available only when the unit is on with reverse action
0 4
US 10
Probe selection for auxiliary proportional output 1 Allows to select which probe value Pb1..Pb6 controls output
1 6
US 11
Minimum value of the auxiliary proportional output 1
0 US12
%
US 12
Maximum value of the auxiliary proportional output 1
US11 100 %
US 13
Auxiliary proportional output 1 setpoint
-50.0
-58
0.0 0
70.0 158
50.0 725
°C °F
Bar
Psi
Dec
int
Dec
int
US 14
Auxiliary proportional output 1 differential
0.1 1
0.0 0
25.0 45
14.0
203
°C °F
Bar
Psi
Dec
int
Dec
int
Auxiliary proportional output n° 2
US 15
Auxiliary proportional output n° 2 operating mode 0= Not enabled 1= Always available with direct action 2= Available only when the unit is on with direct action 3= Always available with reverse action 4= Available only when the unit is on with reverse action
0 4
US 16
Probe selection for auxiliary proportional output 2 Allows to select which probe value Pb1..Pb10 controls output
1 6
US 17
Minimum value proportional output 2
0 US18
%
US 18
Maximum value proportional output 2
US17 100 %
US 19
Auxiliary setpoint proportional output 2
-50.0
-58
0.0 0
70.0 158
50.0 725
°C °F
Bar
Psi
Dec
int
Dec
int
US 20
Differenzential proportional output 2
0.1 1
0.0 0
25.0 45
14.0
203
°C °F
Bar
Psi
Dec
int
Dec
int
Geothermal function
US 21
Geothermal function activation 0= only in chiller 1= only in heat pump 2= chiller and heat pump
0 2
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
US 22
Temperature to activate geothermal function 0.1
1
0.0 0
25.0 45
14.0
203
°C °F
Bar
Psi
Dec
int
Dec
int
US 23
Differential to deactivate geothermal function
0.1 1
0.0 0
25.0 45
14.0
203
°C °F
Bar
Psi
Dec
int
Dec
int
US 24
Time to activate/deactivate geothermal function
0 250 sec
US 25
Probe 1 selection (Pb1..Pb6) for geothermal function 0 6
US 26
Probe 2 selection (Pb1..Pb6) for geothermal function 0 6
US 27
Probes configuration for geothermal function 0= Probe 1 for geothermal function – probe 2 for geothermal function 1= Probe 2 for geothermal function – probe 1 for geothermal function
0 1
US 28
Geothermal function set point -50.0
-58 0 0
70.0 158
50.0 725
°C °F
Bar
Psi
Dec
int
Dec
int
US 29
Geothermal function differential
0.1 1
0.0 0
25.0 45
14.0
203
°C °F
Bar
Psi
Dec
int
Dec
int
US 30
Direct / reverse action for geothermal function 0= direct action 1= reverse action
0 1
US 31
Minimum value for geothermal function 0 US32
%
US 32
Maximum value for geothermal function US31 100 %
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
Condenser fan
Param eters
Description min max M. U. Resolu
tion
FA 1
Fan configuration output 0 = Not enabled 1 = Always on 2 = ON/OFF regulation with steps 3 = ON/OFF Continuous regulation 4 = Proportional speed control
0 4
FA 2
Fan operating mode 0= Dependent from the compressor 1= Independent from the compressor
0 1
FA 3
Operation time at maximun speed when the fans start 0 250 Sec
FA 4
Phase shifting of the fan motor
0 8
Micro
Sec
250µs
FA 5
Number of condensing circuits 0= one condenser circuit 1= two condenser circuits
0 1
FA 6
Pre-ventilation time before turning on the compressor in chiller mode 0 250 Sec
Fan in Chiller mode
FA 7
Minimum speed for condenser fan in Chiller mode. To set the minimum fan speed percentage value (30..100%), it is related to the fan power supply.
30 100 %
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
FA 8
Maximum speed for condenser fan in Chiller mode. To set the maximim fan speed percentage value (30..100%), it is related to the fan power supply.
