Desa Tech CSGF28NTC Owner's Manual

DESA INTERNATIONAL
UNVENTED (VENT-FREE)
NATURAL GAS FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
Variable Manually-
Controlled "A"
Models and
Thermostatically-
Controlled
“C” Models
with
Split Oak Logs
Shown with optional
cabinet mantel,
®
accessories.
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
— Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed
by a qualified installer, service agency, or the gas supplier.
WARNING: Improper installa­tion, adjustment, alteration, ser­vice, or maintenance can cause injury or property damage. Re­fer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be pro­vided. Refer to
bustion and Ventilation
tion on page 4 of this manual.
Air for Com-
sec-
This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state or local codes.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Save this manual for future reference.
DESA INTERNATIONAL
UNVENTED NATURAL GAS FIREPLACE
SAFETY INFORMATION
WARNINGS
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, oper­ate, or service this fireplace. Im­proper use of this fireplace can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early
signs of carbon monoxide poisoning re­semble the flu, with headaches, dizziness, or nausea. If you have these signs, the fire­place may not be working properly. Get fresh air at once! Have fireplace serviced. Some people are more affected by carbon monoxide than others. These include preg­nant women, people with heart or lung dis­ease or anemia, those under the influence of alcohol, and those at high altitudes.
Natural Gas: Natural gas is odorless. An odor-making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all Warnings. Keep this manual for reference. It is your guide to safe and proper operation of this fireplace.
WARNING: Any change to this fireplace or its controls can be dangerous.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. If you smell gas
• shut off gas supply
• do not try to light any appliance
do not touch any electrical switch; do not use any phone in your building
• immediately call your gas supplier
from a neighbor’s phone. F ollow the gas supplier’s instructions
• if you cannot reach your gas supplier,
call the fire department
3. This fireplace shall not be installed in a bedroom or bathroom.
4. Never install the fireplace
• in a recreational vehicle
• where curtains, furniture, clothing, or
other flammable objects are less than 42 inches from the front, top, or sides of the fireplace
• in high traffic areas
• in windy or drafty areas
5. Do not use this fireplace as a wood­burning fireplace. Use only the logs provided with the fireplace.
6. Do not add extra logs or ornaments such as pine cones, vermiculite, or rock wool. Using these added items can cause sooting. Do not add lava rock around base. Rock and debris could fall into the control area of fireplace.
7. Y ou must operate this fireplace with the fireplace screen and hood in place. Make sure fireplace screen and hood are in place before running fireplace.
8. This fireplace is designed to be smoke­less. If logs ever appear to smoke, turn off fireplace and call a qualified ser­vice person. eration, slight smoking could occur due to log curing and fireplace burning manufacturing residues.
9. To prevent the creation of soot, follow the instructions in Cleaning and Main- tenance, page 21.
10. Do not allow fans to blow directly into the fireplace. Avoid any drafts that al­ter burner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
Note:
During initial op-
11. Before using furniture polish, wax, car­pet cleaner, or similar products, turn heater off. If heated, the vapors from these products may create a white pow­der residue within burner box or on adjacent walls or furniture.
12. Do not use a blower insert, heat ex­changer insert or other accessory not approved for use with this heater.
13. This fireplace needs fresh air ventila­tion to run properly . This fireplace has an oxygen depletion sensor (ODS) pi­lot light safety system. The ODS shuts down the fireplace if not enough fresh air is available. See Air for Combus- tion and Ventilation, pages 4 through
6. If fireplace keeps shutting off, see Troubleshooting, pages 22 through 24.
14. Do not run fireplace
• where flammable liquids or vapors
are used or stored
• under dusty conditions
15. Do not use this fireplace to cook food or burn paper or other objects.
16. Never place any objects in the fireplace or on logs.
17. Fireplace front and screen becomes very hot when running fireplace. Keep children and adults away from hot sur­faces to avoid burns or clothing igni­tion. Fireplace will remain hot for a time after shutdown. Allow surf aces to cool before touching.
18. Carefully supervise young children when they are in the room with fireplace.
19. Do not use fireplace if any part has been exposed to or under water . Immediately call a qualified service technician to inspect the fireplace and to replace any part of the control system and any gas control which has been under water.
