Dialight WOSU22BG2, WOSU12BG2 User Manual

9100-127-2989-99 REV B
Wireless Occupancy
Wireless Occupancy Sensor
Sensor
User Guide
This Manual covers both the Wide angle and the Narrow long range
occupancy sensor.
Dialight Part Numbers described here-in are:
WOSU22BG2 Wide angle
WOSU12BG2 Long Range
Wide optic version Long Range Version
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
1
1501 Route 34 South, Farmingdale, NJ 07727
9100-127-2989-99 REV B
Contents
Introduction .................................................................................................................................................................................. 3
Wireless Occupancy Sensor Gen 2 Specifications ...................................................................................................................... 4
Unboxing ...................................................................................................................................................................................... 5
Sensor Overview .......................................................................................................................................................................... 6
Battery Installation/Removal ......................................................................................................................................................... 7
Sensor Lights ............................................................................................................................................................................... 8
Commissioning ........................................................................................................................................................................... 10
Wide Angle Sensor Ceiling Mount .............................................................................................................................................. 11
How to Mount ............................................................................................................................................................................. 12
Long Range Sensor Wall Mount ................................................................................................................................................ 13
How to Mount ............................................................................................................................................................................. 14
Troubleshooting ......................................................................................................................................................................... 15
Troubleshooting Continued: ....................................................................................................................................................... 16
Troubleshooting Continued: ....................................................................................................................................................... 17
2
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
9100-127-2989-99 REV B
Introduction
Keep These Instructions
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
Welcome to the Dialight Wireless Occupancy Sensor user manual. This product allows you to customize your entire lighting network using independent Occupancy Sensors throughout your facility by turning lights on when occupancy has been detected.
This guide provides you with the information you need to get started.
The installation and maintenance must be
Refer to operating temperature ratings of this
device before installing.
DO NOT let the sensor touch hot surfaces.
DO NOT mount near gas or electric heaters
Equipment should be mounted in locations
and at heights where it will not be subjected to tampering by unauthorized personnel.
The use of accessory equipment not
recommended by the manufacturer may cause unsafe conditions.
DO NOT use this equipment for other than
intended use.
DO take pictures of the installation, wiring
and mounting for future reference.
Battery life will vary upon traffic area of the
install
Contact your local Sales representative or
Dialight when necessary
SAVE THESE INSTRUCTIONS!!
carried out by authorized personnel.
Repairs and Installation must only be
carried out by a qualified electrician.
Only genuine or authorized Dialight
replacement parts must be used when unforeseen repairs are required.
Observe the national safety rules and
regulations during installation!
Mounting in extreme heat locations should
be avoided. Failure to do so could void all warranties!
No alterations are allowed without the
written agreement from Dialight Corp. Alterations other than written in this manual will void all warranties.
Batteries should be removed when the
sensor is not being used
It is suggested that a maintenance schedule
be set up for battery replacement.
SAVE THESE INSTRUCTIONS!!
3
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
9100-127-2989-99 REV B
Wireless Occupancy Sensor
Gen 2
Specifications
UL916
, CSA C22.2 NO.205
2x “AA” Lithium Batteries 1.5V
Up to 10 years
2.4Ghz
Passive Infrared
5”D x 2.38”
H
~8.8oz
Housing
: Grey Polycarbonate
Lens:
High density polyethylene
IP66
Green LED
flashes
one time
when motion is detected
A single red
LED3
flash indicates motion detected
R
esets
the processor
Located on bottom of sens
or board, it
will turn the LED indicators ON or
Push and hold for 5 seconds to force sensor to leave its gateway
Push and hold for 5 seconds. Sensor will double blink while trying to join a
Description Wide Angle and Narrow Long Range Wireless High Bay Occupancy
Sensors
Certification
Power Input
Operating Temperature
Estimated Battery Life
Radio Frequency
Sensing Area
Sensing Technology
Dimensions
Weight
Material
IP Ratings
Green LED
Red LED
Reset Button
Operating Temperature: -40°C to +60°C
Wide Angle 20’-30’ (minor – major motion range), 1250 sq ft, 120°
Long Range 100’ (maximum range), 7600 sq ft (floor + distance
coverage), 10° coverage angle
Indicates battery voltage above 2.7 Volts.
Green LED flashes twice every 5 seconds while searching for a network
connection.
and low battery voltage below 2.7 Volts.
LED On/Off Switch
Leave Button
Join Button
gateway, Sensor will stop blinking if it doesn’t join a gateway within 30
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
4
OFF.
minutes.
