Despatch MIC 1422 Installation Manual

MIC 1422
MIC 1422
MIC 1422MIC 1422 MICROBASED CONTROLLER
MICROBASED CONTROLLER
MICROBASED CONTROLLERMICROBASED CONTROLLER INSTRUCTION MANUAL
INSTRUCTION MANUAL
INSTRUCTION MANUALINSTRUCTION MANUAL
E-90 PN 136108 REVISION 10-07
i
ii
TABLE OF CONTENTS
TABLE OF CONTENTS..................................................................................................iii
SECTION 1: PRODUCT DESCRIPTION.......................................................................1
1.1 General .................................................................................................................. 1
1.2 Displays................................................................................................................. 2
1.3 Control................................................................................................................... 2
1.4 Alarms................................................................................................................... 2
1.5 Process Variable/Setpoint Value Re-Transmission Output.................................... 3
SECTION 2: INSTALLATION AND WIRING.................................................................. 5
2.1 Mounting ............................................................................................................... 5
2.2 Wiring Guidelines..................................................................................................7
Installation Considerations........................................................................................ 7
AC Power Wiring....................................................................................................... 8
Wire Isolation ............................................................................................................ 8
Use Of Shielded Cable.............................................................................................. 8
Noise Suppression At The Source............................................................................ 9
2.3 Sensor Placement (Thermocouple or RTD)........................................................10
2.4 Input Connections............................................................................................... 12
2.5 Output Connections ............................................................................................ 17
SECTION 3: OPERATION........................................................................................... 21
3.1 Control Capability................................................................................................21
3.2 Control Responses............................................................................................... 21
3.3 Direct/Reverse Operation of Outputs .................................................................. 22
3.4 On-Off Control..................................................................................................... 22
3.5 Time Proportioning Control ................................................................................. 22
3.6 Current Proportioning Control ............................................................................. 23
3.7 Power Up Procedure...........................................................................................25
3.8 Keypad Operation............................................................................................... 25
3.9 Front Panel Indicators......................................................................................... 26
SECTION 4: CONTROL MODE...................................................................................27
4.1 Operation ............................................................................................................ 27
4.2 Active Setpoint .................................................................................................... 27
4.3 Override Feature................................................................................................. 28
4.4 Alarm Status Display........................................................................................... 28
4.5 Over-Range I Under-Range Display.................................................................... 28
4.6 Manual Control (Percent Output) ........................................................................ 29
4.7 Setup Modes....................................................................................................... 30
SECTION 5: TUNE MODE........................................................................................... 31
5.1 Tune Mode Description....................................................................................... 31
5.2 Manual Tuning Method ....................................................................................... 32
SECTION 6: ALARM MODE ........................................................................................ 35
6.1 Alarm Mode Description...................................................................................... 35
6.2 Loop Alarm Enable.............................................................................................. 40
6.3 Loop Alarm Time................................................................................................. 40
6.4 Logical Combination of Alarms ........................................................................... 41
iii
SECTION 7: TEST MODE ........................................................................................... 43
7.1 Test Mode Description ........................................................................................ 43
SECTION 8: CONFIGURATION MODE ...................................................................... 45
8.1 Configuration Mode Description..........................................................................45
8.2 Hardware Definition Code................................................................................... 48
SECTION 9: CALIBRATION MODE............................................................................. 51
9.1 Entering Calibration Mode................................................................................... 51
9.2 Calibrating The Universal Input...........................................................................51
Calibration Procedure ............................................................................................. 51
9.3 Calibrating The Secondary Analog Input............................................................. 53
Equipment Required ............................................................................................... 53
Calibration Procedure ............................................................................................. 53