20. Do not operate fireplace if any log is broken. Do not operate fireplace if a log is chipped (dime-sized or larger).
21. Turn fireplace off and let cool before servicing. Only a qualified service per­son should service and repair fireplace.
22. Operating fireplace above elevations of 4,500 feet could cause pilot outage.
2
104409
OWNER’S MANUAL
PRODUCT IDENTIFICATION
Middle Log
Front Burner
Front Log
Base Assembly
Figure 1 - Log Base Assembly, Split Oak Set
Top Louver Assembly
Fireplace Hood
Firebox Support
Crossover Log
Rear Log
Top Outer Casing
Rear Burner
LOCAL CODES
Install and use fireplace with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code ANS Z223.1, also known as NFPA 54*.
*Available from: American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
UNPACKING
WARNING: Do not remove the metal data plates attached to the heater base assembly. The data plates contain important warranty information.
1. With utility knife, cut the carton all the way around above the staples on the bottom tray. Lift the carton off the heater. Remove packing. hood is located in the packing on the right hand side of the heater front. Lift the heater off the bottom tray.
2. Locate two screws above top corners of the fireplace screen. Remove and discard these screws. Lift fireplace screen up and pull out to remove.
3. Remove protective packaging applied to logs, log base assembly, and fireplace.
4. Remove fireplace hood from carton insert.
5. Check all items for any shipping dam­age. If damaged, promptly inform dealer where you bought fireplace.
Note:
The
Screen Assembly
Figure 2 - Fireplace
104409
Blower Assembly (Models VSGF28NTC and CSG28NTC, Optional for Model VSGF28NVA)
Bottom Louver Assembly
3
DESA INTERNATIONAL
UNVENTED NATURAL GAS FIREPLACE
PRODUCT FEATURES
OPERATION
This vent-free fireplace is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by both realistic flames and glow­ing embers. When used without the blower, the fireplace requires no electricity making it ideal for emergency backup heat.
SAFETY DEVICE
This fireplace has a pilot with an Oxygen Depletion Sensor Shutoff System (ODS). The ODS/pilot is a required feature for vent­free room heaters. The ODS system shuts off the fireplace if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This fireplace has a piezo ignitor. This sys­tem requires no matches, batteries, or other sources to light fireplace.
BLOWER ASSEMBLY
(VSGF28NTC/CSGF28NTC)
This fireplace has a blower assembly. The blower operates thermostatically. The blower circulates heated air from the fire­place into the room. Use of blower is op­tional. Optional blower accessories are avail­able for model VSGF28NVA.
THERMOSTAT CONTROL MODELS
(VSGF28NTC/CSGF28NTC)
These fireplaces have a thermostat sensing bulb and a control valve. The thermostat con­trols the heat output and flame height. This maintains a consistent room temperature. Even the lowest setting provides realistic flames and glowing embers from two burners. Selecting higher comfort settings allows fireplace to run longer, producing greater heat output. At lower comfort settings, the fireplace will run less. This results in increased heating comfort. This can also result in lower gas bills.
VARIABLE MANUAL CONTROL (VSGF28NVA)
These fireplaces have a variable manual control valve which allows the user to choose the heat setting that best suits his needs. Any setting between low and high may be se­lected by simply turning the control knob.
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ven­tilation air. Read the following in­structions to insure proper fresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy effi­cient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper com­bustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide ad­equate fresh air for these appliances. This will insure proper venting of vented fuel­burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code. NFPA 54/ANS Z223.1, Sec­tion 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on pages 4 through 6 will
help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and win­dows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is de­fined as construction where:
a. walls and ceilings exposed to the
outside atmosphere have a con­tinuous water vapor retarder with a rating of one perm (6 x 10 per pa-sec-m2) or less with open­ings gasketed or sealed
b. weather stripping has been
added on openable windows and doors
c. caulking or sealants are applied
to areas such as joints around window and door frames, be­tween sole plates and floors, be­tween wall-ceiling joints, be­tween wall panels, at penetra­tions for plumbing, electrical, and gas lines, and at other openings.
If your home meets all of the three criteria above, you must provide ad­ditional fresh air. See
From Outdoors
If your home does not meet all of the three criteria above, proceed to
mining Fresh-Air Flow for Fireplace Location
and
, page 6
on page 5.
