Despatch PROTOCOL PLUS Installation Manual

E-101
P. N. 157427
REVISION B
6/2002
PROTOCOL PLUS™ CONTROL
(HEAT/COOL VERSION)
INSTRUCTION MANUAL
SOFTWARE VERSION 3.1
Prepared by: Despatch Industries P.O. Box 1320 Minneapolis, MN 55440-1320 Customer Service 800-473-7373
NOTICE
CAUTION
Users of this equipment must comply with operating procedures and training of operation personnel as required by the Occupational Safety and Health Act (OSHA) of 1970, Section 6 and relevant safety standards, as well as other safety rules and regulations of state and local governments. Refer to the relevant safety standards in OSHA and National Fire Protection Association (NFPA), section 86 of 1990.
Setup and maintenance of the equipment should be performed by qualified personnel who are experienced in handling all facets of this type of system. Improper setup and operation of this equipment could cause an explosion that may result in equipment damage, personal injury or possible death.
Dear Customer, Thank you for choosing Despatch Industries. We appreciate the
opportunity to work with you and to meet your heat processing needs. We believe that you have selected the finest equipment available in the heat processing industry.
At Despatch, our service does not end after the purchase and delivery of our equipment. For this reason we have created the Service Products Division within Despatch. The Service Products Division features our Response Center for customer service. The Response Center will direct and track your service call to ensure satisfaction.
Whenever you need service or replacement parts, contact the Response Center at 1-800-473-7373: FAX 612-781-5353.
Sincerely, Despatch Industries
Despatch Industries
Product Warranty
See separate warranty for Benchtop and Laboratory Ovens (Form BB7)
Parts, Materials and Labor
Seller warrants the equipment manufactured by Seller and not by others, to be free from defects in workmanship and material under normal use and service for a period of (1) year from the date of delivery or the period of two thousand (2,000) accumulated hours of use, whichever period is shorter. Use or service with corrosive or abrasive chemicals or materials is not deemed normal. The period of the foregoing warranty, in the case of furnaces, shall be ninety (90) days or five hundred twenty-five (525) accumulated hours of use, whichever period is shorter. Components manufactured by others, including expendable items, are warranted only in accordance with the warranty, if any, issued by such other manufacturer.
Buyer shall give Seller written notice of any defects with 14 days after discovery thereof, specifying each particular defect discovered. If such notice is properly given, Seller will correct without charge any workmanship that is demonstrated to Seller's satisfaction to have been defective at the time of installation, and will repair or replace, at Seller's option, without charge, f.o.b. Seller's factory, parts covered by this warranty that upon inspection are found defective under normal use within the warranty period above stated. All work of removal and reinstallation, whether or not found defective, and shipping charges for defective or replacement parts shall be at the sole expense of Buyer.
The foregoing warranty shall not apply to (i) work done or materials furnished by others in connection with installation work performed without supervision by Seller's installation supervisors, or (ii) equipment repaired or altered by others unless such repairs or alterations were specifically agreed to in writing by an Officer of Seller. Seller shall not be liable for consequential damages of any kind which occur during the course of installation of equipment, or which result from the use or misuse by Buyer, its employees or others of the equipment supplied hereunder, and Buyer's sole and exclusive remedy against Seller for any breach of the foregoing warranty or otherwise shall be for the repair or replacement of the equipment or parts thereof affected by such breach.
The foregoing warranty shall be valid and binding upon Seller if and only if Buyer loads, operates and maintains the equipment supplied hereunder in accordance with the instruction manual to be provided upon delivery of the equipment. Seller does not guarantee the process of manufacture by Buyer or the quality of product to be produced by the equipment supplied hereunder, and Seller shall not be liable for prospective profits.
Despatch will repair or replace, at Despatch's option, FOB Despatch's factory, parts and materials covered by this warranty. Despatch is not responsible for parts or material failures resulting from misuse, abuse, inadequate preventive maintenance, acts of nature, or non-conforming utilities, including electrical, fuel supply, environmental and intake/exhaust provisions. This warranty also does not cover normal wear or routine maintenance parts and materials expressly designed as expendable/consumable and replaceable. (Note: Laboratory oven electric heaters are warranted for a period of five [5] years from date of shipment; three [3] years from date of shipment for Protocol Plus and DES 2000 temperature controllers.)
Labor services for parts and materials replacement and repair to support this warranty are available at Despatch's normal service fees. This service is provided worldwide by a network of factory trained professionals.
Transportation Costs
All transportation costs to transport defective parts or materials to Despatch, and to transport repaired or replacement parts or materials to Customer, shall be the responsibility of the Customer.
Terms and Conditions
This Warranty shall be deemed valid and binding upon Despatch if and only if the Customer:
1. installs, loads, operates, and maintains the covered product supplied hereunder in accordance with the instruction manual provided upon delivery and product labeling affixed to the subject equipment:
THE REPRESENTATION AND WARRANTIES SET FORTH HEREIN ARE EXCLUSIVE AND IN LIEU OF, AND CUSTOMER HEREBY WAIVES AND DISCLAIMS RELIANCE UPON, ALL OTHER REPRESENTATIONS AND WARRANTIES OF EVERY KIND WHATSOEVER, WHETHER EXPRESS OR IMPLIED, OR ARISING BY OPERATION OF LAW OR IN EQUITY, OR BY COURSE OF PERFORMANCE OR DEALING OR USAGE OF TRADE, INCLUDING, WITHOUT LIMITATION, ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE.
THIS WARRANTY IS PERSONAL TO THE CUSTOMER AND MAY NOT BE TRANSFERRED OR ASSIGNED. ALL LIMITATIONS HEREUNDER, HOWEVER, SHALL BE BINDING ON ALL SUCCESSORS AND ASSIGNS OF CUSTOMER.
2. if applicable, follows the Emergency Procedure set forth in this Warranty; and
3. contacts Despatch's Helpline at 1-800-473-7373 for assistance in diagnosing and troubleshooting the problem immediately upon discovering any damage or malfunction.
Despatch's reasonable determination as to whether a repair, replacement, or service is covered by this Warranty shall be final and binding.
Exclusions
This Warranty DOES NOT cover:
1. damage or malfunctions, or expenses incurred in the process of diagnosing and/or repairing damage or malfunctions, resulting from any of the following: operator error, misuse, abuse, inadequate preventive maintenance, normal wear and tear, service or modifications by other than Despatch authorized technicians, use of the covered product that is inconsistent with the operation manual or labeling, acts of nature (including, without limitation, floods, fire, earthquake, or acts of war or civil emergency), internal or external corrosion, or non-conforming utilities (including, without limitation, electrical, fuel supply, environmental and intake/exhaust installations);
2. repair or replacement of parts or materials designed and intended to be expendable or consumable;
3. routine maintenance; or
4. labor costs incurred for troubleshooting, diagnostics, or testing (except for testing required to verify that a covered defective part or material has been repaired).
Limitations of Liability
Despatch shall not, in any event, be liable for indirect, special, consequential, incidental, or punitive damages or penalties of any kind, including, without limitation loss of revenue, profits or business opportunities resulting from interruption of process or production. In no event shall Despatch be liable for damages in excess of the amounts paid by Customer to Despatch with respect to the applicable product(s). This Warranty does not cover, and Despatch shall not be liable for any losses, costs, damages or expenses resulting from delays in diagnosing or repairing the products, supplying or obtaining replacement parts or materials, strikes, labor stoppages or shortages, fires, accidents, government acts or regulations, or any other causes beyond the control of Despatch.
Non-Compliance By Customer
Despatch reserves the right to suspend and withhold service under this Warranty in the event of non-compliance by the Customer to any terms and conditions of this Warranty or the applicable purchase order or invoice. Further, Despatch shall not be liable for any loss of production, expenses, and inconveniences incurred due to such suspension.
Customer Furnished Equipment Warranty Limitation
This Warranty does not cover diagnosis or repairs of defects in or caused by, lack of performance of, or fitness for purpose of customer-supplied parts or equipment unless specifically noted in the Despatch written order acceptance confirmation.
Performance Commitment
Despatch provides no guarantee of process performance or fitness for purpose, unless specifically noted otherwise in Despatch written order acceptance confirmation. Despatch is providing equipment with design parameters specific only to its equipment.
Procedure Upon Discovery of Defects and Emergencies
In the event Customer becomes aware of any defect in the applicable products, Customer must immediately: (a) shut off fuel or energy supply (gas and electricity), (b) call for emergency assistance, if needed, and (c) notify Despatch Service.