30 100 %
FA 9 Proportional speed control FA01 = 4
Temperature or pressure limit to enable the minimum speed FA 7
ON/OFF regulation FA01 = 2 / 3
SETpoint step n° 1
-50.0
-58
0.0 0
70.0 158
50.0 725
°C °F
Bar
Psi
Dec
int
Dec
int
FA 10 Proportional speed control FA01 = 4
Temperature or pressure limit to enable the maximum speed FA 8
ON/OFF regulation FA01 = 2 / 3
SETpoint step n° 2
-50.0
-58
0.0 0
70.0 158
50.0 725
°C °F
Bar
Psi
Dec
int
Dec
int
FA 11 Proportional speed control FA01 = 4
Proportional band for condenser fan control in chiller To set the temperature/pressure differential between the minimum and the maximum of the fan speed regulation.
ON/OFF regulation FA01 = 2 / 3
Differential step circuit n° 1
0.1 1
0.0 0
25.0 45
14.0
203
°C °F
Bar
Psi
Dec
int
Dec
int
FA 12 Proportional speed control FA01 = 4
CUT-OFF differential in chiller. To set a temperature/pressure differential to stop the fan.
ON/OFF regulation FA01 = 2 / 3
Differential step circuit n° 2
0.1 1
0.0 0
25.0 45
14.0
203
°C °F
Bar
Psi
Dec
int
Dec
int
FA 13
Over ride CUT- OFF in chiller. To set a temperature/pressure differential to keep the minimum fan speed.
0.1 1
0.0 0
25.0 45
14.0
203
°C °F
Bar
Psi
Dec
int
Dec
int
FA 14
CUT-OFF time delay. To set a time delay before activating the CUT-OFF function after the fan start-up. If after the compressor start-up the proportional regulator requires to turn off the fan (cut-off) and FA140, the fan is on at the minimum speed for the time set in this parameter. If FA14=0 the function is disabled.
0 250 Sec
FA 15
Night speed in chiller. To set the maximum fan speed percentage value (30..100%), it is related to the fan power supply.
30 100 %
Fan in Heat pump mode
FA 16
Minimum speed for condenser fan in Heat Pump mode. To set the minimum fan speed percentage value (30..100%), it is related to the fan power supply.
30 100 %
FA 17
Maximum speed for condenser fan in Heat Pump mode. To set the maximum fan speed percentage value (30..100%), it is related to the fan power supply.
30 100 %
FA 18 Proportional speed control FA01 = 4
Temperature or pressure limit to enable the minimum speed FA16
ON/OFF regulation FA01 = 2/3
SETpoint step n° 1
-50.0
-58
0.0 0
70.0 158
50.0 725
°C °F
Bar
Psi
Dec
int
Dec
int
FA 19 Proportional speed control FA01 = 4
Temperature or pressure limit to enable the maximum speed FA17
ON/OFF regulation FA01 = 2/3
SETpoint step n° 2
-50.0
-58
0.0 0
70.0 158
50.0 725
°C °F
Bar
Psi
Dec
int
Dec
int
FA 20 Proportional speed control FA01 = 4
Proportional band for condenser fan control in heat pump To set the temperature/pressure differential between the minimum and the maximum of the fan speed regulation.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 1
0.1 1
0.0 0
25.0 45
14.0
203
°C °F
Bar
Psi
Dec
int
Dec
int
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
FA 21 Proportional speed control FA01 = 4
CUT-OFF differential in heat pump. To set a temperature/pressure differential to stop the fan.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 2
0.1 1
0.0 0
25.0 45
14.0
203
°C °F
Bar
Psi
Dec
int
Dec
int
FA 22
Over ride CUT- OFF in Heat pump. To set a temperature/pressure differential to keep the minimum fan speed.
0.1 1
0.0 0
25.0 45
14.0
203
°C °F
Bar
Psi
Dec
int
Dec
int
FA 23
Night speed in Heat pump. To set the maximum fan speed percentage value (30..100%), it is related to the fan power supply.
30 100 %
Hot start
FA 24
Hot start setpoint 50.0
-58
70.0
158
°C °F
Dec
int
FA 25
Hot start differential 0.0 0 25.0
45
°C °F
Dec
int
3 step condenser Fan in Chiller mode
FA 26 ON/OFF regulation FA01 = 2/3
SETpoint step n° 3
50.0
-58
0.0 0
70.0 158
50.0 725
°C °F
Bar
Psi
Dec
int
Dec
int
3 4 step condenser Fan in heat pump
FA 27 ON/OFF regulation FA01 = 2/3
SETpoint step n° 3
50.0
-58
0.0 0
70.0 158
50.0 725
°C °F
Bar
Psi
Dec
int
Dec
int
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
Antifreeze heaters – Integration heating - boiler
Param eter
Description min max m. u. Risolu
zione
Ar 1
Anti-freeze heaters/integration heating setpoint for air/air unit in Chiller mode. To set a temperature value, below this value the anti-freeze relay is activated.