9.4 Exit From Calibration Mode................................................................................. 54
9.5 Calibration Check................................................................................................54
SECTION 10: ENABLE MODE .................................................................................... 55
10.1 Enable Mode Description.................................................................................. 55
SECTION 11: PRE-TUNE MODE................................................................................ 57
11.1 Pre-Tune Mode Description .............................................................................. 57
SECTION 12: AUTOTUNE MODE............................................................................... 59
12.1 AutoTune Mode and Description....................................................................... 59
12.2 How Auto-Tune Works...................................................................................... 59
SECTION 13: RaPID FEATURE..................................................................................61
13.1 RaPID Description............................................................................................. 61
APPENDIX A: BOARD LAYOUT - JUMPER POSITIONING .......................................63
APPENDIX B: RANGE CODES ................................................................................... 69
For Thermocouple Inputs........................................................................................... 69
For RTD Inputs........................................................................................................... 69
For DC Inputs............................................................................................................. 70
APPENDIX C: RaPID CONTROL FEATURE............................................................... 71
APPENDIX D: SPECIFICATIONS................................................................................ 73
Input Specifications.................................................................................................... 73
Output Specifications................................................................................................. 75
Control Specifications ................................................................................................ 77
Performance............................................................................................................... 78
DC Outputs ................................................................................................................ 79
Operating Conditlons ................................................................................................. 79
Performance Under Operating Conditions ................................................................. 80
Environmental ............................................................................................................ 80
Physical...................................................................................................................... 80
APPENDIX E: SOFTWARE REFERENCE SHEET.....................................................81
APPENDIX F: FLOW CHART OF OPERATION..........................................................84
APPENDIX G: MODEL NUMBER MATRIX.................................................................. 85
iv
SECTION 1: PRODUCT DESCRIPTION
1.1 General
This instrument is a microprocessor based single loop controller capable of measuring, displaying and controlling temperature, pressure, flow, and level from a variety of inputs. Most outputs are easily tuned using the instrument Pre-Tune and Auto-Tune, or RaPID (Response assisted PID) functions.
Control functions, alarm settings and other parameters are easily entered through the front keypad. E2 Technology (100 year life) protects against data loss during AC power outages.
The input is user configurable to directly connect to either thermocouple, RTD, mVDC, VDC or mADC inputs. The instrument can operate from either a 90-264 VAC, 50/60 HZ power supply, or optional 24V AC/DC power supply.
Standard features include:
Auto Tune
Alarm Functions
Auto/Manual Switching
Process Retransmission
Setpoint Retransmission
Setpoint Ramp Rate
Proportioning (Time or Current)/On-Off Control
Single On-Off Control
Single Time Proportioning Control
Single Current Proportioning
Optional features include:
Dual On-Off Control
Dual Time Proportioning
Dual Current Proportioning
Dual Setpoint
Remote Setpoint
Digital Communications
Alarm Outputs
1
1.2 Displays
Each instrument is provided with dual displays and status indicators as shown in Figure 1 -1. The upper display (RED) displays the value of the process variable. The lower display (GREEN) displays the setpoint value.
1.3 Control
The instrument can be programmed for on-off, time proportioning, or current proportioning control implementations depending on the model number. A second control output is an available option. Proportional control implementations are provided with fully programmable PID parameters.
1.4 Alarms
Alarm indication is standard on all instruments. Up to two alarm outputs are possible. Alarm type may be set as Process Direct or Reverse (high or low), Deviation Direct or Reverse (above or below setpoint), Deviation Band Type (closed or open within band), or Loop Reverse or Direct. Alarm status is indicated by LED. An Alarm Inhibit is provided to prevent, when activated, unwanted alarms during power-up.
2
FIGURE 1-1 Keys and Indicators
1.5 Process Variable/Setpoint Value Re-Transmission Output
If the instrument is specified with this option, this output may be scaled over any desired range and re-transmitted.
3
4
SECTION 2: INSTALLATION AND WIRING
2.1 Mounting
Electrical code requirements and safety standards should be observed and installation performed by qualified personnel.
The electronic components of the instrument may be removed from the housing during installation. To remove the components, grip the side edges of the front panel and pull the instrument forward. During re-installation, the vertically mounted circuit boards should be properly aligned in the housing.
Ensure that the instrument is correctly orientated. A stop will operate if an attempt is made to insert the instrument incorrectly.
Recommended panel opening sizes are illustrated in Figure 2-1. After the opening is properly cut, insert the instrument into the panel opening. Ensure that the panel gasket is not distorted and that the instrument is positioned squarely against the panel. Slide the mounting clamp into place on the instrument (see Figure 2-3) and push it forward until it is firmly in contact with the rear face of the mounting panel.