Worldwide Phone 612-781-5356; Worldwide Fax 612-781-5485; North American Phone 800-473-7373
Service
e-mail info@despatch.com; www.despatch.com
Please see reverse side for other service offerings BB5 (5/28/02)
Despatch Industries
Advantage Service Assurance Program (ASAP)
CONTACT: DESPATCH SERVICE AGREEMENTS SPECIALIST at 800-473-7373 or 612-781-5356
or e-mail: info@despatch.com
Despatch continues to deliver exceptional products backed by a strong sense of responsibility and drive for long term customer satisfaction. Your partnership with Despatch can offer even higher value through your subscription to one of Despatch's Advantage Service Assurance Program (ASAP).
Warranty
Despatch's exclusive, comprehensive service programs start with the 1 year parts only warranty which is described on the other side of this document. This warranty can be expanded immediately to meet your most stringent service needs. Despatch Service Products Group will be able to answer your service questions and provide a quotation for the immediate expansion of your product warranty. Call 800-473-7373 or 612-781-5356; or e-mail info@despatch.com.
Immediate Service Response
The key to an effective service program is response. Wherever your location, Despatch is only a phone call away. Our U.S. and Canadian customers can reach Despatch at 1-800-473-7373. Worldwide customers can call 1-612-781-5356 or FAX 1-612-781-5485. Our Customer Service Technicians have over 150 years combined experience and access to detailed design and manufacturing documentation specific to your Despatch unit(s). This exacting level of service is a benefit only Despatch can provide and means that you can expect speedy, accurate and the most cost effective response.
Field Service Network
A worldwide network of factory trained Service Professionals is available to support your Despatch equipment. From routine repair to certified instrument calibration, the Despatch service network is positioned to respond to your needs. As a manufacturer of custom equipment, our service programs are customized to meet your specific needs regarding:
1. Service scope
2. Response time
3. Preventive maintenance frequency and content
4. Payment method
Sustained Service Support
At Despatch, long term customer satisfaction means more than just responding quickly and effectively to our customers' service needs. It means offering comprehensive customer support well beyond the scope and duration of our initial warranty. Despatch offers two basic service packages which are customized to each individual customer's need. These service packages are titled Full Service and Preventive Maintenance Plus+ service agreement products. Each is unique in the industry and offer the following benefits:
1. Priority response for minimum production interruption
2. Preventive maintenance for longer product life
3. Discounts on parts and services
4. Various payment plans to ease budgeting and recording expenses
5. Reduce purchase ordering costs
Worldwide Phone 612-781-5356; Worldwide Fax 612-781-5485; North American Phone 800-473-7373
e-mail info@despatch.com; www.despatch.com
Service
TABLE OF CONTENTS
TABLE OF CONTENTS................................................................................................... i
INTRODUCTION.............................................................................................................1
Theory of Control Operation........................................................................................1
Operating Modes......................................................................................................3
Setup Mode..............................................................................................................3
Fast Start Mode........................................................................................................3
High Limit.................................................................................................................4
Indicators .................................................................................................................4
Displays ...................................................................................................................5
Key Functions..........................................................................................................5
Outputs ....................................................................................................................6
Relay (Continued)....................................................................................................7
Communication........................................................................................................7
Optional Software.....................................................................................................7
INSTRUCTIONS .............................................................................................................8
Start-Up.......................................................................................................................8
Operation.....................................................................................................................9
Manual Mode...........................................................................................................9
Timer Mode............................................................................................................10
Profile Mode...........................................................................................................11
Auto Start Mode.....................................................................................................11
Setup Mode............................................................................................................12
Instructions for Setup Mode Pages............................................................................13
Program Page........................................................................................................13
Profile # ..............................................................................................................15
Sample Profile........................................................................................................16
Auto Start Page (optional)......................................................................................17
Control Page..........................................................................................................20
Communication Page (optional).............................................................................21
Real Time Clock Page (optional)............................................................................21
Relay Outputs Page (optional)...............................................................................22
Test Page...............................................................................................................23
Zone Calibration Page ...........................................................................................24
Sensor Calibration Page........................................................................................26
Enable Page...........................................................................................................28
Digital Inputs (optional) ..........................................................................................29
Error Messages and Alarms ......................................................................................30
Quick Reference and Default Values.........................................................................31
Technical Specifications............................................................................................38
APPENDIX: Temperature Scale Conversion and Optional MRC5000 Setup................39
Temperature Scale Conversion (C/F)........................................................................39
i
ii
INTRODUCTION
The special features of the Protocol PlusTM control include:
PID tuning
Ramp/Soak programming of up to 64 segments
Segment looping and profile linking
Built-in manual reset high limit control
Built-in process timer
Dedicated LED display for process temperature
Multi-purpose two-line LCD display with backlight
Auto-tuning
Security access
Digital inputs for remote profile control
Optional relay outputs for events, alarms, or end-of-cycle signal
Optional real-time-clock
Optional RS232/RS422/RS485 MODBUS communications
Theory of Control Operation
The Protocol Plus is a modular microprocessor based digital temperature controller. The Protocol Plus operates as a dual functioning controller/high limit instrument. The control portion utilizes a time-proportioning voltage signal to control heating devices with minimal temperature fluctuations.
The high limit portion protects the product and/or the oven from overheating. If the product being processed has a critical high temperature limit, the high limit setpoint should be set to a temperature somewhat below the temperature at which the product could be damaged. If the product does not have a critical high temperature limit, the high limit setpoint should be set 5 to 15 degrees higher than the maximum programmed setpoint at which the oven will operate.
1
Protocol Plus Faceplate and Wiring Diagram
2
Operating Modes
The Protocol Plus control has five modes of operation available: Stopped Mode: All control and relay outputs are off. Stopped Mode is integrated
into each of the following four modes of operation.
Manual Mode: Control operates as a single setpoint control until Stopped mode is
accessed
Timer Mode: Control operates as a single setpoint control until preset time period
has expired.
Profile Mode: Control operates as a ramp/soak profiling control until the end of
the profile. 8 profiles are available with up to 8 ramp/soak segments in each profile.
Auto Start Mode (optional): Control may automatically start Manual, Timer, or
Profile mode based on a preset time and day. Requires the optional real-time clock feature.
The optional event outputs can be utilized during Manual, Timer, or Profile modes.
Setup Mode
The control has a Setup Mode which provides access to control configuration and programming of profiles. The Setup Mode contains ten separate electronic Pages where the configuration and programming parameters (Menu items) are found. The Setup Mode Pages are described in detail elsewhere in this manual.
Fast Start Mode
The Protocol Plus control has the ability to automatically start an operating mode when power is applied. This feature may be useful if the same mode of operation is used everyday. The user can turn on the power and the oven will start the desired process automatically. The Fast Start Mode is controlled by the Power-Up Start parameters on the Control page (see Setup Mode).
3
High Limit
The control has an integrated high limit function which will disable the heater output when tripped. If the high limit does trip, the relay will need to be manually reset. When the high limit relay is tripped, the Hi-Limit indicator will be lit. Allow the oven to cool several degrees (or increase the high limit setpoint) and then press the Reset key. The indicator will turn off.
The control will not allow the high limit setpoint to be set below the current setpoint value.
Indicators
The Protocol Plus control has 12 indicating LEDs that provide operational information to the user.
C Power LED: Indicates that power is supplied to the instrument. C Heater LED: Indicates that the heater output is active. C Profile LED: Indicates that the Profile Mode is in operation. C Timer LED: Indicates that the Timer Mode is in operation. C Manual LED: Indicates that the Manual Mode is in operation. C Cycle Complete LED: Indicates that the control is in Stopped mode. C Hi-Limit Alarm LED: Indicates that the high limit relay has tripped (de-energized). C Soak Alarm LED: Indicates that the guaranteed soak deviation is in alarm
condition.
C Outputs 1 through 4: Indicate that the optional relay outputs are in the ON state.
These outputs may be configured as timed event outputs, process temperature trip point outputs, alarm outputs, or as an end of cycle relay output. The ON state can be configured as energized or de-energized.
4
Displays
The Protocol Plus control has two displays. A dedicated LED upper display shows the oven temperature. A two-line LCD lower display provides information on control status and allows changes to be made to the control settings.
Key Functions
The Protocol Plus control has seven keys that provide operation.
Select key: Press to select mode of operation. In Setup Mode, to select profile number or relay. In Profile/Run Mode, press simultaneously with the UP key to advance a segment.
Run/Hold key: Press to activate a mode of operation. If a Profile (or Timer) Mode is running, pressing the Run/Hold key will place the Profile (or Timer) in Hold status. A subsequent press will resume the Profile (Timer).
