dixell ichill IC100C series Instruction Manual

IC100C Series PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 1 di 38
dIXEL
Instruction Manual
IC100C Series PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 2 di 38
INDEX
1. General Advices__________________________ 2
2. User Interface____________________________ 3
3. Key Function ____________________________ 3
4. Keyboard Leds___________________________ 4
5. Remote Keyboard VI610 ___________________ 4
6. Normal Condition read-out _________________ 4
7. Silencing the Buzzer ______________________ 5
8. First Installing ___________________________ 5
9. How to Set the Clock RTC__________________ 5
10. “ Hot Key” Programming __________________ 5
11. Keyboard Programming ___________________ 5
12. Change the Password _____________________ 6
13. Value of Display Read–Out Par. CF36 ________ 6
14. Start / Stop Chiller or Heat Pump ____________ 7
15. Stand- By Function _______________________ 7
16. “M key” the Function Menu_________________ 7
17. Keyboard Functions ______________________ 8
18. How to Turn a Compressr in Off-Line ________ 8
19. Dynamic Set Point ________________________ 8
20. Energy Saving ___________________________9
21. Compressor Functioning __________________ 9
22. Condenser Fan Regulation ________________10
23. Hot Start Function _______________________ 11
24. Automatic Change - Over _________________ 11
25. Defrost Function ________________________ 11
26. Relay Configuration______________________ 12
27. Data Logger ____________________________12
28. Boiler Function__________________________ 12
29. Maintenance Function____________________ 12
30. Black Out ______________________________ 12
31. Installing and Mounting___________________ 12
32. Electrical Wiring_________________________ 13
33. Alarm Code and Events___________________ 14
34. Output Lock for Alarm Event Table _________ 17
35. Connecting Diagram _____________________ 18
36. Parameter description____________________ 19
37. Parameter Table_________________________ 27
38. Technical Data __________________________ 38
1. GENERAL ADVICES
Please read before using this manual
This manual is part of the product and should be kept near the
instrument for easy and quick reference.
The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device.
Check the application limits before proceeding.
1.1 Safety Precaution
Check the supply voltage is correct before connecting the
instrument.
Do not expose to water or moisture: use the controller only
within the operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent formation of condensation
Warning: disconnect all electrical connections before any
kind of maintenance.
Fit the probe where it is not accessible by the End User. The
instrument must not be opened.
In case of failure or faulty operation send the instrument
back to the distributor or to “Dixell s.r.l.” (see address) with a detailed description of the fault.
Consider the maximum current which can be applied to each
relay (see Technical Data).
Ensure that the wires for probes, loads and the power supply
are separated and far enough from each other, without crossing or intertwining.
In case of applications in industrial environments, the use of
mains filters (our mod. FT1) in parallel with inductive loads could be useful.
IC100C Series PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 3 di 38
2. USER INTERFACE
2.1 Display
The display area is divided in three parts: Left Upper Side : It shows the evaporator “water IN /
OUT” temperature or the inlet air of the air/air unit.
Left Lower Side : It shows the temperature or the pressure
of the condenser and the clock time.
Right Side: Icon area.
2.2 Icons of the Display
Icon Meaning
Celsius degrees
Fahrenheit degrees
Bar
Psi
Compressor 1
Compressor 2
Unit in Stand-by
General Alarm
High pressure Alarm
Low pressure Alarm
Anti-freeze electric heater activated
Infrared Transmission activated
Water Flow Alarm
The display is showing a time value
Compressor Maintenance Request
Function Menu activated
3. KEY FUNCTION
1. M to enter the function Menu or to set the clock
1. SET allows to show and modify the set point.
2. In programming mode it selects a parameter and confirm its value.
1. Depending on the programming, push it for 5 s to run the unit in Chiller or Heat Pump mode.
2. Push and release to change the read-out between “IN/OUT water” / supplied air.
3. In programming mode it scrolls the parameter list or and decreases the value of the parameter itself.
4. Depending on the programming, push it for 5 s to run the unit in Chiller or Heat Pump mode.
5. Push and release to change the read-out between “outside air” / defrost temp.
6. In programming mode it scrolls the parameter list or and decreases the value of the parameter itself.
3.1 Key Combination
Enter the programming.
