This appliance may be installed in an aftermarket* manufactured (mobile) home,
where not prohibited by state or local codes.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
OWNER’S OPERATION AND INSTALLATION MANUAL
Variable
Manually-
Controlled
Models and
Thermostatically-
Controlled
“B” Models
with
Split Oak Logs
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing
property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
— Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
®
Shown with optional
cabinet mantel, hearth
base, and trim
accessories.
WARNING: Improper installation,
adjustment, alteration, service,
or maintenance can cause injury
or property damage. Refer to this
manual for correct installation
and operational procedures. For
assistance or additional information consult a qualified installer, service agency, or the
gas supplier.
WARNING: This is an unvented
gas-fired heater. It uses air (oxygen) from the room in which it is
installed. Provisions for adequate
combustion and ventilation air
must be provided. Refer to
Illustrated Parts Lists ..............................................................................................36-43
Warranty Information .............................................................................................Back Cover
SAFETY
INFORMATION
2
W ARNINGS
WARNING ICON G 001
IMPORTANT: Read this owner’s manual carefully and completely before trying
to assemble, operate, or service this fireplace. Improper use of this fireplace
can cause serious injury or death from burns, fire, explosion, electrical shock,
and carbon monoxide poisoning.
DANGER
WARNING ICON G 001
Carbon monoxide poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the
flu, with headaches, dizziness, or nausea. If you have these signs, the fireplace may not be
working properly. Get fresh air at once! Have fireplace serviced. Some people are more
affected by carbon monoxide than others. These include pregnant women, people with heart
or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Propane Gas: Propane gas is odorless. An odor-making agent is added to the gas. The odor
helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present
even though no odor exists.
Make certain you read and understand all Warnings. Keep this manual for reference. It is your
guide to safe and proper operation of this fireplace.
Safety Information continues on next page
103415
Page 3
SAFETY
INFORMATION
Continued
103415
W ARNINGS
WARNING: Any change to this fireplace or its controls can be dangerous.
1. This appliance is only for use with the type of gas indicated on the rating plate. This
appliance is not convertible for use with other gases.
2. Do not place propane supply tank(s) inside any structure. Locate propane supply tank(s)
outdoors.
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use any phone in your building
• immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions
• if you cannot reach your gas supplier, call the fire department
4. This fireplace shall not be installed in a bedroom or bathroom.
5. Never install the fireplace
• in a recreational vehicle
• where curtains, furniture, clothing, or other flammable objects are less than 36
inches from the front, top, or sides of the fireplace
• in high traffic areas
• in windy or drafty areas
6. Do not use this fireplace as a wood-burning fireplace. Use only the logs provided with
the fireplace.
7. Do not add extra logs or ornaments such as pine cones, vermiculite, or rock wool. Using
these added items can cause sooting. Do not add lava rock around base. Rock and debris
could fall into the control area of fireplace.
8. You must operate this fireplace with the fireplace screen in place. Make sure fireplace
screen is in place before running fireplace.
9. This fireplace is designed to be smokeless. If logs ever appear to smoke, turn off
fireplace and call a qualified service person.
smoking could occur due to log curing and fireplace burning manufacturing residues.
10. Do not allow fans to blow directly into the fireplace. Avoid any drafts that alter burner
flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered
burner patterns can cause sooting.
11. Do not use a blower insert, heat exchanger insert or other accessory not approved for use
with this heater.
12. This fireplace needs fresh air ventilation to run properly. This fireplace has an oxygen
depletion sensor (ODS) pilot light safety system. The ODS shuts down the fireplace if
not enough fresh air is available. See Air for Combustion and Ventilation, pages 6
through 8. If fireplace keeps shutting off, see Troubleshooting, pages 28 through 31.
13. Do not run fireplace
• where flammable liquids or vapors are used or stored
• under dusty conditions
14. Do not use this fireplace to cook food or burn paper or other objects.
15. Never place any objects in the fireplace or on logs.
16. Fireplace front and screen becomes very hot when running fireplace. Keep children and
adults away from hot surfaces to avoid burns or clothing ignition. Fireplace will remain
hot for a time after shut-down. Allow surfaces to cool before touching.
17. Carefully supervise young children when they are in the room with fireplace.
18. Do not use fireplace if any part has been exposed to or under water. Immediately call a
qualified service technician to inspect the fireplace and to replace any part of the control
system and any gas control which has been under water.
19. Do not operate fireplace if any log is broken. Do not operate fireplace if a log is chipped
(dime-sized or larger).
20. Turn fireplace off and let cool before servicing. Only a qualified service person should
service and repair fireplace.
21. Operating fireplace above elevations of 4,500 feet could cause pilot outage.
22. To prevent performance problems, do not use propane fuel tanks of less than 100 lbs.
capacity.
Continued
Note:
During initial operation, slight
3
Page 4
PRODUCT
IDENTIFICATION
Top Middle Log
Left
Front
Branch
Front
Burner
Crossover Log
Right Front
Branch
Base Assembly
Figure 1 - Log Base Assembly, Split Oak Set
Rear Log
Rear
Burner
Bottom
Middle Log
Top Louver
Assembly
Firebox
Hood
Screen
Assembly
Top Outer
Casing
Firebox
Support
Bottom Louver
Assembly
4
Figure 2 - Fireplace
Blower Assembly
(Thermostat Models only)
103415
Page 5
LOCAL CODES
Install and use fireplace with care. Follow all local codes. In the absence of local codes, use the
latest edition of The National Fuel Gas Code ANSI Z223, also known as NFPA 54*.
*A vailable from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
UNPACKING
PRODUCT
FEATURES
1. With utility knife, cut the carton all the way around above the staples on the bottom tray. Lift
the carton off the heater . Remove packing.
right hand side of the heater front. Lift the heater off the bottom tray.
2. Locate two screws above top corners of the fireplace screen. Remove and discard these
screws. Lift fireplace screen up and pull out to remove.
3. Remove protective packaging applied to logs, log base assembly , and fireplace.
4. Remove fireplace hood from carton insert.
5. Check all items for any shipping damage. If damaged, promptly inform dealer where you
bought fireplace.
Note:
The hood is located in the packing on the
Operation
This vent-free fireplace is clean burning. It requires no outside venting. There is no heat loss out
a vent or up a chimney . Heat is generated by both realistic flames and glowing embers. When
used without the blower, the fireplace requires no electricity making it ideal for emergency
back-up heat.
Safety Device
This fireplace has a pilot with an Oxygen Depletion Sensor Shutoff System (ODS). The ODS/
pilot is a required feature for vent-free room heaters. The ODS system shuts off the fireplace if
there is not enough fresh air.
Piezo Ignition System
This fireplace has a piezo ignitor. This system requires no matches, batteries, or other sources to
light fireplace.
103415
Blower Assembly (VSGF28PTB/CSGF28PTB)
This fireplace has a blower assembly . The blower operates thermostatically. The blower circulates heated air from the fireplace into the room. Use of blower is optional. An optional blower
accessory is available for models VSGF28PV/ CSGF28PV.
Thermostat Control Models (VSGF28PTB/CSGF28PTB)
These fireplaces have a thermostat sensing bulb and a control valve. The thermostat controls the
heat output and flame height. This maintains a consistent room temperature. Even the lowest
setting provides realistic flames and glowing embers from two burners. Selecting higher
comfort settings allows fireplace to run longer, producing greater heat output. At lower comfort
settings, the fireplace will run less. This results in increased heating comfort. This can also
result in lower gas bills.