Stop key: Press to stop any mode of operation.
Page/Reset key: While in Setup Mode, press to access different Pages of
configuration, Press this key to silence an alarm if the instrument alarm sounds during operation. In an operating mode, if an alarm or error condition occurs, press this key to return the instrument to normal operation once the condition is cleared.
Menu/View key: While running any operating mode, pressing this key will display the high limit setpoint. While in Setup Mode, pressing this key will provide access to each Menu parameter.
keys: Press these keys to adjust parameter settings. In Profile/Stopped Mode, press to select profile to run. In Profile/Run Mode, press key simultaneously with the Select key to force the program to advance one segment.
5
Outputs
The Protocol Plus control has seven different outputs available.
Heating output: The control output is a DC voltage open-collector output which is time-proportioned and designed to control a heat control device such as a solid state relay.
Cooling output: The cooling output is a 4 to 20 ma DC output which is designed to control a cooling device such as a damper motor.
High limit: The high limit output is a form C relay which is energized under normal operating conditions. If the control senses a temperature higher than the high limit setpoint, or if there is a sensor error, the high limit relay will de-energize until the condition is cleared and the Reset key is pressed. When the high limit relay is de-energized, the heater is disabled.
Relay (four optional outputs): The four form A dry contact relay outputs can be configured to function as alarms, events, or end of cycle. These outputs can be utilized in Manual, Timer, or Profile Mode.
Layout for Optional Components
6
Relay (Continued) Use the Relay Card Optional Ay p/n 144562 to add relays to the standard controller. Each relay card contains two relays (maximum of two cards Ay’s allowed).
Communication
The Protocol Plus control has optional MODBUS communication available which can communicate via RS232, RS422, or RS485 to a computer. See communications option assembly p/n 161957 for board and cable assembly. Please refer to the MODBUS communications manual which comes with this option.
Optional Software
The Protocol Manager program allows the operator to start/stop multiple ovens (32 maximum) from a personal computer. A data log can also be used to record process information (p.n. 140008).
7
INSTRUCTIONS Start-Up
These instructions are provided as a quick reference for operating the Protocol Plus control. If the Profile Mode is to be used, or the configuration of the control needs to be changed, please refer to the Setup Mode instructions before operating the control. For more detailed operating instructions refer to the Operation instructions for the mode you wish to use.
Upon initial power-up the control is in Manual/Stopped Mode (unless the Autostart or Fast Start Modes are active). To activate any operating mode from Stopped Mode, press the Select key until the desired mode is displayed, then press the Run key. If the proper Profile number is not displayed when the Profile Mode is accessed, press the or keys until the desired Profile number is displayed, then press the Run key. If no profile numbers can be displayed (display only reads NONE) then no profiles are currently programmed (see Setup Mode).
The temperature setpoint can be adjusted while Manual or Timer Mode is running by pressing the UP or DOWN key.
To momentarily hold the Timer or Profile Mode, press the Hold key. To continue the Timer or Profile Mode, press the Run key.
To return to Stopped Mode at any time, press the Stop key and the cycle complete LED will illuminate.
Note that the control can be configured to automatically activate Manual, Timer or Profile Mode when power is applied (power switch turned on). See Control Page in the Setup Mode to utilize the Fast Start mode.
8
Operation
Manual Mode
Press the Select key until Manual is displayed (note you can press the Run key at any time to activate Manual Mode).
1. Press the Menu key to display the Process Temperature Setpoint (setpt). You can change the Setpoint with the keys.
Note: If the SPChange parameter on the Enable page in Setup Mode has been set to DISABLED, it must be changed to ENABLED before any changes to the process temperature and high limit setpoints can be made.
2. Press the Menu key a second time to display current high limit setpoint (Hi-Lim SP). The value can be adjusted by pressing the keys. If Band is displayed, the high limit band feature is activated (see Control page) and the high limit can not be adjusted.
3. (optional feature) Press the Menu key a third time to display Event1. Press the key to turn on the event or to turn off the event. Repeat for all events which are enabled (up to 4).
4. To start Manual Mode, press the Run key.
The display will change from Stop to Run. To return to Stopped Mode, press the Stop key. While in operation, the process setpoint can be adjusted by using the
keys to change the value while the mode is running. Pressing the Menu key
will display the High Limit Setpoint (HLSP) setting.
If changes to the high limit setpoint or event output configuration are needed, they must be done from the stopped mode.
9
Timer Mode
1. Press the Select key until Timer is displayed (note you can press the Run key at any time to activate Timer Mode).
2. Press the Menu key to display the Process Temperature Setpoint (Setpt). You can change the Setpoint with the keys.
Note that if the SPChange parameter on the Enable page in Setup Mode has been set to DISABLED, it must be changed to ENABLED before any changes to the process temperature and high limit setpoints can be made.
3. Press the Menu key a second time to display current high limit setpoint (Hi-lim SP). The value can be adjusted by pressing the keys. If Band is displayed, the high limit band feature is activated (see Control page) and the high limit can not be adjusted.
4. Press the Menu key a third time to display Time Set. You can change the time setting with the keys.
5. (optional feature) Press the Menu key a fourth time to display Event1. Press the
key to turn on the event or to turn off the event. Repeat for all events which
are enabled (up to 4).
6. Press the Menu key a fifth time to display the current guaranteed soak band (TmrGuarSoak) value. If the process temperature deviates from the setpoint by more than this value, the timer is placed in a hold condition. The timer continues when the process temperature falls within range. Reference the Quick Reference and Default Values section for available settings.
7. To start Timer Mode, press the Run key. The display will change from Stop to Run and the time remaining will be
displayed. To return to Stopped Mode, press the Stop key. While in operation, the process setpoint can be adjusted by using the keys to change the value while the mode is running. Pressing the Menu key will display the High Limit Setpoint.
Pressing the Run/Hold key while the Timer Mode is in operation will put the control in Hold status. The Timer LED will flash to indicate the held status. Press the Run/Hold key again to continue timing. The Timer LED will return to lit status.
10
Profile Mode
1. Press the Select key until Profile is displayed. “None” may be displayed if a profile has not been selected or no profiles entered.
2. Press the key to display the desired profile to run.
3. To start Profile Mode, press the Run key.
The display will change from Stop to Run and the segment time remaining, Temperature Setpoint, Profile #, along with the current segment number, will be displayed. To return to Stopped Mode, press the Stop key.
Pressing the Run/Hold key while the Profile Mode is in operation will put the control in Hold status. Press the Run/Hold key again to continue the mode. The Profile LED will flash to indicate the hold status.
To advance to the next segment while running a profile, press the Select and UP arrow keys at the same time.
Note that ramping down too fast may cause the high limit relay to trip unexpectedly if the high limit band feature is used. This can be avoided by using a separate cooling profile that does not utilized the high limit band and then jumping to that profile to perform rapid cooling.
Auto Start Mode
The Auto Start Mode allows the control to start Manual, Timer, or Profile mode automatically at a preset time and day. See the Auto Start Page in Setup Mode for the time, day, and operating mode settings. The Auto Start Mode requires the optional Real Time Clock feature for operation.
To activate the Auto Start Mode, the control must first be in Stopped Mode.
1. Press the Select key until Auto Start is displayed.
2. Press the Menu key.
3. Press the keys to activate or deactivate the Auto Start feature.
Note that once you activate Auto Start, you can continue to use all operating modes as normal. If an operating mode is running at the time of a preset Auto Start function, and Auto Start is activated, the existing operating mode will override the auto Start function and the Auto Start will not turn on.
To use the Auto Start for the next day, the auto start must show in the LCD display that it is active.
11
Setup Mode
Configuration of the control and programming of the ramp/soak profiles must be done in the Setup Mode. To access Setup Mode, the control must first be in Stopped Mode.
1. Press the Select key until Setup is displayed.
2. Press the Page key and Security will be displayed.
3. Press the Menu key and Password will also be displayed. Use the keys to enter the proper password.
4. Once the proper password is displayed, press the Page key twice to enter the Setup Mode.
To exit Setup Mode, press and hold the Page key for three seconds. The control has two levels of password-protected security. Level one provides access
only to those menu pages that are enabled on the Enable page. Level two provides access to all menu pages, including the Enable page. The default security password values are 1 for level one and 2 for level two.
If an improper password has been entered, the control will remain at the Security display. To enter the proper password, press the Menu key. To exit Setup Mode, press and hold the Page key for three seconds.