Exit the programming.
Push them together for more than 5 sec to start a manual defrost.
PSI
IC100C Series PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 4 di 38
4. KEYBOARD LEDS
Symbol Led Function
On Heat pump
On Chiller
Blinking
Programming phase (It blinks with
led)
Blinking Time delay before defrosting
On Defrost On
Off Defrost Off
Clock Set-up
5. REMOTE KEYBOARD VI610
5.1 Key Function
M allows to enter the menu or to set the clock
time.
SET allows to show and modify the set point. During the programming it selects a parameter and confirm its value. It selects the water IN / OUT or the ambient air read-outs. During the programming it scrolls the parameter code or increases its value.
It selects the external /defrost air temperature read-out. During the programming it scrolls the parameter code or decreases its value.
If pushed for 5s it allows to start the unit in chiller or heat pump function.
If pushed for 5s it allow to start the unit in chiller or heat pump function.
For Air/Air unit
: using the remote keyboard with NTC sensor on board ( VI610S model) and with the parameter CF35 = 2, the read-out and the regulation are controlled by the NTC sensor mounted on the remote keyboard. When the communication between the keyboard and the instrument is broken, the left upper side of the display will show ”noL” (no link message).
6. NORMAL CONDITION READ-OUT
If no alarm conditions are present, the display shows: Left upper side:
Evaporator water Inlet/Outlet (Air/Water,
Water/Water).
Ambient / evaporator outlet temperatures (Air/Air).
Left lower side:
Condensing Temperature / Pressure
Anti-freeze evaporator water (Water/Water with Heat
P.).
The clock .
6.1 Alarm Read-Out
Starting from the normal condition (no alarms), when the instrument detects an alarm event, the left lower side shows the alarm code alternated with the probe value. The corresponding icon slighted.
IC100C Series PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 5 di 38
6.2 Icon Dedicated to the Alarm Read-Outs
The following four icons are dedicated to a better alarm understanding:
Generic Alarm
High pressure alarm
Low pressure alarm
Water flow Alarm
7. SILENCING THE BUZZER
Automatically: just after the alarm condition is recovered. Manually
: push and release one of the four keys; the
buzzer is stopped even if the alarm is still active.
8. FIRST INSTALLING
After giving power supply to the instrument, the left lower display can show “rtC” alternated with the probe value: it is
necessary to set the clock time.
If the probes are not connected, or they are faulty, the display shows the corresponding alarm code. In any case it is possible to proceed with the parameter or clock setting.
9. HOW TO SET THE CLOCK RTC
1. Push the M key for some seconds and wait until the “Hour” label appears. Release the M key.
2. Now push SET: the hour value starts blinking.
3. Use the
n and o to change the value. Confirm by
pushing SET; After some seconds the controller will show the next parameter (Min).
4. Repeat the points 2 and 3 to set the other parameters:
Min: minutes (0÷60) UdAy: day of the week (Sun = Sunday, Mon = Monday, tuE = Tuesday, UEd = Wednesday, tHu = Thursday, Fri = Friday, SAt = Saturday). dAy: day of the month(0÷31) MntH: Month (1÷12) yEAr: Year (00÷99)
10. HOT KEY PROGRAMMING
10.1 Download from the Hot Key (previously
programmed) to the Instrument Memory
The controller power supply is off:
Insert The Hot Key.
Turn the power supply on.
The download starts and lasts some seconds.
During this phase the whole regulation is locked and the “dOL” message is blinking. When finishing the “End “ message will appear if the programming result is good, after 15s the regulation automatically restarts If “Err” message appears the operation has given bad result. Turn the controller off and then on again to repeat the operation or restart the normal regulation.
10.2 Upload the Parameter from the Controller to the Hot Key
The instrument is on:
1. Insert the Hot Key.
2. Enter the function menu.
3. Select the UPL function with the arrow keys.
4. Push SET key. The Upload starts immediately from the instrument to the key memory.
During this phase the whole regulation is locked and the “UPL” message is blinking. When finishing the “End “ message will appear if the programming result is good, after 15s the regulation automatically restarts If “Err” message appears the operation has given bad result. Repeat the points 1-4 for a new Upload.