Variable Manual Control (VSGF28PV/CSGF28PV)
These fireplaces have a variable manual control valve which allows the user to choose the heat
setting that best suits his needs. Any setting between low and high may be selected by simply
turning the control knob.
5
Page 6
AIR FOR
COMBUSTION
AND
WARNING
This heater shall not be installed in a confined space unless provisions are provided for adequate combustion and ventilation air. Read the following instructions
to insure proper fresh air for this and other fuel-burning appliances in your home.
VENTILATION
T oday’s homes are built more energy efficient than ever . New materials, increased insulation, and
new construction methods help reduce heat loss in homes. Home owners weather strip and caulk
around windows and doors to keep the cold air out and the warm air in. During heating months,
home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home needs to breathe. Fresh air must
enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to
operate. You must provide adequate fresh air for these appliances. This will insure proper venting
of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following is exerpts from National Fuel Gas Code. NFPA 54/ANSI Z223.1, Section 5.3, Air
for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classifications:
1. Unusually Tight Contruction; 2. Unconfined Space; 3. Confined Space.
The information on pages 6 through 8 will help you classify your space and provide adequate
ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and
ventilation. However, in buildings of unusually tight construction, you must provide additional
fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings exposed to the outside atmosphere have a continuous
water vapor retarder with a rating of one perm or less with openings
gasketed or sealed
b. weather stripping has been added on openable windows and doors
c. caulking or sealants are applied to areas such as joints around window and
door frames, between sole plates and floors, between wall-ceiling joints,
between wall panels, at penetrations for plumbing, electrical, and gas lines,
and at other openings.
If your home meets all of the three criteria above, you must provide additional
fresh air. See
If your home does not meet all of the three criteria above, proceed to page 7.
Ventilation Air From Outdoors
and
, page 8
and
.
Confined Space and Unconfined Space
The National Fuel Gas Code (ANSIZ2123.1, 1992 Section 5.3) defines a confined space as a
space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the
aggregate input rating of all appliances installed in that space and an unconfined space as a space
whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the
aggregate input rating of all appliances installed in that space. Rooms communicating directly
with the space in which the appliances are installed*, through openings not furnished with doors,
are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation
grills between them.
6
103415
Page 7
AIR FOR
COMBUSTION
DETERMINING AIR FLOW FOR FIREPLACE LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
AND
VENTILATION
Continued
Space: Includes the room in which you will install fireplace plus any adjoining rooms
with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height =___________________ cu. ft. (volume of space)
Example:
If additional ventilation to adjoining room is supplied with grills or openings, add the
volume of these rooms to the total volume of the space.
2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space
can support.
____________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr
the space can support)
Example:
3. Add the Btu/Hr of all fuel burning appliances in the space.
Example:
* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr
used.
_________________ Btu/Hr (maximum the space can support)
_________________ Btu/Hr (actual amount of Btu/Hr used)
Example:
The space in the above example is a confined space because the actual Btu/Hr used is more
than the maximum Btu/Hr the space can support. You must provide additional fresh air.
Your options are as follows:
A. Rework work sheet, adding the space of an adjoining room. If the extra space pro-
vides an unconfined space, remove door to adjoining room or add ventilation grills
between rooms. See Ventilation Air from Inside Building, page 8.
B. Vent room directly to the outdoors. See Ventilation Air from Outdoors, page 8.
C. Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the
space is an unconfined space. You will need no additional fresh air ventilation.
Space size22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling height) =
3168 cu. ft. (volume of space)
3168 cu. ft. (volume of space) ÷ 50 cu. ft. = 63.3 or 63,300 (maximum
Btu/Hr the space can support)
Vent-free fireplace___________________ Btu/Hr
Gas water heater*___________________ Btu/Hr
Gas furnace___________________ Btu/Hr
Vented gas heater___________________ Btu/Hr
Gas fireplace logs___________________ Btu/Hr
Other gas appliances*+ ___________________ Btu/Hr
Total= ___________________ Btu/Hr
Gas water heater40,000Btu/Hr
Vent-free fireplace+28,000Btu/Hr
Total=68,000Btu/Hr
63,300Btu/Hr (maximum the space can support)
68,000Btu/Hr (actual amount of Btu/Hr used)
103415
Continued
7
Page 8
AIR FOR
COMBUSTION
AND
WARNING
If the area in which the heater may be operated is smaller than that defined as an
unconfined space, provide adequate combustion and ventilation air by one of the
methods described in the
National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3.
VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining
unconfined space, you must provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3).
You can also remove door into adjoining room (see option 3, Figure 3). Follow the National FuelGas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation for required
size of ventilation grills or ducts.
W ARNING
Rework worksheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.
12"
Ventilation
Grills
Into Adjoining
Room,
Option 1
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
12"
Figure 3 - Ventilation Air from Inside Building
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent
openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items
directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl
spaces.
IMPORTANT:
controlled power vent. Heated air entering the attic will activate the power vent.
8
Do not provide openings for inlet or outlet air into attic if attic has a thermostat-
Outlet
Air
Outlet
Air
Inlet
Air
Inlet Air
Figure 4 - Ventilation Air from Outdoors
Ventilated
Attic
Crawl Space
Ventilated
To Attic
To
Crawl
Space
103415
Page 9
INSTALLING
NOTICE
A qualified service person must install fireplace. Follow all local codes.
W ARNING
Never install the fireplace
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture, clothing, or other flammable objects are less than
36 inches from the front, top, or sides of the fireplace
• in high traffic areas
• in windy or drafty areas
W ARNING
Models VSGF28PTB/CSGF28PTB have a three-prong, grounded electrical plug.
This plug helps protect you against electrical shock. Only connect plug to a
properly grounded, three-prong receptacle. Do not cut or remove the grounding
prong from this plug.
CAUTION
This fireplace creates warm air currents. These currents move heat to wall surfaces next to fireplace. Installing fireplace next to vinyl or cloth wall coverings or
operating fireplace where impurities in the air (such as tobacco smoke) exist, may
discolor walls.
IMPORTANT:
fireplace in rooms without enough ventilation air may cause mildew to form from too much
moisture. See Air for Combustion and Ventilation, pages 6 through 8.
IMPORTANT:
properly .
Vent-free heaters add moisture to the air. Although this is beneficial, installing
Make sure the fireplace is level. If fireplace is not level, log set will not work
CHECK GAS TYPE
Use only propane gas. If your gas supply is not propane gas, do not install fireplace. Call dealer
where you bought fireplace for proper type fireplace.
ELECTRICAL HOOKUP (Models VSGF28PTB/CSGF28PTB )
This fireplace has a blower assembly with an electrical cord. The electrical cord is five feet in
length. You must locate fireplace within reach of a 120 volt grounded electrical outlet. If not,
you must install an electrical outlet within reach of fireplace power cord.
INST ALLING HOOD
Install hood to top of fireboxas shown in Figure 5. Use 3 Phillips screws provided.
103415
Figure 5 - Installing Hood to Firebox
Continued
9
Page 10
INSTALLING
Continued
ASSEMBLING AND ATTACHING OPTIONAL BRASS TRIM
(Included with Mantel Accessory)
IMPORTANT:
page 13.
