Dimplex System 18, System 30, Combi 24, Combi 38 Installation And Servicing Instructions

SSyysstteemm 1188 SSyysstteemm 3300
System Condensing Boilers
Installation and Servicing Instructions
These instructions should be left with the user
© Dimple
x Boiler
GGAASS CCOOUUNNCCIILL NNUUMMBBEERRSS
NNaattuurraall GGaass
Dimplex System 18 - Gas Council Appliance No:
4411 114499 0022
Dimplex System 30 - Gas Council Appliance No:
4411 114499 0011
22
© Dimple
x Boiler
APPROVED PRODUCT
CCOONNTTEENNTTSS
SSEECCTTIIOONN DDEESSCCRRIIPPTTIIOONN PPAAGGEE
1.0 Introduction 4
2.0 Boiler Layout 7
3.0 Boiler Operation 8
4.0 Technical Data 9
5.0 Dimensions 10
6.0
System Details 11
7.0 Site Requirements 13
8.0 Flue options 17
9.0 Installation 20
10.0 Commissioning 24
11.0 Service Mode 26
12.0 Servicing & Maintenance 27
13.0 Changing Components 30
14.0 Electrical 38
15.0 Spare Parts 39
16.0 Fault Finding 40
17.0 Benchmark 42
18.0 Warranty Terms & Conditions 46
© Dimple
x Boiler
33
11..00 IINNTTRROODDUUCCTTIIOONN
11..11 BBUUIILLDDIINNGG RREEGGUULLAATTIIOONNSS AANNDD BBEENNCCHHMMAARRKK CCHHEECCKKLLIISSTT
Building Regulations (England & Wales) require notification of the installation of a heating appliance to the relevant Local Authority Building Control Department.
From 1 April 2005 this can be achieved via a Competent Persons Self Certification Scheme as an option to notifying the Local Authority directly.
CORGI operates a Self Certification Scheme for gas heating appliances.
With the introduction of Self Certification Schemes, the Benchmark L
ogbook is being withdrawn. However, a similar document in the form of a commissioning checklist and service interval record is incorporated at the back of these instructions.
This company is a member of the Benchmark initiative and fully supports the aims of the programme. Its aim is to improve the standards of installation and commissioning of central heating systems in the UK and to encourage the regular serv
icing of all central heating systems to ensure safety and
efficiency.
Building Regulations require that installations should comply with manufacturer’s instructions. It is therefore important that the commissioning checklist is completed by the installer. The relevant section of Building Regulations only relates to dwellings. Therefore the checklist only applies if the appliance is being installed in a dwelling or some related structure.
44
© Dimple
x Boiler
11..22 IINNSSTTAALLLLAATTIIOONN,, CCOOMMMMIISSSSIIOONNIINNGG,, SSEERRVVIICCEE && RREEPPAAIIRR
This appliance must be installed in accordance with the manufacturer’s instructions and the regulations in force. Read the instructions fully before installing or using the appliance.
In GB, this must be carried out by a competent person as stated in the Gas Safety (Installation & Use) Regulations.
DDeeffiinniittiioonn ooff ccoommppeetteennccee::
A person who works for a CORGI registered company and holding current certificates in the relevant ACS modules, is deemed competent.
In IE, this must be carried out by a competent person as stated in I.S. 813 “Domes
tic Gas Installations”
No modifications or changes can be made to this appliance without prior written permission from Dimplex Boilers.
The manufacturers instructions must not be taken as overriding any statutory requirements. If in doubt contact Dimplex Boilers on 0844 3711121.
WWaarrnniinngg --
Check the inf
ormation on the data plate is
compatible with local supply conditions.
All CORGI registered installers carry a CORGI identification card and have a registration number. You can check your installer is registered by telephoning 0870 4012300 or writing to:-
1 Elmwood Chineham Business Park Crockford Lane Basingstoke RG24 8WG
or check online at www.corgi-gas-safety.com
These appliances meet the requirements of; Gas Appliance Directive 90/396/EEC Efficiency of Hot Water Boilers Directive 92/42/EEC Low Voltage Directive 92/42/EEC Electromagnetic Compatibility Directive 92/31/EEC
Type test certified by:- Notified Body 0087 (Pin 87BT49).
P
roduct/Production certified by:
Notified Body 0086.
For GB/IE only
11..00 IINNTTRROODDUUCCTTIIOONN
11..33 LLEEGGIISSLLAATTIIOONN
TThhee aapppplliiaannccee iiss ssuuiittaabbllee oonnllyy ffoorr iinnssttaallllaattiioonn iinn GGBB aanndd IIEE aanndd sshhoouulldd bbee iinnssttaalllleedd iinn aaccccoorrddaannccee wwiitthh tthhee rruulleess iinn ffoorrccee,, aanndd oonnllyy uusseedd iinn aa ssuuiittaabbllyy vveennttiillaatteedd llooccaattiioonn..
In GB, the installation must be carried out by a CORGI Registered Installer. It must be carried out in accordance with the relevant requirements of the:
• Gas Safety (Installation & Use) Regulations.
• The appropriate Building Regulations either The Building regulations, The Building Regulations (Scotland), Building Regulations (Northern Ireland).
• The Water Fittings Regulations or Water Byelaws in Scotland.
• The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a competent Person and installed in accordance with the current edition of I.S. 813 ‘Domestic Gas Installations’, the current Building Regulations and reference should be made to the current ETCI rules for electrical installation.
AAllll ssyysstteemmss mmuusstt bbee tthhoorroouugghhllyy fflluusshheedd aanndd ttrreeaatteedd wwiitthh iinnhhiibbiittoorr ((sseeee sseeccttiioonn 66..22))..
CCooddeess ooff PPrraaccttiiccee -- rreeffeerr ttoo tthhee mmoosstt rreecceenntt vveerrssiioonn
IInn GGBB tthhee ffoolllloowwiinngg CCooddeess ooff PPrraaccttiiccee aappppllyy:
:
SSttaannddaarrd
d
SSccooppe
e
BS 7967 Carbon monoxide in dwellings and the
combustion performance of gas fired appliances
BS 7967-2 Guide for using electronic portable combustion
gas analysers in the measurement of carbon
monoxide and the determination of combustion
perf
ormance
BS 7967-3 Guide for responding to measurements obtained
from electronic portable combustion gas
analysers
BS 7967-4 Guide for using electronic portable combustion
gas analysers as part of the process of servicing
and maintenance of gas fired appliances
BS 6891 Gas installation
B
S 5546
Installation of hot water supplies for domestic
purposes
BS 5449 Forced circulation hot water systems
BS 6798 Installation of gas fired hot water boilers
B
S 5440 P
art
1
Flues
B
S 5440 Part 2 Ventilation
BS 7074 Expansion vessels and ancillary equipment
for sealed water systems
B
S 7593
T
r
e
a
tment of water in domestic hot water
c
entral heating systems
IInn IIEE tthhee ffoolllloowwiinngg CCooddeess ooff PPrraaccttiiccee aappppllyy:
:
SSttaannddaarrd
d
SSccooppe
e
I.S. 813 Domestic Gas Installation
The
f
ollowing s
tandards give valuable additional information;
B
S 5546
Ins
t
all
a
tion of ho
t
wa
ter supplies for domestic
purposes
BS 5449 Forced circulation hot water systems
B
S 7074
Expans
ion v
es
sels and ancillary equipment
for sealed water systems
BS 7593 Treatment of water in domestic hot water
c
entral heating systems
© Dimple
x Boiler
55
GGAASS LLEEAAKKSS DDOO NNOOTT OOPPEERRAATTEE AANNYY EELLEECCTTRRIICCAALL SSWWIITTCCHHEESS,, OORR UUSSEE AA NNAAKKEEDD FFLLAAMMEE.. TTUURRNN OOFFFF TTHHEE GGAASS SSUUPPPPLLYY.. VVEENNTTIILLAATTEE TTHHEE AARREEAA BBYY OOPPEENNIINNGG DDOOOORRSS AANNDD WWIINNDDOOWWSS.. CCAALLLL OOUUTT YYOOUURR LLOOCCAALL GGAASS SSUUPPPPLLIIEERR TTEELL:: 00880000 111111 999999
CCoonnttrrooll ooff SSuubbssttaanncceess HHaazzaarrddoouuss ttoo HHeeaalltthh Under Section 6 of the Health and Safety at Work Act 1974, it is required to provide information on substances hazardous to health.
The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
Insul
ation Pads - These can cause irritation to skin, eye and respiratory tract. If you have a history of skin complaint you may be susceptible to irritation. High dust levels are usual only if the material is broken. Normal handling should not cause discomfort, but follow normal good hygiene and wash your hands before eating, drinking or going to the lavatory. If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
GGaass aanndd EElleeccttrriicciittyy CCoonnssuummeerr CCoouunncciill ((EEnneerrggyywwaattcchh)) Energywatch is an independent organisation, which protects the interests of gas users. If you need advice concerning energy issues, they may be contacted on their consumer help line number: 08459 060708, or via their website; www.energywatch.org.uk.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or
lack of experience and knowledge, unless they have been
gi
v
en supervision or instructions concerning use of the
ap
plianc
e by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
11..00 IINNTTRROODDUUCCTTIIOONN
1. The appliances incorporate a microprocessor based, fully modul
a
ting air/g
as r
atio control system with direct burner ignition. This provides a modulated heat output, with internal frost protection provided as standard. The heat exchanger is cons
t
ruct
ed from stainless steel encased in high temperature
polymer.
A combined circulating pump, automatic air vent assembly, pressure gauge, safety valve and system expansion vessel are included.
Isolation valves are fitted to the service connections.
The boiler
has a pump o
ver run feature therefore the central heating system must include either a proprietary automatic bypass valve or a radiator must be fitted with lock shield valves. A separate CH expansion vessel is not required if the total CH system content is less than 84 litres. However one is required for systems with volumes greater than 84 litres; refer t
o section 6.5. It
i
s r
ecommended tha
t
a drain cock is fitted at
the lowest point in the system.
66
© Dimple
x Boiler
11..55 DDEESSCCRRIIPPTTIIOONN
RF room thermostats etc, are available as optional extras, howe
v
er
if an e
xternal control is fitted the hole in the fascia must be covered using the fascia blanking panel supplied (Part No. 300635)
2. The boiler is designed for use on Natural Gas (G20). A natural gas to propane conversion kit is available for each Dimplex System Boiler.
3. The boiler is suitable for use only on fully pumped sealed heating systems.
4. The boiler data badge gives details of the model, serial number and Gas Council number and is situated on the inner door panel. It is visible when the case front is removed. (Fig. 1)
5. The boiler model name and serial number are also shown on the information label on the inside of the fascia. This is for user reference.
6. The boiler is intended to be installed in residential / commercial / light industrial E.M.C. environments on a governed meter supply only.
7. The boiler must be installed with one of the purpose designed flues such as the standard horizontal telescopic flue kit, part no. 956120.
8.
AAllll ssyysstteemmss mmuusstt bbee tthhoorroouugghhllyy fflluusshheedd aanndd ttrreeaatteedd wwiitthh
iinnhhiibbiittoorr ((sseeee sseeccttiioonn 66..22))..
11..66 OOPPTTIIOONNAALL EEXXTTRRAASS
• Boiler
• Wall fixing jig
• T
emplates & ‘Quick Fit’ Guide
• Literature Pack
• Plugs and screws
11..77 PPAACCKK CCOONNTTEENNTTSS
11..44 SSAAFFEE MMAANNUUAALL HHAANNDDLLIINNGG
1. The boiler should be handled and lifted by two people. Wear appropriate Personal Protection Equipment e.g. protective gloves, safety footwear etc. Plan your route to minimise the number of turns needed to handle/lift the boiler.
2. Where possible transport the boiler using a sack truck or other suitable trolley. Try to avoid steps, wet or slippery surfaces, unlit areas etc. and take special care on ladders/into lofts.
3. When handling or lifting always use safe techniques - keep your back straight, bend your knees. Don’t twist - move your feet, avoid bending forwards and sideways and keep the load as close to your body as possible.
4. Asses the risks associated with handling and lifting according to the conditions on site. If in doubt seek advice before proceeding. Health and Safety is the responsibility of everyone.
22..00 BBOOIILLEERR LLAAYYOOUUTT
22..11 KKEEYY
1. Expansion Vessel
2. Automatic Air Vent
3. Circulation Pump
4. Drain Off Point
5. Pressure Relief Valve
6. Central Heating System Pressure Gauge
7. PCB
8. Control Box
9. Flexible condensate pipe assembly
10. Flame Sensing Electrode
11.
Spark Electrode
12. Primary Heat Exchanger
13. Fan Assembly
14.
Gas Valve & Swirl Plate Assembly
15. Reset Button
16. Central Heating Temperature Control
17.
Air / Gas Channel
18. Burner & Burner Door
19. Spark Generator
20. Data Badge
21. Flue Sample Point
22. Manual Air Vent
23. Burner On Light
24. Central Heating Mode Light
25.
Di
splay
26. Flue Thermistor
27. Thermal Fuse
© Dimple
x Boiler
77
0
1
2
bar
3
4
0
1
2
bar
3
4
FFiigg.. 11
FFiigg.. 22
1
1
221
1
226
6
227
7
222
2
2
2
3
3
6
6
7
7
8
8
220
0
9
9
117
7
110
0
118
8
111
1
113
3
114
4
1155225
5
224
4
116
6
223
3
112
2
119
9
4
4
5
5
33..00 BBOOIILLEERR OOPPEERRAATTIIOONN
33..11 CCEENNTTRRAALL HHEEAATTIINNGG
1. With a demand for heating, the pump, circulates water through the primary circuit.
2. Once the main burner ignites the fan speed controls the gas rate to maintain the heating temperature measured by the temperature sensors.