11. KEYBOARD PROGRAMMING
To allow an easier identification of parameter meaning, the parameters of the controller have been collected in different families each one named with a peculiar label.
11.1 “Pr1” Programming Level (User Level)
To enter the “Pr1” User Level:
1) Push the SET +
n key for some seconds ( and
Leeds start blinking) the upper display shows
“ALL” that is the first family of parameters.
2) Using
o and n arrows scroll the other family labels.
3) After finding the right one, push SET key to enter and
see all the parameter belonging to that family, the display shows the first parameter label and its value.
Scroll the parameter list with
o and n arrows or modify the
value as described in 11.4.
11.2 “Pr2” Parameter Level (Factory Level)
The “Pr2” parameter level is accessible through password:
IC100C Series PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 6 di 38
1. Reach “Pr1” as described in 11.1.
2. Select the parameter “Pr2”, the “PAS” label appears on the upper side.
3. Push SET: the lower display shows Pas while the upper display 0 blinking.
4. Set the password using
o and n keys.
5. Push SET key to confirm the value.
11.3 How to Move a Parameter from “Pr2” Level
to “Pr1” Level.
Enter the “Pr2” level and select the parameter to move; keeping pressed the SET key push and immediately release the n key. One of the nearest led will light to indicate the presence of the parameter in “Pr1”. Then release also SET key. To move the parameter in “Pr2” again: keep pressed SET key and immediately release the n key. The led turns off so as the parameter is not more visible in “Pr1” but just in
“Pr2”.
11.4 To Change a Parameter Value
1. Access to programming mode Pr1 or Pr2
2. Select the parameter to change.
3. Push SET key to enable its value.
4. Modify the value with
o and n keys.
5. Push SET key again to confirm the new value, after some seconds next parameter will be displayed.
6. Exit the programming: push SET +
o, when a
parameter label is displayed, or wait 15s (time-out) without pushing any keys.
NOTE: The new parameter value is also confirmed if, after changing it, no SET key is pressed for the time-out to exit.
12. CHANGE THE PASSWORD
Before modifying the password you must know the previous value. This operation is possible only under Pr2.
1) Enter Pr1 level.
2) Select the family containing the interested parameters.
3) Push SET key.
4) Using arrows key select the parameter “Pr2”, then push SET key. The lower display shows “PAS” while the upper side is 0 blinking.
5) Use
n and o to set the active PASSWORD. push
SET key to reach the Pr2 level.
6) To modify the password: select the “Pr2” parameter.
7) Push SET key to enter the new value (blinking).
8) Insert the new password with
o and n keys.
9) Push SET key to confirm it.
10) The upper display will blink for few seconds then, next parameter will be showed.
11) Exit the programming by pushing SET + o together or wait the time-out.
13. VALUE OF DISPLAY READ–OUT PAR. CF36
The parameter data can change depending on CF03 parameter value.
13.1 Parameter CF36 = 0
Upper display shows as default Pb1 probe. Lower display: if CF06 =1,2,4, it shows Pb3 probe, if CF07=1,4 it shows Pb4 probe.
13.2 Parameter CF36 = 1
Upper display shows as default Pb2 probe. Lower display: if CF06 =1,2,4, it shows Pb3 probe, if CF07=1,4, it shows Pb4 probe.
13.3 Parameter CF36 = 2
Upper display shows as default Pb1 probe. Lower display shows the clock time.
13.4 Parameter CF36 = 3
Upper display shows Pb2 probe. Lower display shows the clock time. If the default probe is Pb1 value, each time the o key is pressed the upper display shows Pb2 value for 30 seconds with OUT label. When the time is expired, it comes back to default Pb1 read-out. If the default probe is Pb2 value, each time the o key is pressed the upper display shows Pb1 value for 30 seconds with IN label. Then it comes back to default Pb1 read-out.
13.5 Display Read-Out when Remote ON/OFF
The digital input configured as remote OFF: if activated it turns off the controller (also for motocondesing), upper display shows “OFF ” the decimal point led is blinking.