50.0
-58
70.0 158
°C °F
Dec
int
Ar 2
Regulation band for antifreeze in Chiller mode.
0.1 0 25.0 45
°C °F
Dec
Int
Ar 3
Set Anti-freeze heaters/integration heating setpoint for air/air unit in HP mode. To set a temperature value, below this value the anti-freeze relay is activated.
50.0
-58
70.0 158
°C °F
Dec
int
Ar 4
Regulation band for antifreeze in Heat Pump mode 0.1 0 25.0
45
°C °F
Dec
int
Ar 5
Antifreeze heaters / integration heating in defrost 0= ON only with thermoregulation control 1= ON with thermoregulation and during the defrosting cycle
0 1
Ar 6
Probe selection for antifreeze heaters / integration heating in Chiller mode 0= Not enabled 1= Evaporator inlet 2= Evaporator outlet 1 and 2 3= Evaporator outlet 1 and 2 and common outlet
0 3
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Ar 7
Probe selection for antifreeze heaters / integration heating in Heat Pump mode 0= Not enabled 1= Evaporator inlet. 2= Evaporator outlet 1 and 2. 3= Evaporator outlet 1 and 2 and common outlet.
0 3
Ar 8
Thermoregulation probe for anti-freeze / condenser heaters. 0= not enabled. 1= Condenser common water inlet probe. 2= Condenser common water inlet and condenser inlet 1 / 2 probe. 3= Condenser water outlet 1 / 2 probe. 4= Condenser water outlet 1 / 2 and common outlet.
0 4
Ar 9
Anti-freeze heaters control with unit in remote OFF or stand-by mode: 0= Control not enable 1=Controlled by anti-freeze thermoregulation.
0 1
Ar 10
Anti-freeze heaters control for condenser/evaporator faulty probe: 0= Anti-freeze heaters OFF 1= Anti-freeze heaters ON
0 1
Boiler function
Ar 11
Boiler function 0=Not enabled 1=Enabled for integration heating 2= Enabled for heating
0 2
Ar 12
External air temperaure setpoint for boiler heaters -50.0
-58
70.0 158
°C °F
Dec
int
Ar 13
Temperature differential for boiler heaters 0 0 25.0
45
°C °F
Dec
int
Ar 14
Time delay before turning the boiler on 0 250 Min
Boiler function in Chiller mode
Ar 15
Setpoint for boiler heaters in chiller 50.0
-58
70.0 158
°C °F
Dec
int
Ar 16
Proportional band for boiler heaters in chiller 0.1 0 25.0
45
°C °F
Dec
int
Boiler function in heat pump
Ar 17
Setpoint for boiler heaters in Heat Pump 50.0
-58
70.0 158
°C °F
Dec
int
Ar 18
Proportional band for boiler heaters in Heat Pump 0.1 0 25.0
45
°C °F
Dec
int
Ar 19
External air setpoint to stop the compressor as integration function 50.0
-58
70.0 158
°C °F
Dec
int
Ar 20
External air differential to stop the compressor as integration function 0.1 0 25.0
45
°C °F
Dec
int
Water pumps on OFF or STD-BY
Ar 21
Water pump in OFF/ stand-by 0= Aways in OFF 1= ON only with antifreeze thermoregulation control
0 1
Ar 22
Termoregulation probe water pump in antifreeze mode 0= Not enabled 1= Evaporator inlet 2= Evaporator outlet 1 and 2 3= Evaporator outlet 1 and 2 and common outlet 4= External temperature
0 4
Ar 23
Set point for water pump activation
-50.0
-58
70.0 158
°C °F
Dec
int
Ar 24
Differential for water pump deactivation 0.1 1 25.0
45
°C °F
Dec
int
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
Defrost
Param eter
Description min max udm Risolu
zione
dF 1
Defrost configuration: 0= Not enabled 1= Temperature / pressure 2= start depends on par. dF24 stop for time duration 3= start depends on par. dF24 stop for external contact 4= defrost with condenser fan
0 4
dF 2
Temperature or pressure of the defrost start-up
-50.0
-58
0.0 0
70.0 158
50.0 725
°C °F
bar
psi
Dec
int
Dec
Int
dF 3
Temperature or pressure of the defrost stop -50.0
-58
0.0 0
70.0 158
50.0 725
°C °F
bar
psi
Dec
int
Dec
Int
dF 4