Ventilation Air
.
and
Deter-
-11
kg
Confined Space and Unconfined Space
The National Fuel Gas Code (ANS Z223.1, 1992 Section 5.3) defines a confined space
as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are in­stalled*, through openings not furnished with doors, are considered a part of the unconfined space.
This heater shall not be installed in a con­fined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air.
* Adjoining rooms are communicating only if there are doorless passageways or ventila­tion grills between them.
4
104409
OWNER’S MANUAL
AIR FOR COMBUSTION AND VENTILATION
Continued
DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space. Space: Includes the room in which you will install fireplace plus any adjoining rooms with doorless passageways or ventilation grills
between the rooms.
1. Determine the volume of the space (length x width x height). Length x Width x Height = _________________cu. ft. (volume of space)
Example:
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.
_________________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)
Example:
3. Add the Btu/Hr of all fuel burning appliances in the space. Vent-free fireplace ___________________ Btu/Hr Gas water heater* ___________________ Btu/Hr Gas furnace ___________________ Btu/Hr Vented gas heater ___________________ Btu/Hr Gas fireplace logs ___________________ Btu/Hr Other gas appliances* + ___________________ Btu/Hr Total = ___________________ Btu/Hr * Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
_____________ Btu/Hr (maximum the space can support) _____________ Btu/Hr (actual amount of Btu/Hr used)
Example:
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework work sheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-
ing room or add ventilation grills between rooms. See Ventilation Air from Inside Building, page 6.
B. Vent room directly to the outdoors. See Ventilation Air from Outdoors, page 6. C. Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling height) = 3168 cu. ft. (volume of space)
3168 cu. ft. (volume of space) ÷ 50 cu. ft. = 63.3 or 63,300 (maximum Btu/Hr the space can support)
Example:
Gas water heater Vent-free fireplace + Total =
63,300 Btu/Hr (maximum the space can support)
68,000 Btu/Hr (actual amount of Btu/Hr used)
40,000 28,000 68,000
Btu/Hr Btu/Hr Btu/Hr
WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the
104409
National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3
5
or applicable local codes.
Continued
DESA INTERNATIONAL
UNVENTED NATURAL GAS FIREPLACE
AIR FOR COMBUSTION AND VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro­vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3). You can also remove door into adjoining room (see op­tion 3, Figure 3). Follow the National Fuel
Gas Code NFPA 54/ANS Z223.1, Section
5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
WARNING: Rework work­sheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two per­manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces.
IMPORTANT:
inlet or outlet air into attic if attic has a thermo­stat-controlled power vent. Heated air enter­ing the attic will activate the power vent.
Do not provide openings for
12"
Ventilation
Grills
Into Adjoining
Room,
Option 1
Figure 3 - Ventilation Air from Inside Building
Or
Remove Door into Adjoining
Room, Option
3
12"
Outlet Air
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilated Attic
Outlet Air
Inlet Air
Inlet Air
Figure 4 - Ventilation Air from Outdoors
Ventilated
Crawl Space
To Attic
To
Crawl
Space
6
104409
OWNER’S MANUAL
INSTALLATION
NOTICE: A qualified service per­son must install fireplace. Follow all local codes.
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your pri­mary heating system. Do not in­stall this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circu­late the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: Never install the
fireplace
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture, clothing, or other flammable objects are less than 42 inches from the front, top, or sides of the fireplace
• in high traffic areas
• in windy or drafty areas
WARNING: Models VSGF28NTC / CSGF28NTC have a three-prong, grounded electrical plug. This plug helps protect you against electrical shock. Only connect plug to a properly grounded, three-prong receptacle. Do not cut or remove the grounding prong from this plug.
CAUTION: This fireplace cre­ates warm air currents. These cur­rents move heat to wall surfaces next to fireplace. Installing fire­place next to vinyl or cloth wall coverings or operating fireplace where impurities (such as to­bacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls.
Note:
Your fireplace is designed to be used
in zero clearance installations. Wall or fram­ing material can be placed directly against any exterior surface on the rear, sides, or top of your fireplace, except where standoff spacers are integrally attached. If standoff spacers are attached to your fireplace, these spacers can be placed directly against wall or framing materials.
Use the dimensions shown for rough open­ings to create the easiest installation (see Built-In Fireplace Installation, page 13).