Mapping of the Setup Mode is provided in the following sections. To access each parameter Page, which are described in detail in the following sections, press the Page key until the desired page heading is displayed. Press the Menu key to access each Menu parameter. Press the keys to change Menu parameter settings.
Refer to the Quick Reference and Default Values section for available settings for each Menu parameter.
Press the Page key to continue with each Page, or press and hold the Page key for three seconds to exit Setup Mode.
12
Instructions for Setup Mode Pages
Program Page
Programming of the profiles is provided on the Program Page. Eight profiles are available with up to eight ramp and soak segments per profile.
If the optional relay outputs are installed, they must be configured as alarms or events on the Relay Outputs Page before they can be utilized. If configured as event outputs, these relays can be used as time or temperature events.
When entering the Program Page, press the Select key to select the profile you wish to enter/edit, then press the Menu key. The first parameter (Profile #, Segment 1, Ramp Time) will display. Adjust the time value with the keys. Once the proper value is displayed, press the Menu key to continue. Continue with the Menu key to adjust/view each parameter.
If the ramp time value of the current segment is left at 0:00, the next press of the Menu key will advance the control to the High Limit Setpoint parameter for that profile. Continue entering / verifying all parameters until you get to the last parameter (Guaranteed Soak Band). Once all parameters have been properly entered, press the Page key to return to the top of the Profile Page. You can press the Select key to enter/edit another profile, press the Page key to access another page, or press and hold the Page key to exit Setup mode.
While editing any profile, pressing the Select key will advance the control to the time value for the next segment, until the last segment has been reached. This allows faster editing of the profile rather than pressing the Menu key to advance past each parameter.
To run a profile indefinitely, link the profile to itself.
13
Menu Item Display Description Ramp Time Seg 1 Pro-1 Seg-1 Ramp Time Ramp time for segment 1 of profile
Event 1 Set Value* Pro-1 Seg-1 Ramp Event 1 Event 1 setting for segment 1 ramp of profile Event 2 Set Value* Pro-1 Seg-1 Ramp Event 2 Event 2 setting for segment 1 ramp of profile Event 3 Set Value* Pro-1 Seg-1 Ramp Event 3 Event 3 setting for segment 1 ramp of profile Event 4 Set Value* Pro-1 Seg-1 Ramp Event 4 Event 4 setting for segment 1 ramp of profile Soak Temp Seg 1 Pro-1 Seg 1 Soak Temp Soak temperature for segment 1 of profile Soak Time Seg 1 Pro-1 Seg 1 Soak Time Soak time for segment 1 of profile Event 1 Set Value* Pro-1 Seg-1 Soak Event 1 Event 1 setting for segment 1 soak of profile Event 2 Set Value* Pro-1 Seg-1 Soak Event 2 Event 2 setting for segment 1 soak of profile Event 3 Set Value* Pro-1 Seg-1 Soak Event 3 Event 3 setting for segment 1 soak of profile Event 4 Set Value* Pro-1 Seg-1 Soak Event 4 Event 4 setting for segment 1 soak of profile (repeat for segments 2-8, until ramp or soak time = 00:00) High Limit Setpoint Pro-1 Hi-Lim SP High limit setpoint for profile** Loop From Pro-1 Loop From Seq To start a loop action in a profile Loop To Pro-1 Loop To Seq To end a loop action in a profile Loop Count Pro-1 Loop Number Number of times to execute loop Profile Link Pro-1 Link To Pro To jump from this profile to another Guaranteed Soak Pro-1 Guar Band Guaranteed soak band for profile
See the definitions on the following pages for parameter ranges.
* only available if optional relay outputs are installed (repeat all for profiles 2-8) ** Set to Band to use the high limit band feature
14
Profile #
There are eight profiles available.
Segment#
Ramp Time
EV1 through 4
Soak Temp.
Soak Time
EV1 through 4
Recipe segments 1 through 8 may be programmed, each with its own set of events, ramp and soak times, and soak temperature.
The time required to ramp from one setpoint up to another setpoint. Values between 0 and 59:59 are allowable. In the Protocol Plus controller, the profile ramp and soak times are stored without units. Units are set as either hours and minutes (HH:MM) or minutes and seconds (MM:SS). The setpoint will automatically increment from the actual temperature to the soak temperature.
From 1 to 4 events may be programmed into the ramp time portion of each segment here. These typically involve actuating/disabling relays to close/open valves or perform other relay-controlled functions. NOTE: These will only actuate when the controller has the relay cards installed and programmed for an event.
The temperature setpoint of a particular segment is entered here; it can range from -18 to 540 degrees C (0 to 1000 degrees F).
The duration of soak is entered here; the value can range from 0 to 59:59.
From 1 to 4 events may be programmed into the soak portion of each segment here. These typically involve actuating/disabling relays to close/open valves or perform other relay-controlled functions. NOTE: These will only actuate when the controller has the relay cards installed and programmed for an event.
Hi Limit SP
Loop From Loop To Loop Number
Profile Link
Guaranteed Soak Band
The high limit setpoint may be entered here; if the temperature exceeds this value, the hi-limit will alarm and shut off the heater.
Values are No, Seq-1 to Seq-8. Values are No, Seq-1 to Seq-8. Values are 0 - 99.
These values enable the operator to jump from a certain step to another step of the recipe a preset number of times.
Values are STOP/HOLD/1 - 8. When the profile ends, the profile can turn the heater off, hold the temperature setpoint at the end of the profile, or jump to another specified profile.
If the process temperature deviates from the setpoint by more than this value, the soak timer is placed in a hold condition. The timer continues when the process temperature falls within range.
15
Sample Profile
Programming Table Profile Number____1______ Profile Name__________
Seg­ment
Time
Ramp Soak
Events Events
1 2 3 4
Temp-
erature
Time
1 2 3 4
1 01h00 100 01h00 2 02h00 50 00h01 3 00h00 4 5 6 7 8
High Limit Setpoint 115
Loop From Seq No
Loop To Seq No
Loop Number 0
Link To Pro No
Guar Soak Band 10
16
Auto Start Page (optional)
If the optional real time clock has been installed, the Auto Start Page can be configured to automatically start Manual, Timer or Profile Mode at a specified time and day. Note that if Auto Start Enable is set to Yes in the Setup Mode, the Auto Start feature is not turned on - it is available to the operator to be activated in Stopped Mode.
To configure the Auto Start feature:
1. Access the Setup Mode.
2. Press the Page key until Auto Start is displayed.
3. Press the Menu key. If there is no change in the display, the controller may not have the realtime clock option.
4. Set Auto Start Enable to Yes.
5. Using the Menu key, scroll through the options available and use the keys to set the mode desired for each day of the week. You may select from Manual, Timer, or Profile 1 through 8.
6. When the mode is set press the Menu key.
7. Enter the time of day you wish the mode to activate.
8. Continue through the rest of the week by pressing the Menu key, or press the Page key when done.
One Auto Start mode can be set for each day of the week. Exit the Setup mode by pressing and holding the Page key for three seconds. Press the Select key until Auto Start is displayed. Make sure the correct time and day is displayed. If not proper, set it to the correct time on the Real Time Clock Page in the Setup mode. Press the Run key to activate Auto Start. The display will change from Stop to Active. When the preset time and day occurs, the appropriate operating mode will start. You can de-activate Auto Start by pressing the Select key until Auto Start is displayed, then pressing the Stop key.
Note that once you activate Auto Start, you can continue to use all operating modes as normal. If an operating mode is running at the time of a preset Auto Start function, and Auto Start is activated, the existing operating mode will override the Auto Start function and the Auto Start will not turn on.