Minimum defrost duration 0 250 Sec
dF 5
Maximum defrost duration 1 250 Min
dF 6
Time delay between the defrost of two circuits 0 250 Min
dF 7
OFF compressor delay before the defrost 0 250 Sec
dF 8
OFF compressor delay after the defrost 0 250 Sec
dF 9
Defrost interval time of the same circuit 1 99 Min
dF 10
Temperature setpoint for combined defrost of the 1
st
circuit after
parameter DF10 counting
-50.0
-58
70.0 158
°C °F
Dec
int
dF 11
Temperature setpoint for combined defrost end of the 1
st
circuit. -50.0
-58
70.0 158
°C °F
Dec
int
dF 12
Temperature setpoint for combined defrost of the 2
nd
circuit after
parameter DF10 counting
-50.0
-58
70.0 158
°C °F
Dec
int
dF 13
Temperature setpoint for combined defrost end of the 2
nd
circuit -50.0
-58
70.0 158
°C °F
Dec
int
dF 14
Activation of all the steps of the 1
st
circuit during the defrost 0= Not enabled 1= Enabled
0 1
dF 15
Activation of all the steps of the 2
nd
circuit during the defrost 0= Not enabled 1= Enabled
0 1
dF 16
Delay between two compressor activation in defrost (compressors of the same circuit)
0 250 Sec
dF 17
Fan control during defrost / dripping time 0= Not enabled 1= Only in defrost 2= For both functions defrost / dripping time
0 2
dF 18
Pressure / temperature setpoint to force the ventilation ON during the defrost.
-50.0
-58
0.0 0
70.0 158
50.0 725
°C °F
bar
psi
Dec
int
Dec
Int
Forced defrost
dF 19
Minimum time delay before a forced defrost 0 250 sec
dF 20
Pressure / temperature setpoint for a forced defrost -50.0
-58
0.0 0
70.0 158
50.0 725
°C °F
bar
psi
Dec
int
Dec
int
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
dF 21
Forced defrost differential 0.1
1
0.0 0
25.0 45
14.0
203
°C °F
Bar
Psi
Dec
int
Dec
int
Defrost operative mode
dF 22
Defrost start-up in unit with 2 circuits 0= Independent 1= If both have reached the necessary requirements 2= If one has reached the necessary requirements
0 2
dF 23
End defrost in unit with 2 circuits and common ventilation 0= Independent 1= If both have reached the necessary end defrost requirements 2= If one has reached the necessary end defrost requirements
0 2
Start / stop defrost from analog input
Param eters
description min max udm resolut
ion
dF 24
Start / stop defrost probe 0= start and stop with condenser temperature / pressure probe 1= start with evaporator pressure probe / stop with condenser temperature / pressure probe 2= start with condenser temperature / pressure probe / stop with evaporator pressure probe 3= start and stop with evaporator pressure probe
0 3
Supply fan functioning during defrost cycle
dF 25
Set point to enable defrost with condenser fan
-50.0
-58
70.0
158
°C °F
Dec
int
Defrost with condenser fan
dF 26
Supply fan status during the defrost cycle 0= Enabled 1= Not enabled
0 1
Minimum temperature water outlet during defrost
dF 27
Probe selection for minimum temperature outlet during defrost 0 6
dF 28
Set point for minimum temperature outlet during defrost
-50.0
-58
0.0 0
70.0 158
50.0 725
°C °F
bar
psi
Dec
int
Dec
int
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
Alarms
Param eters
Description min max m. u. Resolu
tion
Low alarm
AL 1
Low pressure alarm delay from analog and digital input 0 250 Sec
AL 2
Low pressure alarm delay if the low pressure switch is used for the pump down. AL02= 0 low pressure alarm not enable during compressor switching off from pump down and if compressor OFF AL02 0 low pressure alarm enable after AL02 (starting from compressor switch off) time with compressor OFF
0 250 Sec 10 Sec
AL 3