3. When the demand is satisfied the burner is extinguished and a 5 minute delay occurs before the burner will re-light (anti­cycling), the pump continues to run for a period of 2 minutes (Pump Overrun).
88
© Dimple
x Boiler
33..22 FFRROOSSTT PPRROOTTEECCTTIIOONN MMOODDEE
1. Providing there is mains power supply to the appliance, the frost protection mode is integral. If the system temperature falls below 5°C then the boiler will fire on its minimum se
tting until a flow temperature of 20°C is reached. Further protection can be incorporated by using a system frost thermostat.
33..33 PPUUMMPP PPRROOTTEECCTTIIOONN
1. The pump will automatically operate for 1 minute in every 24 hours to prevent sticking.
Expansion
V
essel
P
rimary
Heat Exchanger
Burner &
Burner Flange
Primary Return
CH flow
Thermistor
CH return
Thermistor
Condensate
Trap
Pressure
Gauge
CH
Return
3 BAR
Pressure Relief
Valve
Pump &
Hydroblock
Automatic
Air
Vent
CH
Flow
Flue Products
M
anual
Bleed Valve
FFiigg.. 33
44..00 TTEECCHHNNIICCAALL DDAATTAA
44..11 PPEERRFFOORRMMAANNCCEE DDAATTAA
© Dimple
x Boiler
99
AApppplliiaannccee CCllaassssiiffiiccaattiioonn CC1133,, CC3333,, CC5533,, BB223
3
SSyysstteemm 118
8
SSyysstteemm 330
0
Mode Rate O
utput (non-condensing)(80-60°C) Max kW 18.1 29.8
Min kW 6.0 8.1
Output (condensing)(50-30°C) Max kW 19.7 32.5
Input Max Rate Net kW 18.4 30.4
G
ross kW 20.4 33.7
Input Min Rate Net kW 5.4 7.6
Gross kW 6.0 8.4
Gas Rate (after 10 min operation - hot) Max m
3
/h 1.95 3.2 Seasonal Efficiency % 90.3 90.3 S
easonal Efficiency (SEDBUK) Band “A” “A” Nox Classification Class “5” “5” Min System Pressure Bar 0.5 0.5 Max System Pressure Bar 2.5 2.5 Max Central Heating Flow Temperature °C 80 80 M
in Central Heating Flow Temperature °C 30 30
GGeenneerraall SSppeecciiffiiccaattiioonns
s
Max lift weight kg 33.6 39.6 Total water capacity Ltr 1.8 3.1 I
ntegral expansion vessel capacity Ltr 8 8 Maximum heating system water content using fitted expansion vessel, @ 0.75 bar Ltr 84 84 Electrical supply 240V 50Hz Fuse at 3A Internal fuse T4H 4A 250V Maximum power consumption W 100 125 IP Rating IPX4 IPX4 Flue gas temperature 80/60 °C 59 75 Flue gas temperature 50/30 °C 41 55
CO
2
value max rate (Nat Gas) (Case must be fitted when taking reading) % 8.8-9.2 8.8-9.2 CO2value min rate (Nat Gas) (Case must be fitted when taking reading) % 8.5-8.9 8.7-9.1 CO value max rate (Nat Gas) (Case must be fitted when taking reading) P.P.M 15-60 15-60 CO value min rate (Nat Gas) (Case must be fitted when taking reading) P.P.M 0-40 0-40
CO
2
value max rate (Propane) (Case must be fitted when taking reading) % 10.8-11.2 10.5-10.9
CO
2
value min rate (Propane) (Case must be fitted when taking reading) % 10.4-10.8 10.3-10.7 CO value max rate (Propane) (Case must be fitted when taking reading) P.P.M 80-160 80-160 CO value min rate (Propane) (Case must be fitted when taking reading) P.P.M 0-40 0-40
Gas Pressure - Natural Gas mbar 18-20 18-20 Gas P
r
es
sure - Propane mbar 37 37
CCoonnnneeccttiioonns
s
Gas 22 mm compression CH flow 22 mm compression CH return 22 mm compression Pressure relief valve outlet 15 mm compression Condensate Drain 21.5 - 22 mm plastic overflow pipe PP..PP..MM == PPaarrttss PPeerr MMiilllliioon
n
55..00 DDIIMMEENNSSIIOONNSS
1100
© Dimple
x Boiler
125mm 125mm
10mm
Condensate
Drain
CH Flow
(22mm)
Gas Inlet
(22mm)
CH Return
(22mm)
Tap Rail
446mm
264mm 182mm
7
96mm
1
50mm
94mm
333mm
148mm185mm
Tube Ø 100mm
FFiigg.. 44
FFiigg.. 55
66..00 SSYYSSTTEEMM DDEETTAAIILLSS
66..11 IINNFFOORRMMAATTIIOONN
1. The Dimplex System Boiler is a ‘Water Byelaws Scheme ­Approved Product’. Reference to the Water Research Council publications, ‘Water fittings and materials directory’ and ‘Water supply byelaws guide’ give full details of byelaws and the IRNs.
© Dimple
x Boiler
1111
66..33 SSYYSSTTEEMM CCOONNTTRROOLL
1. It
i
s r
ecommended that external controls e.g. room thermostat are fitted to further improve the operating efficiency of the boiler and system.
66..22 HHEEAATTIINNGG CCIIRRCCUUIITT
1. The appliance is suitable for fully pumped SEALED SYSTEMS ONLY.
Treatment of Water Circulating Systems
Failure to flush and add inhibitor to the system will invalidate the appliance warranty.
• Central heating water systems will be subject to corrosion unless an appropriate water treatment is applied. This means that the efficiency of the system will deteriorate as corrosion sludge accumulates within the system, risking damage to pump and valves, boiler noise and circulation problems.
• When fitting new systems flux will be evident within the system, which can lead to damage of system components.
• All systems must be thoroughly drained and flushed out. Using, for example Betz-Dearborn Sentinel X300 or X400 or Fernox Superfloc Universal Cleanser. They should be used following the flushing agent manufacturer’s instructions.
• System additives - corrosion inhibitors and flushing agents/descalers should comply to BS7593 requirements, e.g. Betz-Dearborn Sentinel X300 and Fernox-Copal which should be used following the inhibitor manufacturer’s instructions.
• It is important to check the inhibitor concentration after installation, system modification and at every service in ac
cor
dance with the manufacturer’s instructions. (Test kits are
available from inhibitor stockists.)
• F
or information or advice regarding any of the above contact
Technical Enquiries - Tel: 0844 3711121.
• If thermostatic radiator valves are fitted, a radiator must be fitted with two lock shield valves or the system must include a proprietary automatic bypass valve, to enable correct operation of the pump o
v
er-run
f
acility.
66..00 SSYYSSTTEEMM DDEETTAAIILLSS
66..44 SSYYSSTTEEMM FFIILLLLIINNGG AANNDD PPRREESSSSUURRIISSIINNGG
1. A filling point connection on the central heating return pipework must be provided for initial filling and pressurising and subsequent topping up of the system.
A filling loop is provided loose with the boiler
2. The filling method adopted must comply with all relevant water supply regulations and use approved equipment.
3. Further details are given in; for GB: Guidance G24.2 and recommendation R24.2 of the Water Regulations Guide. f
or IE: the current edition of I.S. 813 “Domestic Gas
Installations”.
4. The sealed primary circuits may be filled or topped up using a temporary connection between the circuit and a supply pipe, provided a ‘Listed’ double check valve or some other no less effective backflow prevention device is permanently connected at the inlet to the circuit and the temporary connection is removed after use.
1122
© Dimple
x Boiler
66..55 EEXXPPAANNSSIIOONN VVEESSSSEELL
1. The appliance expansion vessel is pre-charged to 1 bar. Therefore the minimum cold fill pressure is 2 bar. The vessel is suitable for correct operation for system capacities up to 84 litres. For greater system capacities an additional expansion vessel must be fitted. For GB refer to BS 7074 Pt 1. For IE, the current edition of I.S. 813 “Domestic Gas Installations”.
66..66 PPRREESSSSUURREE RREELLIIEEFF VVAALLVVEE
1. The pressure relief valve is set at 3 bar, therefore all pipew
ork,
fit
tings, etc. should be suitable for pressures in
excess of 3 bar and temperature greater than 100°C.
2. The pressure relief discharge pipe should be not less than 15mm diameter, run continuously downward, and discharge outside the building, preferably over a drain. It should be r
out
ed in such a manner
tha
t
no hazar
d occurs to occupants or causes damage to wiring or electrical components. The end of the pipe should terminate facing down and towards the wall.
NNOOTTEE:: BBooiilliinngg wwaatteerr//sstteeaamm ccoouulldd ddiisscchhaarrggee ffrroomm tthhee ppiippee,, tthheerreeffoorree iitt sshhoouulldd bbee tteerrmmiinnaatteedd aawwaayy ffrroomm wwiinnddoowwss aanndd ddoooorrss..
Mains
Supply
CH
Return
Pressure Relief Discharge Pipe
Temporary
Loop
Stop
Valve
Stop
Valve
Double
Check
Valve
GasCH
Flow
Condensate
1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
2
3
4
5
6
7
FLOW RATE Ltr/min
PUMP HEAD (mH
2
O)
System 18
System 30
AVAILABLE PUMP HEADS
FFiigg.. 88
FFiigg.. 77
Expansion Vessel
P
ressure
R
elief V
alve
Vessel charge and initial sy
s
t
em pressure
Total water content of system using 8 litres capacity expansion vessel supplied with appliance
For systems having a larger capacity multiply the t
otal system capacity in litres by this factor to obtain the total minimum expansion vessel capacity required in litres
bar
litres
0.5960.75
84
0.093
1.0731.5
50
FFiigg.. 66
FFiigg.. 99
FFiigg.. 1100
NNOOTTEE:: DDoo nnoott uussee tthhee pprreessssuurree rreelliieeff vvaallvvee ttoo ddrraaiinn tthhee ssyysstteemm,, bbeeccaauussee ddiirrtt aanndd ddeebbrriiss ccoouulldd pprreevveenntt tthhee vvaallvvee sseeaattiinngg ccoorrrreeccttllyy..
77..00 SSIITTEE RREEQQUUIIRREEMMEENNTTSS
77..11 LLOOCCAATTIIOONN
1. The boiler may be fitted to any suitable wall with the flue passing through an outside wall or roof and discharging to atmosphere in a position permitting satisfactory removal of combustion products and providing an adequate air supply. The boiler should be fitted within the building unless otherwise protected by a suitable enclosure i.e. garage or outhouse. (The boiler may be fitted inside an unvented cupboard - see section
7.3).
2. If the boiler is fitted in a room containing a bath or shower reference must be made to the relevant requirements. In GB this is the current I.E.E. Wiring Regulations and Building R
egulations.
In IE reference should be made to the current edition of I.S. 813 “Domestic Gas Installations” and current ETCI rules. (Fig. 11 shows zone dimensions for a bathtub. For other examples refer to Section 601 of the current I.E.E. Wiring Regulations) reference must be made to the relevant requirements. The boiler is IPX4 rated and can be fitted in Zone 2 (Fig. 11).
3. If the boiler
is to be fitted into a building of timber frame construction then reference must be made to the current edition of Institute of Gas Engineers Publication IGE/UP/7 (Gas Installations in Timber Framed Housing).
© Dimple
x Boiler
1133
77..22 CCLLEEAARRAANNCCEESS
1. A flat vertical area is required for the installation of the boiler.
2. These dimensions include the necessary clearance around the boiler for case removal, spanner access and air movement. Additional clearances may be required for the passage of pipes around local obstructions such as joists running parallel to the f
r
ont face of the boiler.
Zone 2
Zone 2
Zone 1
Zone 0
Zone 3
Zone 3
Window Recess
Zone 2
Window
Recess
Zone 2
0.6 m 2.4 m
Zone 2 Zone 3
Zone 2Zone 1
Zone 0
Zone 3
Outside Zones
Ceiling
Window Recess
Zone 2
3.0 m
2.25 m
0.6 m 2.4 m
285mm Wall
450mm Min
For Servicing
Purposes
5mm Min In Operation
5mm Min
446mm
5mm Min
796mm
200mm
200mm
5mm Min
5mm Min
285mm Wall
285mm Wall
FFiigg.. 1111
FFiigg.. 1122
77..00 SSIITTEE RREEQQUUIIRREEMMEENNTTSS
77..33 VVEENNTTIILLAATTIIOONN OOFF CCOOMMPPAARRTTMMEENNTTSS
1. Where the appliance is installed in a cupboard or compartment, no air vents are required. Where an open flued system is used - Flue kit E (B23 classification) then an air vent communicating directly with outside air must be provided in the same room or internal space of the flue duct air inlet. Minimum free area:
System 18 = 88cm
2
System 30 = 159cm
2
In addition if an open flued system is used - Flue kit (B23 classification) and the boiler is fitted in a compartment, then high and low le
vel ventilation is required.
BS 5440-2:2000 gives guidance on compartmental ventilation.
2. When the boiler is installed in a cupboard or compartment and either flue kit A, B, C, D or F (Classification C13, C33, C53) is used, then no compartmental ventilation is required.