Note: The mounting clamp tongues may engage either on the sides or the top/bottom of the instrument housing, Therefore, when installing several instruments side-by-side in one cut out, use the ratchets on the top/bottom faces.
FIGURE 2-1 Panel Cut-Out Dimensions
5
FIGURE 2-2 Main Dimensions
MIC1422
FIGURE 2-3 Panel Mounting the Controller
6
2.2 Wiring Guidelines
Electrical noise is a phenomenon typical of industrial environments. The following are guidelines that must be followed to minimize the effect of noise upon any instrumentation.
Installation Considerations
Listed below are some of the common sources of electrical noise in the industrial environment:
Ignition Transformers
Arc Welders
Mechanical contact relay(s)
Solenoids
Before using any instrument near the device listed, the instructions below should be followed:
1. If the instrument is to be mounted in the same panel as any of the listed devices,
separate them by the largest distance possible. For maximum electrical noise reduction, the noise generating devices should be mounted in a separate enclosure.
2. If possible, eliminate mechanical contact relay(s) and replace with solid state relays.
If a mechanical relay being powered by an instrument output device cannot be replaced, a solid state relay can be used to isolate the instrument.
3. A separate isolation transformer to feed only instrumentation should be considered.
The transformer can isolate the instrument from noise found on the AC power input.
4. If the instrument is being installed on existing equipment, the wiring in the area
should be checked to insure that good wiring practices have been followed.
7
AC Power Wiring
Neutral (For 115 VAC) It is good practice to assure that the AC neutral is at or near ground potential. To verify this, a voltmeter check between neutral and ground should be done. On the AC range, the reading should not be more than 50 millivolts. If it is greater than this amount, the secondary of this AC transformer supplying the instrument should be checked by an electrician. A proper neutral will help ensure maximum performance from the instrument.
Wire Isolation
Four voltage levels of input and output wiring may be used with the unit:
Analog input or output (i.e. thermocouple, RTD, VDC, MVDC, or mADC)
SPDT Relays
SSR driver outputs
AC power
The only wires that should run together are those of the same category. If they need to be run parallel with any of the other lines, maintain a minimum 6 inch space between the wires. If wires must cross each other, do so at 90 degrees. This will minimize the contact with each other and reduces "cross talk". "Cross Talk" is due to the EMF (Electro Magnetic Flux) emitted by a wire as current passes through it. This EMF can be picked up by other wires running in the same bundle or conduit.
In applications where a High Voltage Transformer is used (i.e. ignition systems) the secondary of the transformer should be isolated from all other cables.
This instrument has been designed to operate in noisy environments, however, in some cases even with proper wiring it may be necessary to suppress the noise at its source.
Use Of Shielded Cable
Shielded cable helps eliminate electrical noise being induced on the wires. All analog signals should be run with shielded cable. Connection lead length should be kept as short as possible, keeping the wires protected by the shielding. The shield should be grounded at one end only The preferred grounding location is the sensor, transmitter or transducer.
8
Noise Suppression At The Source
Usually when good wiring practices are followed no further noise protection is necessary. Sometimes in severe electrical environments, the amount of noise is so great that it has to be suppressed at the source. Many manufacturers of relays, contactors, etc. supply "surge suppressors" which mount on the noise source.
For those devices that do not have surge suppressors supplied, RC (resistance­capacitance) networks and/or MOV (metal oxide varistors) may be added.
Inductive Coils - MOV's are recommended for transient suppression in inductive coils connected in parallel and as close as possible to the coil. See Figure 2-4. Additional protection may be provided by adding an RC network across the MOV.
FIGURE 2-4
Contacts - Arcing may occur across contacts when the contact opens and closes. This results in electrical noise as well as damage to the contacts. Connecting a RC network properly sized can eliminate this arc.
For circuits up to 3 amps, a combination of a 47 ohm resistor and 0.1 microfarad capacitor(1000volts)is recommended. For circuits from 3 to 5 amps, connect 2 of these in parallel. See Figure 2-5, below.