IMPORTANT:
ture to the air. Although this is beneficial, installing fireplace in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Com- bustion and Ventilation, pages 4 through 6.
IMPORTANT:
level. If fireplace is not level, log set will not work properly.
Vent-free heaters add mois-
Make sure the fireplace is
CHECK GAS TYPE
Use only natural gas. If your gas supply is not natural gas, do not install fireplace. Call dealer where you bought fireplace for proper type fireplace.
ELECTRICAL HOOKUP
(Models VSGF28NTC/ CSGF28NTC)
This fireplace has a blower assembly with an electrical cord. The electrical cord is five feet in length. You must locate fireplace within reach of a 120 volt grounded electri­cal outlet. If not, you must install an electri­cal outlet within reach of fireplace power cord. This same information applies if in­stalling optional blower accessories to Model VSGF28NVA.
INSTALLING HOOD
Install hood to rail already installed in fire­place as shown in Figure 5. Use 3 Phillips screws provided.
Rail
Hood
Screw
Figure 5 - Installing Hood
104409
Continued
7
DESA INTERNATIONAL
UNVENTED NATURAL GAS FIREPLACE
INSTALLATION
Continued
ASSEMBLING AND ATTACH­ING OPTIONAL BRASS TRIM (Included with Mantel Accessory)
IMPORTANT:
box in a wall, do not attach brass trim at this time. See page 13.
Note:
The instructions below show assem-
bling and attaching brass trim to fireplace.
1. Remove packaging from three pieces of brass trim.
2. Locate four brass screws, two adjust­ing plates with set screws, and two shims in the hardware packet.
3. Align shim under adjusting plate as shown in Figure 6.
4. Slide one end of adjusting plate/shim in slot on mitered edge of top brass trim (see Figure 6).
5. Slide other end of adjusting plate/shim in slot on mitered edge of side brass trim (see Figure 6).
6. While firmly holding edges of brass trim together, tighten both set screws on the adjusting plate with slotted screwdriver.
7. Repeat steps 1 through 6 for other side.
8. Tighten trim hanging screws (#10 x
6.25 shoulder) into holes in cabinets. Place the assembled trim onto fireplace cabinet. Align hanging notches on trim with hanging screws on side of fire­place (see Figure 7). Push trim firmly into place, sliding hanging notches over hanging screws.
Side Brass Trim
Slot
Figure 6 - Assembling Brass Trim
If you are recessing the fire-
Set Screws
Adjusting Plate
Shim
Mitered Edge
Top Brass Trim
Slot
Trim Hanging Screws
Assembled Brass Trim
Figure 7 - Attaching Brass Trim to Fireplace
Hanging Notches on Trim
INSTALLING OPTIONAL BLOWER ACCESSORY (FOR MODEL VSGF28NVA)
The following instructions are for optional blower accessories GA3700 and GA3700T. If you do not have this accessory and wish to purchase one, see Accessories on pages 26 and 27 of this manual.
Installing Optional GA3700 Blower Accessory
1. Remove screws that attach log base as­sembly to fireplace. Carefully lift up log base assembly and remove from fire­place, taking care to pull flexible gas line through the access holes (see Figure 8)
CAUTION: Do not pick up log base assembly by burners. This could damage burners. Only handle base by grates.
2.
Place the blower against lower rear wall of firebox outer wrapper with the ex­haust port directed upward. Align the holes in top mounting tabs of blower with holes in wall of wrapper (see Fig­ure 9). Using 2 screws provided, mount blower and tighten screws securely.
3. Be certain that all wire terminals are securely attached to terminals on blower motor and that the screw retain­ing the green ground wire is tight.
4. Place control knob provided on plastic control shaft of speed control.
5. Mount the speed control on the front leg of the left floor support bracket us­ing 2 screws provided (see Figure 10).
Flexible Gas Line
Screws
Log Base
Figure 8 - Removing Log Base from Fireplace
Lower Rear Wall of Firebox
Exhaust Post
Screws
Figure 9 - Mounting Blower to Firebox
Blower
.