1144
© Dimple
x Boiler
77..44 GGAASS SSUUPPPPLLYY
1. The gas installation should be in accordance with the relevant standards. In GB this is BS 6891. In IE this is the current edition of I.S. 813 “Domestic Gas Installations”.
2. The connection to the appliance is a 22mm copper tail located at the rear of the gas service cock (Fig. 13).
3. Ensure that the pipework from the meter to the appliance is of adequate size, and the demands of any other gas appliance in the property are taken into consideration. Do not use pipes of a smaller diameter than the boiler gas connection (22mm).
4. For boilers connected to use LPG (propane), the inlet pressure must be 37mbar.
NNOOTTEE::
The comple
ted installation should always be tested
for gas tightness
77..55 EELLEECCTTRRIICCAALL SSUUPPPPLLYY
1. External wiring must be correctly earthed, polarised and in accordance with relevant regulations/rules. In GB this is the current I.E.E. Wiring Regulations. In IE reference should be made t
o the cur
r
en
t
edition of the ET
GI rules.
2. The mains supply is 230V - 50Hz fused at 3A
NNOOTTEE::
The mains supply connection must allow complete electrical isolation of the appliance and system controls only. Connection may be via a fused double-pole isolator with a contact separation of at least 3mm in all poles and servicing the boiler
and sy
s
t
em con
t
rols only. Any additional mains cable should comply fully with the current I.E.E. wiring regulations.
FFiigg.. 1133
Gas Serv
ice
Cock
77..00 SSIITTEE RREEQQUUIIRREEMMEENNTTSS
77..66 CCOONNDDEENNSSAATTEE DDRRAAIINN
NNOOTTEE::
The appliance is fitted with a trap the depth of which is >= 75mm, therefore no other traps are required in the condensate run.
The condensation discharge pipe must not rise at any point along its length. There MUST be a fall of AT LEAST 2.5° (50mm per metre) along the entire run.
1. The condensate outlet will accept 21.5mm (3/4in) plastic overflow pipe which should discharge internally into the household drainage system, downstream of all other traps. if this is not possible, discharge into an outside drain is ac
ceptable.
2. Ensure the discharge of condensate complies with any national or local regulations in force. BBSS 66779988::22000000 && PPaarrtt HHII ooff tthhee BBuuiillddiinngg RReegguullaattiioonnss ggiivvee ffuurrtthheerr gguuiiddaannccee..
3. Metal pipework is NOT suitable for use in condensate discharge systems.
4. The pipe should be a minimum of 21.5mm diameter and must be supported properly.
5.
IItt iiss aaddvviissaabbllee ttoo kkeeeepp tthhee ccoonnddeennssaattee ppiippee iinntteerrnnaall..
6.
EExxtteerrnnaall rruunnss ggrreeaatteerr tthhaann 33 mmeettrreess oorr rruunnss iinn ccoolldd aarreeaass
sshhoouulldd uussee 3322mmmm wwaassttee ppiippee aanndd bbee iinnssuullaatteedd..
7. If the boiler is fitted in an unheated location the entire condensate discharge pipe should be treated as an external run.
8. In all cases discharge pipe must be installed to aid disposal of the condensate.
9. When discharging condensate into a soil stack or waste pipe the effects of existing plumbing must be considered. If soil pipes or waste pipes are subjected to internal pressure fluctuations when WC’s are flushed or sinks emptied then back-pressure may force water out of the boiler trap and cause appliance lockout. Ex
amples ar
e shown of the
f
ollowing methods of terminations
(se
e figs. 14,15 & 16): i) to an internal soil & vent pipe ii) via and internal discharge branch (e.g. sink waste) iii) to a drain or gully i
v) to a purpose made soakaway
10. In e
x
ceptional circumstances, such as when a boiler is installed in a basement without drainage, it may be necessary t
o ins
t
all a condensate pump to carry condensate up to ground/
d
r
ain le
v
el. Such pr
oducts ar
e a
v
ail
able
from most plumbing merchants. For help with selecting a condensate pump contact Dimplex Boilers - Tel: 0844 3711121.
WWAARRNNIINNGG::
There must be no air breaks in the condensate
pipework or drainage system (see Fig. 17).
© Dimple
x Boiler
1155
5
0
mm p
e
r me
tre
o
f p
ip
e
r
u
n
2.5° Minimum fall
4
50mm min
T
ermination to an internal soil and vent pipe
50mm per metre of pipe r
un
2.5° Minimum fall
External termination via internal discharge branch
e
.g sink waste - downstream
Sink
Pipe must terminate above water level but below surrounding surface.
50mm per metre of pipe r
un
2.5° Minimum fall
Termination to a purpose made soak-away
Holes in the soak-away must face away from the building
500mm min
NNOOTT AALLLLOOWWEEDD
TThheerree sshhoouulldd bbee
nnoo aaiirr ggaap
p
FFiigg.. 1144
FFiigg.. 1155
FFiigg.. 1177
FFiigg.. 1166
77..00 SSIITTEE RREEQQUUIIRREEMMEENNTTSS
77..77 FFLLUUEE
1. This high efficiency boiler will discharge a plume of water vapour from the flue. This should be considered when siting the flue terminal.
2. The following guidelines indicate the general requirements for siting balanced flue terminals. For GB recommendations are given in BS 5440 Pt 1. For IE recommendations are given in the current edition of I.S. 813 “Domestic Gas Installations”.
3. If the terminal discharges onto a pathway or passageway, check that combustion products will not cause a nuisance and that the terminal will not obstruct the passageway.
4. If a terminal is less than 2 metres above a balcony,above ground or above a flat roof to which people have access, then a suitable terminal guard must be provided - Part No: 951507.
IIMMPPOORRTTAANNTT::
• Only
OONNEE
of the 25mm clearances (Positions ‘O’ to ‘S’ in
the chart below) is allowable per installation.
• Under car ports we recommend the use of the plume displacement kit.
• The terminal position must ensure the safe and nuisance
- free dispersal of combustion products.
1166
© Dimple
x Boiler
NNOOTTEE:: TThhee mmiinniimmuumm ddiissttaannccee ffrroomm aa fflluuee tteerrmmiinnaall ttoo aa bboouunnddaarryy lliinnee iiss 330000mmmm..
IIff ffiittttiinngg aa pplluummee ddiivveerrtteerr kkiitt,, tthhee aaiirr iinnlleett sshhoouulldd bbee aa mmiinniimmuumm ooff 110000mmmm ffrroomm
aannyy ooppeenniinngg wwiinnddoowwss oorr ddoooorrss..
NNOOTTEE AA:: AA tteerrmmiinnaall sshhoouulldd bbee nnoo cclloosseerr tthhaann 115500mmmm ttoo aann ooppeenniinngg iinn tthhee bbrriicckkwwoorrkk iinntteennddeedd ttoo aaccccoommmmooddaattee aa ffiittttiinngg ssuucchh aass aa wwiinnddooww ffrraammee..
NNOOTTEE:: FFiittttiinngg ooff tthhee ddeefflleeccttoorr eellbbooww iiss rreeccoommmmeennddeedd wwhheenn iinnssttaalllliinngg bbooiilleerr ttoo mmiinniimmuumm cclleeaarraannccee ooff 2255mmmm aass ddeettaaiilleedd iinn ppoossiittiioonnss OO && PP..
A
M,L
M,L
N
C
F
P
O
O
R
N
S
C
C
N
Flue terminals that require a guard fitting
P
B
J
H
N
N
G
Q
K
D
E
PPoossiittiioon
n
DDeessccrriippttiioon
n
MMiinniimmuumm DDiissttaannccee ((mmmm)
)
A Horizontally to an opening, air brick, opening window - see note A 300 B
A
bo
ve an opening, air brick, opening window etc. - see note A 300
C
Below an opening, air
brick, opening window e
tc. - see note A 300
D Below windows or openings on pitched roofs 2000
E
A
djac
ent to windows or openings on pitched and flat roofs 600
F
F
r
om an adjacent opening window (vertical only) 1000 G From an adjacent wall to flue (vertical only) 300 H
Horiz
ontally from a terminal on the same wall 300
J
V
ertically from a terminal on the same wall 1500
K From an opening in a carport (e.g. door, window) into the dwelling 1200
L
From a terminal facing a terminal (horizontal flue) 1200 F
rom a terminal facing a terminal (vertical flue) 600
M
From a surface or boundary line facing a terminal 600 N Above ground, roof or balcony level 300 O From an internal or external corner 25
P From a vertical drain pipe or soil pipe 25 Q Below balconies or car port roof 25 R Below eaves 25
S Below gutters, soil pipes or drain pipes 25
300mm Min 300mm Min
Adjoining Properties Boundary Line
TTEERRMMIINNAALL PPOOSSIITTIIOONN
FFiigg.. 1188
FFiigg.. 1199
88..00 FFLLUUEE OOPPTTIIOONNSS
© Dimple
x Boiler
1177
88..11 CCOONNCCEENNTTRRIICC AAIIRR//FFLLUUEE DDUUCCTT SSPPEECCIIFFIICCAATTIIOONNSS
The different flue applications shown in Fig. 20 are available as kits comprising the connecting parts to the appliance and end terminal. Flue extension ducts and extension elbows are available as accessories.
88..22 KKiitt AA ++ TTeelleessccooppiicc HHoorriizzoonnttaall WWaallll TTeerrmmiinnaall ((CC1133)) -- PPaarrtt NNoo.. 995566112200
60/100mm concentric, horizontal flue system Fig. 21, with a maximum length of 10M. The standard telescopic terminal is 615mm max length and 430mm min length, but can be cut to a minimum flue length of 250mm, which is suitable for single, 100mm (4”), brick walls.
NNoottee::
If the telescopic flue kit is installed without any flue extensions, it can be fitted horizontally. The maximum length for 60/100mm horizontal concentric flue = 10M
NNoottee::
Dimplex System 18 only, with maximum concentric flue length of 10m, the heat input will be reduced by 7.6%
88..33 KKiitt BB VVeerrttiiccaall CCoonncceennttrriicc FFlluuee TTeerrmmiinnaall ((CC3333)) -- HHBBLL PPaarrtt 995566008811
60/100mm concentric, vertical flue system, Fig. 22, with a maximum length of 12M. The kit comprises of the roof terminal, vertical adaptor with sampling point and bracket. The ma
ximum length i
s me
asur
ed
f
rom the top of the appliance casing to the underside of the air cowl. For installation details refer to the flue kit instructions.
Chimney flue liner kit
- Part no. 956082
Vertical flue kit - Part no. 956081
V
ertical flue kit - Part no. 956081
with flat roof flashing plate
Split pipe vertical flue outlet kit
- Part no. 956080
with flat roof flashing plate
Raised external flue outlet kit
- Part no. 956084
Vertical flue kit - Part no. 956081
External vertical flue kit
- Part no. 956085
S
tandard telescopic horizontal flue kit
- Part no. 956120
O
ptional Flue Systems
The pluming from the flue may cause nuisance to neighbours or other buildings.
60/100 flue accessories:
0.5m flue extension duct - 956092 1m flue extension duct - 956093 9
3 flue extension elbow - 956091
4
5 flue extension elbow (2x) - 956090
Vertical flue turret - 956087
Ø60/100mm concentric standard horizontal wall terminal. M
ax. length 10,000mm.
M
in. length 250mm.
Standard telescopic horizontal flue kit - Part no. 956120
H
orizontal terminal has a built-in fall in the flue to allow condensate to drain away.
If horizontal flue requires extension pipe. the flue should be installed such that there is no section less than 1
.5° - 3° to the horizontal,
falling back towards the boiler.
9
3 flanged elbow (concentric)
with sampling point
Kit A +
Vertical flue kit - Part no. 956081
Suitable for 25 - 45°
Pitch Angle
Length
Kit B
60/100 flue accessories:
0.5m flue extension duct - 956092 1m flue extension duct - 956093 93 flue extension elbow - 956091 45 flue extension elbow (2x) - 956090 Pitched roof flashing kit - 956089 Flat roof flashing plate - 840512 93 flanged flue elbow - 956086 Max. length12m. Min. length 0.6m.
Roof terminal with rain cover and pitched roof flashing kit.
Vertical flue socket with sampling point.
Top of Boiler
to underside of Cowl
FFiigg.. 2200
FFiigg.. 2211
FFiigg.. 2222
88..00 FFLLUUEE OOPPTTIIOONNSS
1188
© Dimple
x Boiler
88..55 KKiitt CC HHoorriizzoonnttaall AAnnttii--PPlluummee FFlluuee KKiitt ((CC1133)) -- PPaarrtt NNoo.. 995566008844
This kit is recommended if the condensate plume from the flue may cause a nui
sance or affect the surroundings. The air inlet remains outside and the flue duct is routed separately using a 60mm duct enclosed by a protective 80mm tube. To calculate the maximum lengths of 60/100 concentric flue and 60mm flue ducts, use the table below.
For installation details refer to the flue kit instructions. Dimensions from vertical terminals to opening windows should be in line with Fig. 19.
(For use with Standard horizontal telescopic flue kit - Part no. 956120 - only).
This kit is useful for deflecting the condensate plume away from walls or boundaries. It should only be used to deflect the condensate plume left or right.
60/100mm concentric vertical flue system. Maximum length = 12m. The flue kit contains two additional 45° elbows and 2.5 metres of 60/100 concentric ducts as well as a special wall bracket to pass the guttering (see Fig. 26). The conc
en
t
ric
flu
e will be routed vertically alongside the outside wall to above the roofline. Special seals are required to prevent rainwater penetrating the pipe joints. F
or installation details refer to the flue kit instructions.
