Modified instructions for delayed start and remote
communication. Modbus User’s Programming Manual
added (E-106/ PN320813, Version 3/2013, Updated for
Engineering Issue 8).
1.2
6/2013
K. Livingston
Minor edits
2 Version 1.2
Revision History
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
PREFACEProtocol 3 Controller Owner’s Manual
4 Version 1.2
5.6.1.1. Access the Configuration Menu .......................................................... 49
5.6.1.2. Work with the Alarm Menu ................................................................. 49
5.6.1.3. Using Alarms to Switch Relay Outputs ............................................... 50
5.6.1.4. Alarm Application Example ................................................................ 51
5.6.1.5. Glossary of Alarm Terms .................................................................... 52
5.6.2. Working with Calibration Offsets ........................................................... 54
5.6.2.1. Access the Configuration Menu .......................................................... 54
5.6.2.2. Working with Input Configuration ...................................................... 54
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
Protocol 3 Owner’s Manual PREFACE
Version 1.2 5
Figure 17. USB Port on Front Panel. ................................................................................ 43
Figure 18. USB Files and Folders Requirements (as seen from Windows Explorer). ..... 43
Figure 19. Configuration Menu (see also Table 16 for more information). ..................... 46
Figure 4. How High, Low and Band process alarms are implemented. ........................... 53
Figure 20. Service Information Screen. ............................................................................ 58
Figure 21. Standard Digital Input Wiring. ........................................................................ 59
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
ABOUT THIS MANUALProtocol 3 Controller Owner’s Manual
Values displayed on screens are examples only. Though
those values may be typical, contact Despatch Industries for
the final value.
Users of this equipment must comply with operating
procedures and training of operation personnel as required
by the Occupational Safety and Health Act (OSHA) of 1970,
Section 6 and relevant safety standards, as well as other
safety rules and regulations of state and local governments.
Refer to the relevant safety standards in OSHA and National
Fire Protection Association (NFPA), section 86 of 1990.
All rights reserved. No part of the contents of this manual may be reproduced, copied, or
transmitted in any form or by any means including graphic, electronic, or mechanical methods or
photocopying, recording, or information storage and retrieval systems without the written
permission of the publisher, unless it is for the purchaser's personal use.
Printed and bound in the United States of America.
The information in this manual is subject to change without notice and does not represent a
commitment on the part of Despatch Industries. Despatch Industries does not assume any
responsibility for any errors that may appear in this manual.
In no event will Despatch Industries be liable for technical or editorial omissions made herein,
nor for direct, indirect, special, incidental, or consequential damages resulting from the use or
defect of this manual.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
Protocol 3 Controller Owner’s Manual ABOUT THIS MANUAL
Danger!
Only fully-trained and qualified personnel should setup and
maintain this equipment. Improper setup and operation of this
equipment could cause an explosion that may result in
equipment damage, personal injury or possible death.
Modbus communication protocols require the Protocol 3
controller be updated to version 2.3 or higher.
Global Headquarters
Contact
Service & Technical
Support
Despatch Industries
8860 207th Street
Lakeville, MN 55044
USA
International/Main: 1-952-469-5424
US toll free: 1-888-337-7282
Fax: 1-952-469-4513
info@despatch.com
www.despatch.com
Service: 1-952-469-8230
US toll free: 1-800-473-7373
Service @despatch.com
Version 1.2 7
The information in this document is not intended to cover all possible conditions and situations
that might occur. The end user must exercise caution and common sense when installing or
maintaining Despatch Industries products. If any questions or problems arise, call Despatch
Industries at 1-888-DESPATCH or 1-952-469-5424.
1.2. Manufacturer & Service
Despatch has specialized in thermal processing for over 100 years. Technical expertise gained
over those years helps provide innovative solutions to critical applications in vertical markets and
cutting edge technology worldwide. Despatch products are backed by a drive for long-term
customer satisfaction and a strong sense of responsibility. The worldwide network of factorytrained Service Professionals is available to support your Despatch equipment. From full service
preventive maintenance to routine repair and certified calibration and uniformity, the Despatch
service network is positioned to respond to your business needs. Our service programs are
customized to meet your specific needs using our Advantage Service Assurance Program
(ASAP). For more information on ASAP, visit www.despatch.com.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
ABOUT THIS MANUALProtocol 3 Controller Owner’s Manual
Danger!