Note:
The instructions below show assembling and attaching brass trim to fireplace.
1. Remove packaging from three pieces of brass trim.
2. Locate four brass screws, two adjusting plates with set screws, and two shims in the hardware
packet.
3. Align shim under adjusting plate as shown in Figure 6.
4. Slide one end of adjusting plate/shim in slot on mitered edge of top brass trim (see Figure 6).
5. Slide other end of adjusting plate/shim in slot on mitered edge of side brass trim (see Figure 6).
6. While firmly holding edges of brass trim together, tighten both set screws on the adjusting
plate with slotted screwdriver.
7. Repeat steps 1 through 6 for other side.
If you are recessing the firebox in a wall, do not attach brass trim at this time. See
Top Brass Trim
Side Brass Trim
Set Screws
Adjusting
Plate
Shim
Slot
Mitered Edge
Slot
Figure 6 - Assembling Brass Trim
8. Tighten trim hanging screws (#10 x 6.25 shoulder) into holes in cabinets. Place the assembled trim onto fireplace cabinet. Align hanging notches on trim with hanging screws on
side of fireplace (see Figure 7). Push trim firmly into place, sliding hanging notches over
hanging screws.
Trim Hanging
Screws
Assembled
Brass Trim
10
Hanging
Notches on Trim
Figure 7 - Attaching Brass Trim to Fireplace
103415
Page 11
INSTALLING
INSTALLATION CLEARANCES
Continued
WARNING
Maintain the minimum clearances. If you can, provide greater clearances from
floor, ceiling, and adjoining wall.
Carefully follow the instructions below . This will ensure safe installation.
Minimum Wall and Ceiling Clearances (see Figure 8)
A. Clearances from the side of the fireplace opening to any combustible wall should not be
less than 16 inches for a cabinet mantel or 12 inches for a corner installation.
B. Clearances from the top of the fireplace opening to the ceiling should not be less than 42
inches.
MINIMUM CLEARANCE
Note: Clearances
are the same if
using optional
cabinet mantel or
built-in installation.
16"
Face or
Cabinet
Mantel
12"
Corner
Mantel
Figure 8 - Minimum Clearance to Wall and Ceiling
Side Wall - 16 " Cabinet and
42"
Face Mantel
Ceiling - 42" Corner Mantel
Floor - 0"
CONVENTIONAL FIREPLACE INSTALLATION
Conventional installation of this fireplace involves installing fireplace along with the corner,
face, or cabinet mantel with hearth base accessories against a wall in your home. Follow the
instructions below to install the fireplace in this manner.
W ARNING
For conventional installation, it is recommended you use the cabinet mantel,
corner mantel, face mantel, or hearth bases specified in this manual. Surface
clearances may not be sufficient with other cabinet mantels and hearth bases.
This may create a fire hazard. See
mantels and hearth bases.
Note:
The instructions below show installation using the cabinet mantel and the
G3000F/G3001U series hearth base accessories. The hearth base accessory shown is optional
for this installation. You can install fireplace and cabinet mantel directly on the floor . The corner
mantel and face mantel accessories cannot be installed with the G3000F/G3001U hearth base.
You must install corner and face mantel directly on the floor. If mounting fireplace and cabinet
mantel to the floor or using face mantel or corner mantel, an optional G3005 Slim Base kit may
be installed.
1. Assemble cabinet mantel, hearth base, and trim accessories. Assembly instructions are
included with each accessory.
2. When installing blower, install a properly grounded, 120 volt three-prong electrical outlet at
fireplace location if an outlet is not there. If possible, locate outlet so cabinet mantel will
cover it when installed (see Figure 9, page 12).
Accessories,
pages 34 and 35 for correct
103415
Continued
11
Page 12
INSTALLING
Continued
3. Install gas piping to fireplace location. This installation includes an approved flexible gas
line (if allowed by local codes) after the manual shutoff valve. The flexible gas line must be
the last item installed on the gas piping. See Installing Gas Piping to Fireplace Location,
page 15.
4. Place hearth base accessory against wall at installation location. Cut an access hole in hearth
top to run flexible gas line to fireplace (see Figure 9). Make sure to locate access hole so
cabinet mantel will cover it when installed. Note: You can secure base to floor using wood
screws. Countersink screw heads and putty over.
Hearth Base
Figure 9 - Placing Hearth Base Accessory Against Wall
Flexible Gas Line
Electrical Outlet
Gas Line Access
Hole
5. Route flexible gas line through access hole in hearth base.
6. Center cabinet mantel on hearth base (see Figure 10). Make sure mantel is flush against wall.
Cabinet Mantel
12
Figure 10 - Installing Cabinet Mantel
7. Break off nailing flanges (see Figure 11) with hammer or pliers.
Nailing Flanges
Figure 11 - Location of Nailing Flanges
8. Place cardboard or other protective material on top of hearth base. Carefully set fireplace on
protective material, with back of fireplace inside mantel opening.
103415
Page 13
INSTALLING
Continued
9. Attach flexible gas line to fireplace gas regulator . See Connecting Fireplace to Gas Supply,
page 17.
10. If blower is installed, route blower electrical cord through access holes in either side of fireplace.
Note:
Bushing may be moved if necessary. Plug electrical cord into electrical outlet.
11.Carefully insert fireplace into cabinet mantel. Be careful not to scratch or damage hearth
base, cabinet mantel, or any laminate trim on hearth base. Remove protective material from
top of hearth base and from front of fireplace (if any). Note: You can secure fireplace to
hearth or floor. Open lower louver. Locate screw holes in bottom of base. Tighten wood
screws through these holes and into hearth or floor.
12.Check all gas connections for leaks. See Checking Gas Connections, page 18.
Figure 12 - Inserting Fireplace Into Cabinet Mantel
BUILT-IN FIREPLACE INSTALLATION
Built-in installation of this fireplace involves installing fireplace into a framed-in enclosure.
This makes the front of fireplace flush with wall. If installing a mantel above the fireplace, but
you must follow the clearances shown in Figure 16, page 15. Follow the instructions below to
install the fireplace in this manner.
HeightFront WidthDepth
Actual Framing ActualFraming ActualFraming
3
32
/8" 33"34 5/16" 35 1/2"16 11/16" 17 3/4"
1. Frame in rough opening. Use dimensions shown in Figure 13 for the rough opening.
17 3/4"
33"
103415
35 1/2"
Figure 13 - Rough Opening for Installing in Wall
Continued
13
Page 14
INSTALLING
Continued
If installing in a corner, use dimensions shown in Figure 14 for the rough opening. The height
is 33" which is the same as the wall opening above.
39 3/8"
27 7/8"
35 1/2"
55 5/8"
Figure 14 - Rough Opening for Installing in Corner
2. If using blower, install and properly ground GA3555, three-prong 120 volt electrical outlet, in
fireplace. Follow instructions included in kit.
3. Install gas piping to fireplace location. This installation includes an approved flexible gas line
(if allowed by local codes) after the manual shutoff valve. The flexible gas line must be the
last item installed on the gas piping. See Installing Gas Piping to Fireplace Location, page
16.
4. Carefully set fireplace in front of rough opening with back of fireplace inside wall opening.
5. Attach flexible gas line to gas supply. See Connecting Fireplace to Gas Supply, page 17.
6. Plug electrical cord into electrical outlet installed in step 2.
7. Carefully insert fireplace into rough opening.
8. Attach fireplace to wall studs using nails or wood screws through holes in nailing flange (see
Figure 15).