88..66 PPlluummee DDiivveerrtteerr TTeerrmmiinnaall KKiitt PPaarrtt NNoo.. 995566110033
88..77 KKiitt DD EExxtteerrnnaall VVeerrttiiccaall FFlluuee ((CC3333)) -- PPaarrtt nnoo.. 995566008855
9
3 flanged elbow (concentric)
w
ith sampling point
R
aised external flue outlet kit -
Part no. 956084
Kit C
Raised Ø60mm flue outlet duct with Ø
80mm anti-freeze pipe. Max height of raised flue from top of boiler to centre of outlet 8.5m M
in height 1m.
93 flanged elbow (concentric) with sampling point
Max. lengths (from top of boiler to AIR COWL 12m Min. length 1m.
Kit D
Ø60/100mm concentric air/flue pipe ­Part no. 956093 (1m extension) and Part no, 956092 (0.5m extension)
For outside installations the pipe joints have to be covered with special “lip-seal” to prevent rain ingress.
Ensure all horizontally fitted pipes are routed with a
1.5-3° fall towards the boiler.
External vertical flue kit - Part no. 956085
Roof terminal with rain cover.
88..44 TToottaall EEqquuiivvaalleenntt LLeennggtthhss ffoorr CCoonncceennttrriicc ((6600//110000mmmm)) fflluuee ssyysstteemmss
FFiigg.. 2244
FFiigg.. 2233
FFiigg.. 2255
FFiigg.. 2266
CCoommppoonneenntt
45° Bend
93° Bend
0.5m Extension
1.0m Extension
Support Bracket
EEqquuiivvaalleenntt lleennggtthh iinn mmeettrreess
0.5m
1.0m
0.5m
1.0m
N/A
PPaarrtt nnuummbbeerr
956090 - 2 off
956091
956092
956093
840517
CCoonncceennttrriicc ((6600//110000mmmm))
fflluuee lleennggtthh ((mmeettrreess))
00..33 00..55
4455°° BBeenndd
11..00 11..55 22..00 22..55 33..00 33..55 44..00 44..55 55..00
MMaaxxiimmuumm ((6600//8800mmmm)) fflluuee
lleennggtthh aalllloowweedd ((mmeettrreess))
99..22
EExxaammppllee:: IIff rreeqquuiirreedd lleennggtthh ooff 6600//110000mmmm ccoonncceennttrriicc == 11mm
tthheenn mmaaxxiimmuumm 6600//8800 lleennggtthh == 88..55mm
99..00 88..55 88 77..55 77 66..55 66 55..55 55 44..55
SSuuppppoorrtt BBrraacckkeett
9933°° BBeenndd
00..55mm EExxtteennssiioonn
11..00mm EExxtteennssiioonn
88..00 FFLLUUEE OOPPTTIIOONNSS
© Dimple
x Boiler
1199
88..88 KKiitt EE CChhiimmnneeyy FFlluuee LLiinneerr KKiitt ((BB2233)) -- PPaarrtt nnoo.. 995566008822
NNoottee:: Dimplex System 18 and 30: Maximum flue length = 30m. Minimum length for all Dimplex System boilers = 5m.
This kit is suitable for open flue application in accordance with BS5440 parts 1 & 2 where a room sealed flue installation is impractical. The kit comprises of a flue adaptor from the appliance to the chimney, a flexible plastic flue liner with connection parts and chimney terminal (see Fig. 27). Further guidance on ventilation requirements is given in section 7.3.
See ‘Total equivalent lengths for concentric (60/100mm) flue systems’
88..1100 KKiitt FF:: TTwwiinn FFlluuee SSyysstteemm ((CC5533)) -- PPaarrtt nnoo.. 995566008800
NNoottee:: Maximum flue length (air duct + flue duct) = 38m. Minimum
flue length (air duct + flue duct) = 10m.
The kit
compri
ses of a twin adapt
or suitable for 80mm ducts, from which the air intake is taken from the adjacent outside wall (see Fig. 28) and the flue duct is routed vertically through the roof. It
i
s
nnoott
r
ecommended t
o r
out
e the
flue duct through living
spac
e areas, i.e. bedrooms, living rooms etc. For installation details refer to the instructions provided with the twin flued kit.
Centralising brackets
Chimney terminal
93 flanged elbow (concentric) with sampling point
Ø60/100mm concentric chimney adaptor pipe.
T
he chimney must be swept
a
nd cleared of any debris
a
nd obstructions.
Chimney p
late
Flexible corrugated plastic flue liner Ø80mm according to EN 14471 Max. length 30m. Min. length 5m.
KIT E
Chimney flue liner kit - Part no. 956082
Ø80mm air intake
Split flue system
Roof terminal with pitched roof flashing kit.
If the flue pipe passes through compartment from wall/floors, the requirements set out in Building Regulations Part B must be followe
d.
Ø80mm twin adaptor with sampling point.
If the flue pipe are boxed in then access must be provided to inspect the flue ducts during installation and subsequent service visits. The access panels and flue boxing should be sealed from the room.
Split pipe vertical flue outlet kit ­Part no. 956080
Kit F
FFiigg.. 2277
FFiigg.. 2288
CCoommppoonneenntt
90° Bend
45° Bend
1.0m Extension
2.0m Extension
EEqquuiivvaalleenntt lleennggtthh iinn mmeettrreess
AAiirr DDuucctt
4.0m
2.0m
1.0m
2.0m
FFlluuee DDuucctt
8.0m
4.0m
2.0m
4.0m
PPaarrtt nnuummbbeerr
956100
956099
956101
956102
88..99 KKiitt EE:: KKeeyy fflluuee ddiimmeennssiioonnss ++ AAcccceessssoorriieess
Minimum length 60/100mm horizontal flue 100mm From boiler to chimney Maximum length 60/100mm horizontal flue 2000mm From boiler to chimney
Minimum length 60/100mm vertical flue 200mm From boiler to chimney Maximum length 60/100mm vertical flue 2000mm From boiler to chimney
Minimum length 80mm flue liner 5000mm From adaptor to chimney terminal Maximum length 80mm flu
e liner
30000mm
From adaptor to chimney terminal
AAcccceessssoorry
y
LLeennggtth
h
PPaarrtt NNuummbbeer
r
80mm Fle
xitube
flue liner 10m 956110 80mm Flexitube flue liner 20m 956111 80mm Flexitube flu
e liner 30m 956112
Boiler vertical flue adaptor/turret socket N/A 956087
99..00 IINNSSTTAALLLLAATTIIOONN
99..11 UUNNPPAACCKKIINNGG && IINNIITTIIAALL PPRREEPPAARRAATTIIOONN
TThhee ggaass ssuuppppllyy,, ggaass ttyyppee aanndd pprreessssuurree mmuusstt bbee cchheecckkeedd ffoorr ssuuiittaabbiilliittyy bbeeffoorree ccoonnnneeccttiioonn
1. Remove the top cardboard tray from the carton.
2. The wall fixing jig is packed in its own cardboard sleeve. Carefully slide this out of the carton.
3. To avoid scratching the boiler outercase, keep the outer carton in place.
4. After reviewing the site requirements (see Section 7.0), pos
ition the fixing template on the wall ensuring it is level both
horizontally and vertically.
5. Mark the position of the fixing holes for the wall plate and boiler lower fixing holes.
6. Mark the position of the centre of the flue hole (rear exit). For side flue exit, mark as shown (Fig. 4).
7. If r
equired, mark the position of the gas and water pipes.
Remove the template.
8. Cut the hole for the flue (minimum diameter 110mm).
9. Drill the wall as previously marked to accept the wall plugs supplied. Secure the wall fixing jig using the fixing screws.
10. Using a spirit level ensure that the fixing jig is level before finally tightening the screws.
11. Flush and clean the system using an appropriate cleanser (Fig. 30).
12. Connect the gas and water pipes to the valves on the wall fixing jig.
13. Fit the filling loop as described in the instructions supplied with it.
2200
© Dimple
x Boiler
FFiigg.. 3300
Flushing Pipe
C
en
tral Heating Flow
or Return Pipe
FFiigg.. 2299
99..00 IINNSSTTAALLLLAATTIIOONN
99..22 FFIITTTTIINNGG TTHHEE BBOOIILLEERR
1. Remove the sealing caps from the boiler connections.
NOTE: A small amount of water may drain from the boiler once the caps are removed.
2. Check the sealing washers are located correctly in the taps on the wall jig.
3. Lift the boiler as indicated by the shaded areas. The boiler should be lifted by TWO PEOPLE. Engage the slots at the top rear of the boiler on the wall plate (Fig. 31) (see
SSaaffee MMaannuuaall
HHaannddlliinngg
page 6).
4. Ensure the boiler is correctly located on the wall jig and the connections align. Tighten all the connections.
© Dimple
x Boiler
2211
99..33 FFIITTTTIINNGG TTHHEE PPRREESSSSUURREE RREELLIIEEFF DDIISSCCHHAARRGGEE PPIIPPEE
1. Remove the two screws securing the front panel to the underside of the boiler. Rotate the bottom of the panel out slightly and lift the panel upwards off its retaining studs on top of the appliance.
2. Determine the route of the discharge pipe.
3. Taking care not to disturb the case sealing grommet, the pipework must be at least 15mm diameter and run continuously downwards to a discharge point outside the building.
4. Complete the discharge pipework and route it to the outside discharge point.
99..44 CCOONNDDEENNSSAATTEE DDRRAAIINN
1. Connect the condensate drain to the trap outlet pipe.
Ensure the discharge of condensate complies with any national or local regulations in force.
2. The connection will accept 21.5 - 22mm plastic overflow pipe which should g
ener
ally di
schar
ge internally into the household drainage system. If this is not possible, discharge into an outside drain is acceptable.
FFiigg.. 3333
Pressure Relief Di
schar
g
e Pipe
Front Panel Retaining Stud
XX 22
XX 22
FFiigg.. 3311
FFiigg.. 3322
99..00 IINNSSTTAALLLLAATTIIOONN
99..55 FFIITTTTIINNGG TTHHEE FFLLUUEE
HHOORRIIZZOONNTTAALL TTEELLEESSCCOOPPIICC FFLLUUEE
1. For correct flue installation please refer to the installation instructions that are provided with the individual flue kit as described in sections 7 & 8.
2. Measure the required flue length as shown in Fig. 34. Refer to section 8 to determine whether any extension kits are required. Installations using only the standard ducts or standard ducts with straight extensions are described in this section. Installation instructions for all other flue systems are included in the various flue kits.
3. Ensure that all (inner and outer tube) sealing rings are provided and assemble the air/flue ducts as shown in the flue instructions.
4. Ensure that the flue and air seals are correctly fitted before assembly and that each section is fully engaged.
NOTE: NEVER CUT THE SWAGED END. Where necessary the plain ends of the extension ducts may be cut. Always ensure that the cut is square and free of burrs or debris. It is essential that the terminal is fitted the correct way up. See flue kit instructions (i.e. rain shield at the top).
IINNSSTTAALLLLIINNGG TTHHEE AAIIRR//FFLLUUEE DDUUCCTT FFRROOMM IINNSSIIDDEE TTHHEE RROOOOMM Detailed installation instructions are included in the flue kit. (Flue hole diameter 130mm).
1. Push the terminal through the wall taking care to ensure that the terminal is the correct way round and the external wall-sealing ring does not become dislodged.
2. Assemble the flue system extension ducts as necessary, referring to Fig. 35.
3. Pull the flue system towards the appliance to seat the e
xternal sealing ring against the outside wall, ensuring that the
duct joints are not disturbed.
4. Use the internal sealing ring to make good the internal hole and check that the terminal is correctly located on the outside wall. W
here possible this should be visually checked from
outside the building (Fig. 35).
5. Finally loca
te and secure the elbow to the appliance using
the four screws provided.
IINNSSTTAALLLLIINNGG TTHHEE AAIIRR//FFLLUUEE DDUUCCTT FFRROOMM OOUUTTSSIIDDEE TTHHEE BBUUIILLDDIINNGG Detailed installation instructions are included in the flue kit. Flu
e hole diameter 100mm - 110mm.
1. Secure the flue elbow with seal to the appliance using 4 scr
ews.
2. Fit
the e
xt
er
nal wall se
aling ring o
ver the flue and then from
outs
ide the building, push the flue system through the wall taking care to ensure that the terminal is the correct way ar
ound.
3. Loosely fit the internal wall sealing ring over the inside end of the
flu
e.
4. Assemble the flue system extension ducts as necessary r
eferring to the flue kit instructions and fit to the elbow.
5. Fit the flue terminal to the flue system, ensuring that the duct
joints are not disturbed and that the external sealing ring
is seated against the outside wall.
6. Finally use the in
ternal sealing ring to make good the internal hole. Check that the external wall sealing ring and the t
er
minal is correctly located on the outside wall.
2222
© Dimple
x Boiler
FFiigg.. 3344
FFiigg.. 3355
‘L’ = Total flue length from flue outlet
centre to outside wall face
LL
Fibre Seal
Fitted
22
Align the assembled flue system elbow to appliance and secure
33
Slide internal wall
sealing ring to wall to
form a good seal
11
Insert assembled flue
system from inside the
r
oom. Ext
ernal wall
sealing ring opens
External Wall
Sealing Ring
Terminal
To p Internal Wall Sealing Ring
99..00 IINNSSTTAALLLLAATTIIOONN
99..66 MMAAKKIINNGG TTHHEE EELLEECCTTRRIICCAALL CCOONNNNEECCTTIIOONNSS
The boiler is fitted with a 1.5m length of 3 core cable. This can be connected to the fused 3A 230V 50Hz supply.