9
FIGURE 2-5
2.3 Sensor Placement (Thermocouple or RTD)
Two-wire RTDs should be used only with lead lengths less than 10 feet. If the temperature probe is to be subjected to corrosive or abrasive conditions, it should
be protected by the appropriate thermowell. The probe should be positioned to reflect true process temperature:
In liquid media - the most agitated area
In air - the best circulated area
10
FIGURE 2-6 Wiring Label
1/4 DIN
11
2.4 Input Connections
In general, all wiring connections are made to the instrument after it is installed. Avoid Electrical Shock. AC power wiring must not be connected to the source distribution panel until all wiring connection procedures are completed.
Caution: This equipment is designed for installation in an enclosure which provide adequate protection against electric shock. Local regulations regarding electrical installation should be rigidly observed. Consideration should be given to prevention of access to the power terminations by unauthorized authorized personnel. Power should be connected via a two pole isolating switch (preferably situated neat the equipment) and a 1 A fuse, as shown in Figure 2-7.
FIGURE 2-7 Main Supply
The instrument will operate on 90-264V AC 50/60 Hz line supply. The power consumption is approximately 4 VA. If the instrument has relay outputs in which the contacts are to carry line voltage, it is recommended that the relay contact line supply be switched and fused in a similar manner, but separate from the instrument line supply.
12
FIGURE 2-7A 24V Nominal AC/DC Supply
The supply connection for the 24V AC/DC option of the instrument are as shown below. Power should be connected via a two pole isolating switch and a 315 mA slow-blow (anti-surge type T) fuse. With the 24V AC/DC supply option fitted, these terminals will accept the following supply voltage ranges:
24V (nominal) AC 50/60 Hz - 20 - 50 V 24V (nominal) DC - 22 - 65 V
FIGURE 2-8 Thermocouple (T/C) Input
Make thermocouple connections as illustrated below. Connect the positive leg of the thermocouple to terminal 2 and the negative leg to terminal 3.
Note: Thermocouple must not be grounded! Damage to the cold junction in the control will result!
13
FIGURE 2-9 RTD Input
Make RTD connections as illustrated below. For a three wire RTD, connect the resistive leg of RTD to terminal 1 and the common legs to terminals 2 and 3. For a two wire RTD, connect one leg to terminal 2 and the other leg to terminal 3 as shown below. A jumper wire supplied by the customer must be installed between terminals 2 and 3. Input conditioning jumper must be positioned correctly (see Appendix B) and Hardware Definition Code must be correct (see Section 8, Configuration Mode).
FIGURE 2-10 Volt, mV Input
Make volt and millivolt connections as shown below. Terminal 2 is positive and terminal 3 is negative. Input conditioning jumper must be positioned correctly (see Appendix A) and Hardware Definition Code must be correct (see Section 8, Configuration Mode).
mADC Input Make mADC connections as shown below. Terminal 4 is positive and terminal 1 is
negative. Input conditioning jumper must be positioned correctly (see Appendix A) and Hardware Definition Code must be correct (see Section 8, Configuration Mode).
14
FIGURE 2-11 Remote Digital Communications - RS485
Make digital communication connections as illustrated below.
FIGURE 2-12 Remote Setpoint Input - V/mA/mV and Potentiometer
Connections are illustrated below. Terminal 6 is positive and terminal 7 is negative. The remote setpoint input can be configured for linear DC mv, linear DC mA, linear DC Volt or potentiometer. Make sure that the input selected matches the Second Input Usage selected in the Hardware Definition Mode and the Secondary Analog Input conditioning jumper is positioned correctly (see Appendix A.)
15
FIGURE 2-13 Remote Setpoint Selection
Connections are made as shown.
FIGURE2-14 Dual Setpoint Selection
Connections are made as shown.
16
2.5 Output Connections
FIGURE 2-15 Relay Output 1 (Control Output 1)
Connections are made to Output 1 relay as illustrated below. The contacts are rated at 2 amp resistive, 120/240 VAC.
FIGURE 2-16 SSR Driver Output 1 (Control Output 1)
Connections are made to Output 1 SSR Driver as illustrated below. The solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output impedance is 250 ohms.
FIGURE 2-17 mADC Output 1 (Control Output 1)
Make connections for DC Output 1 as illustrated below.
17
FIGURE 2-18 Relay Output 2 (Control Output 2 OR Alarm 2)
Connections are made to Output 2 relay as illustrated below. The contacts are rated at 2 amp resistive, 120/240 VAC.