Low pressure alarm setpoint from analogue input -50.0
-58
0.0 0
70.0 158
50.0 725
°C °F
bar
psi
Dec
int
Dec
int
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
AL 4
Low pressure alarm differential from analogue input 0.1
1
0.0 0
25.0 45
14.0
203
°C °F
bar
psi
Dec
int
Dec
Int
AL 5
Maximum number of low pressure events from digital/analogue inputs: Always manual reset if AL05 = 0 Always automatic reset if AL05 =16 From automatic to manual reset if AL05= 1..15
0 16
AL 6
Low temperature/pressure alarm during defrost 0= Not enabled 1= Enabled
0 1
AL 7
Low temperature/pressure alarm delay during defrost 0 250 Sec
AL 8
Low temperature/pressure alarm with unit in OFF or stand – by: 0 = Not enabled 1= Alarm enabled
0 1
High Alarm
AL 9
High temperature/pressure alarm from analogue input -50.0
-58
0.0 0
70.0 158
50.0 725
°C °F
bar
psi
Dec
int
Dec
int
AL 10
High temperature/pressure alarm differential from analogue input 0.1
1
0.0 0
25.0 45
14.0
203
°C °F
bar
psi
Dec
int
Dec
int
Oil Alarm
AL 11
Low oil pressure / level delay from digital input 0 250 Sec
AL 12
Minimum time for low oil pressure / level from digital input activation in normal working condition.
0 250 Sec
AL 13
Maximum number of low oil pressure/level events: Always manual reset if AL13= 0 Always automatic reset if AL13 =16 From automatic to manual reset if AL13 = 1..15
0 16
AL 14
Low oil pressure / oil level when the compressor is OFF 0= alarm disabled 1= alarm enabled
0 1
Condenser Flow alarm
AL 15
Condenser water flow configuration 0= Not enabled 1= Enabled only in chiller mode 2= Enabled only in heat pump mode 3= Enabled in chiller and heat pump mode
0 3
AL 16
Condenser flow switch delay after pump activation 0 250 Sec
AL 17
Flow switch activation time to generate the manual condenser flow alarm
0 250 Sec
AL 18
Flow switch activation time to generate the automatic condenser flow alarm
0 250 Sec
AL 19
Flow switch deactivation time to reset the condenser flow alarm 0 250 Sec
Evaporator Flow alarm
AL 20
“Evaporator flow switch / supply fan overload” delay after pump activation
0 250 Sec
AL 21
Flow switch activation time to generate the manual evaporator flow alarm
0 250 Sec
AL 22
“Evaporator flow switch / supply fan overload” activation time to generate the automatic alarm
0 250 Sec
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
AL 23
“Evaporator flow switch / supply fan overload” deactivation time to reset the alarm
0 250 Sec
Compressor overload alarm
AL 24
Compressor overload alarm delay after compressor start-up 0 250 Sec
AL 25
Maximum number of compressor overload alarm per hour Always manual reset if AL20 = 0 Always automatic reset if AL20 =16 From automatic to manual reset if AL20 =1..15
0 16
AL 26
Enable compressor overload if compressor is deactivated 0= compressor overload alarm disabled 1= compressor overload alarm enabled
0 1
AL 27
Compressor overload alarm operation 0= swith off only the compressor 1= switch off the circuit
0 1
Pump down alarm
AL 28
Maximum number of pump down alarm events per hour in stop condition. After this number the alarm is logged, displayed and signalled with alarm relay + buzzer. Always manual reset if AL28 = 0 Always automatic reset if AL28 =16 From automatic to manual reset if AL28 =1..15
0 16
AL 29
Maximum number of pump down alarm events per hour in start-up condition. After this number the alarm is logged, displayed and signalled with alarm relay + buzzer. Always manual reset if AL29 = 0 Always automatic reset if AL29 =16 From automatic to manual reset if AL29 =1..15 and parameter AL30 config.