9. Check all gas connections for leaks. See Checking Gas Connections, page 18.
10.Install brass trim after final finishing and/or painting of wall (see Figure 7, page 10).
14
Nails or Wood
Screws
Nailing Flanges
Figure 15 - Attaching Fireplace to Wall Studs
103415
Page 15
INSTALLING
Continued
Mantel Clearances for Built-In Installation
If placing mantel above built-in fireplace, you must meet minimum clearance between mantel
shelf and top of fireplace opening.
Mantel Shelf
10"
8"
6"
2
1
/2
"
Underside of
Mantel Shelf
All minimum
distances are
in inches
20"24
Figure 16 - Minimum Mantel Clearances for Built-In Installation
1
/2
Distances to
Underside of
Mantel
"27
1
/2
"30"
Top of
Fireplace
Opening
If your installation does not meet the above minimum clearances, you must:
• raise the mantel to an acceptable height, OR
• remove the mantel.
INSTALLING GAS PIPING TO FIREPLACE LOCATION
NOTICE
A qualified service person must connect fireplace to gas supply. Follow all local
codes.
103415
CAUTION
Never connect heater directly to the propane supply. This heater requires an
external regulator (not supplied). Install the external regulator between the heater
and propane supply.
Installation Items Needed
Before installing fireplace, make sure you have the items listed below .
• piping (check local codes)
• sealant (resistant to LP/propane gas)
• manual shutoff valve *
• test gauge connection *
• sediment trap
* An A.G.A. design-certified manual shutof f valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the optional A.G.A. design-certified manual
shutoff valve from your dealer. See Accessories, page 34.
• tee joint
• pipe wrench
• approved flexible gas line with gas
connector (if allowed by local
codes) (not provided)
Continued
15
Page 16
INSTALLING
Continued
The installer must supply an external regulator. The external regulator will reduce incoming gas
pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you
do not reduce incoming gas pressure, heater regulator damage could occur. Install external
regulator with the vent pointing down as shown in Figure 17. Pointing the vent down protects it
from freezing rain or sleet.
External
Regulator
Propane Supply Tank
Vent Pointing
Down
Figure 17 - External Regulator with Vent Pointing Down
CAUTION
Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used
in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to
allow proper gas volume to fireplace. If pipe is too small, undue loss of pressure
will occur.
Installation must include a manual shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT
tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure
17, page 17).
Check your building codes for any special requirements for locating manual shutoff valve to
fireplaces.
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into
pipe. Excess sealant in pipe could result in clogged fireplace valves.
CAUTION
Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
16
Install sediment trap in supply line as shown in Figure 18, page 17. Locate sediment trap where
it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze.
A sediment trap traps moisture and contaminants. This keeps them from going into fireplace gas
controls. If sediment trap is not installed or is installed wrong, fireplace may not run properly.
103415
Page 17
INSTALLING
Continued
Approved
Flexible Gas
Line
A.G.A. Design-Certified Manual
Shutoff Valve with 1/8" NPT Tap*
3" Minimum
From Gas Meter
(5" W.C. to 10.5" W.C.
Pressure)
Sediment
Tee Joint
Pipe Nipple
Trap
Figure 18 - Gas Connection
* Purchase the optional A.G.A. design-certified manual shutof f valve from your dealer. See
Accessories, page 34.
Cap
CONNECTING FIREPLACE TO GAS SUPPLY
Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• Phillips screwdriver
• sealant (resistant to propane/LP gas, not provided)
1. Remove fireplace screen. Remove two screws that hold fireplace screen in place for shipping. These screws are located near top of screen. Discard screws. Lift fireplace screen up
and pull out to remove.
2. Remove screws that attach log base assembly to fireplace (see Figure 19). Carefully lift up
log base assembly and remove from fireplace (see Figure 19).
Note:
If adding the G8000 series brick liner accessory , install it now. Follow instructions in
G8000 accessory kit.
CAUTION
Do not pick up log base assembly by burners. This could damage
burners. Only handle base by grates.
103415
Continued
Figure 19 - Removing Log Base Assembly From Fireplace
17
Page 18
INSTALLING
Continued
3. Route flexible gas line from manual shutoff valve to fireplace. Route flexible gas supply line
through one of the access holes.
NOTICE
Most building codes do not permit concealed gas connections. A flexible gas line
is provided to allow accessibility from the fireplace. The flexible gas supply line
connection to the manual shutoff valve should be accessible.
4. Attach a 45° flare union gas connector to flexible gas line from gas supply (see Figure 20).
Connect flare union to flexible gas line attached to gas regulator of fireplace (see Figure 20).
5. Check all gas connections for leaks. See Checking Gas Connections, below.
6. Replace log base assembly back into fireplace. Feed flexible gas line into fireplace base area
while replacing log base assembly. Make sure the entire flexible gas line is in fireplace base
area. Reattach log base assembly to fireplace with screws removed in step 3.
To Fireplace
Gas Regulator
Flexible Gas Line from
Fireplace Gas Regulator
➞
Flare Union
Flexible Gas Line from
Manual Shutoff Valve
Figure 20 - Attaching Flexible Gas Lines Together
Manual Shutoff Valve
To Gas Meter
➞
CHECKING GAS CONNECTIONS
W ARNING
Test all gas piping and connections for leaks after installing or servicing. Correct
all leaks at once.
W ARNING
Never use an open flame to check for a leak. Apply a mixture of liquid soap and
water to all joints. Bubbles forming show a leak. Correct all leaks at once.
18
Pressure Testing Gas Supply Piping System
Test Pressures In Excess Of 1/2 PSIG
1. Disconnect fireplace and its individual manual shutoff valve from gas supply piping system.
Pressures in excess of 1/2 psig will damage fireplace gas regulator.
2. Cap off open end of gas pipe where manual shutoff valve was connected.
3. Pressurize supply piping system by either using compressed air or opening main gas valve
located on or near gas meter.
4. Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas
joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Re-connect fireplace and manual shutoff valve to gas supply. Check re-connected fittings for
leaks.
103415
Page 19
INSTALLING
ON
POSITION
OFF
POSITION
Continued
Test Pressures Equal To or Less Than 1/2 PSIG
1. Close manual shutoff valve (see Figure 21).
2. Pressurize supply piping system by either using compressed air or opening main gas valve
located on or near gas meter.
3. Check all joints from gas meter to manual shutoff valve (see Figure 22). Apply mixture of
liquid soap and water to gas joints. Bubbles forming show a leak.
4. Correct all leaks at once.
Pressure Testing Fireplace Gas Connections
1. Open manual shutoff valve (see Figure 21).
2. Open main gas valve located on or near gas meter .
3. Make sure control knob of fireplace is in the OFF position.
4. Check all joints from manual shutoff valve to thermostat gas valve (see Figure 22). Apply
mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light fireplace (see Operating Fireplace, pages 22 and 23 [Thermostat-controlled models] or
pages 24 and 25 [Manually-controlled models]). Check all other internal joints for leaks.
7. Turn off fireplace (see To Turn Off Gas to Appliance, page 23 [Thermostat-controlled
models] or page 25 [Manually-controlled models]).