To connect an external control proceed as follows:-
1. Lower the drop down door.
2. Remove the two screws holding the controls box and ease the box away from the boiler. The electrical connections are made at the left hand side on the rear of this box.
3. Slacken the cable clamp on the terminal block (Fig. 36). Insert
the external control wiring through the clamp and route
it to the terminal block. Tighten the cable clamp.
4. Refer to the instructions supplied with the control.
IIMMPPOORRTTAANNTT::
The room thermostat
MMUUSSTT
be suitable for
230V switching.
Ensure that the external control input cable (s) have suf
ficient slack to allow the control box to drop down.
5. Route external control cables away through the mains cable grommet supplied.
© Dimple
x Boiler
2233
99..77 PPRREELLIIMMIINNAARRYY EELLEECCTTRRIICCAALL CCHHEECCKKSS
1. Prior to commissioning the boiler preliminary electrical sy
s
tem checks should be carried out.
2. These should be performed using a suitable meter, and include checks for Earth Continuity, Resistance to Earth, Short Circuit and Polarity.
L1 brown
L2 red
green/yellow
green/yellow (earth)
Fused supply 3A 230V~50Hz
brown (live)
red linkwire230V - Switch Live
230V - To external control
Permanent live
blue (neutral)
N blue
L3 orange
Connect external control using L2 & L3
Disconnect link wire
To boiler
FFiigg.. 3377
FFiigg.. 3366
1100..00 CCOOMMMMIISSSSIIOONNIINNGG
1100..11 CCOOMMMMIISSSSIIOONNIINNGG TTHHEE BBOOIILLEERR
IIMMPPOORRTTAANNTT:: TThhee aaiirr vveenntt oonn ttoopp ooff tthhee bbooiilleerr mmuusstt bbee OOPPEENN wwhheenn ffiilllliinngg tthhee ssyysstteemm.. AAttttaacchh aa ttuubbee ttoo tthhee aaiirr vveenntt ttoo ssaaffeellyy ccoolllleecctt aannyy eexxcceessss wwaatteerr ((FFiigg.. 3388))..
GGaass TTiigghhttnneessss
1. Ensure the gas service cock on the boiler is turned on (Fig. 40). The entire gas installation must be tested for gas tightness and purged in accordance with BS6891.
2. Open the service cocks to the CH flow and CH return supplies.
3. C
onnect the filling loop and fill and vent the CH system.
NNOOTTEE::
Ensure the boiler is completely vented using the
manual air vent on top of the boiler.
4. Drain, flush and refill the boiler and system in accordance with BS7593 (Fig. 30).
NNOOTTEE::
Failure to flush the system and to add inhibitor will
in
validate the appliance warranty.
5. Pressurise the system to 1.5 bar (Fig. 42).
EElleeccttrriiccaall SSaaffeettyy CChheecckkss oonn tthhee CCoonnttrroollss SSyysstteemm aanndd BBooiilleerr
6. Carry out earth continuity, resistance to earth, short circuit and polarity checks using a suitable meter.
7. Switch on the electricity supply to the boiler.
8. Set the controls to call for heat. The boiler will now operate. Check the system for correct operation.
9. Replace the outer door and two securing screws.
2244
© Dimple
x Boiler
0
1
2
bar
3
4
Air Vent
Tube
FFiigg.. 3399
FFiigg.. 3388
FFiigg.. 4400
FFiigg.. 4411
FFiigg.. 4422
FFiigg.. 4433
CH Return
CH Flow
Gas Inlet
Boiler Drain Point
0
1
2
bar
3
4
1100..00 CCOOMMMMIISSSSIIOONNIINNGG
1100..22 FFAACCTTOORRYY SSEETTTTIINNGGSS
1. With the boiler firing at maximum gas rate, check that the inlet pressure at the appliance is 19mbar +/- 1mbar when measured at the inlet pressure test point (Fig. 44). To set the boiler to maximum gas rate see section
11.0 (Service Mode).
2. Check the maximum and minimum gas rate at the gas meter according to the table below using a stopwatch.
NNOOTTEE::
This boiler is supplied factory set for operation on natural gas. No further adjustments of the air/gas ratio valve or measurement of the combustion performance are necessary at the time of installation and commissioning. This is provided the appliance has been installed according to these instructions and the inlet gas pressure is within our specification.
© Dimple
x Boiler
2255
NNOOTTEE::
If any doubts exist over the above checks then the combustion of the appliance can be measured as described in Section 12.0 of these ins
t
ructions pr
o
viding;
• The person carrying out the measurement has been
assessed as competent in the use of a flue gas analyser and the interpretation of the results.
• The flue gas analyser used, meets the requirements of
BS7927 or BS-EN50379-3.
The
flu
e g
as analy
ser
i
s calibrated in accordance with the
manufacturers requirements.
1100..33 IINNLLEETT PPRREESSSSUURREE AANNDD GGAASS RRAATTEE CCHHEECCKKSS
1. On completion of the gas inlet pressure and gas rate checks, it is necessary to check the following:
• The appliance installation conforms to these instructions.
The installation and integrity of the full flue system including the se
als in the
flue pipes.
The boiler
combustion circuit, including the burner door
seal, combustion door seal.
2. The recorded combustion values should be compared with the v
alues in Table 1 and Table 2 (see Section 12.2).
3. If the combustion value(s) is outside the values specified in Section 12.2 (Tables 1 & 2), do not attempt to adjust the air/g
as r
a
tio valve, please ring the helpline number -
00884444 337711 11112211.. IIff iinn ddoouubbtt -- AASSKK..
1100..44 CCOOMMBBUUSSTTIIOONN CCHHEECCKKSS DDUURRIINNGG CCOOMMMMIISSSSIIOONNIINNGG
GGaass RRaatteess ((NNaattuurraall GGaass)) aafftteerr 55 mmiinnuutteess ffrroomm ccoolld
d
MMaaxxiimmuumm RRaatte
e
BBooiilleerr MMooddeel
l
m3/h ft3/h m3/h ft3/h
SSyysstteemm 1188
1.95 68.8 0.57 20.1
SSyysstteemm 3300
3.2 113 0.8 28.2
MMiinniimmuumm RRaatte
e
FFiigg.. 4444
NNOOTTEE::
Factory set - warranty
void if adjusted
Throttle Adjuster Screw
GGaass VVaallvvee
Inlet Test Point
1111..00 SSEERRVVIICCEE MMOODDEE
2266
© Dimple
x Boiler
NNOOTTEE::
Service Mode automatically stops after 10 minutes and the boiler returns to normal operation.
1. Turn the CH knob fully clockwise - Note the knob will turn past the maximum temperature mark (Fig. 45).
2. The CH light will flash continuously - the boiler is now running at minimum rate.
1. Set the boiler into Service Mode at Minimum Rate.
2. Whilst in Service Mode at Min Rate, turn the CH knob to 12 ‘O’ clock position and then back to fully clockwise (past the maximum temperature indicator) within 3 seconds. The boiler will now run at maximum gas rate for 10 minutes.
3. To exit Service Mode, turn the CH knob anti-clockwise to the temperature previously set by the customer. The CH light will now stop flashing.
1111..11 TTOO SSEETT TTHHEE BBOOIILLEERR AATT MMIINNIIMMUUMM GGAASS RRAATTEE
1111..22 TTOO SSEETT TTHHEE BBOOIILLEERR AATT MMAAXXIIMMUUMM GGAASS RRAATTEE
FFiigg.. 4455 FFiigg.. 4466
0
1
2
bar
3
4
1122..00 SSEERRVVIICCIINNGG AANNDD MMAAIINNTTEENNAANNCCEE
1122..11 RROOUUTTIINNEE SSEERRVVIICCIINNGG AANNDD AALLLL MMAAIINNTTEENNAANNCCEE TTHHAATT IINNVVOOLLVVEESS TTHHEE EEXXCCHHAANNGGEE OOFF PPAARRTT OOFF TTHHEE CCOOMMBBUUSSTTIIOONN CCIIRRCCUUIITT
1. During routine servicing, e.g. an annual service check, and
after all maintenance that involves the exchange of parts of the combustion circuit, we recommend that (in this order) the integrity of the full flue system and combustion circuit seals, the inlet gas pressure, gas rate and combustion performance is verified.
NNOOTTEE::
The combustion circuit on this appliance comprises of the PCB, fan, air/gas ratio valve, burner, burner door, combustion box door, injector and flue system.
2. T
o ensure continued safe and efficient operation of the appliance it is recommended that the boiler is serviced at least annually. Servicing must be performed by a competent person. BS 7967-1 gives guidance on identifying and managing sources of fumes, smells, spillage/leakage of combustion products and carbon monoxide detector activation.
SSaaffeettyy CChheecckkss On any service visit always check;
a. Condition of flue system, both air and combustion products ducts. b. Condition of seals and joints. c. For evidence of leakage of combustion products. d. For evidence of heat staining. e. For operation at maximum heat input. f. The general condition of the boiler and its components.
11.. CCoommbbuussttiioonn cchheecckkss mmuusstt bbee ccaarrrriieedd oouutt wwiitthh tthhee oouutteerrccaassee ffiitttteedd..
2. Remove the sampling cap from the boiler flue elbow or boiler vertical flue adaptor.
3. Insert the pr
obe
f
r
om the port
able electronic combustion
analyser into the sampling point.
4. W
ith the appliance operational, connect the flue gas
analyser to the flue sampling point as shown in Fig. 47.
NNOOTTEE::
The out
er
case mus
t
be
fit
t
ed
f
or all combustion
checks.
5. W
ith the boiler
a
t
minimum r
ate and then at maximum rate (allowing the combustion to stabilise at each rate before taking a reading) carry out the combustion checks as follows:
CCOOMMBBUUSSTTIIOONN CCHHEECCKKSS AATT MMIINNIIMMUUMM RRAATTEE
6. The combus
tion v
alues at minimum gas rate and maximum
g
as r
a
t
e mus
t
be checked us
ing a suit
able calibrated flue gas
analyser. Further guidance is detailed in BS7967 parts 1 to 4.
7. Se
t
the boiler
in
to Service Mode at Min Rate
(see section 11.1).
8. Check the Carbon Monoxide (CO) and Carbon Dioxide (CO
2
) readings are within the range quoted in the tables opposite (T
able 1).
© Dimple
x Boiler
2277
1122..22 CCOOMMBBUUSSTTIIOONN CCHHEECCKKSS
0
1
2
b a r
3
4
FFiigg.. 4477
Flue Gas Sampling Point
MMiinniimmuumm GGaass RRaatte
e
NNG
G
Boiler Model
(kW)
1188
3300
Carbon
Monoxide
CO
p.p.m
0 - 40
0 - 40
Carbon Dioxide
C
O
2
%
8.5 - 8.9
8.7 - 9.1
LLPPG
G
Carbon
Monoxide
CO
p.p.m
80 - 160
80 - 160
Carbon Dioxide
C
O
2
%
10.4 - 10.8
10.3 - 10.7
MMaaxxiimmuumm GGaass RRaatte
e
NNG
G
Boiler Model
(kW)
1188
3300
C
arbon
Monoxide
C
O
p.p.m
15 - 60
15 - 60
C
arbon
Dioxide
CO
2
%
8.8 - 9.2
8.8 - 9.2
LLPPG
G
C
arbon
Monoxide
C
O
p.p.m
80 - 160
80 - 160
C
arbon
Dioxide
CO
2
%
10.8 - 11.2
10.5 - 10.9
TTaabbllee 11
TTaabbllee 22
1122..00 SSEERRVVIICCIINNGG AANNDD MMAAIINNTTEENNAANNCCEE
1122..22 CCOOMMBBUUSSTTIIOONN CCHHEECCKKSS
CCOOMMBBUUSSTTIIOONN CCHHEECCKKSS AATT MMAAXXIIMMUUMM RRAATTEE
9. Set the boiler to Maximum gas rate.
10. Check the Carbon Monoxide (CO) and Carbon Dioxide (CO2) readings are within the range quoted in the tables opposite (Table 2).
11. If the combustion value(s) is outside the values specified in Tables 1 and 2 and the integrity of the full flue system and combustion circuit seals, the inlet gas pressure and gas rate have been verified, it is possible to make an adjustment to the combustion settings by adjustment of the air/gas ratio valve. See Section 12.3 Adjustment of the Gas Valve.
2288
© Dimple
x Boiler
1122..33 AADDJJUUSSTTMMEENNTT OOFF TTHHEE GGAASS//AAIIRR RRAATTIIOO VVAALLVVEE
CCOOMMBBUUSSTTIIOONN SSEETTTTIINNGG AADDJJUUSSTTMMEENNTT
1. Adjustment of the offset screw is not allowed.
2. If the ma
ximum rate setting is adjusted, then the
combustion values must be checked at minimum rate.
NNOOTTEE::
DO NOT ATTEMPT TO FIT OR ADJUST THE GAS/AIR
RATIO VALVE UNLESS;
• The person carrying out the measurement has been assessed as competent in the use of a flue gas analyser and the interpretation of the results.
• The flue gas analyser used, meets the requirements of BS7927 or BS-EN50379-3.
• The flue gas analyser is calibrated in accordance with the manufacturers requirements.