Failure to heed warnings in this instruction manual and on the
oven could result in personal injury, property damage or death.
This icon signifies information that describes an unsafe
condition that may result in death, serious injury, or damage
to the equipment.
Danger!
Danger is the signal word used to indicate a hazardous
situation that, if not avoided, will result in death or severe
injury.
Warning!
Warning is the signal word used to indicate a hazardous
situation that, if not avoided, could result in death or severe
injury.
Caution!
Caution is the signal word used to indicate a hazardous
situation that, if not avoided, could result in moderate or
minor injury.
Notice
Notice is the signal word used to indicate a hazardous
situation that, if not avoided, could result in property damage.
This icon signifies supplemental important information.
LOG OUT
Bold, 10 point sans-serif typeface indicates a specific key or
button on screen to click.
8 Version 1.2
1.3. Organization of this Manual
This owner’s manual contains the most comprehensive set of information for the Despatch
Protocol 3™ controller, including installation instructions, theory of operation, operating
instructions, among other things.
1.4. Conventions
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
ABOUT THIS MANUALProtocol 3 Controller Owner’s Manual
Item
Description
S
0 to 1762°C
32 to 3204°F
T
‐240 to 400°C
‐400 to 752°F *
Optional decimal place can be displayed up to 999.9°C/F
Thermocouple
Calibration:
±0.1% of full range, ±1LSD (±1°C for internal CJC if enabled).
Linearization better than better ±0.2°C (±0.05 typical) on
ranges marked * in the table above. Linearization for other
ranges is better than ±0.5°C. BS4937, NBS125 & IEC584.
Supported RTD Types
& Ranges:
Type
Range °C
Range °F
3‐Wire
PT100
‐199 to 800°C
‐328 to 1472°F
NI120
‐80 to 240°C
‐112 to 464°F
Optional decimal place can be displayed up to 999.9°C/F
RTD Calibration:
0.1% of full range, ±1LSD
Linearization:
Linearization better than ±0.2°C (±0.05 typical).
PT100 input to BS1904 & DIN43760 (0.00385Ω/Ω/°C).
RTD Excitation:
Sensor current 150μA ±10%
Lead Resistance:
<0.5% of span error for max 50Ωper lead, balanced
Supported Linear
Types & Ranges:
Type
Range
Offset Range
mA DC
0 to 20mA DC
4 to 20mA DC
mV DC
0 to 50mV DC
10 to 50mV DC
V DC
0 to 5V DC
1 to 5V DC
V DC
0 to 10V DC
2 to 10V DC
Scalable from ‐9999 to 10000. Decimal point selectable from 0
to 3 places, but limited to 5 display digits (e.g. 9999.9)
Maximum Overload:
1A on mA input terminals, 30V on voltage input terminals
DC Calibration:
±0.1% of full range, ±1LSD
DC Input Multi‐Point:
Linearization:
Up to 15 scaling values can be defined anywhere between 0.1
and 100% of input
Item
Description
Relays
Type & Rating:
Single pole single throw (SPST); 2A resistive at 120/240VAC
Lifetime:
>200,000 operations at rated voltage/current
Isolation:
Basic Isolation
10 Version 1.2
Table 2. Outputs.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
Protocol 3 Controller Owner’s Manual ABOUT THIS MANUAL
Item
Description
Linear DC
Resolution:
8 bits in 250mS (10 bits in 1s typical, >10 bits in >1s typical)
Accuracy:
±0.25% of range, (mA @ 250W, V @ 2kW). Degrades linearly
to ±0.5% for increasing burden (to specification limits)
Isolation:
Basic Isolation
Item
Description
Temperature:
Operating: 0°C to 55°C (32°F to 131°F)
Storage: –20°C to 80°C (-4°F to 176°F)
Relative Humidity:
20% to 95% non‐condensing
Supply Voltage and
Power:
100 to 240VAC ±10%, 50/60Hz, 20VA
Item
Description
EMI:
CE: Complies with EN61326
Safety Considerations:
CE: Complies with EN61010‐1. UL, cUL to UL61010C‐1.