Manual
Shutoff
Valve
Open
Closed
Figure 21 - Manual Shutoff Valve
Manual Shutoff Valve
Propane
Supply Tank
103415
Manual Gas Valve
Figure 22 - Checking Gas Joints
Continued
19
Page 20
INSTALLING
INSTALLING LOGS (Split Oak Design Models)
Continued
WARNING
Failure to position the parts in accordance with these diagrams or failure to use
only parts specifically approved with this heater may result in property damage or
personal injury.
Each log is marked with a number. These numbers will help you identify the log when installing.
It is very important to install these logs exactly as instructed. Do not modify logs. Only use logs
supplied with heater.
1. Place front logs (#1L and #1R) on top of the grate. Make sure the notches in the bottom of
the logs fit over the grate prongs (see Figure 23). Push back of logs flush with metal grate
bar. Note: 18" model has only one front log.
2. Rest bottom middle log (#2) behind metal posts on front burner. Make sure the grooves in the
bottom of the log fit over the grate. Bring the log forward next to the metal posts. The pegs
on the log must be on top (see Figure 24).
3. Slide the grooves in the back of the rear log (#3) against the rear grate prongs. Make sure the
peg on the log is on top (see Figure 25).
4. Place the top middle log (#4) on the bottom middle log (#2). Make sure the pegs of the
bottom middle log fit securely in the holes of the top middle log (see Figure 26).
Bottom Middle Log (#2)
Peg
Notch
Front Log (#1L)
Front Log (#1R)
Peg
Groove
Metal Post
Grate
Prongs
Metal Grate Bar
Figure 23 - Installing Front Logs
Groove
in Back
of Log
Grate
Prong
Rear
Burner
(#1L and #1R)
Peg
Rear Log (#3)
Groove
in Back
of Log
Grate
Prong
Groove
Metal Post
Figure 24 - Installing Bottom
Middle Log (#2)
Hole
Peg
Peg
Grate
Top Middle Log (#4)
Hole
Bottom
Middle Log
20
Figure 25 - Installing Rear Log (#3)
Figure 26 - Installing Top Log (#4)
103415
Page 21
INSTALLING
Continued
4. Place the crossover log (#5) on the back log and the top middle log. Make sure the peg on
the rear log is in the hole in the bottom of the crossover log. The crossover log should fit in
the cutout of the top middle log (see Figure 27).
Crossover
Log (#4)
Hole
Cutout
Peg
Figure 27 - Installing Crossover Log (#5)
W ARNING
You must operate this fireplace with the fireplace screen in place. Make sure
fireplace screen is in place before running fireplace.
5. Install fireplace screen by slipping notches of fireplace screen over screws on front of
fireplace (see Figure 28).
103415
Notches
Screws for
Mounting
Screen
Figure 28 - Installing Fireplace Screen
21
Page 22
FOR YOUR SAFETY READ BEFORE LIGHTINGOPERATING
FIREPLACE
Thermostat-
Controlled Models
W ARNING
If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow
these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next
to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob
will not push in or turn by hand, don’t try to repair it, call a qualified service technician
or gas supplier. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately call a qualified
service technician to inspect the appliance and to replace any part of the control system and
any gas control which has been under water.
LIGHTING INSTRUCTIONS
22
W ARNING
You must operate this fireplace with the fireplace screen in place. Make sure
fireplace screen is installed before running fireplace.
NOTICE
During initial operation of new fireplace, burning logs will give off a paper-burning
smell. Orange flame will also be present. Open window to vent smell. Operate
fireplace on HI position to burn off odor. This will only last a few hours.
1. STOP! Read the safety information on page above.
2. Make sure manual shutoff valve is fully open.
3. Turn control knob clockwise
Ignitor Button
Figure 29 - Control Knob and Ignitor Button Location
4. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor.
If you smell gas, STOP! Follow “B” in the safety information above. If you don’t smell
gas, go to the next step.
5. Turn control knob counterclockwise
knob for five (5) seconds (see Figure 29, above).
Note:
If running fireplace for first time, there will be air in gas line. You may need to
press in control knob for 30 seconds or longer. This will allow air to bleed from the
gas system.
Clockwise
to the OFF position.
C-clockwise
Control Knob
to the PILOT position. Press in control
103415
Page 23
OPERATING
FIREPLACE
Thermostat-
Controlled Models
Continued
6. Continue pressing control knob in. Press and release ignitor button. This will light pilot.
The pilot is attached to the front burner. If needed, keep pressing ignitor button until
pilot lights.
Note:
If pilot does not stay lit, contact a qualified service person or gas supplier for
repairs. Until repairs are made, light pilot with match. To light pilot with match, see
Manual Lighting Procedure, below.
7. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds,
release control knob.
Note:
If pilot goes out, repeat steps 3 through 7. This fireplace has a safety interlock
system. Wait one (1) minute for system to reset before lighting pilot again.
• If control knob does not pop out when released, contact a qualified service
person or gas supplier for repairs.
Pilot Burner
Thermocouple
Ignitor Electrode
Figure 30 - Pilot
8. Turn control knob counterclockwise
should light. Set control knob to any heat level between HI and LO.
C-clockwise
to desired heating level. The burners
CAUTION
Do not try to adjust heating levels by using the manual shutoff valve.
TO TURN OFF GAS TO APPLIANCE
Shutting Off Fireplace
Turn control knob clockwise
Shutting Off Burners Only (pilot stays lit)
Turn control knob clockwise
Clockwise
to the OFF position.
Clockwise
to the PILOT position.
THERMOSTA T CONTROL OPERATION
You can set the thermostat control knob to any comfort level between HI and LO. The
thermostat will gradually modulate the heat output and flame height from higher to lower
settings, or pilot, in order to maintain the comfort level you select. The ideal comfort
setting will vary by household depending upon the amount of space to be heated, the
output of the central heating system, etc.
Note:
Selecting the HI setting will cause the burner to remain on without modulating down
in most cases.
103415
MANUAL LIGHTING PROCEDURE
1. Follow steps 1 through 5 under Lighting Instructions, page 22.
2. Depress control knob and light pilot with match.
3. Keep control knob pressed in for 30 seconds after lighting pilot. After 30
seconds, release control knob. Now follow step 8, above.
Continued
23
Page 24
OPERATING
FOR YOUR SAFETY READ BEFORE LIGHTING
FIREPLACE
Manually-Controlled
Models
W ARNING
If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow
these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next
to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob
will not push in or turn by hand, don’t try to repair it, call a qualified service technician
or gas supplier. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately call a qualified
service technician to inspect the appliance and to replace any part of the control system
and any gas control which has been under water.
LIGHTING INSTRUCTIONS
24
W ARNING
You must operate this fireplace with the fireplace screen in place. Make sure
fireplace screen is installed before running fireplace.
NOTICE
During initial operation of new fireplace, burning logs will give off a paper-burning
smell. Orange flame will also be present. Open window to vent smell. Operate
fireplace on HI position to burn off odor. This will only last a few hours.
1. STOP! Read the safety information on above.
2. Make sure manual shutoff valve is fully open.
3. Turn control knob clockwise
Control Knob
Figure 31 - Control Knob and Ignitor Button Location
4. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor.
If you smell gas, STOP! Follow “B” in the safety information above. If you don’t smell
gas, go to the next step.
5. Slightly depress and turn control knob counterclockwise
tion. Press in control knob for five (5) seconds (see Figure 31, above).