17
Menu Item Display Description Range Enable
Autostart Sunday mode Sunday time Monday mode Monday time Tuesday mode Tuesday time Wednesday mode Wednesday time Thursday mode Thursday time Friday mode Friday time Auto Start Fri
Saturday mode Saturday time
Auto Start Enable Enable (yes) or disable (no) the Auto Start Sun
Mode Auto Start Sun Time Auto Start Mon Mode Auto Start Mon Time Auto Start Tue Mode Auto Start Tue Time Auto Start Wed Mode Auto Start Wed Time Auto Start Thu Mode Auto Start Thu Time Auto Start Fri Mode
Time Auto Start Sat Mode Auto Start Sat Time
No, Yes Autostart function Set mode on Sunday to activate Off, Manual, Timer, Pro-1 to Pro-8
Set time on Sunday for mode to activate Set mode on Monday to activate Off, Manual, Timer, Pro-1 to Pro-8
Set time on Monday for mode to activate Set mode on Tuesday to activate Off, Manual, Timer, Pro-1 to Pro-8
Set time on Tuesday for mode to activate Set mode on Wednesday to activate Set time on Wednesday for mode to activate Set mode on Thursday to activate Off, Manual, Timer, Pro-1 to Pro-8
Set time on Thursday for mode to activate Set mode on Friday to activate Off, Manual, Timer, Pro-1 to Pro-8
Set time on Friday for mode to activate Set mode on Saturday to activate Off, Manual, Timer, Pro-1 to Pro-8
Set time on Saturday for mode to activate
00:00 to 23:59
00:00 to 23:59
00:00 to 23:59
Off, Manual, Timer, Pro-1 to Pro-8
00:00 to 23:59
00:00 to 23:59
00:00 to 23:59
00:00 to 23:59
18
PID Page
The PID Page contains parameters which control the response to the setpoint and process variable input. To access the PID Page, enter the Setup Mode. Press the Page key until PID is displayed. Press the Menu key. Each parameter can be changed by pressing the Menu key until the desired parameter is displayed, and then pressing the
keys to change the value.
Menu Item Display Description Range Display units PID Temp Unit Set display units to °C or °F Proportional band PID PB(H) Set proportional band for tuning Integral reset PID I(H) Rep/min Set integral reset for tuning 0 to 100 Sec/repeat Derivative Rate PID D(H) in sec Set derivative rate for tuning 0 to 500 Sec. AutoTune PID AutoTune Enable auto tuning function DIS EN Proportional band PID PB(C) Set proportional band for tuning Integral reset PID I(C) Rep/min Set integral reset for tuning 0 to 100 Sec/repeat Derivative Rate PID D (C) in sec Set derivative rate for tuning 0 to 500 Sec. Heat Offset PID Heat Offset Set PB up or down from Setpoint Cool Offset PID Cool Offset Set PB up or down from Setpoint
°C or °F
1 to 56°C (1 to 100°F)
1 to 56°C (1 to 100°F)
-6 to 6°C (-11 to 11°F)
-6 to 6°C (-11 to 11°F)
The AutoTune parameter disables or enables the AutoTune function. To utilize AutoTuning:
1. Access the Setup Mode.
2. Press the Page key until the display reads AutoTune. Press the key to enable the AutoTune.
3. Press the Page key for three seconds to exit Setup Mode.
4. Cycle power to the instrument.
5. Set Manual Mode to run. The display will alternately display AutoTune and Manual.
If the Manual Mode setpoint is less than 50 degrees higher than the actual process temperature, the AutoTune function will create an error condition. This can be cleared by either cooling off the process temperature or increasing the setpoint until there is more than 50 degrees between them. Once the AutoTune function is allowed to complete tuning, the AutoTune parameter will disable by itself.
If you wish to cancel the AutoTune function, press the STOP key, access the PID page in Setup Mode, and set the AutoTune parameter to Disable.
19
Control Page
The Control Page contains various parameters which control miscellaneous functions. To access the Control Page, enter the Setup Mode. Press the Page key until Control is displayed. Press the Menu key. Each parameter can be changed by pressing the Menu key until the desired parameter is displayed, and then pressing the keys to change the value.
Menu Item Display Description Range Cycle Time Control Cycle
Time Sec High limit setpoint High limit band
Power fail recovery
Recovery time limit
Powerup start enable Powerup Start Mode Hysteresis Control
Process out low Process out high Time scale Control
Key press beep End of cycle beep Alarm beep Control
Control type Control
Control Hi-Lim
SP***
Control Hi-Lim
Band
Control PwrFRec Controls response to loss of
Control
PFRTime****
ControlPwrUpStrt Allows mode to automatically
Control StrtMode Operating mode for powerup start
Hysteresis
Control
RetOutLo
Control RetOutHi Process value for retransmit
TimeScale
Control KeyBeep Internal beeper sounds when key
Control
EOCBeep
AlarmBeep
Ctrl Heat/Cool
Set cycle time in seconds for control output Maximum value for all high limit setpoints If=0, high limit setpoint= Control Hi-Lim SP If>0, high limit setpoint= Control SP* + Band
power Control aborts to Stopped mode if
power is lost for time period longer then set value
start when power is first applied
Hysteresis for all alarms and temperature events Process value for retransmit output = 1VDC
output = 5VDC Time scale setting for program and timer mode**
is pressed Internal beeper sounds at end of cycle Internal beeper sounds for alarms
Set control type
1 to 60 seconds MinHiLimSP - MaxHiLimSP* Off, 3°C to 11°C (5°F to 20°F)
Stop, Restart, Hold, Resume 00m00s to 99m59s
Disable, Enable Off, Manual, Timer, Pro-1 to Pro-8 1°C to 56°C (1°F to 100°F)
hh:mm or mm:ss On or Off On or Off On or Off
Heat, cool, heat/cool
* includes ramping setpoints during profiles and controlled ramps ** power fail recovery time limit is always MM:SS regardless of time scale setting *** high limit setpoint is a read-only item which is calculated on Enable page **** requires real-time-clock feature
20
Communication Page (optional)
The Communication Page contains parameters for the communications feature. To access the Communications Page, enter the Setup Mode (see description earlier in this manual). Press the Page key until Communication is displayed. Press the Menu key. Each parameter can be changed by pressing the Menu key until the desired parameter is displayed, and then pressing the keys to change the value.
Menu Item Display Description Range Address Communication CommAddr Sets address node for
control
Mode Communication Mode Turns on/off
communications
Baud Rate Communication BaudRate Sets interface speed 2400, 4800, 9600, 19.2K, Parity Communication Parity Sets parity for interface None, Odd, Even
1 to 255 OFF, Modbus
38.4K
Real Time Clock Page (optional)
The Real Time Clock Page allows the control to be configured to have an operating mode begin automatically at a specific time on a specific day of the week. The real time clock feature is required for using the Power Failure Recovery mode Time Limit feature (see Control Page). The real-time-clock is a seven day, 24 hour clock with battery backup.
To access the Real Time Clock Page, enter the Setup Mode. Press the Page key until Clock is displayed. Press the Menu key. (If there is no change in the display, the controller may not have the realtime clock option.) Each parameter can be changed by pressing the Menu key until the desired parameter is displayed, and then pressing the
keys to change the value.
Menu Item Display Description Range Day of the
week Time of day Reset clock
Clock Day Setting for current day of the week Sun, Mon, Tue, Wed, Thu, Fri, Sat Clock HH:MM Setting for current time of the day 00:00 to 23:59 Clock UP to
Reset CLK*
Press the key to set the clock to entered values
Ready, Done
* If the key is not pressed, the clock values will retain their original values. The display will change to Done if the clock is reset
21
Relay Outputs Page (optional)
The Relay Outputs Page configures the four alarm/event outputs. Each output has a dedicated indicator light and can be configured as a temperature alarm, profile event, or end of cycle output. Temperature alarms can be of type process high, process low, deviation high, deviation low, or deviation band.
To access the Relay Page, enter the Setup Mode (see description earlier in this manual). Press the Page key until Relay is displayed. Press the Select key until the desired relay output is selected. Press the Menu key. Each parameter can be changed by pressing the Menu key until the desired parameter is displayed, and then pressing the keys to change the value. To configure a specific relay, press the Select key until the desired relay appears.
NOTE: If Relay 0 appears, then no relays are installed (see relay kit assembly p.n.
144562).
Menu Item Display Description Range Type of relay Relay 1
RelayType
Action of relay Relay 1
RelayAction Type of alarm* Alarm setpoint* Alarm deviation* Inhibit alarm* Relay 1
Type of event** Event setpoint***
Relay 1
AlarmType
Relay 1 AlmHi/Lo
SP
Relay 1
AlmDevBand
ALMInhibit
Relay 1
EventType
Relay 1 Event SP Setpoint for temperature event SPLoLim to SPUpLim****
(repeat for relay outputs 2-4, if available) * appears only for alarm types
** appears only for time or temperature event types *** appears only for temperature event types
Turning on the Alarm Inhibit function disables the alarm output on power up until the process temperature has reached a non-alarming condition ("safe").
If the relay output has been configured as latching, the RESET key must be pressed to return the output to the non-alarm state once the alarm condition has cleared.