0 16
AL 30
Select if the pump down alarm must change from automatic to manual reset: 0= Always automatic reset 1= Manual reset after AL29 alarm events
0 1
Anti-freeze alarm in Chiller mode
AL 31
Minimum antifreeze setpoint in chiller -50.0
-22
AL32
°C °F
Dec
int
AL 32
Maximum antifreeze setpoint in chiller
AL31
70.0
158
°C °F
Dec
int
AL 33
“Antifreeze / low ambient temperature (air / air unit) / low temperature air outlet (air/air)” alarm setpoint temperature
AL31 AL32 °C/°F Dec/int
AL 34
“Antifreeze / low ambient temperature (air / air unit) / low temperature air outlet (air/air)” alarm differential temperature
0.1 1 25.0 45
°C °F
Dec
int
AL 35
Alarm delay for anti-freeze, low ambient air temperature or low outlet air temperature
0 250 Sec
AL 36
Maximum number anti-freeze, low ambient air temperature or low outlet air temperature alarm in chiller Always manual reset if AL36 = 0 Always automatic reset if AL36 = 16 From automatic to manual if AL36 = 1. .15
0 16
AL 37
Anti-freeze alarm configuration in chiller 0= when the antifreeze alarm is activated the compressors are switched off; the display shows the alarm label, the buzzer and alarm relay are not activated 1= when the antifreeze alarm is activated the compressors are switched off; the display shows the alarm label, the buzzer and alarm relay are activated, the antifreeze heathers are acivated
0 1
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
AL 38
Probe selection for antifreeze alarm in chiller mode 0= disabled 1= evaporator inlet temperature 2= evaporator 1 / 2 outlet temperature 3= evaporator 1 / 2 outlet temperature and common outlet temperature 4= external air temperature
0 4
AL 39
Probe selection for condenser antifreeze alarm 0= disabled 1= condenser common inlet temperature 2= condenser 1 / 2 inlet temperature and common inlet temperature 3= condenser 1 / 2 outlet temperature 4= condenser 1 / 2 outlet temperature and common outlet temperature
0 4
Anti-freeze alarm in Heat pump mode
AL 40
Minimum limit of the setpoint in heat pump mode -50.0
-58
AL39
°C °F
Dec
int
AL 41
Maximum limit of the setpoint in heat pump mode
AL38
70.0 158
°C °F
Dec
int
AL 42
Anti-freeze alarm setpoint in heat pump Setpoint temperature for low anti-freeze alarm, low ambient temperature (air/air), low temperature air outlet (air/air)
AL31 AL32 °C/°F Dec/int
AL 43
Differential of anti freeze alarm in heat pump mode. To reset the anti­freeze, low ambient Temperature (air/air), low temperature air outlet (air/air) alarms.
0.1 1 25.0 45
°C °F
Dec
int
AL 44
Antifreeze alarm delay (low outlet temperature for air/air unit) at the stert up in heat pump mode
0 250 Sec
AL 45
Anti-freeze alarm delay for low air ambient temperature or low outlet air temperature in heat pump normal condition.
0 250 Sec
AL 46
Maximum number of anti-freeze alarm events for low air ambient temperature or low outlet air temperature in heat pump. It sets the alarm reset condition: Always manual reset AL46 = 0 Always automatic reset AL46 = 16 From automatic to manual reset if AL46 = 1..15
0 16
AL 47
Anti-freeze alarm configuration in heat pump 0= to turn the compressors off when the anti-freeze control probe is lower than AL33 (after the time delay), the display shows the alarm label. Buzzer and Alarm relay are not activated. 1= to turn the compressors off when the anti-freeze control probe is lower than AL33 (after the time delay), the display shows the alarm label. Buzzer and Alarm relay are activated.
0 1
AL 48
Probe selection for antifreeze alarm in heat pump mode 0= disabled 1= evaporator inlet temperature 2= evaporator 1 / 2 outlet temperature 3= evaporator 1 / 2 outlet temperature and common outlet temperature 4= external air temperature
0 4
Compressor high discharge temperature
AL 49
Compressor high discharge temperature setpoint
0 0
150 302
°C °F
Dec /
int int
AL 50
Compressor high discharge temperature differential 0 0 25.0
45
°C °F
Dec
int
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
AL 51
Number of compressor high discharge temperature events per hour to determine the alarm reset condition: Always manual reset if AL51 = 0 Always automatic reset if AL51 =16 From automatic to manual if AL51 = 1..15
0 16
Generic alarm 1
AL 52
Maximum number of generic alarm events (each event stop the regulation) before turning the alarm from automatic to manual: Always manual AL52 = 0 Always automatic AL52 =16 From manual to utomatic if AL52 value is between 1 and 15
0 16
AL 53
Generic alarm delay time after the digital input activation 0 250 Sec
AL 54
Generic alarm delay time after the digital input is not activate 0 250 10 sec 10 sec
Generic alarm / signal 2
AL 55
Functioning generic alarm n° 2 0= only signal always automatic reset 1= the alarm block the unit reset depends on the value of parameter AL56
0 1
AL 56
Maximum number of generic alarm events before turning the alarm from automatic to manual: Always manual AL56 = 0 Always automatic AL56 =16 From manual to utomatic if AL56 value is between 1 and 15
0 16
AL 57
Generic alarm delay time after the digital input activation 0 250 Sec
AL 58
Generic alarm delay time after the digital input is not activate 0 250 Sec 10 sec
Alarm relay
AL 59
Enable alarm relay with unit in off or stand – by: 0= Alarm output not enabled 1= Alarm output enabled
0 1
Password reset: Alarm log – Compressor overload
AL 60
Password value to reset the alarm log or the compressor overload alarm.