Note:
If running fireplace for first time, there will be air in gas line. You may need to
press in control knob for 30 seconds or longer. This will allow air to bleed from the
gas system.
Clockwise
to the OFF position.
IGNITOR
Ignitor Button
C-clockwise
to the PILOT posi-
103415
Page 25
OPERATING
FIREPLACE
Manually-Controlled
Models
Continued
6. Continue pressing control knob in. Press and release ignitor button. This will light
pilot. The pilot is attached to the front burner. If needed, keep pressing ignitor button
until pilot lights.
Note:
If pilot does not stay lit, contact a qualified service person or gas supplier for
repairs. Until repairs are made, light pilot with match. To light pilot with match, see
Manual Lighting Procedure, below.
7. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds,
release control knob.
Note:
If pilot goes out, repeat steps 3 through 7.
• If control knob does not pop out when released, contact a qualified service
person or gas supplier for repairs.
Pilot Burner
Thermocouple
Ignitor Electrode
Figure 32 - Pilot
8. Slightly depress and turn control knob counterclockwise
C-clockwise
to the HIGH
position. Both burners should light. Set control knob to either HIGH or LOW.
VARIABLE CONTROL OPERATION
The variable control valve can be set to any heat setting and flame height desired, by
simply turning the control knob until that setting is attained. Even the lowest setting
provides realistic flames and glowing embers from two burners. Selecting higher settings
produces greater heat output. This results in increased heating comfort.
W ARNING
Do not operate heater between locked positions.
CAUTION
Do not try to adjust heating levels by using the manual shutoff valve.
TO TURN OFF GAS TO APPLIANCE
Shutting Off Fireplace
1. Turn control knob clockwise
2. Slightly depress control knob and turn clockwise
3. Slightly depress control knob and turn clockwise
Clockwise
to the HIGH position.
Clockwise
to the PILOT position.
Clockwise
to the OFF position.
103415
Shutting Off Burners Only (pilot stays lit)
1. Turn control knob clockwise
2. Press in and turn clockwise
Clockwise
to the HIGH position.
Clockwise
to the PILOT position.
MANUAL LIGHTING PROCEDURE
1. Follow steps 1 through 5 under Lighting Instructions, page 24.
2. Depress control knob and light pilot with match.
3. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds,
release control knob. Now follow step 8, above.
Continued
25
Page 26
OPERATING
FIREPLACE
VSGF28PTB/
CSGF28PTB Models
BLOWER OPERA TION
W ARNING
This fireplace has a three-prong, grounded electrical plug. This plug helps protect
you against electrical shock. Only connect plug to a properly grounded, threeprong receptacle. Do not cut or remove the grounding prong from this plug.
Locate the blower switch by opening lower louver on fireplace. Blower switch is located at
lower left inside louver door.
Thermostat-controlled blowers have three settings: ON, OFF, and AUTO. In the ON
position, the blower will operate constantly. In the OFF position, the blower will not
operate. In the AUTO position, the blower will start when the thermostat senses a sufficient increase in firebox temperature.
Note:
Your gas logs and thermostat blower will not turn on and off at the same time. The
fireplace may run for several minutes before the blower turns on. After the heater modulates to the pilot position, the blower will continue to run. The blower will shut off after
the firebox temperature decreases.
Note:
It is safe to operate fireplace with blower turned off. However, the blower helps
distribute heated air from the fireplace.
VSGF28PV Model
Only
INSPECTING
BURNERS
BLOWER KIT MODEL GA3700
This optional non-thermostat blower kit has a rotary dial which allows infinitely adjustable blower speed control. Follow installation instructions included with blower.
Check pilot flame pattern and burner flame patterns often.
PILOT FLAME PATTERN
Figure 33 shows a correct pilot flame pattern. Figure 34 shows an incorrect pilot flame pattern.
The incorrect pilot flame is not touching the thermocouple. This will cause the thermocouple to
cool. When the thermocouple cools, the fireplace will shut down.
Thermocouple
Pilot Burner
Thermocouple
Pilot Burner
26
Figure 33 - Correct Pilot Flame
Pattern
If pilot flame pattern is incorrect, as shown in Figure 34
• turn fireplace off (see To Turn Off Gas to Appliance, page 23 [Thermostat-controlled models} or page 25 [Manually-controlled models])
• see Troubleshooting, pages 28 through 31
Figure 34 - Incorrect Pilot Flame
Pattern
103415
Page 27
INSPECTING
BURNERS
FRONT BURNER FLAME PATTERN
Figure 35 shows correct front burner flame pattern. Figure 36 shows incorrect front burner
flame pattern. The incorrect burner flame pattern shows yellow tipping at top of blue flame.
Continued
W ARNING
If front burner flame pattern shows yellow tipping, your fireplace could produce
increased levels of carbon monoxide. Follow instructions at bottom of this page.
Yellow flame on rear burner is normal.
NOTICE
Do not mistake orange flames with yellow tipping. Dirt or other fine particles are
burned by fireplace, causing brief patches of orange flame.
CORRECT FLAME PATTERN AT HIGH POSITION
Figure 35 - Correct Front Burner Flame Pattern
Yellow
Tipping At
Top of
Blue
Flame
INCORRECT FLAME PATTERN AT HIGH POSITION
Figure 36 - Incorrect Front Burner Flame Pattern
If front burner flame pattern is incorrect, as shown in Figure 36
• turn fireplace off (see To Turn Off Gas to Appliance, page 23 [Thermostat-controlled
models} or page 25 [Manually-controlled models])
• see Troubleshooting, pages 28 through 31
103415
27
Page 28
CLEANING
AND
MAINTENANCE
W ARNING
Turn off fireplace and let cool before cleaning.
CAUTION
You must keep control areas, burners, and circulating air passageways of fireplace
clean. Inspect these areas of fireplace before each use. Have fireplace inspected
yearly by a qualified service person. Fireplace may need more frequent cleaning
due to excessive lint from carpeting, bedding material, etc.
ODS/PILOT AND BURNERS
• Use a vacuum cleaner or small, soft bristled brush to clean.
LOGS
• If you remove logs for cleaning, refer to Installing Logs, pages 20 and 21, to properly replace
logs.
• Replace log(s) if broken or chipped (dime-sized or larger).
TROUBLE-
SHOOTING
Note:
All troubleshooting
items are listed in order of
operation.
W ARNING
Turn off fireplace and let cool before servicing. Only a qualified service person
should service and repair fireplace.
CAUTION
Never use a wire, needle, or similar object to clean ODS/pilot. This can damage
ODS/pilot unit.
OBSERVED
PROBLEM
When ignitor button is
pressed, there is no
spark at ODS/pilot
POSSIBLE
CAUSE
1. Ignitor electrode not connected to ignitor cable
2. Piezo ignitor nut is loose
3. Ignitor cable pinched or
wet
4. Broken ignitor cable
5. Bad piezo ignitor
6. Ignitor electrode broken
7. Ignitor electrode positioned wrong
REMEDY
1. Reconnect ignitor cable
2. Tighten nut holding piezo
ignitor to base panel of log set.
Nut is located behind base
panel.