1. This remote on/off command overrides the instrument keyboard commands.
2. The keyboard commands are active only when the digital input is not active.
3. When the remote off is not activated the controller automatically restarts.
13.6 Upper Display Read-Out with Par. CF02=1
(Motocondensing Unit)
Upper display shows:
“ON” with digital input active “OFF” with digital input not active.
If the chiller function is selected it turns to OnC. If the Heat Pump is selected it turns to OnH. Even for the Motocondensing function the user is allowed to check the probe values using key arrows and to verify and manage the alarm events.
IC100C Series PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 7 di 38
14. START / STOP CHILLER OR HEAT PUMP
By pressing
key for 5 seconds the unit starts or stops the Chiller cycle if the parameter CF31 =0, otherwise if parameter CF31 =1, it starts / stops in Heat Pump mode.
The
led blinks for 5 seconds then it turns on. To change from Chiller to HP or vice versa, it is necessary to stop the cycle and then restart the new.
By pressing
key for 5seconds, the unit starts or stops the Heat Pump cycle if parameter CF31 =0, otherwise, if parameter CF31 =1, it starts / stops in Chiller mode.
The
led blinks for 5 seconds then it turns on. To change from Chiller to HP or vice-versa, it is necessary to stop the cycle and then restart the new.
15. STAND- BY FUNCTION
Each time the Chiller or Heat Pump cycles are stopped, the unit goes in stand-by and the
icon turns on.
The controller stand-by allows to:
Show the probe values using key arrows.
Show and manage the alarm events.
16. “M KEY THE FUNCTION MENU
Entering the function Menu allows to:
1. Show and reset the active alarms.
2. Show and reset the time running hour counters of the
loads.
3. Enable the infra-red communication device.
4. Show the time delay to achieve and start the defrost
(only for Heat Pump).
5. Upload the parameters from the controller to the Hot
Key (see 10.2).
6. Show the alarm log.
7. Reset the alarm log. During the Menu operations the “menu” icon is on.
16.1 Access to Function Menu
Push and release the M key. The ” menu” icon is on.
16.2 Exit from function Menu
Push and release the M key or wait the time out. The “menu” icon disappears.
16.3 How to Show the Alarm Events
Enter the function Menu:
1. Use
o or n keys to find the “ALrM” label.
2. Push and release the SET key.
3. Use
o or n keys to scroll the alarm list.
To exit the function Menu push and release the M key or wait the time-out. The “menu” icon disappears.
16.4 How to Reset an Alarm Event
1) Enter the function Menu.
2) Use
o or n keys to find the “ALrM” label.
3) Push and release the SET key, the lower display shows the alarm code.
4) Upper display: rSt label if the alarm can be reset, NO label if it is not possible.
Use
o or n keys to scroll the alarm list.
5) Push SET key, when rSt is lighted, to reset the alarm, after a while the read-out move to next alarm.
6) To exit the function menu push and release the M key or wait the time-out. The “menu” icon disappears.
16.5 Time Running Hour Counter of the Loads
Enter the function Menu. Use
o or n keys to find on the lower display:
C1Hr (Compressor n°1 hour counter),
C2Hr (Compressor n°2 hour counter),
PFHr (Water pump or supply fan hour counter).
The upper display shows the time running hour value.
The clock icon
is lighted.
16.6 Reset the Hour Counters
1. Enter the function Menu.
2. Use
o or n keys to find on the lower display the
C1Hr, C2Hr or PFHr.
3. Push SET key for 3seconds: the upper display turns to 0 indicating the reset.
4. To exit the function menu push and release the M key or wait the time-out. The “menu” icon disappears.
16.7 Show the Time Delay to Start the Defrost
1. Enter the function Menu.
2. Use o or n keys to find, on the upper display, the dEF (defrost) label, the lower display shows the time delay to reach and start the defrost (minutes and
seconds), the icon
is blinking.
3. To exit the function menu push and release the M key or wait the time-out. The “menu” icon disappears.
16.8 Infrared Transmission Procedure
1. Enter the function Menu.
2. Use o or n keys to find, on the lower display, the “Ir” label while, the upper display shows label ALr = ALARM ;
Par = PARAMETER; LOG = RECORDED DATA.
3. Push and release SET key.
IC100C Series PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 8 di 38
4. If the password is active enter its value.
5. The infrared icon
is now lighted. The controller starts sending the data. You have 1 minute to place the IR receiver device in front of the instrument.