Set function of relay Off, Alarm, Cycl, Ev1 to Ev4 Set coil and contact state of
relay Set alarm type for relay High, Low, Plus, Minus, Band
Setpoint for alarm Deviation band for alarm 1 to 56°C (1 to 100°F) Inhibits alarm until "safe"
condition is reached Set event type for relay Time or Temp
NDE, NE, NDEL, NEL*****
-73°C to 760°C (-100°F to 1400°F)
En or Dis
22
Test Page
The Test Page contains parameters which allow manual control of the heat control and optional relay outputs and should be used only for testing the functionality of the control instrument. Do not operate the oven for processes using the Test Page.
To access the Test Page, enter the Setup Mode (see description earlier in this manual). Press the Page key until Test is displayed. Press the Menu key. Each parameter can be changed by pressing the Menu key until the desired parameter is displayed, and then pressing the keys to change the value.
Menu Item Display Description Range Heater output High limit relay Relay 1 output Relay 2 output Relay 3 output Relay 4 output HiLim Sensor
Test HeatOut Activate SSR output 100% Test HiLimOut Activate high limit alarm
(de-energize relay)
Test Rly1 Out Energize relay output 1 Test Rly2 Out Energize relay output 2 Test Rly3 Out Energize relay output 3 Test Rly4 Out Energize relay output 4 Test HL Temp
(push and hold up)
Displays sensor reading*
*Push key to refresh display When the Test Page is entered, all outputs are automatically set to off. When exiting
the Test Page, all outputs will return to their previous condition regardless of the Test Page settings.
On On On On On On
23
Zone Calibration Page
The Zone Calibration Page allows adjustment of the displayed temperature versus the actual temperature measured by the control thermocouple. This may be desirable in certain conditions where the center of the oven chamber is not the same temperature as the control thermocouple. This may occur when the oven is not allowed to soak at a constant temperature for long periods of time, or the oven is being used at high temperature.
There is also a Factory Calibration Recovery which will restore the factory calibration values when the control was first shipped by the manufacturer. This may be helpful if the calibration has been lost and a calibration instrument is not readily available. To use the Factory Calibration Recovery feature only, bypass the Zone 1 and Zone 2 calibration parameters by pressing the Menu key.
To access the Zone Calibration Page, enter the Setup Mode (see description earlier in this manual). Press the Page key until Zone Cal is displayed. Press the Menu key. Each parameter can be changed by pressing the Menu key until the desired parameter is displayed, and then pressing the keys to change the value.
Menu Item Display Description Range Zone 1 actual Zone1 displayed Zone 2 actual Zone2 displayed Factory calibration*
Zone Cal Zone1Act Zone Cal Zone1Dis Zone Cal Zone2Act Zone Cal Zone2Dis Zone Cal FactCal
Point at which Zone 1 is set (center of chamber) Desired displayed value for Zone 1 setting Point at which Zone 2 is set (center of chamber) Desired displayed value for Zone 2 setting Restores the factory calibration values
*Only use when no calibration instrument is available, push key to restore factory values.
Press the Page key to exit the Zone Calibration Page. Two points of display calibration (temperature offset) are available. The Zone 1 Actual
and Zone 2 Actual parameters are the two temperature points where the offset is to take effect. These values are adjustable. The Zone 1 and Zone 2 Displayed parameters are the values the user wishes to have displayed at the Actual temperatures, and are also adjustable.
-73°C to 760°C (-100°F to 1400°F)
-73°C to 760°C (-100°F to 1400°F)
-73°C to 760°C (-100°F to 1400°F)
-73°C to 760°C (-100°F to 1400°F) Ready or Done (push- key)
24
As an example, the control is displaying 400°F with the setpoint being 400°F, but the center of the oven chamber is actually 395°F. This can occur due to oven wall losses and product loading variations. The operator may change the zone calibration so that the center of the oven is 400°F when the display reads 400°F. In this case operate the oven in manual mode with a setpoint of 400°F. Record the center of the chamber (as measured with an independent sensor). Access the Zone Calibration Page and enter this measured value as the Zone 2 Actual value, with 400° as the Zone 2 Displayed value.
Zone 1 can be adjusted using the same method at a lower temperature. The instrument will then create a linear offset based on the Zone1 and Zone 2 Actual temperature values. Note that the oven does not have to be heated to adjust the zone parameters if the zone values are known based on prior experience.
25
Sensor Calibration Page
The Sensor Calibration Page has parameters which can change the internal calibration of the temperature sensor input signal. There is a low and high calibration point for both the control sensor and the high limit sensor. To calibrate the instrument, allow the control to warm up for at least 30 minutes.
To access the Sensor Calibration Page, enter the Setup Mode (see description earlier in this manual). Press the Page key until Control Sensor is displayed. Press the Menu key.
The control may have the optional process value retransmission output feature. The output is a 1 to 5VDC signal. To calibrate the retransmit signal, the RetOutLo and RetOutHi values from the Control Page must be known. You may bypass calibrating the control and high limit sensor input to access only the retransmit calibration by pressing the Menu key until RetCalLo is displayed (skip steps 4-17).
To re-calibrate the instrument:
1. Disconnect the control and high limit sensor thermocouples.
2. Connect a calibration instrument with a type J thermocouple output to the control sensor input. Allow the control to warm up at least 30 minutes.
3. Access Setup Mode.
4. Press Page key until -100F is displayed.
5. Press Menu key until Ctrl Sens -100F is displayed.
6. With Ctrl Sens -100F displayed, adjust the calibration instrument to Type J thermocouple, -100 degrees Fahrenheit output.
7. Wait 30 seconds. Press the key.
8. With Ctrl Sens 1400F displayed, adjust the calibration instrument to 1400 degrees Fahrenheit output (Type J thermocouple).
9. Wait 30 seconds. Press the key.
10. When the control displays Ctrl Sens Done, disconnect the calibration instrument from the control sensor input and connect it to the high limit sensor input. Reconnect the control sensor thermocouple.
11. Press the Menu key until HL Sens -100F is displayed.
12. With the control displaying HL Sens -100F, adjust the calibration instrument to -100 degrees Fahrenheit output (Type J thermocouple).
13. Wait 30 seconds. Press the key.
14. With the control displaying HL Sens 1400F, adjust the calibration instrument to 1400 degrees Fahrenheit output (Type J thermocouple).
15. Wait 30 seconds. Press the key.
16. When the control displays HL Sens Done, disconnect the calibration instrument from the high limit sensor input. Re-connect the high limit sensor thermocouple.
17. To skip calibration of the retransmit signal, press the Page key twice to exit the Sensor Calibration Page.
18. To calibrate the retransmit signal, press the Menu key until RetCalLo is displayed.
26
19. Connect a calibration instrument with a type J thermocouple output to the control sensor input.
20. Connect a voltage measurement device to the retransmit output terminals.
21. Set the calibration instrument output to the temperature value of the RetOutLo parameter from the Control Page.
22. Adjust the RetCalLo * value using the keys until the voltage measurement device reads 1VDC.
23. Press the Menu key.
24. Set the calibration instrument output to the temperature value of the RetOutHi parameter from the Control Page.
25. Adjust the RetCalHi * value using the keys until the voltage measurement device reads 5VDC.
26. Press the Menu key.
27. Press the Page key to exit the Sensor Calibration Page.
28. Calibration is now complete. Disconnect the calibration instrument and voltage measurement device (if used).
29. Verify that the control and high limit sensor thermocouples are connected.
Menu Item Display Description Range Control Sensor Cal
HiLim Sensor Cal
Retransmit Cal RetCalLo XXXX *
Ctrl Sens -100F Ctrl Sens 1400F Ctrl Sens Done HL Sens -100F HL Sens 1400F HL Sens Done
RetCalHi XXXX *
Calibrate Sensor Low End Calibrate Sensor High End Control Sensor Cal Complete Calibrate HiLim Sensor Low End Calibrate HiLim Sensor High End HiLim Sensor Cal Complete Calibrate Retransmit Output Low Calibrate Retransmit Output High
-100 to 1400°F
-100 to 1400°F (read only)
-100 to 1400°F
-100 to 1400°F (read only)
0 to 4096** 0 to 4096***
*Note that the actual RetCalLo and RetCalHi values displayed are of no importance.
27
Enable Page
The Enable Page controls access to the other Setup Pages. The setpoint minimum and maximum values, and the security passwords are also set on the Enable Page. To access the Enable Page, enter the Setup Mode using a level 2 access code (see description earlier in this manual). Press the Page key until Enable is displayed. Press the Menu key. Each parameter can be changed by pressing the Menu key until the desired parameter is displayed, and then pressing the keys to change the value.
NOTE: Changing the enable to “yes” for each page will allow access to the page in Level 1 security.