3. At Maximum Gas Rate; put the appliance into Service Mode at Maximum Gas Rate (see Section 11.2).
4. W
ait
5 minut
es t
o allow the boiler to stabilise.
5. If the Carbon Dioxide (CO
2
) level is outside the required
v
alu
es gi
ven in Section 12.2 (Table 2) then adjust the throttle screw (Fig. 48) until the CO2is at the correct setting level. See Table 4. Clockwise to decrease CO2, anti-clockwise to increase CO2.
NNOOTTEE::
Only turn the throttle in small steps of
nnoo mmoorree tthhaann
11//88
tthh
ooff aa ttuurrnn
and wait
1 minut
e aft
er
e
ach adjus
tmen
tfor
the combustion reading to stabilise.
IIMMPPOORRTTAANNTT::
After any adjustment of the gas valve, it is essential to check the combustion levels at minimum gas rate (Table 1). If the Carbon Monoxide or Carbon Dioxide levels are outside the range quoted, call Dimplex Boilers Ltd Technical Helpline on 0844 3711121. If in doubt ASK!
TTaabbllee 44
FFiigg.. 4488
NNOOTTEE::
Factory set - warranty
v
oid if adjusted
Throttle Adjuster Screw
GGaass VVaallvvee
Inlet Test Point
CCaarrbboonn DDiiooxxiiddee ((CCOO22)) aacccceeppttaabbllee sseettttiinngg lleevveell aatt MMaaxxiimmuumm
GGaass RRaattee aafftteerr 55 mmiinnuutteess ooppeerraattiioon
n
NNaattuurraall GGaass %
%
BBooiilleerr MMooddeel
l
SSyysstteemm 1188
9.0 11.0
SSyysstteemm 3300
9.0
10.7
LLPPGG ((PPrrooppaannee)) %
%
1122..00 SSEERRVVIICCIINNGG AANNDD MMAAIINNTTEENNAANNCCEE
1122..11 AANNNNUUAALL SSEERRVVIICCIINNGG
8. Remove the two screws securing the front panel to the underside of the boiler. Lift the panel upwards off its retaining studs on top of the appliance.
9. Disconnect the two leads to the fan and one lead to the gas valve.
10. Undo the nut on the gas inlet pipe to the valve and retain the sealing washer.
11. Remove the four nuts holding the burner door plate and remove the valve and fan assembly (Fig. 51).
12. Clean any debris from the heat exchanger using a soft brush and check that the gaps between the tubes are clear.
13. Inspect the burner, electrode positions and insulation, cleaning or replacing if necessary.
14. Check the condition of the burner door seals, replacing if necessary. Check for gas tightness and check combustion cir
cuit is sealed.
15. Reassemble in reverse order.
16. To check if the condensate pipe is clear, carefully remove the pipe from the bottom of the primary heat exchanger. Blow down the pipe to ensure it is clear. If required loosen any debris with a small conical brush and flush through with water. Before reassembly, fill the condensate pipe with water to ensure a water trap is formed. Finally, ensure the grommet fitted to the condensate pipe is correctly located into the hole in the bottom of the boiler case.
17. Complete the relevant Service Interval Record section of the Benchmark Commissioning Checklist at the rear of this publication and then hand it back to the user.
© Dimple
x Boiler
2299
FFiigg.. 5511
FFiigg.. 4499
FFiigg.. 5500
FFiigg.. 5522
Gas Inlet Nut
Front Panel
Retaining Stud
XX 44
XX 22
XX 22
Burner Door Seal
Inner Seal
1133..00 CCHHAANNGGIINNGG CCOOMMPPOONNEENNTTSS
IIMMPPOORRTTAANNTT::
When changing components ensure that both the gas and electrical supplies to the boiler are isolated before any work is started.
See Section 12 : “Annual Servicing” for removal of case, panel, door etc.
3300
© Dimple
x Boiler
1133..11 IIGGNNIITTEERR
1. Disconnect the two feed wires, earth wire and electrode lead noting their positions (Fig. 53).
2. Undo the two screws securing the igniter to its bracket and remove the igniter. Reassemble in reverse order.
1133..22 SSPPAARRKK AANNDD SSEENNSSIINNGG EELLEECCTTRROODDEESS
1. Disconnect the electrode leads, noting their positions (Fig. 56).
2. Using a 3mm Hex key, remove the retaining screws securing each of the electrodes to the burner door and remove the electrodes.
3. Check the condition of the sealing gaskets and replace if necessary. Reassemble in reverse order and then check that the electrode gaps are as shown in Fig. 54 & 55.
FFiigg.. 5533
FFiigg.. 5544
FFiigg.. 5555
FFiigg.. 5566
Igniter
Gasket
6mm ± 0.5
to Burner
4mm ± 0.5
10mm ± 0.5
1133..00 CCHHAANNGGIINNGG CCOOMMPPOONNEENNTTSS
1133..33 GGAASS VVAALLVVEE AANNDD FFAANN
1. Disconnect the two leads to the fan and one lead to the gas valve.
2. Undo the nut on the gas inlet pipe to the valve and retain the sealing washer.
3. Remove the three securing screws holding the air/gas Channel to the burner door plate and remove the valve and fan assembly (Fig. 57).
4. Remove the three screws holding the valve and swirl plate to the fan adaptor plate.
NNOOTTEE::
Mark on the adaptor plate which holes are being used by the screws. Using the wrong holes on re-assembly will cause mis-alignment of the gas valve.
FFaann OOnnllyy
6. Remove the three screws holding the fan adaptor to the fan.
7. Remove the four screws securing the fan to the air/gas channel. R
eassemble in reverse order ensuring all seals are in
place.
NNOOTTEE::
The gas valve throttle should be adjusted in accordance with the instructions supplied in the spares kit See Section 10.
© Dimple
x Boiler
3311
FFiigg.. 5577
Swirl Plate
F
an
Fan Gasket
Burner Door
Air/Gas Channel
Fan Adaptor Plate
Injector Plate
Inject
or
Injector ‘O’ Ring
Gas Valve
1133..00 CCHHAANNGGIINNGG CCOOMMPPOONNEENNTTSS
1133..44 BBUURRNNEERR
1. Remove the valve and fan assembly as described in Section
13.3.
2. Examine the gasket and replace if necessary.
3. Undo the four nuts securing the burner door and remove from the heat exchanger.
4. Slowly withdraw the burner from the burner plate taking care not to damage the insulation (Fig. 58).
5. Reassemble in reverse order.
3322
© Dimple
x Boiler
1133..55 IINNSSUULLAATTIIOONN
1. Remove the electrode leads, noting their positions. Remove the electrodes as described in section 13.2.
2. R
emove the valve and fan assembly as described in Section
13.3.
3. Examine the gasket and replace if necessary.
4. Undo the four nuts securing the burner door and remove from the heat exchanger.
5. Slowly withdraw the burner from the burner door.
6. Replace the insulation if necessary.
7. Check the burner door seals.
8. The rear insulation is retained by a screw and large washer, remove these and draw the insulation out of the heat exchanger (Fig. 59).
9. Reassemble in reverse order.
Burner
Insulation
Gasket
Air/Gas Channel
Rear Insulation
Washer
Insulation
Retaining Screw
Burner Assembly
Burner Door
Burner Door Seal
FFiigg.. 5588
FFiigg.. 5599
Inner Seal
1133..00 CCHHAANNGGIINNGG CCOOMMPPOONNEENNTTSS
1133..66 FFLLUUEE//HHEEAATT TTEEMMPPEERRAATTUURREE TTHHEERRMMOOSSTTAATT
1. Disconnect the electrical plug.
2. Turn the sensor 90° anticlockwise to remove - it is a bayonet connection (Fig. 60).
3. Reassemble in reverse order.
© Dimple
x Boiler
3333
1133..77 TTHHEERRMMAALL FFUUSSEE
1. The thermal fuse is non-changeable. If the fuse fails contact Dimplex Technical Department.
1133..88 CCEENNTTRRAALL HHEEAATTIINNGG FFLLOOWW TTEEMMPPEERRAATTUURREE TTHHEERRMMIISSTTOORR
1. Di
sconnect the electrical plug.
2. Ease the sensor clip away from the pipe and remove (Fig. 61).
3. Reassemble in reverse order.
1133..99 CCEENNTTRRAALL HHEEAATTIINNGG RREETTUURRNN TTEEMMPPEERRAATTUURREE TTHHEERRMMIISSTTOORR
1. Disconnect the electrical plug.
2. Ease the sensor clip away from the pipe and remove (Fig. 61).
3. Reassemble in reverse order.
0
1
2
bar
3
4
FFiigg.. 6600
FFiigg.. 6611
‘O’ Ring
Thermal Fuse
Central Heating Flow
Temperature Thermistor
C
en
t
r
al Heating Return
Temperature Thermistor
Flue/Heat Temperature
Thermostat
1133..00 CCHHAANNGGIINNGG CCOOMMPPOONNEENNTTSS
1133..1100 PPUUMMPP -- HHEEAADD OONNLLYY
1. Drain the primary circuit and disconnect the wiring connector from the pump head.
2. Remove the four socket head screws securing the pump head to the body and draw the head away (Fig. 62).
3. A replacement Grundfos 15-60 head can now be fitted (Fig. 62)(Part No: 500672).
4. Reassemble in reverse order.
5. Replace the wiring connector into the socket on the pump he
ad.
3344
© Dimple
x Boiler
1133..1111 HHYYDDRROOBBLLOOCCKK
1. Dr
ain the primary circuit.
2. Remove the stainless clip at the base of the hydro-block and di
sconnect the pipe (Fig. 63).
3. Un-lock the locking clip on the return port.
4. Disconnect the discharge pipe from the pressure relief valve.
5. Remove the two securing screws from below the boiler.
6. Carefully remove the hydro-block and change the relevant components.
7. Reassemble in reverse order taking care to replace all the clips correctly. Ensure the locking clip is in the ‘Locked’ position as shown opposite.
Pump Head
F
r
on
t
Stainless Clip
R
ear
Stainless Clip
Un-Locked
(v
iewed from pipe end)
Locked
(v
iewed from pipe end)
XX 22
FFiigg.. 6622
FFiigg.. 6633
1133..00 CCHHAANNGGIINNGG CCOOMMPPOONNEENNTTSS
1133..1122 AAUUTTOOMMAATTIICC AAIIRR VVEENNTT
1. Drain the primary circuit and rotate the automatic air vent
1
/
4
turn and remove from the pump body.
2. Examine the ‘O’ ring seal, replacing if necessary, and fit it to the new automatic air vent.
3. Reassemble in reverse order.
© Dimple
x Boiler
3355
1133..1133 PPRREESSSSUURREE GGAAUUGGEE
1. Drain the primary circuit and undo the nut on the pressure gauge capillary.
2. Examine the ‘O’ ring seal, replace if necessary.
3. Unclip the facia from the control box
4. Lever the barbs securing the gauge to remove the gauge from the control box (Fig. 64).
5. Reassemble in reverse order.
1133..1144 PPRREESSSSUURREE RREELLIIEEFF VVAALLVVEE
1. Drain the primary circuit.
2. Disconnect the discharge pipe from the valve. Ease off the retaining clip (Fig. 66).
3. No
t
e the orien
t
a
tion of the v
alv
e, rotate it and withdraw it
from the manifold.
4. Fit
the new v
alv
e and ‘O’ ring and set to the previously
noted orientation. Reassemble in reverse order.
FFiigg.. 6644
FFiigg.. 6655
FFiigg.. 6666
Automatic Air Vent
‘O’ Ring
Pressure Gauge
Pressure
R
elief Valve
R
e
t
aining Clip
‘O’ Ring
Di
schar
g
e Pipe
Capillary
‘O’ Ring
‘O’ Ring
1133..00 CCHHAANNGGIINNGG CCOOMMPPOONNEENNTTSS
3366
© Dimple
x Boiler
1133..1166 EEXXPPAANNSSIIOONN VVEESSSSEELL
1. Drain the primary circuit and undo the nut on the vessel connection pipe.
2. Remove the two screws holding the retaining bracket and remove the bracket (Fig. 67).
3. Carefully slide out the vessel from the boiler.
4. Reassemble in reverse order.
Expansion Vessel
Vessel Connection Pipe
Retaining
Bracket
FFiigg.. 6677
FFiigg.. 6688
Flue Elbow
Flue Adaptor
Main He
a
t
Exchanger
Left
Hand
R
e
t
aining Br
acke
t
Right Hand Retaining Bracket
Flow Pipe R
e
t
aining Clip
Return Pipe Retaining Clip
Manual Air Vent
1133..1177 MMAAIINN HHEEAATT EEXXCCHHAANNGGEERR
1. Drain the primary circuit.
2. Remove the electrode leads, noting their positions as described in section 13.2.
3. Remove the valve and fan assembly as described in Section
13.3.
4. Examine the gasket and replace if necessary.
5. Undo the four nuts securing the burner door and remove the cover plate from the heat exchanger.
6. R
emo
v
e the tw
o clips
from the flow and return pipes on the
bottom of the heat exchanger and slide out the pipes (Fig. 68).
7. Remove the clip holding the manual air vent and remove the pipe
f
r
om the t
op of the heat exchanger.
8. Remove the four screws holding the left and right hand retaining brackets and remove the brackets.
9. R
emove the four screws securing the flue to the top of the boiler. Lift the flue adaptor out of the flue outlet in the top of the heat exchanger.