6. On the receiver, push RX key to enable the receiving: the RX led blinks during the interlacing procedure. During the data transferring the RX is lighted, it turns off to signal the end of the procedure.
7. To exit the function menu push and release the M key or wait the time-out. The “menu” icon disappears.
16.9 How to See the Alarm Log
1. Enter the function Menu.
2. Use o or n keys to find ALOG label.
3. Push SET key: the lower display shows the alarm code, the upper display shows “n°” followed by the progressive number.
4. With o or n scroll the alarm list.
5. To exit from ALOG function push M key or wait the time-out delay is expired.
The memory contains 50 alarm events structured in a FIFO list. Each new alarm will take the place of the oldest alarm contained in the FIFO list. ( the read-out is ordered from the oldest to the newest)
16.10 How to Reset the Alarm Log
1) Enter the function Menu.
2) Select the ALOG label showed on the lower display.
3) Push SET key.
4) Select with o or n keys the ArSt (Alarm reset) label on the lower display, the upper display is PAS.
5) Push SET key and then enter the password PAS, upper display shows 0 blinking.
6) Write the right password number.
7) The ArSt label starts blinking for 5s, to confirm the alarm logging data is reset.
After finishing the display restarts from normal condition.
17. KEYBOARD FUNCTIONS
17.1 How to See the Set Point Value
Push and release the SET key. Lower display shows: SetC set of chiller mode;
SetH set of heat pump mode. The upper display shows the corresponding set value. (SetH is available only if configured for Heat Pump).
17.2 How to Change the Set Point Value
1) Push SET key for more than 3 seconds.
2) The setpoint value is now blinking.
3) Use o and n
to increase or decrease the new value.
When finishing, push and release SET key again or wait for the time-out to exit the programming.
17.3 How to See the Set Point with Energy Saving or Dynamic Set Functions Enabled
When working in Chiller or Heat Pump, the first time SET key is pushed the lower display shows SEtC (set chiller); or SEtH (set heat pump) and the upper shows its value. When the “Energy Saving” is activated, by pressing SET key again, the lower display shows “SEtS” (set saving) while the upper display will turn to the real setpoint value used to control the unit during this function. When working with “Dynamic Set”, by pushing SET again, the lower display shows “SEtd” (set dynamic), while the upper display will turn to the real setpoint value used to control the unit during this function. The SEtS or SETd appears only if the corresponding functions are activated.
18. HOW TO TURN A COMPRESSR IN OFF-LINE
A compressor can be turned off for maintenance or if it is in bad condition, without interfering with the normal cycle of the unit. Therefore, it is not necessary to stop the unit or the cycle.
1. Access the programming mode.
2. Find and then set the parameter CO12 = 1 (compressor 1 = OFF: out of the process control).
3. If necessary find and then set also the parameter CO13 = 1 (2
nd
comp. / step 1stcomp.= OFF). To restore the compressor in the process control set the C012 and/or C013 parameter = 0.
19. DYNAMIC SET POINT
This function is useful to save energy or to run the unit with particular external air temperature condition. It allows to increase or reduce the setpoint with a positive or negative proportional offset. This value is combined with parameters Sd02 (for Chiller) or Sd03 (for HP), the 4...20mA analogue input or the outside air temperature. The Dynamic Set is enabled if:
- The parameters Sd01 = 1 and CF06 = 3, Pb3 probe configured as 4..20mA signal;
- The parameter Sd01 = 1 and CF07 = 3, Pb4 probe configured as outside air temperature. If the parameter CF07=3, by pushing and releasing the n key the upper display shows for 30 seconds the outside air temperature while the lower display shows Et (external temperature) label.
Pb3 probe configured as 4..20mA input signal (below)
IC100C Series PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 9 di 38
Pb4 probe with positive differential (below)
Pb4 probe with negative differential (below)
20. ENERGY SAVING
It is daily or weekly configurable function with “hour time table” (if RTC on board) or depending from external digital input. During the Energy Saving cycle the real setpoint is calculated with the parameters ES10 and ES12: SET+ES10 for chiller, SET+ES12 for Heat Pump. The differential for the function cut-in/out is depending by
ES11 for Chiller and ES13 for Heat Pump.