Menu Item Display Description Range Profiles Enable Profile
1-8
Autostart Enable Auto
Start
PID Enable PID Controls access to PID Page Yes or No Control Enable Control Controls access to Control Page Yes or No
Controls access to Program Page Yes or No Controls access to AutoStart
Page
Yes or No
Communication Enable
Communication Real Time Clock Relay outputs Enable Relay
Test Enable Test Controls access to Test Page Yes or No Zone
Calibration Sensor Calibration Setpoint lower limit Setpoint upper limit High limit overhead Password level 1 Enable
Password level 2 Enable Setpoint
Change
Analog Output Type
Enable Clock Controls access to Real Time
1-4
Enable Zone
Cal
Enable Sensor
Cal
Enable
SPLowerLim
Enable
SPUpperLim
Enable
HiLimOH
Password 1
Password 2
Enable
SPChange
Enable Analog
Type
Controls access to Communication Page
Clock Page Controls access to Relay Page Yes or No
Controls access to Zone Calibration Page Controls access to Sensor Calibration Page Sets minimum setpoint allowed
Sets maximum setpoint allowed Sets maximum high limit setpoint
allowed* Sets password for access level 1 0 to 1000
Sets password for access level 2 0 to 1000 Set to DISABLE to lock out
setpoint and high limit setpoint changes in Manual and Timer Modes Sets Analog Output type Ctrl or Proc
Yes or No Yes or No
Yes or No Yes or No
-73°C to 760°C (-100°F to 1400°F)
-73°C to 760°C (-100°F to 1400°F)
3 to 11°C (5 to 20°F)*
Yes or No
* Maximum high limit setpoint = SPUpperLim + HiLimOH
28
Digital Inputs (optional)
The Protocol Plus control can be run by external inputs wired to the control from an external source such as a PLC or control panel switches. The external run operation can Run, Hold or Stop profiles 1 through 7 (profile 8 can not be operated externally). Refer to the table below for the inputs required for the desired operation. NOTE: A profile must be created in the program page before trying to run a profile number.
Input 1 Input 2 Input 3 Profile Selected ON OFF OFF 1
OFF ON OFF 2 ON ON OFF 3 OFF OFF ON 4 ON OFF ON 5 OFF ON ON 6 ON ON ON 7 OFF OFF OFF none
To start the selected profile, set Input 1, 2, 3 or 4 to ON. To hold a profile, set Input 4 to OFF. To stop a profile, set all inputs to OFF.
Digital Inputs
29
Error Messages and Alarms
The Alarm Status Hi-limit LED is flashing. This indicates a problem with the thermocouple, or the Hi-limit setpoint has been exceeded. Once the problem has corrected, press the Reset pushbutton.
The Alarm Status Soak LED is flashing. This indicates that the oven temperature has not entered or dropped out of the soak band and the soak timer has stopped.
The top LED Display reads OPEN. This indicates that either the Control or the Hi-limit thermocouple is disconnected or broken. The lower LCD display should indicate which thermocouple is the problem. Repair or replace the thermocouple.
The lower LCD display reads CONTROL SENS ERR. This indicates that the Control thermocouple is disconnected or broken. The upper LED display should indicate OPEN showing a thermocouple problem. Repair or replace the thermocouple.
The lower LCD display reads HI-LIM SENS ERR. This indicates that the Hi-limit thermocouple is disconnected or broken. Repair or replace the thermocouple.
The lower LCD display reads HIGH LIMIT ALARM. This indicates that the Hi-limit temperature setpoint has been exceeded. Determine if the setting is set too close to the setpoint, the SSR is defective, or the calibration is incorrect.
30
Quick Reference and Default Values
Program Page
Menu Item Display Default Range Setting Ramp Time Seg 1 Pro-1 Seg-1 Ramp Time 00:00 00m00s to
99h59s
Event 1 Set Value Pro-1 Seg-1 Ramp Event 1 Off Off, On Event 2 Set Value Pro-1 Seg-1 Ramp Event 2 Off Off, On Event 3 Set Value Pro-1 Seg-1 Ramp Event 3 Off Off, On Event 4 Set Value Pro-1 Seg-1 Ramp Event 4 Off Off, On Soak Temp Seg 1 Pro-1 Seg 1 Soak Temp 68°F SPLowerLim to
SPUpperLim *
Soak Time Seg 1 Pro-1 Seg 1 Soak Time 00:00 00m00s to
99h59s
Event 1 Set Value Pro-1 Seg-1 Soak Event 1 Off Off, On Event 2 Set Value Pro-1 Seg-1 Soak Event 2 Off Off, On Event 3 Set Value Pro-1 Seg-1 Soak Event 3 Off Off, On Event 4 Set Value Pro-1 Seg-1 Soak Event 4 Off Off, On (repeat for segments 2-8) High Limit Setpoint Pro-1 Hi-Lim SP Max
HiLimSP Loop From Pro-1 Loop From XX No No, Seg-1 to Loop To Pro-1 Loop To XX No No, Seg-1 to Loop Count Pro-1 Loop Number 0 0 to 99
Profile Link Pro-1 Link To XX Stop Stop, Hold, Guaranteed Soak Pro-1 Guar Band Off Off, 1 to 760°C (repeat for profiles 2-8)
MinHiLimSP to MaxHiLimSP *, Band **
Seg-8 Seg-8
Pro-1 to Pro-8 (1400°F)
* See Enable Page ** Band value is set on Control Page
31
Programming Table Profile Number__________ Profile Name__________
Seg­ment
Time
Ramp Soak
Events Events
1 2 3 4
Temp-
erature
Time
1 2 3 4
1 2 3 4 5 6 7 8
High Limit Setpoint
Loop From Seq
Loop To Seq
Loop Number
Link To Pro
Guar Soak Band
32
Autostart
Menu Item Display Default Range Setting
Enable Autostart Auto Start Enable No No, Yes Sunday mode Auto Start Sun Mode Off Off, Manual, Timer, Pro-1 to Pro-8 Sunday time Auto Start Sun Time 00:00 00:00 to 23:59 Monday mode Auto Start Mon Mode Off Off, Manual, Timer, Pro-1 to Pro-8 Monday time Auto Start Mon Time 00:00 00:00 to 23:59 Tuesday mode Auto Start Tue Mode Off Off, Manual, Timer, Pro-1 to Pro-8 Tuesday time Auto Start Tue Time 00:00 00:00 to 23:59 Wednesday mode Auto Start Wed Mode Off Off, Manual, Timer, Pro-1 to Pro-8 Wednesday time Auto Start Wed Time 00:00 00:00 to 23:59 Thursday mode Auto Start Thu Mode Off Off, Manual, Timer, Pro-1 to Pro-8 Thursday time Auto Start Thu Time 00:00 00:00 to 23:59 Friday mode Auto Start Fri Mode Off Off, Manual, Timer, Pro-1 to Pro-8 Friday time Auto Start Fri Time 00:00 00:00 to 23:59 Saturday mode Auto Start Sat Mode Off Off, Manual, Timer, Pro-1 to Pro-8 Saturday time Auto Start Sat Time 00:00 00:00 to 23:59
PID
Menu Item Display Default Range Setting
Display units PID Temp Unit °C °C or °F Proportional band PID PB(H) 6°C 1 to 56°C (1 to 100°F) Integral reset PID I(H) Rep/min 2 0 to 100 seconds/repeat Derivative Rate PID D(H) in sec 0 0 to 500 seconds AutoTune PID AutoTune Disable Disable, Enable Proportional Band PID PB(C) 6°C 1 to 56°C (1 to 100°F) Integral reset PID I(C) Rep/min 2 0 to 100 seconds/repeat Derivative Rate PID D(C) in sec 0 0 to 500 seconds Heat Offset PID Heat Offset 0°C Cool Offset PID Cool Offset 0°C
-6 to 6°C (-11 to 11°F)
-6 to 6°C (-11 to 11°F)
33
Control
Menu Item Display Default Range Setting
Cycle Time Control Cycle Time 1 1 to 60 seconds High limit setpoint Control Hi-Lim SP Max HiLimSP MinHiLimSP - MaxHiLimSP* High limit band Control Hi-Lim Band Off Off, 3°C to 11°C (5°F to 20°F) Power fail recovery Control PwrFRec Stop Stop, Restart, Hold, Resume Recovery time limit Control PwrFTime 00m00s 00m00s to 99m59s Powerup start enable Control EPwrStrt Dis Dis, En Powerup Start Mode Control StrtMode Off Off, Manual, Timer, Pro-1 to Pro-8 Hysteresis Control Hyst 3°C 1°C to 56°C (1°F to 100°F) Process out low Control RetOutLo 80°C -73°C to 760°C (-100°F to 1400°F) Process out high Control RetOutHi 400°C -73°C to 760°C (-100°F to 1400°F) Time scale Control TimeScale hh:mm hh:mm or mm:ss Key press beep Control KeyBeep On On or Off End of cycle beep Control EOCBeep Off On or Off Alarm beep Control AlarmBeep Off On or Off Control Type Control Ctrl Heat/Cool Heat, Cool, Heat/Cool