0 999
Reset High pressure / temperature alarm
AL 61
Maximum number of high pressure / temperature alarm events before turning the alarm from automatic to manual: Always manual AL61 = 0 Always automatic AL61 =16 From manual to utomatic if AL61 value is between 1 and 15
0 16
High water evaporator inlet temperature
AL 62
Maximum number of high water temperature alarm events Always manual reset if AL62 = 0 Always automatic reset if AL62 =16 From automatic to manual reset if AL62 =1..15
1 16
AL 63
High water temperature alarm delay time starting from ON compressor
0 250 Sec 10 sec
AL 64
High water evaporator inlet temperature set point -50.0
-58
70.0 158
°C °F
Dec
int
AL 65
High water evaporator inlet temperature differential 0.1 1 25.0
45
°C °F
Dec
int
AL 66
Probe selection for high water evaporator inlet temperature Allows to select which probe (Pb1..Pb6) the function uses
1 6
Low water evaporator inlet temperature
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
AL 67
Maximum number of low water temperature alarm events Always manual reset if AL67 = 0 Always automatic reset if AL67 =16 From automatic to manual reset if AL67 =1..15
1 16
AL 68
Low water temperature alarm delay time starting from ON compressor 0 250 Sec 10 sec
AL 69
Low water evaporator inlet temperature set point -50.0
-58
70.0 158
°C °F
Dec
int
AL 70
Low water evaporator inlet temperature differential 0.1 1 25.0
45
°C °F
Dec
int
AL 71
Probe selection for low water evaporator inlet temperature Allows to select which probe value NTC/PTC Pb1..Pb6
1 6
Inlet / outlet water tempearture differential alarm
AL 72
Inlet / outlet water tempearture differential alarm enable 0= disabled 1= only in chiller mode 2= only in heat pump mode 3= in chiller and heat pump mode
0 3
AL 73
Maximum number of Inlet / outlet water tempearture differential alarm Always manual reset if AL73 = 0 Always automatic reset if AL73 =16 From automatic to manual reset if AL73 =1..15
1 16
AL 74
Inlet / outlet water tempearture differential alarm delay time starting from ON compressor
0 250 Sec 10 sec
AL 75
Inlet / outlet water tempearture differential alarm set point in chiller mode
-50.0
-58
70.0 158
°C °F
Dec
int
AL 76
Inlet / outlet water tempearture differential alarm differential in chiller mode
0.1 1 25.0 45
°C °F
Dec
int
AL 77
Inlet / outlet water tempearture differential alarm set point in heat pump mode
-50.0
-58
70.0 158
°C °F
Dec
int
AL 78
Inlet / outlet water tempearture differential alarm differential in heat pump mode
0.1 1 25.0 45
°C °F
Dec
int
AL 79
Probe 1 selection for Inlet / outlet water tempearture differential alarm Allows to select which probe value NTC/PTC Pb1..Pb6
1 6
AL 80
Probe 2 selection for Inlet / outlet water tempearture differential alarm Allows to select which probe value NTC/PTC Pb1..Pb6
1 6
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
14 BLACK-OUT
After the black-out is restored:
1. The instrument restores the same operating mode lost after the supply failure.
2. If active, the defrost is aborted.
3. All the timers and time parameters are reloaded.
4. The manual alarm is not reset.
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
15 WIRING CONNECTIONS
15.1 HARDWARE RESOURCES FOR IC206CX MODEL
6 digital outputs (relays) MAX current on the relay contacts relè 5(2)A 250V - MAX common current 10A 250V 11 digital inputs (free of voltage) 6 analogue inputs:
4 NTC / PTC probes
2 NTC / PTC / pressure transducer 4÷20 mA / pressure transducer ratio-metric 0÷ 5.0 Volt
4 modulating outputs:
2 configurable 0 ÷ 10 Volt
2 configurable 0 ÷ 10.0 Volt or cut of phase (for modulating condenser fan)
1 output to connect a remote keyboard (max 2 remote keyboards) 1 TTL output for “Hot Key 64” or for XJ485CX (interface module for monitoring system)
15.2 HARDWARE RESOURCES FOR 208CX MODELS
8 digital outputs (relays) MAX current on the relay contacts relè 5(2)A 250V - MAX common current 10A 250V 11 digital inputs (free of voltage) 6 analogue inputs:
4 NTC / PTC probes
2 NTC / PTC / pressure transducer 4÷20 mA / pressure transducer ratio-metric 0÷ 5.0 Volt
4 modulating outputs:
2 configurable 0 ÷ 10 Volt
2 configurable 0 ÷ 10.0 Volt or cut of phase (for modulating condenser fan)
1 output to connect a remote keyboard (max 2 remote keyboards) 1 TTL output for “Hot Key 64” or for XJ485CX (interface module for monitoring system)
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
16 INSTALLING AND MOUNTING
16.1 PANEL CUT- OUT
The instrument must be mounted on vertical panel, with panel cut-out 71x29mm, and fixed using the special bracket supplied. Avoid locations subject to heavy vibration, corrosive gases or excessive dirt. Ensure ventilation around the instrument.
16.2 VERTICAL BOARDS VI620CX PANEL CUT-OUT
The remote terminals are for panel mounting, panel cut-out 72x56 mm, and screwed with two screws. The IP65 can be reached with the gasket RGW-V (optional).
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
WALL MOUNTING: use the vertical V-KIT (black, white and grey) as described in the following scheme:
17 ELECTRICAL CONNECTIONS
The instrument is provided with:
2 removable terminal blocks MOLEX MICROFIT 14 and 18 ways for power supplay / digital and analogue inputs and modulating outputs
1 removable terminal blocks AMP 12 ways for the relay outputs
5 ways connector for TTL RS485 interface outputs.
Wire size:
1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
signal cable AWG 24
power supply cable AWG 22
relay output AWG 17
General notes:
Check the connecitons and the line voltage before turning on the power supply.
Keep low voltage cables, such as analogue/digital inputs/outputs and probes, away from power
cables and terminals.
Respect the maximum load current of each relay output, in case of power loads use filtered contactors.
18 TECHNICAL DATA
Housing: self extinguishing ABS. Case: frontal 32x74 mm; depth 60mm Mounting: panel mounting in a 29x71mm panel cut-out Frontal protection: IP65 Display:
Top Display 4 digits with d.p.
Bottom Display 4 digits with d.p.
Power supply:
12Vac -10%÷+15% or
24 Vac/dc ±10% 50/60 Hz
Power absorption: 10VA max. Analog Inputs: 4 configurable (NTC/PTC/dig. input) + 2 configurable (NTC/PTC/4÷20ma/0÷5Volt/dig.
input)
Digital inputs: # 11 (free voltage) Relay outputs: IC206CX: 6 SPDT 5(2) A, 250Vac, IC208CX: 8 SPDT 5(2) A, 250Vac
Max. current on common line: 10A
Data storing: on the non-volatile memory (EEPROM). Operating temperature: 0÷55 °C. Storage temperature: -30÷85 °C. Relative humidity: 20÷85% (no condensing) Measuring range: - 50÷110 °C (- 58 ÷ 230 °F) NTC / -50.0÷150 °C (-58÷302 °F) PTC or 0÷ 50 bar
(0÷725 psi)
Resolution: 0,1 °C or 1 °F Accuracy of the controller at 25°C: ±0,7 °C ±1 digit
Dixell S.p.A. Z.I. Via dell’Industria, 27 32010 Pieve d’Alpago (BL) ITALY tel. +39 - 0437 - 98 33 - fax +39 - 0437 ­98 93 13 E-mail:dixell@dixell.com http://www.dixell.com
Loading...