3. Free ignitor cable if pinched by
any metal or tubing. Keep
ignitor cable dry
4. Replace ignitor cable
5. Replace piezo ignitor
6. Replace ignitor
7. Replace ignitor
28
103415
Page 29
TROUBLE-
SHOOTING
Continued
OBSERVED
PROBLEM
When ignitor button is
pressed, there is spark
at ODS/pilot but no
ignition
POSSIBLE
CAUSE
1. Gas supply turned off or
manual shutoff valve
closed
2. Control knob not in PILOT
position
3. Control knob not pressed
in while in PILOT position
REMEDY
1. Turn on gas supply or open
manual shutoff valve
2. Turn control knob to PILOT
position
3. Press in control knob while in
PILOT position
ODS/pilot lights but
flame goes out when
control knob is released
4. Air in gas lines when
installed
5. ODS/pilot is clogged
6. Gas regulator setting is not
correct
1. Control knob not fully
pressed in
2. Control knob not pressed
in long enough
3. Manual shutoff valve not
fully open
4. Thermocouple connection
loose at control valve
5. Pilot flame not touching
thermocouple, which
allows thermocouple to
cool, causing pilot flame to
go out. This problem could
be caused by one or both
of the following:
A) Low gas pressure
B) Dirty or partially
clogged ODS/pilot
6. Thermocouple damaged
7. Control valve damaged
8. On thermostat models,
safety interlock system has
been triggered
4. Continue holding down control
knob. Repeat igniting operation
until air is removed
5. Clean ODS/pilot (see Cleaningand Maintenance, page 28) or
replace ODS/pilot assembly
6. Replace gas regulator
1. Press in control knob fully
2. After ODS/pilot lights, keep
control knob pressed in 30
seconds
3. Fully open manual shut-off
valve
4. Hand tighten until snug, then
tighten 1/4 turn more
5. A) Contact local propane/LP g
s company
B) Clean ODS/pilot (see
Cleaning and Maintenance,
page 28) or replace ODS/pilot
assembly
6. Replace thermocouple
7. Replace control valve
8. Wait one minute for safety
interlock system to reset.
Repeat ignition operation
103415
One or both burners do
not light after ODS/
pilot is lit
1. Burner orifice(s) clogged
2. Burner orifice(s) diameter
is too small
3. Inlet gas pressure is too
low
4. Mislocated crossover tube
1. Clean burner(s) (see Cleaningand Maintenance, page 28) or
replace burner orifice(s)
2. Replace burner orifice(s)
3. Contact local propane gas/LP
company
4. Contact qualified service person
Continued
29
Page 30
TROUBLE-
SHOOTING
Continued
OBSERVED
PROBLEM
Delayed ignition of one
or both burners
POSSIBLE
CAUSE
1. Manifold pressure is too
low
2. Burner orifice(s) clogged
3. Mislocated crossover
tube
REMEDY
1. Contact local propane gas
company
2. Clean burner(s) (see Cleaning andMaintenance, page 28) or replace
burner orifice(s)
3. Contact qualified service person
Burner backfiring during
combustion
Yellow flame in front
burner during burner
combustion
Slight smoke or odor
during initial operation
Fireplace produces a
whistling noise when
burners are lit
1. Burner orifice is clogged
or damaged
2. Damaged burner
3. Gas regulator defective
1. Not enough air
2. Gas regulator defective
1. Residues from manufacturing processes and logs
curing
1. Turning control knob to
HI position when burners
are cold
2. Air in gas line
3. Air passageways on
fireplace blocked
4. Dirty or partially clogged
burner orifice(s)
1. Clean burner (see Cleaning andMaintenance, page 28) or replace
burner orifice
2. Replace damaged burner
3. Replace gas regulator
1. Check burner(s) for dirt and
debris. If found, clean burner(s)
(see Cleaning and Maintenance,
page 28)
2. Replace gas regulator
1. Problem will stop after a few
hours of operation
1. Turn control knob to LO position
and let warm up for a minute
2. Operate burners until air is
removed from line. Have gas line
checked by local propane gas
company
3. Observe minimum installation
clearances (see page 11)
4. Clean burners (see Cleaning andMaintenance, page 28) or replace
burner orifice(s)
30
Moisture/condensation
noticed on windows
1. Not enough combustion/
ventilation air
1. Refer to Air for Combustion andVentilation requirements (page 6)
103415
Page 31
TROUBLE-
W ARNING
SHOOTING
Continued
If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
IMPORTANT:
supplies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc.,
create fumes. These fumes may mix with combustion air and create odors. These odors will
disappear over time.
OBSERVED
PROBLEM
Fireplace produces a
clicking/ticking noise
just after burners are lit
or shut off
Fireplace produces
unwanted odors
Operating fireplace where impurities in air exist may create odors. Cleaning
POSSIBLE
CAUSE
1. Metal expanding while
heating or contracting
while cooling
1. Fireplace burning vapors
from paint, hair spray,
glues, cleaners, chemicals, new carpet, etc.
(See
IMPORTANT
statement above)
2. Gas leak. See Warning
statement above
REMEDY
1. This is common with most
fireplaces. If noise is excessive,
contact qualified service person
1. Open window and ventilate
room. Stop using odor causing
products while fireplace is
running
2. Locate and correct all leaks (see
Checking Gas Connections,
page 18)
103415
Fireplace shuts off in use
(ODS operates)
Gas odor even when
control knob is in OFF
position
Gas odor during combustion
Moisture/condensation
noticed on windows
1. Not enough fresh air is
available
2. Low line pressure
3. ODS/pilot is partially
clogged
1. Gas leak. See Warning
statement above
2. Control valve defective
1. Foreign matter between
control valve and burner
2. Gas leak. See Warning
statement above
1. Not enough combustion/
ventilation air
1. Open window and/or door for
ventilation
2. Contact local propane/LP gas
company
3. Clean ODS/pilot (see Cleaningand Maintenance, page 28)
1. Locate and correct all leaks (see
Checking Gas Connections,
page 18)
2. Replace control valve
1. Take apart gas tubing and
remove foreign matter
2. Locate and correct all leaks (see
Checking Gas Connections,
page 18)
1. Refer to Air for Combustion andVentilation requirements (page 6)
31
Page 32
TECHNICAL
SERVICE
You may have further questions about installation, operation, or troubleshooting. If so,
contact DESA International’s Technical Service Department at 1-800-DESA LOG
(1-800-337-2564).
SERVICE
HINTS
REPLACEMENT
PARTS
When gas pressure is too low
• pilot will not stay lit
• burners will have delayed ignition
• fireplace will not produce specified heat
When gas quality is bad
• pilot will not stay lit
• burners will produce flames and soot
• fireplace will backfire when lit
You may feel your gas pressure is too low or gas quality is bad. If so, contact your local natural
gas supplier.
Note:
Use only original replacement parts. This will protect your warranty coverage for parts
replaced under warranty .
Parts Under Warranty
Contact authorized dealers of this product. If they can’t supply original replacement part(s), call
DESA International’s Technical Service Department at 1-800-DESA LOG (1-800-337-2564).
When calling DESA International, have ready
• your name
• your address
• model number of your fireplace
• how fireplace was malfunctioning
• type of gas used (propane or natural gas)
• purchase date
Usually, we will ask you to return the defective part to the factory.
32
Parts Not Under Warranty
Contact authorized dealers of this product. If they can’t supply original replacement part(s), call
DESA International’s Parts Department at 1-800-972-7879 for referral information.
When calling DESA International, have ready
• model number of your fireplace
• the replacement part number
103415
Page 33
SPECIFICATIONS
Btu (Low/High)20,000/28,000
Type GasPropane/LP Gas Only
IgnitionPiezo
Manifold Pressure7.9" W.C.
