Dimplex CFH60, CFH90, CFH120 Instructions Manual

- 1 -
CFH60, CFH90 & CFH120
Electronic Wall Mounted Fan Heater
IT
FR
UK DE
PL
08/19438/0 - Issue 4
Products comply with the European Safety Standard: EN 60335-2-30 and the European Standards for Electromagetic Compatibility (EMC) EN55014-1 / A2: 2002 and EN55014-2:2003. These cover the essential requirements of EEC directives 2006/95/EC and 2004/108/EC
- 2 -
2
1
6
5
L
H
D1
100mm
Min.
2.0m MIN
D2
500mm
Min.
45
o
Max.
500mm
Min.
1000mm
Min.
70m
m
70mm
3a 3b
1 2
4
y
2
3
x
1
L H D1 D2
CFH60 386 360 565 630 CFH90 386 360 565 630
CFH120 386 360 565 630
x
y
w
z
- 3 -
- 4 -
UK ...................................................... 5
DE ...................................................... 7
FR ...................................................... 9
NL ...................................................... 11
IT ...................................................... 13
PL ...................................................... 15
- 5 -Dimplex Industrial Fan Heater
Models : CFH60, CFH90 & CFH120
UK
IMPORTANT: THESE INSTRUCTIONS SHOULD BE READ CAREFULLY AND RETAINED FOR FUTURE REFERENCE
General
A range of robust, high power wall mounting fan heaters designed to coordinate with the Dimplex range of Air Curtains, providing environmental heating in commercial and light industrial environments.
The heaters work by gradually raising the air temperature in the building and should be positioned so as best to achieve an even temperature distribution.
The product range has outputs of 6kW, 9kW and 12kW, and each product contains on-board electronics that enables ‘daisy-chain’ linking to an electronic control panel (CFCH) or building energy management system.
Connectivity between heater and control panel is achieved using LAN (Local Area Network) cable i.e. CAT5, CAT5E or CAT6, pin confi guration is straight through 1 to 1.
The electronic controller has a number of features including thermostatic control. For more details on these refer to the CFCH instruction leafl et.
The switch panel CFCH should not be installed in a toilet or bathroom.
Model Heat
Output
kW
Electrical
Supply
Electrical
Load
(per phase)
A
WeightKGMin
Installed
height M
CFH60 3 / 6
220-240V~ 1PN 26.0
13 2220-240V~ 3P 15.6
380-415V~ 3PN 9.0
CFH90 6 / 9
220-240V~ 1PN 38.8
14 2220-240V~ 3P 23.0
380-415V~ 3PN 13.3
CFH120 6 / 12
220-240V~ 1PN 51.6
14 2
220-240V~ 3P 30.4
380-415V~ 3PN 17.5
Wall Mounting
Remove the wall mounting bracket from the back of the heater and using it as a guide (see Fig. 2) mark off the hole positions on a suitable wall (a minimum of 2 metres is required from the fl oor level to the bottom of the bracket). Solid brick or concrete walls must be drilled and plugged. Fix the wall mounting bracket to the wall and assemble the heater to the extension tube using a bolt and wiring nut fi tted into hole 1 shown in Fig 3a. Rotate the heater as shown in Fig. 3b, and fi x the heater into position using the remaining bolt and wing nut in hole 2. Pivot and rotate the heater into the desired position and tighten all three wing nuts. A 6mm Allen key can be used as an aid to tightening the bolts.
Electrical and Control Connections
Note: The installation of this appliance should be carried out by a competent electrician and be in accordance with the current IEE wiring regulations.
All products are fi tted with microprocessor control. Electrical power and control connections for all CFH models are made by removing the control housing and bottom panel. The control housing (‘y’ in Fig. 4) is detached by removing the two quick release fasteners and hinging the housing as shown. The bottom panel (‘x’ in Fig. 4) is detached by removing two screws and lifting off as shown.
Note: A suitable local isolating switch must be provided in the electrical supply circuit as close as possible to the heater with at least 3mm clearance on each pole.
Wiring Diagrams Fig. 7
A - PCB
B - Mains in terminal blocks C - Cut-out circuit D - LAN Sockets E - Elements M - Motor Feed appropriate supply cable (see ‘x’ in Fig. 5) to terminal blocks ‘z’.
Make electrical connections as shown in Fig. 7 and fi x the cable in back panel using cable gland. Using LAN cable (see ‘y’ in Fig. 5) make the control connections to BUS IN socket ‘w’ also shown in Fig. 5. Fix this cable in the back panel using cable gland and feed back to the electronic control panel (CFCH) using suitable conduit if required. Refer to CFCH instructions for installation and connections of electronic control panel. Replace the bottom panel and control housing and switch on power to heater and installed electronic control panel. Ensure that all control settings function correctly.