10. C
ar
efully slide the he
at exchanger out of the boiler.
11. Reassemble in reverse order.
1133..00 CCHHAANNGGIINNGG CCOOMMPPOONNEENNTTSS
1133..1188 PPCCBB
1. Ensure supply voltage is fully isolated.
2. Undo the screws holding the control box and gently ease the box forward (Fig. 69).
3. Locate the retaining barbs on the top of the fascia and unclip them from the control box.
4. Unclip the PCB from the plastic control box.
5. Note the positions of all the connections on the PCB and disconnect them. (DO NO
T REMOVE THE YELLOW BCC (Fig. 69))
6. Carefully unclip and remove the ribbon cable from the PCB and withdraw.
7. Fit all the connection plugs to the new PCB including the ribbon cable, take care not to damage the PCB.
8. U
nless specifically instructed
NNOOTT
t
o do so by the Dimplex Service Department, always fit the new BCC if supplied with the replacement PCB.
NNOOTTEE::
Always double check the label on the BCC card to ensure it is the correct BCC for the boiler model to which it is being fitted. NNEEVVEERR FFIITT AANN IINNCCOORRRREECCTT BBCCCC..
9. Reassemble in reverse order, ensuring that the control knob are reset to their previous positions
© Dimple
x Boiler
3377
1133..1199 BBCCCC
1. Ensure supply voltage is fully isolated.
2. Di
sman
tle the con
t
rol box as described above to gain access
t
o the PCB (Fig. 69).
3. Note the orientation of the existing BCC (if fitted) and carefully remove by sliding it off the edge of the PCB.
4. Re-fit the new BCC by sliding it onto the edge of the PCB, ensuring the orientation is correct.
NNOOTTEE::
Alway
s double check the l
abel on the B
CC card to ensure it is the correct BCC for the boiler model to which it is being fitted. NNEEVVEERR FFIITT AANN IINNCCOORRRREECCTT BBCCCC..
5. Reassemble as above.
6. Power up boiler, and briefly press the reset button, wait for a
t
least 5 seconds and then briefly press the reset button
ag
ain.
7. The boiler should now be checked for correct operation.
P
CB
Facia
Control Box
Retaining Barbs
Pressure
Gauge
User Interface
Control Knob
FFiigg.. 6699
BCC
1144..00 EELLEECCTTRRIICCAALL
1144..11 IILLLLUUSSTTRRAATTEEDD WWIIRRIINNGG DDIIAAGGRRAAMM
3388
© Dimple
x Boiler
br
b
g/y
bk
g
o
br
b
g/y
gr
br
b
br
b
g/y
r
L3
L2 L1N
LCD DISPLAY
RIBBON TO PCB
RIBBON TO LCD DISPLAY
MAINS POWER 230V ~ AC
GAS VALVES 230Vac
FAN 230Vac
RETURN TEMP THERMISTER (5K NTC)
BOILER
TO PC
COM PORT
F
LOW TEMP
T
HERMISTER
(5K NTC)
BOILER PUMP 230Vac
DETECTION ELECTRODE
IGNITION ELECTRODE
SPARK GENERATOR 230Vac
ROOMSTAT OR LINK
1B MAINS
1C BOILER PUMP
2A GAS VALVES
3 FAN
5
COM PORT
6 FLOW N.T.C.
BOILER CHIP CARD BCC
6 RETURN N.T.C.
2B IGNITER / FLAME SENSOR
b
k
bk
b
b
y
FLUE TEMP T
HERMISTER
(5K NTC)
T
HERMAL FUSE
o
g
br
w
y
Key - Cable Colours
g Green y Yellow b
Blue r Red bk Black o Orange g/y Green / Yellow br Brown gr Grey w White
br
b
g/y
8
FAN CONTROL
8
FLUE
(IF FITTED)
4 HYDROBLOCK DIVERTER
y
o b g/y r br
1155..00 SSPPAARREE PPAARRTTSS
1155..11 SSHHOORRTT PPAARRTTSS LLIISSTT
© Dimple
x Boiler
3399
KKeeyy GGCC NNuummbbeerr DDeessccrriippttiioonn QQTTYY PPtt.. NNoo.. 1 H29-740 Electrode - Ignition c/w Gasket 1 988526 2 H38-213 Detection Electrode c/w Gasket 1 988540 3 H29-236 Spark Generator c/w Lead 1 500665 4a TBA System 18 gas control valve assembly NG 1 988675 4b TBA System 30 gas control valve assembly NG 1 988676 5 H38-215 Fan Assembly 1 601016 6a H29-171 Burner (System18) 1 700600 6b H29-173 Burner (System 30) 1 700602 7 TBA Burner Door Insulation 1 352671 8a H38-217 Heat Exchanger (System18) 1 451101 8b TBA Heat Exchanger (System 30) 1 451151 9 H29-202 Pump Head 6m 1 500672 11 H29-237 Expansion Vessel 1 451020 12 TBA 3 Bar Pressure Relief valve 1 500751 13
H29-213 Water Temperature sensor 2 500661 14 H38-219 Flue Thermistor 1 500662 16 E23-541 Pressure Gauge 4bar 1 450961 17 TBA Auto Air Vent 1 500752 18a TBA Dimplex System 18 NG PCB Kit 1 988684 18b TBA Dimplex System 30 NG PCB Kit 1 988583 22 H29-179 Valve - Manual Bleed 1 300730 23 H38-226 Heat Exchanger seal & Clip Kit 1 988546 24 H29-208 Hydroblock - O-Ring and Clip 1 988669 25 TBA Hydroblock Manual bleed cock 1 500708
1
2
3
4
5
6
8
7
12
13
14
11
16
9
22
17
23
24
25
18
1166..00 FFAAUULLTT FFIINNDDIINNGG
4400
© Dimple
x Boiler
1. The mains electrical supply to the boiler and system controls are turned on.
2. The gas service cock is open.
3. External controls are calling for heat.
4. The system is filled with water and is correctly pressurized.
To follow the operational sequence of the boiler, press the reset button for approximately 3 seconds until the two dots on the LCD display are flashing. With no demand for Heat or DHW, the di
splay will show
00.
On Demand for heat or DHW, the display will show the con
troller sequence. See table opposite.
To reset the display to normal operation, press the reset button for approximately 1 second. The display will revert to show the current boiler temperature.
NNOOTTEE::
To reset the appliance after a lockout, press the Red
button.
1166..11 BBAASSIICC CCHHEECCKKSS
1166..44 CCHHEECCKKIINNGG GGAASS VVAALLVVEE SSOOLLEENNOOIIDD CCOOIILLSS
1166..22 OOPPEERRAATTIIOONNAALL SSEEQQUUEENNCCEE OOFF BBOOIILLEERR
1166..33 RREESSIISSTTAANNCCEE VVAALLUUEESS Ω FFOORR FFLLOOWW,, RREETTUURRNN AANNDD FFLLUUEE TTHHEERRMMIISSTTOORRSS
DDiissppllaayy
00
01 02 03 04 05 06 07 08 09
10
11 12 13 14
EExxppllaannaattiioonn
Standby - Burner off
Fan on - Checking RPM feedback
F
an on - Checking RPM feedback
Pre purge of combustion circuit
Pre-ignition - gas valve closed
Gas valve open and ignition on
Flame stabilisation check
Flame established -
BBuurrnneerr oonn ppeerriioodd ssttaarrttss
BBuurrnneerr ooffff ppeerriioodd ssttaarrttss..
Check gas valve solenoids are de-energised
Check gas valve solenoids are de-energised and check for no flame
Post purge of combustion circuit
Volatile or non-volatile lockout has occurred
Not used
Not used
Sequence fault
BBeeffoorree cchheecckkiinngg ffoorr aa ffaauulltt ccoonnddiittiioonn ccaarrrryy oouutt eelleeccttrriiccaall cchheecckkss ttoo eennssuurree tthhee bbooiilleerr hhaass EEaarrtthh ccoonnttiinnuuiittyy,, ccoorrrreecctt ppoollaarriittyy aanndd LLiivvee aanndd NNeeuuttrraall
ccoonnnneeccttiioonnss hhaavvee nnoo sshhoorrtt cciirrccuuiitt..
TTeemmppeerraattuurree °°CC
5
RReessiissttaannccee OOhhmmss ((Ω))
12890 7856 6245 5000 3265 2185 1242 625 456 390 337
NNOOTTEE::
Allow a tolerance of approximately +/- 10%.
15 20 25 35 45 60 80 90 95 100
1. The solenoid coils can be checked by measuring the resistance in Ohms (Ω).
2. C
onnect a multimeter across pins 1 and 5,
resistance = 3770 Ω.
NNOOTTEE::
Allow a tolerance of approximately +/- 10% on
r
es
i
s
t
anc
e r
e
ading.
Pin 1
Pin 2
Pin 3 - Earth C
onnection
GGaass VVaallvvee EElleeccttrriiccaall CCoonnnneeccttiioonnss
Pin 4
Pin 5
Flow and R
eturn Thermistors
Flue Thermistor
1166..00 FFAAUULLTT FFIINNDDIINNGG
© Dimple
x Boiler
4411
DDEESSCCRRIIPPTTIIOONN OOFF CCAAUUSSEESS
Overheated appliance – Water temperature greater than 105°C. This causes a Non volatile lockout requiring a manual reset.
No Flame –No flame signal on ignition. The boiler makes up to 5 ignition attempts on loss of flame signal. Failure after 5 attempts causes a Non volatile lockout requiring a manual reset. No Flame –Loss of flame signal during normal operation Up to 5 loss of flame during normal operation is allowed before Non volatile lock out occurs requiring manual reset. The loss of flame count is reset when the boiler thermostat is satisfied
Temporarily overheated appliance – Water temperature is greater than 95°C This causes a volatile lockout that will automatically reset when the temperature drops below the boiler thermostat setting
Overheat on Flue system – Flue temperature greater than 92°C Non volatile lock out requiring a manual reset
Flame Simulation – Flame detection when gas valve is closed This causes a Non volatile lockout requiring manual reset
Flow thermistor failure Volatile lock out that will automatically reset when fault is repaired OR Thermal fuse has activated (Heat exchanger temperature greater than 165°C) Volatile lock out that will reset when fault is repaired
Flue thermistor failure Volatile lock out that will automatically reset when fault is repaired
CH return thermistor fault V
olatile lock out that will automatically reset when fault is repaired
Gas vale solenoid failure
Fan failure
Boiler Chip Card Error. B
C
C i
s no
t
suit
able for the boiler model
Boiler
Chip C
ard Error
BCC is not connected
Boiler Chip Card Error
Boiler
Chip C
ar
d Error
Boiler Chip Card Error
Boiler Chip Card Error
R
e
turn Temperature is greater than Flow temperature +12°. Temperature difference between Flow and Return is greater than 45°C. Volatile lock out that will reset when fault is repaired.
No wa
t
er flow across Heat exchanger Return temperature has not changed by more than 1° within first 15seconds from boiler firing
Boiler
Chip C
ard Error
AACCTTIIOONNSS
Check for power failure Check Pump operation Check there is no air in Heat exchanger and check system bypass Check Temperature thermistors are located on pipe work correctly Check resistance of thermistors
Check gas supply and inlet operating (working) pressure Check Gas valve operation and continuity across gas valve electrical lead. Check condensate drain is not blocked Check entire flue system is connected correctly and terminated correctly Check detection (flame sensing) Electrode and lead
Check Pump operation Check there is no air in Heat exchanger and check system bypass Check Temperature thermistors are located on pipe work correctly Check resistance of thermistors
Check there is no air in Heat Exchanger and CH system. Check entire flue system is connected correctly and terminated correctly Check minimum and maximum gas rates are correct Check
for correct water circulation Check Heat exchanger flue ways are clean Check continuity of sensor leads
Check detection (flame sensing) electrode is clean Check burner surface is clean Check Gas valve operation and gas valve electrical supply
Check resistance across thermistor and check continuity of sensor leads at PCB connection 6 Major fault. Possible causes are:­Complete dry fire that requires a replacement heat exchanger. Leak of Hot gases from combustion circuit. Faulty sensor that requires main Heat exchanger replacing
Check resistance across thermistor and check continuity of sensors leads at PCB connection 8
Check resistance across thermistor and check continuity of ther
mistor leads at PCB connection 6
Check resistance across Gas valve solenoid Check con
tinuity of Gas v
alv
e lead at PCB connection 2A
Check electrical supply to fan and continuity of fan leads at PCB connections 3 Check signal control connections to fan and continuity at PCB connection 8
Replace with Correct BCC
R
efit
BCC; ensure it is located correctly
Replace BCC
BCC is damaged, Replace BCC
R
epl
ac
e with correct BCC
Replace with correct BCC
Reset the boiler following the BCC fitting Instructions
Check Flow and R
e
turn Sensors are correctly connected Check Resistances of Flow and of Return thermistors Check for air in Heat Exchanger Check heating system Pipework is correct
Check Flow and R
e
turn Sensors are correctly connected Check Resistances of Flow and of Return thermistors Check for air in Heat Exchanger Check heating system Pipework is correct
R
ese
t the boiler following the BCC fitting instructions
EERRRROORR CCOODDEE
1
4
5
6
7
11
12
13
16
20
24
34
35
36 37 38 39
41
42
50
BBOOIILLEERR CCHHIIPP CCAARRDDSS ((BBCCCC)) AARREE OONNLLYY FFIITTTTEEDD IIFF TTHHEE PPCCBB HHAASS BBEEEENN RREEPPLLAACCEEDD OORR CCOONNVVEERRTTEEDD TTOO LLPPGG
1177..00 BBEENNCCHHMMAARRKK
4422
© Dimple
x Boiler
GAS BOILER SYSTEM COMMISSIONING CHECKLIST
C
ONTROLS
Tick the appropriate boxes
Time and Temperature Control to Heating Room Thermostat and Programmable
Load/Weather Optimum Start
Programmer/Timer
Room Thermostat Compensation Control
Time and Temperature Control to Hot Water Cylinder Thermostat and Programmer/Timer Combination Boiler
Heating Zone Valves Fitted Not Required
Hot Water Zone Valves Fitted Not Required
Thermostatic Radiator Valves Fitted Not Required
Automatic Bypass to System Fitted Not Required
B
oiler Interlock Provided
ALL SYSTEMS
The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer’s instructions Yes
What system cleaner was used?
