Despatch MIC 1162 Installation Manual

MIC 1162
MIC 1162
MIC 1162MIC 1162 HIGH/LOW LIMIT CONTROLLER
HIGH/LOW LIMIT CONTROLLER
HIGH/LOW LIMIT CONTROLLERHIGH/LOW LIMIT CONTROLLER INSTRUCTION MANUAL
INSTRUCTION MANUAL
INSTRUCTION MANUALINSTRUCTION MANUAL
E-89 PN 136107 REVISION 10-07
TABLE OF CONTENTS
TABLE OF CONTENTS................................................................................................... i
SECTION 1: PRODUCT DESCRIPTION.......................................................................1
1.1 General................................................................................................................. 1
1.2 Displays................................................................................................................ 1
1.3 Alarms .................................................................................................................. 1
1.4 Process Variable/Setpoint Value Retransmission Output..................................... 2
SECTION 2: INSTALLATION AND WIRING.................................................................. 3
2.1 General Information.............................................................................................. 3
2.2 Wiring Guidelines ................................................................................................. 5
2.2.1 Installation Considerations.............................................................................5
2.2.2 AC Power Wiring............................................................................................ 6
2.2.3 Wire Isolation................................................................................................. 6
2.2.4 Use Of Shielded Cable .................................................................................. 7
2.2.5 Noise Suppression At The Source.................................................................7
2.3 Sensor Placement (Thermocouple or RTD) .........................................................9
2.4 Input Connections............................................................................................... 10
2.5 Output Connections............................................................................................13
SECTION 3: OPERATION........................................................................................... 15
3.1 Power Up Procedure .......................................................................................... 15
3.2 Keypad Operation............................................................................................... 15
3.3 Displays.............................................................................................................. 16
3.3.1 Alarm Status Display.................................................................................... 16
3.3.2 Over-Range/Under-Range Display ..............................................................16
3.4 Front Panel Indicators ........................................................................................ 17
3.5 Exceeding Limit Setpoint.................................................................................... 17
3.6 Annunciator ........................................................................................................ 18
3.7 Remote Reset (Optional).................................................................................... 18
SECTION 4: CONTROL MODE...................................................................................19
SECTION 5: SETPOINT CHANGE MODE ..................................................................21
SECTION 6: CONFIGURATION.................................................................................. 22
SECTION 7: SET-UP MODE ....................................................................................... 25
SECTION 8: ENABLE MODE ....................................................................................... 28
SECTION 9: CALIBRATION ........................................................................................ 29
APPENDIX A: BOARD LAYOUT - JUMPER POSITIONING ........................................ 32
APPENDIX B: HARDWARE DEFINITION CODE.........................................................35
APPENDIX C: INPUT RANGE CODES........................................................................37
APPENDIX D: SPECIFICATIONS................................................................................. 38
APPENDIX E: ORDER MATRIX ...................................................................................42
APPENDIX F: SOFTWARE REFERENCE SHEET ......................................................43
i
ii
SECTION 1: PRODUCT DESCRIPTION
1.1 General
This instrument is a microprocessor based single loop controller capable of measuring and displaying temperature, pressure, flow, and level from a variety of inputs. The control is configurable to be either high-limit, low-limit, or both types.
Control functions, alarm settings and other parameters are easily entered through the front keypad. E2 Technology (100 year life) protects against data loss during AC power outages.
The input is user configurable to directly connect to either thermocouple, RTD, mVDC, VDC or mADC inputs. The instrument can operate from either a 90-264 VAC, 50/60 HZ power supply, or optional 24V AC/DC power supply.
1.2 Displays
Each instrument is provided with dual displays and status indicators as shown in Figure 1 -1. Typically, the upper display displays the value of the process variable, while the lower display displays the setpoint value. Alternate displays can be selected in the Setup Mode.
1.3 Alarms
Alarm indication is standard on all instruments. Up to two alarm outputs are optional. Alarm type may be set as Process Direct or Reverse (high or low), Logical Combination of the two alarms, Annunciator Direct or Reverse, High Limit, or Low Limit. Alarm status is indicated by LED.
1
FIGURE 1-1 Keys and Indicators
1.4 Process Variable/Setpoint Value Retransmission Output
If the instrument is specified with this option, this output may be scaled over any desired range and re-transmitted, through optional Output 3.
2
SECTION 2: INSTALLATION AND WIRING
2.1 General Information
Electrical code requirements and safety standards should be observed and installation performed by qualified personnel.
The electronic components of the instrument may be removed from the housing during installation. To remove the components, grip the side edges of the front panel and pull the instrument forward. During re-installation, the vertically mounted circuit boards should be properly aligned in the housing.
Ensure that the instrument is correctly orientated. A stop will operate if an attempt is made to insert the instrument incorrectly.
Recommended panel opening sizes are illustrated in Figure 2-1. After the opening is properly cut, insert the instrument into the panel opening. Ensure that the panel gasket is not distorted and that the instrument is positioned squarely against the panel. Slide the mounting clamp into place on the instrument and push it forward until it is firmly in contact with the rear face of the mounting panel.
Note: The mounting clamp tongues may engage either on the sides or the top/bottom of the instrument housing. Therefore when installing several instruments side-by-side in one cut-out, use the ratchets on the top/bottom faces.
3
FIGURE 2-1 Panel Cut-Out Dimensions
FIGURE 2-2 Main Dimensions
4
FIGURE 2-3 Panel Mounting the Controller
2.2 Wiring Guidelines
Electrical noise is a phenomenon typical of industrial environments. The following are guidelines that must be followed to minimize the effect of noise upon any instrumentation.