Note: The factory supplied unit can accept three phase voltage of ~380­415V. For single phase 220-240V and three phase ~220-240V refer to the electrical wiring label fi xed to the underside of the bottom panel. To change between different voltage systems, rearrange the push-on connections as per the required wiring diagram. Contact your supplier for further details.
Operation using Control Panel - CFCH
Switch on electrical supply to the fan heater and the electronic control panel. When all units are powered up and there is a connection between the controller and the master unit, an LED will turn on in the controller to indicate the units are functioning. Refer to the CFCH instruction leafl et on the operation of the electronic control panel.
Do not switch the heater off at the isolator when the unit is running as this will prevent the fan overrun operating. This can cause a nuisance cut out as the excess heat cannot be dissipated.
- 6 -
UK
Delayed Shutdown
Door Switch (3min Runback): By wiring in a normally open contact to
the door switch connections shown in Fig. 7, the following operation is achieved:
• Up to 1 minute after contact closed, unit runs at set condition.
• Between 1 & 2 minutes. unit runs half & half settings.
• Between 2 & 3 minutes. unit runs fan only settings.
• Over 3 minutes. unit enters stand-by mode.
PIR Sensor (45min Runback): By changing the PCB mounted links shown in Fig. 7 the runback timer will operate as follows:
• Up to 15 minutes after contact closed, unit runs at set condition.
• Between 15 & 30 minutes. unit runs half & half settings.
• Between 30 & 45 minutes. unit runs fan only settings.
• Over 45 minutes. unit enters stand-by mode.
Modular Linking
A number of fan heaters can be connected together in a ‘daisy chain’ fashion. A total of ten units can be controlled from a single electronic control panel. The required connections can be made in a daisy chain fashion as shown in Fig. 8. (References shown below).
ECP - Electronic Control Panel MU - Master Unit SU - Slave Unit MLC - Modular Linking Cable CPC - Control Panel Cable To make these connections remove one of the small knock-outs and feed
an appropriate LAN cable (not supplied) to the BUS OUT control socket (‘D’ in Fig. 8) of the Master Unit. Fix this cable in the back panel using suitable cable gland (not supplied). Continue this process for all linked heaters. Replace the control housing of each heater and power up all units. Ensure that all control settings function correctly.
Thermal Safety Cut-out
The power supply to the heating elements will be interrupted if one or a combination of the following abnormal events occurs:
1. Air inlet or outlet grilles are obstructed.
2. Internal ventilation is impaired due to build up of dust and fl uff.
3. Blower unit stalls.
Note: Before re-setting the cut-out, the reason for activation must be determined and corrective action taken. To reset the thermal safety cut-out, access reset tab by removing the panel shown in Fig. 6 and push the reset tab in direction of arrow.
Maintenance
WARNING: Disconnect electrical supply to all connected units prior to carrying out maintenance.
Optimum performance and long service from this product will only be realised if regular maintenance is carried out. Dimplex recommends regular checks dependant on normal use or more frequent checks where the unit is installed in arduous conditions or used continually for more than 10 hours per day.
Standard Maintenance
Where the product is subject to use not exceeding 10 hours per day:
Every 3 months the fan wheels, impellors, heating elements, air inlet and outlet grilles should be cleaned, removing dust and debris with a suitable soft brush.
Every 12 months all moving parts should be checked for free running with appropriate remedy/adjustment made where necessary.
Extended Maintenance
Where the product is subject to arduous conditions or is used continually for more than 10 hours per day:
Each month the fan wheels, impellors, heating elements and air inlet and outlet grilles should be checked and cleaned, removing dust and debris with a suitable soft brush. Every 6 months all moving parts should be checked for free running with appropriate remedy/adjustment made where necessary.
Recycling
For electrical products sold within the European Community. At the end of the electrical products useful life it should not be disposed of with household waste. Please recycle where facilities exist. Check with your Local Authority or retailer for recycling advice in your country.
Cleaning
WARNING: DISCONNECT SUPPLY before carrying out maintenance.
External appearance can be maintained by wiping occasionally with a damp cloth. For stain removal, a weak soap solution can be applied with a cloth and the surface wiped dry. Care must be taken to avoid any moisture ingress into the product.
After Sales Service
Should you require after sales service or should you need to purchase any spares, please contact the retailer from whom the appliance was purchased or contact the service number relevant to your country on the warranty card. Please do not return a faulty product to us in the fi rst instance as this may result in loss or damage and delay in providing you with a satisfactory service.
Please retain your receipt as proof of purchase.
Loading...
+ 14 hidden pages