Left Floor Support Bracket
Screws
Speed Control
Control Knob
Figure 10 - Attaching Speed Control to Firebox
Control Shaft
8
104409
OWNER’S MANUAL
INSTALLATION
Continued
6. Plug in blower power cord.
a. If your f ireplace system is installed
as a freestanding unit with an ac­cessory mantel, determine whether
the power cord will exit the left side or the right side of the firebox. In­stall 1 plastic bushing provided into the 1.5" hole in the floor support bracket on the exit side (see Figure
11). Install the second plastic bush­ing provided into the 1.5" hole in the outer casing through which the power cord will exit. Route power cord through both plastic bushings and plug the power cord into a prop­erly grounded 3-prong wall recep­tacle near the firebox.
b.If your fireplace system installa-
tion is recessed, plug the power cord into a properly installed duplex out­let. (If an outlet is not available, the Vanguard accessory model GA3555 Outlet kit with/ cover can be installed in your fireplace which will supply a convenient 3-prong grounded elec­trical outlet for your blower. Refer to the installation manual provided with the model GA3555 accessory for instructions on wiring the duplex outlet.)
7. Check to make sure that the power cord is completely clear of the blower wheel and that there are no other foreign ob­jects in blower wheel. Turn blower on and check for operation. Turn blower off by rotating knob fully counterclock­wise before continuing.
9. Replace log base assembly in fireplace. Feed flexible gas supply line into fire­place base area while replacing log base assembly. Make sure the entir e flexible gas line is in fireplace base area.
Note:
If firebrick is installed, make sure the back of the firebox bottom slides under the rear panel of the firebrick. (lift the firebrick up if necessary.)
CAUTION: Do not pick up log base assembly by burners. This could damage burners. Only handle base by grates.
10.
Reattach log base assembly to fireplace with screws removed in step 1 on page 8.
Note:
Discard the remaining hardware items.
WARNING: Failure to position the parts in accordance with sup­plied diagrams or failure to use only parts specifically approved with this heater may result in dam­age or personal injury.
Variable
Blower
Motor
Fan Switch
On
Black
Off
WhiteWhite
Black Black
Black
110/115 V.A.C.
Green
Wiring Diagram
WARNING
WARNING ICON G 001
Never attempt to service heater while it is plugged in, operating, or hot. Burns and electrical shock could result. Only a qualified service person should service or repair heater.
If any of the original wire as supplied with the appliance must be replaced, it must be replaced with 105°C wire or it’s equivalent.
Variable
Fan Switch
Off
On
110/115
V.A.C.
120 Vac. 60 Hz. . 78 Amps DESA International, Bowling Green, KY
Black
Green
Black
Black
Black WhiteWhite
Blower
Motor
101584-05
Figure 12 - Location of Wiring Diagram Decal 3" from Blower
WARNING: Never touch the
blower wheel while in operation.
8.
Peel off the backing paper and stick the supplied wiring diagram decal on the fire­box bottom approximately 3" to the right of the blower speed control (Figure 12)
104409
Right Floor Support Bracket
Figure 11 - Installing Plastic Bushing for
.
Power Cord
9
Plastic Bushing
Continued
DESA INTERNATIONAL
AUTO
OFF
ON
3 2 1
UNVENTED NATURAL GAS FIREPLACE
INSTALLATION
Continued
Installing Optional GA3700T Blower Accessory
1. Remove screws that attach log base as­sembly to fireplace (do not discard). Carefully lift up log base assembly and remove from fireplace, taking care to pull flexible gas line through the ac­cess holes (see Figure 13).
CAUTION: Do not pick up log base assembly by burners. This could damage burners. Only handle base by grates.
2. Place the blower against lower rear wall of firebox outer wrapper with the ex­haust port directed upward. Align the holes in top mounting tabs of blower with holes in wall of wrapper (see Fig­ure 14). Using two #8 screws provided, mount blower and tighten screws firm ly.
3. Route terminals end of power cord through large hole near top of left floor support bracket. Make sure to pass the cord from the outside (left side) towards the center of firebox (see Figure 15).
4. Using two #6 screws provided attach power cord mounting plate to the out­side face of left floor support bracket. Drive screws from inside (right side) of floor support bracket. Attach the plate so that the power cord is directed towards rear of firebox (see Figure 15). Tighten screws firmly.
5. Remove the three screws (do not dis­card) and cover plate from center of firebox wrapper rear wall. Discard this cover plate.