Pollution Degree 2, Installation Category II
Front Panel Sealing:
IP65 rating. IP20 behind the panel. (IP rating not recognized /
approved by UL)
Front Panel Cleaning:
Wash with warm soapy water and dry immediately. Close the
USB cover (if fitted) before cleaning.
Item
Description
Display Type:
160 x 80 pixel, monochrome graphic LCD with a dual color
(red/green) backlight
Display Area:
66.54mm (W) x 37.42mm (H)
Display Characters:
0 to 9, a to z, A to Z, plus ( ) ‐ and _
Version 1.2 11
Table 3. Operating Conditions (For indoor use).
Table 4. Conformance Norms.
Table 5. Display.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
Dependent on sample rate and number of values recorded.
Two values can be recorded for up to 7 days at 10s intervals.
More values or faster sample rates deduce the maximum
duration.
RTC Battery Type:
VARTA CR 1616 3V Lithium. Clock runs for >1 year without
power (Part # 274030)
RTC accuracy:
Real Time Clock error <1 second per day
12 Version 1.2
Table 6. Data Recorder.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
Electrical panels contain high voltage. Disconnect and lock out the
power supply before working inside any electrical panels. Failure to
lock out the power supply will result in death or injury.
Version 1.2 13
2. Safety
2.1. Safety Information
Do not work on the Protocol 3 controller without reading and understanding this section which
contains important information and warnings. Ignoring these warnings can result in death, serious
injury or damage to the machine and product.
2.1.1. Lockout
Machine lockout places the Protocol 3 controller into a zero energy state and prevents accidental
machine start up. Always follow the Lockout Procedure described in this Section before cleaning,
maintaining or repairing the Protocol 3 controller. An accidental start-up, while working on the
Protocol 3 controller, can result in serious injury or death.
2.1.1.1. Lockout Requirements
1. Every power source that can energize any element of the Protocol 3 controller must be shut
off at the closest possible power source. This includes air, water, nitrogen and electricity,
including the Disconnect Switch.
2. After energy sources are locked out, test to ensure circuits are de-energized.
2.1.1.2. Lockout Procedure with Despatch Products
Personnel authorized to lockout equipment must have the necessary locks to perform the lockout.
1. Physically disconnect all electrical power to the machine or lockout (with a padlock) the
appropriate breaker or disconnects.
2. Close all valves and bleed off any pressure.
3. Test for power by attempting a start with the machine controls.
4. Identify the Lockout Condition with a tag on the electrical disconnect and pneumatic shut off
valves.
5. When work is complete, remove all tags and restore the machine to its working state.
2.2. Maintenance
Only qualified and trained personnel should perform maintenance or repair.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
Contact with energized electrical sources will result in serious
injury or death.
Danger!
Always disconnect all power before extinguishing a fire.
Attempting to extinguish a fire in a machine connected to
electrical power will result in serious injury or death.
14 Version 1.2
2.3. Electrical Power
Only qualified and trained personnel should perform electrical maintenance or electrical repair.
Before performing maintenance, disconnect all electrical power from the machine. Use a
padlock and lockout all disconnects feeding power to the machine.
Never clean or repair the controller when in operation.
Unauthorized alterations or modifications to Protocol 3 controller are strictly forbidden.
Never modify any electrical circuits. Unauthorized modifications can impair the function and
safety of the Protocol 3 controller.
2.4. Fire
Keep the Protocol 3 controller clean and free of scrap materials, oil or solvents to prevent the
possibility of fire. In the event of fire, use a fire extinguisher as follows.
1. De-energize the machine immediately by pushing an Emergency Stop push button (if
supplied).
2. Turn off the remote main disconnect (customer supplied disconnect).
3. If the fire is in the workspace, keep the door closed.
4. Extinguish the fire.
2.5. Equipment Lockout Requirements
To prevent injury or equipment damage during inspection or repair, the Protocol 3
controller must be locked out.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
Protocol 3 Controller Owner’s Manual THEORY OF OPERATION
Figure 1. Operator Interface.
Version 1.2 15
3. Theory of Operation
The Protocol 3 is a microprocessor based digital
temperature controller designed for simple and flexible
oven operation (Figure 1). The Protocol 3 controller
operates as a dual-functioning controller/high limit
instrument. The control portion utilizes a
time-proportioning voltage signal to control heating
devices with minimal temperature fluctuations.