1501 Route 34 South, Farmingdale, NJ 07727
9100-127-2989-99 REV B
Unboxing
Included in the box:
This Manual Qty 1 – Wireless Occupancy Sensor Qty 3 – #8 Plywood Screws Qty 3 – #8-32 Machine Screws Qty 2 – Lithium “AA” Batteries Qty 2 – Battery Clips
Take Note of the following information:
Dialight Catalog Number:
Date Code:
Install Date:
5
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
9100-127-2989-99 REV B
Sensor Overview
Mounting Plate with Twist Lock
LED Indicators
Sensor Housing
Sensor Lens
3 Mounting Holes
Front View
2.38”
5.0”
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
6
9100-127-2989-99 REV B
Battery Installation/Removal
Removing Battery Cover
To remove the sensor, twist sensor cover counterclockwise to unlock it from the back plate.
Once cover has been removed you’re now ready to add or remove the batteries.
7
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
9100-127-2989-99 REV B
Sensor Lights
Installing Batteries
1. Remove AA batteries from their packaging.
2. Install batteries in the battery holder on the sensor making sure to orient them
according to the +/- symbols on the holder. Install provided battery clips.
Battery Holder (BAT2)
Battery Holder (BAT 1)
3. Lock sensor to the back plate. Installation is the opposite of removal.
4. The sensor is now on and ready to be discovered.
NOTE: There is no on/off switch in the sensor. To power off the sensor, remove the batteries from unit.
To turn on the LED Indicators
1. Twist open the sensor from the mounting plate.
2. Move the LED switch to the right to turn on the LED indicators.
NOTE: Turning switch to on will cause increase current draw to the batteries and will shorten life based on the amount of motion detection.
LED On/Off Switch
3. Twist close the sensor back on to the mounting plate.
8
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
9100-127-2989-99 REV B
Sensor Notifications: NOTE there are only 1 led of each color. Below is for clarity
One green blinking LED1 Motion means motion has been detected and indicates a battery voltage of more than
2.7V.
Green LED1 Motion blinking twice in a second means sensor is looking for a network to join and battery voltage is more than 2.7V. Sensor will double green blink while looking for a network for 30 minutes and then stop. Press the join button for 5 seconds to start a new 30 minute search.
A single red LED3 Low Bat flash indicates motion detected and low battery voltage below 2.7 Volts. Battery needs to be
replaced. Only replace batteries with same size and type. ____________________________________________________________________________________
Red LED3 Low Bat blinking twice in a second means sensor
is looking for a network and battery voltage is under 2.7V.
9
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
9100-127-2989-99 REV B
Commissioning
NOTE: In order to confirm proper location it is advised to mount the sensor before discovering it.
Adding Sensor to Gateway
1. When the green LED blinks twice a second on the sensor, the sensor is ready to be
discovered/commissioned.
2. Use a Dialight gateway to discover the sensor. (Please refer to the gateway owner’s
manual for further instructions under the devices page.)
3. Once the sensor has been added to the gateway, the green LED will stop blinking at
the rate of twice a second. You have now connected the sensor to the gateway.
4. The green LED will then blink when motion is detected.
NOTE: There is a 90 second ideal mode after a trigger detection. Thus quick repeating will not trigger additional events. See the Gateway manual for setting up the sensor
Removing the Sensor from a Gateway
Due to failure or relocation
1. Go to the sensor and open it and hold the SW3 Leave button for 5 seconds
2. Sensor LED’s should now be double blinking
3. Check the gateway’s GUI to verify sensor was removed from device list. (Please refer to
your gateway owner’s manual for further instructions.)
4. Your sensor is now ready to be added to another gateway.
SW1 RESET
10
SW3 LEAVE
SW2 JOIN
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
9100-127-2989-99 REV B
Wide Angle Sensor Ceiling
Mount
Sensor should be mounted 6ft away from any open air vent or
2.7 meters or 8.8 feet
Where to Mount
The wide optic sensor is best used as a ceiling mounted sensor. The recommended install for this sensor is 2.7 meters or 8.8 feet from the floor.
strong air supply openings.
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
11
1501 Route 34 South, Farmingdale, NJ 07727
9100-127-2989-99 REV B
How to Mount
How to Mount (Installation should be performed by properly trained personnel)
1. Use the senor’s mounting plate to mark the surface of the ceiling with the appropriate
hole spacing.