Inlet Gas Pressure (in. of water)
Maximum14"
Minimum11"
Shipping Weight128 lbs. Thermostat Model
122 lbs. Manual Model
WIRING
DIAGRAM
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring
errors can cause improper and dangerous operation. Verify proper operation after
servicing.
Fan Switch
(Off/On/Auto)
2
Off
110/115
V.A.C.
Figure 37 - Blower Wiring Diagram for Thermostat-Controlled Models
Black
White
Green
Auto
1
3
On
Red
Blue
Fan
Switch
(N.O.)
Blower
Motor
103415
33
Page 34
ACCESSORIES
Purchase these fireplace accessories from your local dealer. If they can not supply these accessories, call DESA International’s Sales Department at 1-800-432-2382 for information. You can
also write to the address listed on the back page of this manual.
CABINET MANTEL
GM100F Series - Walnut Finished
GM101U Series - Unfinished
GM106F Series - Oak Finished with Medium Stain
GM1007U Series - Unfinished
Shown with optional base and laminate hearth and mantel
trim accessories.
Dimensions (WxHxD): 56-3/4" x 48-3/4" x 20-5/8"
FACE MANTEL
GM400F Series - Walnut Finished
GM401U Series - Unfinished
Shown with optional slim base.
Dimensions (WxHxD): 56-3/4" x 48-3/4" x 7"
HARDWOOD HEARTH BASE
G3000F Series- Walnut Finished
G3001U Series - Unfinished
G3006F Series - Oak Finished with Medium Stain
G3006U Series - Unfinished Oak
The hearth base creates a handsome riser for the
fireplace (cannot be used with corner mantel or
face mantel).
Dimensions (WxHxD): 58" x 6-1/2" x 28-9/16"
SLIM HEARTH BASE
G3005J Series - Jade Marble Laminate
G3005S Series - Sandstone Marble Laminate
G3005B Series - Black Onyx Marble Laminate
The slim hearth base allows you to further customize your fireplace.
Dimensions (WxHxD): 41-7/8" x 5/8" x 10"
MANUAL SHUTOFF
VALVE - GA5010
For all models. Manual
shutoff valve with 1/8" NPT
tap. Fits 1/2" NPT pipe.
34
BLOWER
ACCESSORY GA3700
Manual variable control for
VSGF28PV only
103415
Page 35
ACCESSORIES
Continued
CORNER MANTEL
GM200F Series - Walnut Finished
GM201U Series - Unfinished
Shown with optional laminate mantel trim accessory.
Dimensions (WxHxD): 60-7/8" x 48-3/4" x 34-5/8"
103415
Hearth Base Trim
Mantel Trim
LAMINATE TRIM FOR HEARTH OR MANTEL
G3002J Series - Jade Marble Laminate Mantel Trim
G3003J Series - Jade Marble Laminate Hearth Base Trim
G3002S Series - Sandstone Marble Laminate Mantel Trim
G3003S Series - Sandstone Marble Laminate Hearth Base Trim
G3002B Series - Black Onyx Marble Laminate Trim
G3003B Series - Black Onyx Marble Laminate Hearth Base Trim
Mantel trim for cabinet, face, or corner mantel. Hearth base trim for hardwood hearth bases.
FIREBOX BRICK LINER - G8000 Series
Ceramic fiber firebox liner adds the look of real brick.
BRASS TRIM ACCESSORY - GA6090
Included with accessory mantels
DUPLEX OUTLET KIT - GA3555
For built-in installation
35
Page 36
ILLUSTRATED
PARTS
BREAKDOWN
Log Base Assembly
V ariable ManuallyControlled Models
This list contains replaceable parts used in your fireplace. When ordering parts,
follow the instructions listed under Replacement Parts on page 32 of this manual.
This list contains replaceable parts used in your fireplace. When ordering parts,
follow the instructions listed under Replacement Parts on page 32 of this manual.
This list contains replaceable parts used in your fireplace. When ordering parts,
follow the instructions listed under Replacement Parts on page 32 of this manual.
VSGF28PTB/CSGF28PTB
PARTS AVAILABLE — NOT SHOWN
102032-01Louvered Door Hinge2
099038-01Strain Relief Bushing1
100639-01Caution Decal1
103590-01Decal Strip1
103415
41
Page 42
ILLUSTRATED
PARTS
VSGF28PV
BREAKDOWN
Fireplace
14
17
7
6
9
4
11
11
11
15
12
16
8
16
1
2
3
16
5
16
7
18
16
13
10
42
103415
Page 43
P ARTS LIST
Fireplace
KEY
NO.PART NUMBERDESCRIPTIONQTY.
1101357-01Top Outer Casing1
2103207-01Outer Casing1
3102758-01CKRight Front Side1
4102759-01CKLeft Front Side1
5098304-01Phillips Pan Head Screw, #109
6101351-01CKTop Front1
7102455-01Top Louver Assembly2
8101353-01CKMiddle Front1
9101712-02Firebox Hood1
10101348-01Firebox Support2
11099230-01Shoulder Screw4
12101872-03Firebox Top1
13103208-01Outer Base1
14101838-03CJFirebox Wrapper1
15101514-01CJCover1
16M11084-26Hex Screw, #1055
17098304-03Phillips Pan Head Screw, #84
18101727-03Screen Assembly1
This list contains replaceable parts used in your fireplace. When ordering parts,
follow the instructions listed under Replacement Parts on page 32 of this manual.
VSGF28PV
PARTS AVAILABLE — NOT SHOWN
102032-01Louvered Door Hinge2
099038-01Strain Relief Bushing1
100639-01Caution Decal1
103590-01Decal Strip1
103415
43
Page 44
WARRANTY INFORMATION
KEEP THIS WARRANTY
Model
Serial No.
Date Purchased
Always specify model and serial numbers when communicating with the factory.
We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our
standard written warranty. We make no other warranty, expressed or implied.
LIMITED WARRANTY
VENT-FREE PROPANE GAS FIREPLACE
DESA International warrants this product to be free from defects in materials and components for three (3) years and five
(5) years on stainless steel burners from the date of first purchase, provided that the product has been properly installed,
operated and maintained in accordance with all applicable instructions. To make a claim under this warranty the Bill of
Sale or cancelled check must be presented.
This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s) required to restore
this heater to proper operating condition and an allowance for labor when provided by a DESA Authorized Service Center.
Warranty part(s) MUST be obtained through authorized dealers of this product and/or DESA International who will
provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty. The heater
MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail
or become damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation.
Travel, diagnostic cost, labor, transportation and any and all such other costs related to repairing a defective heater will
be the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE
PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES
AND LIMITS THE DURATION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO THREE (3) YEARS ON ALL COMPONENTS AND FIVE (5) YEARS ON STAINLESS STEEL BURNERS FROM THE DATE OF FIRST PURCHASE; AND
DESA INTERNATIONAL’S LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE PRODUCT
AND DESA INTERNATIONAL SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER
INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or
consequential damages, so the above limitation on implied warranties, or exclusion or limitation on damages may not apply
to you.
This warranty gives you specific legal rights, and you may also have other rights that vary from state to state.
For information about this warranty write:
2701 Industrial Drive
P.O. Box 90004
Bowling Green, KY 42102-9004
103415-01
Rev. A
02/97
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.