The high limit portion protects the product and/or the
oven from overheating. If the product being processed has a critical high temperature limit, the
high limit setpoint should be set to a temperature somewhat below the temperature at which the
product could be damaged. If the product does not have a critical high temperature limit, the high
limit setpoint should be set 5 to 15 degrees higher than the maximum programmed setpoint at
which the oven will operate.
The Protocol 3 controller provides three primary operating modes:
Manual: Oven operates continuously at a fixed temperature until turned off.
Timer: Oven operates at a fixed temperature for a user-selected time period, and then
automatically turns off.
Profile: Temperatures increase or decrease as defined by 255 segments that can be allocated
to 64 ramp and soak profiles. The profiles can be linked to provide additional temperature
combinations.
The Protocol 3 controlled is equipped to allow a ramp/soak temperature control, which maintains
oven temperature with either a fixed setpoint or a ramp/soak profile.
3.1. System Control—In General
The Protocol 3 controller provides outputs for the cooling fan, door lock switch/door release
pushbutton, and optional beacon light
A number of profiles for oven heating cycles are stored in the Protocol 3 controller. Access
profiles using the Protocol 3 keypad
The Protocol 3 controls the solenoid valves in an inert atmosphere oven for purge, maintain
and water cooling operation
The Protocol 3 can also be operated remotely with a PC running Protocol Manager software.
3.1.1. High-Limit Function
The Protocol 3 controller has an integrated high limit function which disables the heater output
when tripped. The High-Limit temperature is displayed as HLPV (Manual Mode only).
If the high limit trips, the Hi-Limit indicator will light and the relay must be manually reset.
Allow the oven to cool several degrees below the setpoint (or increase the high limit setpoint) and
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
THEORY OF OPERATIONProtocol 3 Controller Owner’s Manual
16 Version 1.2
3.1.2. Outputs
The Protocol 3 controller comes standard with an output signal that can transmit temperature
data, setpoint data or control power to a user-supplied recording device. Output relays (five) can
also signal user-specified events or alarm to external devices (Figure 2 and Figure 3).
Heating output: The control output is a DC voltage open-collector output which is
time-proportioned and designed to control a heat control device such as a solid state relay.
High limit: The high limit output is a SPDT relay which is energized under normal operating
conditions. If the control senses a temperature higher than the high limit setpoint, or if there is
a sensor error, the high limit relay will de-energize until the condition is cleared and Reset is
pressed. When the high limit relay is de-energized, the heater is disabled.
Retransmission: The retransmission output is a signal that is proportional to the process
temperature, setpoint or control power:
o 0-5V
o 0-10V
o 2-10V
o 020 ma
o 4-20 ma
o 0-10VDC Power Supply
The signal can be an input to other devices such as a chart recorder.
Relays: The five SPST dry contact relay outputs can be configured to function as alarms,
events, or end of cycle. These outputs can be utilized in Manual, Timer or Profile Modes.
3.2. Remote Communication
When used with a PC running Protocol Manager™ software, the Protocol 3 controller allows an
operator to remotely control the oven, download recipes and log data.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
Protocol 3 Controller Owner’s Manual THEORY OF OPERATION
Protocol Plus Rear Panel
Protocol 3 Rear Panel
Former
Connections
New Power
Connections
Former SSR
Connections
New SSR
Connections
Former Control
Connections
Former Hi-limit
Connections
New Control
Connections
New Hi-limit
Connections
Relays
Figure 3. Protocol Plus to Protocol 3 Connection Conversions.
Figure 2. Typical Controller Output Sticker.
Version 1.2 17
and Hi-Limit
Thermocouple
Power
Thermocouple
Thermocouple
and Hi-Limit
Thermocouple
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
All grounding and safety equipment must be in compliance with
applicable codes, ordinances and accepted safe practices.
Terminal Block
Former
Protocol Plus Connections
New
Protocol 3 Connections
Three pin terminal block for
power leads
Terminals 30, 31, 32
Terminals 1, 2, 3
Five pin terminal block for
SSR and Hi-limit
Terminals 17, 18, 19, 20, 21
Terminals 26, 27, 28, 29, 30
Remove the four-pin terminal
block from thermocouples and
rewire with two three-pin
blocks.
