Diamondback DPLS1 User Manual

DPLS1
Drain Pan Level Sensor/Control
Provides electronic overflow protection for Drain Pans in all Mr. Slim and CITY MULTI indoor units MFZ, MS, MSY/Z, SEZ, SLZ, PCA/PCFY, PDFY, PEA/PEAD/PEFY, PKA/PKFY, PLKA/PLFY, PMFY, and PVFY
Meets requirements as listed alternative to secondary drain pans in all indoor unit installations covered by the
International Mechanical Code and adaptations.
Drain Panel Level Sensor/Control
Installation Instructions
The DPLS1 Drain Pan Level Sensor / Control provides protection against drain pan overflow in Mitsubishi Electric Mr. Slim and CITY MULTI Indoor Units. The unit will sense a high condensate level in the drain pan. Should this occur the control shuts down the indoor unit before an overflow can occur. A thermistor error code will be produced should the DPLS1 activate indicating a fault which must be resolved before the unit will re-start.
This unit provides electronic overflow protection for Drain Pans in all Mr. Slim and CITY MULTI indoor units: MFZ, MS, MSY/Z, SEZ, SLZ, PCA/PCFY, PDFY, PEA/PEAD/PEFY, PKA/PKFY, PLA, PLKA/PLFY, PMFY, and PVFY.
Meets requirements as listed alternative to secondary drain pans in all indoor unit installations covered by the International Mechanical Code and adaptations.
DPLS1 – COMPONENTS
Control Box Water Sensor Splice Connector M2 Wire Harness
P Wire Harness M1 Wire Harness
Work Safe, READ THIS!
ATTENTION: FAILURE TO READ AND COMPLY WITH ALL WARNINGS, CAUTIONS AND INSTRUCTIONS PRIOR TO STARTING INSTALLATION MAY CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE AND VOID WARRANTY.
This device must be installed in accordance with Equipment Manufacturer’s instructions and in accordance with all applicable local codes, including plumbing, drainage and electrical
The DPLS1 is powered by a twenty-year life Lithium battery, which has been factory, installed prior to shipment. This allows installation of the sensor and control to be accomplished without needing external electric power for operation. There is an audible indication of low battery condition. Should the battery ever need to be replaced at any time see the BATTERY INSTALLATION INSTRUCTIONS in this document.
1
3400 Lawrenceville Suwanee Rd Suwanee, GA 30024 Tele: 678-376-2900 Service: 877-391-2900 www.mehvac.com
© 2011 Mitsubishi Electric & Electronics USA, Inc.
DPLS1 Drain Panel Level Sensor/Control
ULU
L
DPLS1 Drain Pan Level Sensor/Control
Protected under one or more patients
Table 1: Description of Wire Harnesses
Type of Wire
Harness
Indoor Unit Models
Connector to Indoor Unit Control
Board
Connector to Thermistor
Connector to
Control Box
M2 Wire Harness
MS MSZ/Y MFZ
2 pin, female connector (with black heat shrink) to CN111
2 pin, male connector to: RT11 (Room Temp. Thermistor)
2 pin, male connector
P Wire Harness
PKA PCA PEA(D)
SEZ
2 pin, female connector to CN20
2 pin, male connector to: TH1 (Room Temp. Thermistor)
2 pin, male connector
PKFY-P**NBMU-E
PLFY-P**NCMU-E
PMFY-P**NBMU-E
PVFY-P**E00A
PEFY-P**NMHU-E
2 pin, female connector to CN20, CN21 or CN29
2 pin, male connector to:
TH1 (Room Temp. Thermistor) or
TH22 (Pipe Temp. Thermistor/Liquid) or
TH23 (Pipe Temp
Thermistor/Gas)
M1 Wire Harness
PKA
PCA PEA(D) SEZ PKFY-P**NH/KMU-E PLFY-P**NBMU-E PCFY-P**NKMU-E
PEFY-P**NMS/AU-E
4 pin, female connector to CN44
4 pin, male connector to
TH2 (Pipe Temp. Thermistor/Liquid) and
TH5 (Pipe Temp. Thermistor/Gas)
2 pin, male connector
MS
4 pin, female connector to CN112
4 pin, male connector to
RT12 (Coil Temp. Thermistor)
MSZ/Y
4 pin, male connector to
RT12 (Coil Temp. Thermistor Main) and
RT13 (Coil Temp. Thermistor Sub)
MFZ 4 pin, female connector to CN113
4 pin, male connector to
RT15 (Coil Temp. Thermistor)
4F Wire Harness
All indoor units, with CN-4F Connector on
4 pin terminate to CN-4F if available - CN-4F is used for other function use
If CN-4F not available
2 pin, male connector
Control Board Thermistor Connection Method
Protected under one or more patents © 2011 Mitsubishi Electric & Electronics USA, Inc.
Type of Harness Indoor Unit Models Connector to Indoor Unit Control Board Connector to Thermistor Connector to Control Box
M2 Wire Harness
P Wire Harness
M1 Wire Harness
MS MSZ/Y MFZ
PKA PCA PEA(D) PLA SEZ
SLZ
PKFY-P**NBMU-E
PLFY-P**NCMU-E
PMFY-P**NBMU-E
PVFY-P**E00A
PEFY-P**NMHU-E
PLA PKA PCA PEA(D) SEZ PKFY-P**NH/ KMU-E PLFY-P**NBMU-E PCFY-P**NKMU-E PEFY-P**NMS/AU-E
MS
MSZ/Y
INSTALLATION OF DPLS1
(To ensure proper performance of product, instructions must be followed.)
MFZ 4 pin, female connector to CN113
Drain Pan Level Sensor/Control:
1. Disconnect (and lock-out, if required) all power to the Mr. Slim or CITY MULTI Indoor Unit at the Disconnect Switch (if installed) or at the main disconnect panel serving the indoor and/or outdoor unit.
2. Connect DPLS1 Splice Connector to the selected mating Wire Harness Connector – see wiring harness selection above. Connect the Control Box’s Splice C onnector to the mating connector on the Wire Harness (Fig 1).
2 pin, female connector (with black
heat shrink) to CN111
2 pin, female connector to CN20
2 pin, female connector to CN20,
4 pin, female connector to CN44
4 pin, female connector to CN112
CN21 or CN29
2 pin, male connector to:
RT11 (Room Temp. Thermistor)
2 pin, male connector to:
TH1 (Room Temp. Thermistor)
2 pin, male connector to:
TH1 (Room Temp. Thermistor) or
TH22 (Pipe Temp.
Thermistor/Liquid) or
TH23 (Pipe Temp
Thermistor/Gas)
4 pin, male connector to
TH2 (Pipe Temp. Thermistor/Liquid) and
TH5 (Pipe Temp. Thermistor/Gas)
4 pin, male connector to RT12 (Coil Temp. Thermistor)
4 pin, male connector to
RT12 (Coil Temp. Thermistor – Main) and
RT13 (Coil Temp. Thermistor – Sub)
4 pin, male connector to RT15 (Coil Temp. Thermistor)
2 pin, male connector
2 pin, male connector
2 pin, male connector
Fig 1
2