What inhibitor was used? Quantity
litres
CENTRAL HEATING MODE Measure and Record:
Gas Rate
m
3
/hr OR
ft3/hr
Burner Operating Pressure (if applicable)
mbar OR Gas Inlet Pressure mbar
Central Heating Flow Temperature
°C
Central Heating Return Temperature
°C
COMBINATION BOILERS ONLY
Is the installation in a hard water area (above 200ppm)? Yes No
If yes, has a water scale reducer been fitted? Yes
No
What type of scale reducer has been fitted?
DOMESTIC HOT WATER MODE Measure and Record:
Gas Rate
m
3
/hr OR
ft3/hr
Burner Operating Pressure (at maximum rate)
mbar OR Gas Inlet Pressure (at maximum rate) mbar
Cold Water Inlet Temperature
°C
Hot water has been checked at all outlets Yes
Temperature °C
Water Flow Rate
l/min
CONDENSING BOILERS ONLY
The condensate drain has been installed in accordance with the manufacturer’s instructions and/or BS5546/BS6798 Yes
ALL INSTALLATIONS
If required by the manufacturer, record the following CO
2
% OR CO ppm OR CO/CO2Ratio
The heating and hot water system complies with the appropriate Building Regulations Yes
The boiler and associated products have been installed and commissioned in accordance with the manufacturer’s instructions Yes
The operation of the boiler and system controls have been demonstrated to and understood by the customer Yes
The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained and left with the customer Yes
*
All installations in England and Wales must be notified to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme. A Building Regulations Compliance Certificate will then be issued to the customer.
©Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk
Commissioning Engineer’s Signature
Customer’s Signature
(To confirm satisfactory demonstration and receipt of manufacturer’s literature)
T
his Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating
compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
Failure to install and commission this equipment to the manufacturer’s instructions may invalidate the warranty but does not affect statutory rights.
Customer Name Telephone Number
A
ddress
B
oiler Make and Model
Boiler Serial Number
Commissioned by (print name) CORGI ID Number
Company Name Telephone Number
Company Address
Commissioning Date
T
o be completed by the customer on receipt of a Building Regulations Compliance Certificate
*
:
B
uilding Regulations Notification Number (if applicable)
1177..00 BBEENNCCHHMMAARRKK
© Dimple
x Boiler
4433
I
t is recommended that your heating system is serviced regularly and that the appropriate Service Record is completed.
Service Provider
B
efore completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s
i
nstructions.
A
lways use the manufacturer’s specified spare part when replacing controls.
SERVICE 1 Date
E
nergy Efficiency Checklist completed?
Yes
No
Engineer Name
Company Name
T
elephone Number
CORGI ID Number
Comments
Signature
SERVICE 3 D
ate
Energy Efficiency Checklist completed?
Yes
No
Engineer Name
C
ompany Name
Telephone Number
CORGI ID Number
Comments
Signature
SERVICE 5 Date
Energy Efficiency Checklist completed?
Yes
No
Engineer Name
Company Name
Telephone Number
CORGI ID Number
Comments
Signature
SERVICE 7 Date
Energy Efficiency Checklist completed?
Yes
No
Engineer Name
Company Name
Telephone Number
CORGI ID Number
Comments
Signature
SERVICE 9 Date
Energy Efficiency Checklist completed? Yes
No
Engineer Name
Company Name
Telephone Number
CORGI ID Number
Comments
Signature
SERVICE 2 Date
E
nergy Efficiency Checklist completed?
Yes
No
Engineer Name
Company Name
T
elephone Number
CORGI ID Number
Comments
Signature
SERVICE 4 D
ate
Energy Efficiency Checklist completed?
Yes
No
Engineer Name
C
ompany Name
Te lephone Number
CORGI ID Number
Comments
Signature
SERVICE 6 Date
Energy Efficiency Checklist completed?
Yes
No
Engineer Name
Company Name
Te lephone Number
CORGI ID Number
Comments
Signature
SERVICE 8 Date
Energy Efficiency Checklist completed?
Yes
No
Engineer Name
Company Name
Te lephone Number
CORGI ID Number
Comments
Signature
SERVICE 10 Date
Energy Efficiency Checklist completed? Yes
No
Engineer Name
Company Name
Te lephone Number
CORGI ID Number
Comments
Signature
SERVICE RECORD
1177..00 BBEENNCCHHMMAARRKK
4444
© Dimple
x Boiler
MAINS PRESSURE HOT WATER STORAGE SYSTEM COMMISSIONING CHECKLIST
*
llA installations in England and Wales must be notified to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme.
A Building Regulations Compliance Certificate will then be issued to the customer.
©Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk
ALL SYSTEMS PRIMARY SETTINGS
(indirect heating only)
Is the primary circuit a sealed or open vented system? Sealed
Open
W
hat is the maximum primary flow temperature?
°C
ALL SYSTEMS
What is the incoming static cold water pressure at the inlet to the system? bar
Has a strainer been cleaned of installation debris (if fitted)? Ye s
No
I
sthe installation in a hard water area (above 200ppm)? Yes
N
o
I
f yes, has a water scale reducer been fitted? Yes
N
o
What type of scale reducer has been fitted?
What is the hot water thermostat set temperature?
°C
What is the maximum hot water flow rate at set thermostat temperature (measured at high flow outlet)?
l/min
Time and temperature controls have been fitted in compliance with Part L of the Building Regulations? Yes
Type of control system (if applicable) Y Plan
S Plan Other
Is the cylinder solar (or other renewable) compatible? Ye s
No
What is the hot water temperature at the nearest outlet? °C
All appropriate pipes have been insulatedupto1metre or the point where they become concealed Yes
UNVENTED SYSTEMS ONLY
Where is the pressure reducing valve situated (if fitted)?
What is the pressure reducing valve setting?
bar
Has a combined temperature and pressure relief valve and expansion valve been fitted and discharge tested? Yes
No
The tundish and discharge pipework have been connected and terminated to Part G of the Building Regulations Yes
Are all energy sources fitted with a cut out device? Yes
No
Has the expansion vessel or internal air space been checked? Yes
No
THERMAL STORES ONLY
What store temperature is achievable? °C
What is the maximum hot water temperature?
°C
ALL INSTALLATIONS
The hot water system complies with the appropriate Building Regulations Yes
The system has been installed and commissioned in accordance with the manufacturer’s instructions Yes
The system controls have been demonstrated to and understood by the customer Yes
The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained and left with the customer Yes
Commissioning Engineer’s Signature
Customer’s Signature
(To confirm satisfactory demonstration and receipt of manufacturer’s literature)
T
his Commissioning Checklist is to be completed in full by the competent person who commissioned the storage system as a means of
d
emonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
F
ailure to install and commission this equipment to the manufacturer’s instructions may invalidate the warranty but does not affect statutory rights.
C
ustomer Name Telephone Number
A
ddress
Cylinder Make and Model
C
ylinder Serial Number
Commissioned by
(print name) Registered Operative ID Number
Company Name Telephone Number
C
ompany Address
Commissioning Date
To be completed by the customer on receipt of a Building Regulations Compliance Certificate
*
:
Building Regulations Notification Number (if applicable)
1177..00 BBEENNCCHHMMAARRKK
© Dimple
x Boiler
4455
SERVICE RECORD
It is recommended that your hot water system is serviced regularly and that the appropriate Service Record is completed.
Service Provider
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
S
ERVICE 1
D
ate
E
ngineer Name
Company Name
T
elephone Number
C
omments
Signature
S
ERVICE 2
D
ate
E
ngineer Name
Company Name
T
elephone Number
C
omments
Signature
SERVICE 3 Date
Engineer Name
C
ompany Name
Telephone Number
Comments
Signature
SERVICE 4 Date
Engineer Name
C
ompany Name
Telephone Number
Comments
Signature
SERVICE 5 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 6 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 7 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 8 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 9 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 10 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
1177..00 BBEENNCCHHMMAARRKK
4466
© Dimple
x Boiler
VENTED CYLINDER COMMISSIONING CHECKLIST
This Commissioning Checklist is to be completed in full by the competent person who commissioned the
c
ylinder as a means of demonstrating compliance with the appropriate Building Regulations and should
remain attached to the cylinder for future reference.
Failure to install and commission this equipment to the manufacturer’s instructions may invalidate the
warranty but does not affect statutory rights.
C
ommissioned by (print name)
Company Name
Company Address
T
elephone Number Commissioning Date
T
o be completed by the customer on receipt of a Building Regulations Compliance Certificate
*
:
Building Regulations Notification Number (if applicable)
ALL CYLINDERS
The vent pipe has been installed to BS6700/BS5449 Yes
What is the static head?
metres
H
as an immersion heater been fitted? Yes
No
If yes, does it have a non-auto resetting energy cut out? Yes
N
o
Is the cold feed cistern supported in accordance with BS4213? Yes
Is the cylinder solar (or other renewable) compatible? Yes
No
All appropriate pipes including the vent pipe have been insulated
up to 1metre or the point where they become concealed Yes
*
Where an installation is notifiable in England & Wales this will be made to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme. A Building Regulations Compliance Certificate will then be issued to the customer.
©Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk
Commissioning Engineer’s Signature
Customer’s Signature
(To confirm satisfactory demonstration and receipt of manufacturer’s literature)
INDIRECT ONLY
A cylinder thermostat has been fitted in the recommended position Yes
The hot water is controlled by a programmer or time switch Yes
Is the system fully pumped? Yes
No
Typ e of control system Y Plan
S Plan Other
1188..00 WWAARRRRAANNTTYY TTEERRMMSS && CCOONNDDIITTIIOONNSS
1188..11 DDIIMMPPLLEEXX 55YYRR WWAARRRRAANNTTYY
1. Registration must be completed within 30 days of installation. Failure to return within 30 days will invalidate your warranty. Registration if ef
f
ect
ed b
y r
e
turning the enclosed registration card to the commercial center of Dimplex at 5 Spartan Close, Tachbrook Park, Leamington Spa,
CV34 6RR. Proof of postage should be obtained.
2. The Benchmark document must be completed by installer/householder at the time of installation and must be presented to our engineer at subseq
u
ent visits.
3. The boiler must be serviced annually, at the householders expenses in accordance with manufacturer’s instructions, and this service must be booked thr
ou
gh Dimple
x by calling 0844 371 1121
4. The service must be carried out by a Dimplex approved central heating engineer. Any work carried out by a non-Dimplex approved engineer will invalidate this warranty.
5. Appropriate system cleaning (e.g. power flush) and the correct use of additives must be carried out at the time of installation. Failure to cle
anse the sy
s
t
em will in
validate this warranty. Evidence of cleansing should be presented to our engineer upon request.
6. This warranty applies only to manufacturing problems with the boiler; damage caused through misuse, incorrect operation, foreign bodies in the heating system, system faults and failures are not covered.
7.
This warranty applies only if the boiler is installed and used in accordance with the manufacturer’s instructions, in normal domestic applications.
8.
P
roviding all the above Terms and Conditions are met, this warranty covers functional parts and labour.
9.
Dimple
x of
f
er
the op
portunity
f
or a system audit and commissioning check within 30 days of registration. This is chargeable at the same rate as an annual service and if taken up then the first annual service will be provided free of charge. Failure to take up this offer may invalidate the full warranty which will revert to a standard 2 year warranty which will require an annual service In year 2 in any event.
10.
F
ailur
e t
o meet any of the above Terms and Conditions will invalidate this warranty.
© Dimple
x Boiler
4477
SSAALLEESS AANNDD SSEERRVVIICCEE HHEELLPPLLIINNEE:: 00884444 337711 11112211
© Dimple
x Boiler
P
art
No: 751262 - Is
su
e 2 - 2/2/09
Dimple
x Boiler
s i
s con
tinually impr
o
ving its products and therefore
reserve the right to change product specifications without prior notice.
Er
r
ors & omissions excepted.
DDiimmpplleexx BBooiilleerrss
2200//2222 FFiirrsstt AAvveennuuee
BBlluueebbrriiddggee IInndduussttrriiaall EEssttaattee
HHaallsstteeaadd
EEsssseexx CC0099 22EEXX
Telephone Sales and Service:
00884444 337711 11112211
Fax:
0011778877 447744558888
e-mail:
ssaalleess@@ddiimmpplleexxbbooiilleerrss..ccoo..uukk
eennqquuiirriieess@@ddiimmpplleexxbbooiilleerrss..ccoo..uukk
ttrraaiinniinngg@@ddiimmpplleexxbbooiilleerrss..ccoo..uukk
website:
wwwwww..ddiimmpplleexxbbooiilleerrss..ccoo..uukk
Loading...