Control Thermocouple
Terminals 13, 14
Control Thermocouple
Terminals 17, 18
Hi-limit Thermocouple
Terminals 15, 16
Hi-limit Thermocouple
Terminals 32, 33
Warning!
Disconnect the main power switch or power cord before
attempting any repair or adjustment.
18 Version 1.2
4. Assembly & Setup
4.1. Install the Protocol 3 Controller
When replacing a Protocol 3 controller, follow the steps below. Tools required for installation
include ¼” socket set with #1 bit, #2 Philips screwdriver.
1. Disconnect the power.
2. Unplug all terminals on the rear of the control, noting the proper connections (Figure 3).
3. Remove the retaining clips for the controller.
4. Remove the controller.
5. Insert the new controller into the panel.
6. Fasten the retaining clips.
7. Re-plug all terminals.
8. Secure the control panel.
4.2. Protocol 3 Controller Conversion with NO Options
To replace the older model Protocol Plus controller with the newer Protocol 3 controller, connect
terminal blocks as indicated in Table 7 and Figure 3.
Table 7. Protocol Plus to Protocol 3 Controller Conversion.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
Protocol 3 Controller Owner’s Manual ASSEMBLY &SETUP
Version 1.2 19
4.3. Setting Up Remote Communication
Remote communication between the Protocol 3 controller and a PC running the Despatch
Protocol Manager software involves providing each controller with a unique address and
following the communication protocol procedures. Up to 32 separate controllers can be run from
a PC running the Despatch Protocol Manager software. See the Protocol Manager Instruction
Manual for the complete set-up procedure.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
WORKING WITH OPERATING MODESProtocol 3 Controller Owner’s Manual
Users and operators of this controller must comply with
operating procedures and training of operating personnel as
required by the Occupational Safety and Health Act (OSHA) of
1970, Section 5 and relevant safety standards, and other safety
rules and regulations of state and local governments. Refer to
the relevant safety standards in OSHA and National Fire
Protection Association (NFPA), Section 86 of 1990.
Keypad
Button
Function
Figure 4. Select a Mode Display.
20 Version 1.2
5. Working with Operating Modes
5.1. User Controls
Each Protocol 3 Controller has six keypad switches (Table 8). Use the buttons to navigate user
menus, adjust parameter values and control outputs. In configuration screens, a context sensitive
scrolling help-text displays user-guides about the function of the keys across the bottom of the
screen.
The Protocol 3 Controller has nine LEDs which indicate a variety of instrument functions (Table
9).
When the Protocol 3 Controller is first powered ON, the screen displays Select a Mode (Figure
4). Use and to navigate and to select the highlighted mode.
Table 8. Keypad Buttons and Functions.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
Protocol 3 Controller Owner’s Manual WORKING WITH OPERATING MODES
Keypad
Button
Function
Navigate to previous screen
Press to move back to the previous parameter or screen in the current
mode.
NOTE: Pressing this switch updates the instrument to the value
displayed. If editing a parameter, ensure the current (highlighted)
parameter value is correct before pressing.
Navigate down through menu/parameter lists
Menus and configuration choice screens: Press to move to the next item on
the list.
Editable values: Press to decrease. Press and hold to speed the change.
Trend View: press to move the Cursor Line back through stored data
points.
Navigate up through menu/parameter lists
Menus and configuration choice screens: Press to move to the previous
item on the list.
Editable values: Press to increase. Press and hold to speed the change.
Trend View: press to move the Cursor Line forward through stored data
points.
Navigate to next item on a screen or to next screen
Press to move forward to the next parameter or screen in the current mode.
Enables Edit on parameters in the Main Mode selections.
NOTE: Pressing this switch updates the instrument to the value
displayed. If editing a parameter, ensure the current (highlighted)
parameter value is correct before pressing.
Manual, Timer and Profile Mode: press to stop current process
In Manual Mode, pressing switch disables the controlling output
In Timer Mode, pressing switch stops timer and disables controlling output
In Profile Mode, pressing switch stops current profile and disables
controlling output
Reset Latched High Limit relay if below alarm condition
If High Limit alarm is active, press to release the High Limit relay.
NOTE: This switch releases the High Limit relay only if the controller is
Version 1.2 21
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.