2.2.1 Installation Considerations
Listed below are some of the common sources of electrical noise in the industrial environment:
Ignition Transformers
Arc Welders
Mechanical contact relay(s)
Solenoids
Before using any instrument near the device listed, the instructions below should be followed:
5
1. If the instrument is to be mounted in the same panel as any of the listed devices,
separate them by the largest distance possible. For maximum electrical noise reduction, the noise generating devices should be mounted in a separate enclosure.
2. If possible, eliminate mechanical contact relay(s) and replace with solid state relays.
If a mechanical relay being powered by an instrument output device cannot be replaced, a solid state relay can be used to isolate the instrument.
3. A separate isolation transformer to feed only instrumentation should be considered.
The transformer can isolate the instrument from noise found on the AC power input.
4. If the instrument is being installed on existing equipment, the wiring in the area
should be checked to insure that good wiring practices have been followed.
2.2.2 AC Power Wiring
Neutral (For 115 VAC) It is good practice to assure that the AC neutral is at or near ground potential. To verify this, a voltmeter check between neutral and ground should be done. On the AC range, the reading should not be more than 50 millivolts. If it is greater than this amount, the secondary of this AC transformer supplying the instrument should be checked by an electrician. A proper neutral will help ensure maximum performance from the instrument.
2.2.3 Wire Isolation
Three voltage levels of input and output wiring may be used with the unit:
Analog input or output (i.e. thermocouple, RTD, VDC, mVDC, or mADC)
SPDT Relays
AC power
The only wires that should run together are those of the same category. If they need to be run parallel with any of the other lines, maintain a minimum 6 inch space between the wires. If wires must cross each other, do so at 90 degrees. This will minimize the contact with each other and reduces "cross talk". "Cross Talk" is due to the EMF (Electro-Magnetic Flux) emitted by a wire as current passes through it. This EMF can be picked up by other wires running in the same bundle or conduit.
In applications where a High Voltage Transformer is used (i.e. ignition systems) the secondary of the transformer should be isolated from all other cables.
6
This instrument has been designed to operate in noisy environments, however, in some cases even with proper wiring it may be necessary to suppress the noise at its source.
2.2.4 Use Of Shielded Cable
Shielded cable helps eliminate electrical noise being induced on the wires. All analog signals should be run with shielded cable. Connection lead length should be kept as short as possible, keeping the wires protected by the shielding. The shield should be grounded at one end only. The preferred grounding location is the sensor, transmitter or transducer.
2.2.5 Noise Suppression At The Source
Usually when good wiring practices are followed no further noise protection is necessary. Sometimes in severe electrical environments, the amount of noise is so great that it has to be suppressed at the source. Many manufacturers of relays, contactors, etc. supply “surge suppressors" which mount on the noise source.
For those devices that do not have surge suppressors supplied, RC (resistance­capacitance) networks and/or MOV (metal oxide varistors) may be added.
Inductive Coils - MOV's are recommended for transient suppression in inductive coils connected in parallel and as close as possible to the coil. See Figure 2-4. Additional protection may be provided by adding an'RC network across the MOV.
7
FIGURE 2-4
Contacts - Arcing may occur across contacts when the contact opens and closes. This results in electrical noise as well as damage to the contacts. Connecting a RC network properly sized can eliminate this arc.
For circuits up to 3 amps, a combination of a 47 ohm resistor and 0.1 microfarad capacitor (1 000 volts) is recommended. For circuits from 3 to 5 amps, connect 2 of these in parallel. See Figure 2-5.
FIGURE 2-5
8
2.3 Sensor Placement (Thermocouple or RTD)
Two wire RTD's should be used only with lead lengths less than 10 feet. If the temperature probe is to be subjected to corrosive or abrasive conditions, it should
be protected by the appropriate thermowell. The probe should be positioned to reflect true process temperature:
In liquid media - the most agitated area In air - the best circulated area
FIGURE 2-6 Wiring Label
9
2.4 Input Connections
In general, all wiring connections are made to the instrument after it is installed. Avoid electrical shock. AC power wiring must not be connected to the source distribution panel until all wiring connection procedures are completed.
FIGURE 2-7A Main Supply The instrument will operate on 90-264V AC 50/6OHz main supply. The power consumption is approximately 4 VA. Connect the line voltage, hot and neutral, to terminals 9 to 10 respectively as illustrated below.
FIGURE 2-7B 24V (Nominal) AC/DC Supply The supply connections for the 24V AC/DC versions of the instrument are shown below.
FIGURE 2-8 Thermocouple (T/C) Input Make thermocouple connections as illustrated below. Connect the positive leg of the thermocouple to terminal 5 and the negative leg to terminal 4.
FIGURE 2-9
10
RTD Input Make RTD connections as illustrated below. For a three wire RTD, connect the resistive leg of the RTD to terminal 6 and the common legs to terminals 4 and 5. For a two wire RTD, connect one leg to terminal 5 and the other leg to terminal 6 as shown below. A jumper wire supplied by the customer must be installed between terminals 4 and 5. Input conditioning jumper must be positioned correctly (see Appendix A) and Hardware Definition Code must be correct (see Appendix B).
FIGURE 2-10 Volt, mV Input Make volt and millivolt connections as shown below. Terminal 5 is positive and terminal 4 is negative. Input conditioning jumper must be positioned correctly (see Appendix A) and Hardware Definition Code must be correct (see Appendix B).
mADC Input Make mADC connections as shown below. Terminal 4 is positive and terminal 6 is negative. Input conditioning jumper must be positioned correctly (see Appendix A) and Hardware Definition Code must be correct (see Appendix B).
11
Loading...
+ 35 hidden pages