20.1 Daily Programming
The daily programming is based on 7 parameters ES03­>ES09 corresponding to the 7 days of the week; the value
1 enable the function for that day. Eg: ES03 = 1 means that the Energy Saving is activated for the whole 24 hours on Monday. If needed, repeat the operation for the whole week ES04(Tue)..ES09(Sun).
20.2 Hour Time Table (with RTC)
Based on two parameters: ES01 Energy Saving start hour and ES02 Energy Saving stop hour.
Eg: ES01 = 8.0 and ES02 = 10.0 it means that the Energy Saving is active from 8 to 10.0
for all the days of the week. Eg: ES01 = 23.0 and ES02 = 8.0 it means that the Energy Saving is active from 23.0 to 8.0
of the next morning; for all the days of the week. This function is disabled if the parameters ES01 / ES02 are both 0.
20.3 Energy Saving with External Contact
The function is enabled when the digital input, configured as Energy Saving, is activated by remote contact.
21. COMPRESSOR FUNCTIONING
21.1 Compressor Control in Chiller Mode
Parameter CF21=0,3 (1 Compressor selected)
Parameter CF21=1 (1 compressor with step)
Parameter CF21=2 ( 2 compressor )
21.2 Compressor Regulation for Heat Pump
Parameter CF21=0,3 (1 compressor)
IC100C Series PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 10 di 38
Parameter CF21=1 (1 compressor with step)
Parameter CF21=2 (2 compressors)
22. CONDENSER FAN REGULATION
22.1 ON/OFF Fan in Chiller Mode
22.2 ON/OFF Fan in Heat Pump
22.3 Triac or 4..20mA Output in Chiller Mode
22.4 Triac or 4..20mA Output in Heat Pump
IC100C Series PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 11 di 38
23. HOT START FUNCTION
Available only if the parameter CF01=1 air/air unit configured as heat pump, it allows to start the supply air fan only if the temperature of the condenser side is enough hot. This avoid to push cold air flow into the ambient.
23.1 Hot Start Fan Graphic Function
FA25 Set point of the Hot Start
Set the temperature value, detected by the Pb2 probe, under which the fan is keep locked. FA26 Differential of the Hot Start Set the differential to regulate the fan ON/OFF.
24. AUTOMATIC CHANGE - OVER
It automatic changes the chiller <-> heat pump functioning of the unit in correlation with the external temperature condition. The changing occurs only when the following condition are satisfied, otherwise the unit turns to stand-by:
1. CF01=1,3,5,7 (Heat Pump selected).
2. CF28=2 and CF07=3 (Pb4 external air temperature).
3. Pb4 probe is not faulty. The Change Over function is regulated by parameters: CF29 is the set point and it represents the Pb4 value under which the controller turns to Heat Pump mode. CF30 represents the temperature differential to turns to Chiller mode. The user can find helpful information by pushing and
releasing
n key so as the upper display shows the Pb4
value while the lower display shows Et label.
24.1 Graph Regulation of the Change-Over
When the temperature value is within the CF30 range, the changeover is allowed only though keyboard.
25. DEFROST FUNCTION
The defrost cycle is enabled only if the following condition are satisfied:
1. CF01=1,3,7 configuration chiller unit with heat pump.
2. dF01=1 defrost cycle enabled.
3. CF20=0 relay n°4 configured as reversing valve.
4. The unit is working in heat pump mode.
5. Pb3 or Pb4 must be configured as control
condensing probe without active faulty probe alarms. If only one of these conditions is not satisfied the defrost does not operate.
25.1 Forced Defrost
This function is enabled only if dF05 <> 0 and allows to operate a defrost even during the counting of the time delay dF10 and if the temperature/pressure value lower than the parameter dF19 value for the dF05 time value. If during the time delay dF05 the temperature/pressure becomes higher than the parameters dF1+dF20 (differential) value then the whole procedure is stopped and the time delay dF05 will be reloaded.