*see Enable Page Communication (optional)
Menu Item Display Default Range Setting
Address Communication CommAddr 1 1 to 255 Mode Communication CommMode OFF OFF, Modbus Baud rate Communication Baud Rate 19.2K 2400, 4800, 9600,
19.2K, 38.4K
Parity Communication Parity None None, Odd, Even
34
Real Time Clock
Menu Item Display Default Range Setting
Day of the week Clock Day Mon Sun, Mon, Tue,
Wed, Thu, Fri, Sat
Time of day Clock HH:MM 00:00 00:00 to 23:59 Reset clock Clock UP to Reset CLK* Ready Ready, Done
* if the key is not pressed, the clock values will retain their original values, the display will change to Done if the clock is reset
Relay Outputs (optional) Push Select key to select relay. If Relay 0 appears, no relays are installed
Menu Item Display Default Range
Type of relay Relay 1 RelayType Off Off, Alarm, Cycl, Ev1 to Ev4 Action of relay Relay 1 RelayAction NDE NDE, NE, NDEL, NEL***** Type of alarm* Relay 1 AlarmType High High, Low, Plus, Minus, Band Alarm setpoint* Relay 1 AlmHi/Lo SP 538°C -73°C to 760°C (-100°F to 1400°F) Alarm deviation* Relay 1 AlmDevBand 3°C 1 to 56°C (1 to 100°F) Inhibit alarm* Relay 1 ALMInhibit On En or Dis Type of event** Relay 1 EventType Time Time or Temp Event setpoint *** Relay 1 Event SP SPUpLim SPLoLim to SPUpLim****
(repeat for relay outputs 2-4, if available) * appears only for alarm types
** appears only for time or temperature event types *** appears only for temperature event types **** see enable page ***** Normally de-energized and non-latching, normally energized and non-latching, normally de-energized and
latching, normally energized and latching
Table of Settings
Relay Type Action Alarm/
Event Type
Setpoint Alarm
Deviation
Alarm Inhibit
35
Test
Menu Item Display Default Range Setting
Heater output Test HeatOut Off On High limit relay Test HiLimOut Off On Relay 1 output Test Rly1 Out Off On Relay 2 output Test Rly2 Out Off On Relay 3 output Test Rly3 Out Off On Relay 4 output Test Rly4 Out Off On High Limit Sensor Test HL Temp (sensor reading)
Zone Cal
Menu Item Display Default Range Setting
Zone 1 actual Zone Cal Zone1Act 38°C -73°C to 760°C (-100°F to
1400°F)
Zone1 displayed Zone Cal Zone1Dis 38°C -73°C to 760°C (-100°F to
1400°F)
Zone 2 actual Zone Cal Zone2Act 260°C -73°C to 760°C (-100°F to
1400°F)
Zone2 displayed Zone Cal Zone2Dis 260°C -73°C to 760°C (-100°F to
1400°F)
Factory calibration* Zone Cal FactCal Ready Ready or Done (push- key)
*only use when no calibration instrument is available
Sensor Cal
Menu Item Display Default Range Setting
Control Sensor Cal Ctrl Sens 0F
Ctrl Sens 1000F Ctrl Sens Done
HiLim Sensor Cal HL Sens 0F
HL Sens 1000F HL Sens Done
Retransmit Cal RetCalLo XXXX *
RetCalHi XXXX *
* note that the actual RetCalLo and RetCalHi values displayed are of no importance. ** press keys until retransmission output = 1VDC *** press keys until retransmission output = 5VDC
-100°F 1400°F Done
-100°F 1400°F Done 0 4096
-100 to 1400°F
-100 to 1400°F (read only)
-100 to 1400°F
-100 to 1400°F (read only) 0 to 4096** 0 to 4096***
36
Enable Page
Menu Item Display Default Range Setting
Profiles Enable Profile 1-8 Yes Yes or No Autostart Enable Auto Start No Yes or No PID Enable PID Yes Yes or No Control Enable Control No Yes or No Communication Enable Communication No Yes or No Real Time Clock Enable Clock No Yes or No Relay outputs Enable Relay 1-4 No Yes or No Test Enable Test No Yes or No Zone Calibration Enable Zone Cal No Yes or No Sensor Calibration Enable Sensor Cal No Yes or No Setpoint lower limit Enable SPLowerLim 20°C -73°C to 760°C (-100°F to
1400°F)
Setpoint upper limit Enable SPUpperLim 260°C -73°C to 760°C (-100°F to
1400°F)
High limit overhead Enable HiLimOH 5°C 3 to 11°C (5 to 20°F)* Password level 1 Enable Password 1 1 0 to 1000 Password level 2 Enable Password 2 2 0 to 1000 Manual/Timer mode
setpoint change Analog Output Type Enable Analog Type Ctrl Ctrl
Enable SPChange Yes Yes or No
* Maximum high limit setpoint (MaxHiLimSP) = SPUpperLim + HiLimOH Minimum high limit setpoint (MinHiLimSP) = SPLowerLim + HiLimOH
37
Technical Specifications
UL, cUL listed: UL file E136675 CE compliance to:
Power supply:
Temperature:
Humidity: 90% or less, non-condensing Sensor inputs:
Temperature display:
Message display:
Time base: +/- 4 seconds accuracy in 24 hours
EMC Directive 89-366/EEC
European Standard EN55011/1991
European Standard EN50082-2/1995
100 to 240 VAC +10% -15%, 50-60Hz, 30VA Maximum
12 to 24 VAC/VDC +/-10%, DC to 60Hz, 30VA Maximum
Storage -20 to 60°C
Operating 0 to 50°C
Type J thermocouple -73°C to 760°C (-100°F to 1400°F)
Input impedance 1M ohm or greater
Common mode noise rejection of 140db@60Hz
Common mode input voltage of +/-12.0VDC
Sample rate of at least 1 sample per second
Stability of +/- 0.5EC per 5EC change in ambient temperature
Repeatability of +/- 0.5EC, or +/-0.1% of sensed temperature (whichever is
greater)
Accuracy (@ 77°F +/-0.2 percent of span (+/-3°F)
Supply Voltage Influence of +/-0.5EC per 10% change in nominal line voltage
1 degree resolution (C or F)
Accuracy after calibration of +/- 1EC, or +/-0.2% of sensed temperature
(whichever is greater) @25EC
Four-digit seven-segment LCD, 0.43 inches high (11mm)
Readout Stability (+/-1°F/10°F Change in ambient temperature)
Two-line, 16 alpha-numeric 5x7 dot matrix characters per line
0.2 inches high (5mm)
Heat control output: SSR Drive 24VDC nominal @ 70mA Cooling control output: 4-20ma DC > 0-800 Ohm Load Relay output: (plug-in
module) Communications:
(plug-in module)
Remote inputs: (plug-in module)
Front panel: NEMA 4X (with gasket) Dimensions: 3.57H x 7.24W x 2.84D inches (91H x 184W x 72D mm) Panel opening: 3.63H x 7.30W inches (92H x 185W mm)
Form A dry contact, rated 3 amps @ 24-264VAC
RS232 Single drop, isolated
RS422 Multi-drop, isolated
RS485 Multi-drop, isolated
Dry-contact closure type with less than 250 ohm ON resistance
38
APPENDIX: Temperature Scale Conversion and Optional MRC5000 Setup
Temperature Scale Conversion (C/F)
The Protocol Plus controller can be operated in either C or F. The default setting for the controller is C. Changing from one to the other is as follows:
1. Go into the Setup Mode on the controller.
2. Press the Select Key until Setup is displayed.
3. Press the Page key and Security will be displayed.
4. Press the Menu Key and Password will be displayed. Use the arrow keys to enter the proper password. The default password is 2 for level two.
5. Once the proper password is displayed, press the Page key until PID is displayed.
6. Press the Menu key and Temp Unit along with C or F will be displayed. Use the arrow keys to change the setting.
7. Once the proper setting is displayed, press and hold the Page key for approximately three seconds to exit the Setup Mode.
39
Loading...