2. Drill holes in ceiling.
3. Align sensor mounting plate to the ceiling matching the drilled holes.
4. Use the three provided screws and secure sensor to the ceiling.
5. Attach and lock the sensor to the mounting plate.
Mounting Plate
Screws
Sensor
Ceiling
12
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
9100-127-2989-99 REV B
Avoid placing sensors where obstacles can block the
3.2 meters
or 10.5 feet
Long Range Sensor Wall Mount
Where to Mount
The long range sensor is best used as a wall mounted sensor. The recommended install for this sensor is 3.2 meters or 10.5 feet from the floor.
sensor’s line of sight.
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
13
9100-127-2989-99 REV B
How to
Mount
How to Mount (Installation should be performed by properly trained personnel)
1. Use the senor’s mounting plate to mark the surface of the wall with the appropriate
whole spacing.
2. Drill holes in wall.
3. Align sensor mounting plate to the wall matching the drilled holes.
4. Use the three provided screws and secure sensor to the wall.
5. Attach and lock the sensor to the mounting plate.
Wall
Sensor
Screws
Mounting Plate
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
14
9100-127-2989-99 REV B
Troubleshooting
Sensor is not discovered by the gateway. NOTE: This section requires the Dialight Gateway and to be connected to a computer using the GUI interface.
Steps to solve:
1. On the gateway web page verify that discovery is turned on.
2. Follow the provided instructions to turn the internal LED switch to ON.
3. Check the condition of the LED lights through the front lens of the sensor.
4. If the red LED is blinking then the batteries need to be replaced.
5. If the green LED is double blinking then the sensor is still trying to join a network, then: a. Verify that it is within 100 ft. of a light that has already joined the network. b. Verify the lights are powered by commanding them to turn on from the web
page.
c. Replace the sensor.
6. If the green LED is not blinking at all then: d. Remove both batteries. e. Replace the batteries, verifying correct orientation. f. When plugging in the second battery, if the red and green LED’s do not come
on for 2 seconds, then:
i. Try new batteries.
ii. Replace the sensor.
15
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
9100-127-2989-99 REV B
Troubleshooting Continued:
g. After plugging in the second battery watch the behavior of the green LED. If the
green LED double blinks then this sensor will try to join a network for 30 minutes. If the red LED is blinking then replace the batteries.
h. If the Green LED is not blinking then it has already joined a network, possibly a
different network than the desired network. Hold the leave button for 5 seconds to make the sensor leave the network. It will then double green blink and be ready to join a new network.
Motion at the sensor does not turn on any lights.
Steps to solve:
1. Verify that motion at the sensor blinks the green LED once. If you don’t see it blink once
then wait 90 seconds and try again as the sensor has a 90 second blackout time in which motion cannot be re-triggered.
a. If the sensor blinks green once then it is operating correctly. Continue with step
2.
b. If the sensor blinks red once then replace the batteries. c. If the sensor does not blink at all then open the sensor and press the reset
button.
d. If the green and red LEDs do not light for two seconds then verify the batteries
are installed with the correct orientation. If they were correct then replace the batteries.
e. If the green and red LED do light for two seconds then observe the behavior of
the green LED.
f. If the green or red LED is double blinking then this sensor is not joined to a
network. Go to the system control and discover it.
g. If there is no double blinking then the sensor is joined to a network. Try trigger
motion and see if the green led blinks once.
h. If it blinks for motion then the sensor is working correctly.
Continue to step 2.
i. If it does not blink for motion. j. Confirm the led SW2 is set to on. k. If not then replace the sensor
16
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
9100-127-2989-99 REV B
Troubleshooting Continued:
2. On the gateway web page verify that the sensor in question is assigned to a group and
that a motion event is currently ON in the schedule (see gateway manual).
3. On the gateway web page verify that the nodes in the network show with no
connection errors (consult gateway manual).
4. Follow the provided instructions to turn the sensor LED switch to ON.
5. Check the condition of the LED lights through the front lens of the sensor.
6. If the red LED is blinking then the batteries need to be replaced.
7. If the green LED is double blinking then the sensor is trying to join a network. Follow steps
in the gateway manual to discover the sensor and see if the problem persists.
8. From your gateway’s wireless devices page, display the motion sensors (consult the
gateway manual for instructions).
9. Wait until no motion sensor in the network is showing motion present.
10. Trigger motion on the sensor in question.
11. If the green LED behind the front lens of the sensor does not blink once then: a. Try new batteries. b. Replace the sensor.
12. If the green LED does blink then verify that one sensor on the gateway web page shows
motion present for a relatively short period of time.
13. If motion is shown on one sensor node then verify that that sensor is assigned to global
mode or the group that you want to light up.
14. If none show motion present then this sensor is likely part of a different gateway
network. Follow steps in this manual to remove the sensor from a different gateway.
17
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
Loading...