25.2 Combined Defrost
This function is enabled only if CF07 = 5 and with Pb4 configured as NTC probe therefore it is used for external temperature on the evaporator coil during the heat pump mode. The detected temperature allows to calculate a better defrost cycle giving the start and the end commands for the cycle itself. Functioning: The Pb3 probe gives the input signal, to start the time delay counting, when its value is lower than dF03 parameter. After the delay dF10 the controller check Pb4 value: if lower than dF11 the defrost procedure starts otherwise the unit still works in Heat Pump. Just after the temperature decreases under dF11 the defrost is enabled. The combined defrost stops just when Pb4 probe value reaches the end defrost temperature in dF12. If the combined defrost is enabled is possible through key, to see the external temperature showed on the upper display for 30 seconds while the lower display shows dEF label.
25.3 Manual Defrost
The unit is working with 1 or 2 compressor running. The start defrost temperature/pressure value must be lower than dF03. If the “combined defrost” is enabled, Pb4 value must be lower than dF11. If the above conditions are satisfied, by pushing SET + o for more than 5s the defrost cycle immediately starts.
IC100C Series PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 12 di 38
26. RELAY CONFIGURATION
Relay n° 1 = Compressor 1 Relay n° 2-3 automatically change their configuration depending on the unit configuration. Relay n° 2 = Anti-freeze heater CF01 = 2-3-4-5; integration heater with CF01 = 0 - 1 Relay n° 3 = Water pump, with CF01 = 2-3-4-5; supply air fan CF01 = 0 –1
Value of par.CF20
Relay
0 1
°n 4
Inversing
valve
Fan ON/OFF
Value of par.CF21
Relay
0 1 2 3
°n 5 Alarm
Stage of the 1
st
compressor.
2
nd
compre
ssor
Fan
ON/OFF
When working with one compressor with one stage valve: the relay n°5 is configured as stage valve CF21=1: the polarity of the stage valve is determined by C010.
CO10 = 0 RL1 comp. RL5 parz.
No call OFF OFF Compressor call ON OFF 1st Stage call ON ON
CO10 = 1 RL1 comp. RL5 parz.
No call OFF ON Compressor call ON ON 1st Stage call ON OFF
27. DATA LOGGER
The data recording is enabled if the log time LG08 > 0. The recordable data can be included enabling the LG01 to
LG07 parameters.
28. BOILER FUNCTION
The electric heater can be activated as heating integration control Ar20=0 or heating control Ar20=1 during the heat pump functioning mode. It is enabled only if:
Unit configured in Heat Pump mode CF01=3-5.
Pb4 configured as external air probe CF07=3.
28.1 Heating Integration Control Ar20=0
The Boiler function starts when the Pb4 probe value decreases under Ar21 value. If the water temperature detected by the regulation probe is lower than the ST03 parameter, the electric resistance heater is activated. The on/off algorithm of the electric resistance heater is the same as the compressor control with Heat Pump mode.
If the external air temperature becomes higher than Ar21 + Ar22 (differential), the integration function stops working and the unit restarts (or still work) with Heat Pump mode.
28.2 Heating Control Ar20=1
The Boiler function begins when the Pb4 probe decreases under Ar21 value. When the delay is expired, if the water temperature detected by the regulation probe is lower than the ST03 parameter, the compressors are stopped while the electric resistance heater is activated. The on/off algorithm of the electric resistance heater is the same as the compressor control with Heat Pump mode. If the external air temperature becomes higher than Ar21 + Ar22 (differential), the Boiler functions stops working and the unit restarts with Heat Pump mode, compressors and fans restart working.
29. MAINTENANCE FUNCTION
CO14 for 1st compressor, CO15 for 2nd compressor and CO16 for water pump or supplied air fan (air/air) are the
maximum time running hours to signal a maintenance request, the icon
is blinking. The icon only indicates the need of a check: nothing else happens. It stops blinking just after resetting the hour counter under the function Menu.
30. BLACK OUT
After a black-out:
1. The controller restarts from the pervious status.
2. The defrost cycle is stopped.
3. All the working time delay will be reloaded.
31. INSTALLING AND MOUNTING
31.1 “C” Format (32*74mm)
The instrument shall be mounted on panel, in a 29x71 mm hole, and fixed using the special bracket supplied. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-C) as shown in figure 1.
Loading...
+ 26 hidden pages