FIGURE 2-19 SSR Driver Output 2 (Control Output 2 OR Alarm 2)
Connections are made to Output 2 SSR Driver as illustrated below. The solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output impedance is 250 ohms.
FIGURE 2-20 mADC Output 2 (Control Output 2)
Make connections for DC Output 2 as illustrated below.
18
FIGURE 2-21 Relay Output 3 (Alarm 1)
Connections are made to Output 3 relay as illustrated below. The contacts are rated at 2 amp resistive, 120/240 VAC.
FIGURE 2-22 SSR Driver Output 3 (Alarm 1)
Connections are made to Output 3 SSR Driver as illustrated below. The solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output impedance is 250 ohms.
FIGURE 2-23 mADC Output 3 (Recorder Output Only)
Make connections for DC output 3 as illustrated below.
19
20
SECTION 3: OPERATION
3.1 Control Capability
The capabilities available in a specific unit are dependent upon the hardware options specified when the instrument is ordered. Refer to Appendix E for the decoding of the instrument model number. Current proportioning control cannot be implemented if a current output was not ordered. The available output types and quantity of each are as follows:
Type of Output Quantity Available
SPDT mechanical relay output Up to three
SSR Driver Up to three
mADC current output Up to two
3.2 Control Responses
Each instrument may be configured to provide three mode proportional control. Proportional control is provided with Proportional Band, Integration, and Derivative responses. The PID parameters are defined as follows:
Out 1 Out2 P (Proportional) Proportional Band Pb1 Pb2 I (integration) Automatic Reset ArSt ArSt D (Derivative) Rate rAtE rAtE
Manual Reset is provided for use in lieu of, or in conjunction with automatic reset. A cycle time adjustment parameter is provided for use with each time proportioning control output.
21
3.3 Direct/Reverse Operation of Outputs
Direct operation is typically used with cooling applications. On-Off direct output(s) will turn on when the process variable exceeds setpoint. Proportional direct output(s) will increase the percentage of output as the process value increases within the proportional band.
Reverse operation is typically used with heating applications. On-Off reverse output(s) will turn off when the process variable exceeds setpoint. Proportional reverse output(s) will decrease the percentage of output as the process value increases within the proportional band.
Output 2 will be Direct when Output 1 is selected as Reverse, and Reverse when Output 1 is selected as Direct.
3.4 On-Off Control
On-Off control can be implemented with SPDT relay or SSR driver output(s) by setting the corresponding proportional band (Pb) to O.O. On-Off operation can be assigned to Output 1 only (Output 2 not present), Output 1 AND Output 2, or Output 2 only (Output 1 is time proportional or current proportional). A hysteresis adjustment is provided for On-Off outputs, "HySl " for Output 1 only, "HySt" for Output 1 AND Output 2, or "HyS2" for Output 2 only. This adjustment is in % of input span and defines the bandwidth of the hysteresis. Relay chatter can be eliminated by proper adjustment of this parameter. When operating in On-Off control, the output(s) will turn on or off depending upon the setpoint, the process value, and the hysteresis adjustment.
3.5 Time Proportioning Control
Time Proportioning control can be implemented with a SPDT relay or SSR driver. Time proportioning control can be selected for either Output 1 or Output 1 and Output 2, depending on hardware configuration. Time proportioning control is accomplished by cycling the output on and off during a prescribed period of time when the process variable is within the proportional band.
Ex: Calculated output % = 40%; Cycle time adjustment = 32 seconds
Output on time =.4 x 32 = 12.8 seconds Output off time = .6 x 32 = 19.2 seconds
22
When the unit is operating in the Control Mode, the control algorithm determines the output % required to correct for any difference between the process value and the setpoint. The output calculation is affected by Tune Mode parameter adjustments. See Figure 3-1 for proportional bandwidth effect on the output.
3.6 Current Proportioning Control
Current Proportioning control can be implemented on units provided with mADC current output(s). Current Proportioning control provides a 4 to 20 mADC or 0-20 mADC output in response to process value and setpoint. As with Time proportioning, the calculated output % for Current proportioning is affected by the Tune Mode parameter adjustments.
See Figure 3-1 for proportional bandwidth effect on the output.
23
FIGURE 3-1 Proportional Band 1
24
Loading...
+ 63 hidden pages