6. Mount the supplied thermostatic switch and cover assembly into firebox wrap­per wall. Do this by feeding terminal ends of wire harness into the hole. Al­low wires to fall to bottom of firebox cavity (see Figure 16).
7. Using three screws from step 5, attach switch and cover assembly to firebox wrapper rear wall. Tighten screws firmly (see Figure 16).
8. Mount selector switch to front flange of left floor support bracket. Align graphics on switch upright and push firmly to snap switch into rectangular hole. Push the selector switch to the off (middle) position (see Figure 15).
9.
Install three plastic wire clips provided into floor support bracket (see Figure 15). Secure by pushing clips firmly into holes.
WARNING: Failure to connect all wires properly as indicated may cause electrical short circuit or personal injury. A qualified electrician should check that all connections are made properly.
10. Attach green ground wire ring termi­nal to floor support bracket using #10 sheet metal grounding screw provided (see Figure 15). Tighten screw firmly.
11. Attach all five remaining wiring termi­nals to the appropriate switch or motor terminal. Carefully note the correct color coding (see Figures 17 and 19, page 11). Push female wire terminals fully onto male terminal.
12. Secure wires into the appropriate plas­tic wire clips (see Figure 17, page 11).
Flexible Gas Line
Screws
Log Base
Figure 13 - Removing Log Base from Fireplace
Lower Rear Wall of Firebox Outer Wrapper
Exhaust Port
#8 Screws
Figure 14 - Mounting Blower to Firebox
Selector Switch
Figure 15 - Installing Power Cord, Mounting Plate, and Selector switch
Figure 16 - Installing Switch and Cover Assembly
Blower
Floor Support Bracket
#6 Screws
Switch and Cover Assembly
#10 Screw
Wire Clips
10
104409
OWNER’S MANUAL
INSTALLATION
Continued
13. Plug in blower power cord.
If your fireplace system is installed as a freestanding unit with an acces­sory mantel, install one plastic bush-
ing (provided) into the 1.5" hole in the lower left side of the outer casing (see Figure 18). Route power cord through plastic bushing. Plug the power cord into a properly grounded three-prong wall receptacle near the firebox.
If your fireplace system installation is recessed, install one plastic bushing
provided into the 1.5" hole near the middle of the left floor support bracket (see Figure 18). Route power cord through plastic bushing. Plug the power cord into a properly installed duplex outlet. (If an outlet is not available, the accessory model GA3555 Outlet Kit with cover can be installed in your fire­place. This will supply a convenient three-prong grounded electrical outlet for your blower. Refer to the installa­tion manual provided with the model GA3555 accessory for instructions on wiring the duplex outlet.)
14.
Check to make sure that the power cord and wires are completely clear of the blower wheel and that there are no other foreign objects in blower wheel. Turn blower on by pushing the selector switch to the on position and check for opera­tion. Turn b lower of f before continuing.
16. Replace log base assembly in fireplace. Feed flexible gas supply line into fire­place base area while replacing log base assembly. Mak e sure the entire flexible gas line is in fireplace base area.
Note:
If firebrick is installed, make sure the back of the firebox bottom slides under the rear panel of the firebrick (lift the firebrick up if necessary.
IMPORTANT: Do not pick up log base assembly by burners. This could damage burners. Only handle base by grates.
17.
Reattach log base assembly to fireplace with screws removed in step 1, page 10.
Blue Wire
AUTO
3
OFF
2
ON
1
Red Wire
Figure 17 - Wire Attachment
Black Wire
WARNING: Failure to posi­tion the parts in accordance with supplied diagrams or failure to use only parts specifically ap­proved with this heater may re­sult in damage or personal injury.
To Switch and Cover Assembly
Blue Wire
White Wire
NOTE:
Green Wire
To prevent short circuit, white wire MUST be connected to motor.
WARNING: Never touch the
blower wheel while in operation.
15. Peel off the backing paper and stick the supplied wiring diagram decal on the firebox bottom approximately 12" in front of blower.
Note:
If any of the original wire as supplied with the appliance must be replaced, it must be replaced with 105˚C wire or it's equivalent.
104409
Bushing Location for Freestanding Installation
Bushing Location for Recessed Installation
Figure 18 - Installing Bushings
11
Fan Switch
110/115
V.A.C.
(Off/On/Auto)
Off
Black
White
Green
Auto
1
2
3
Red
On
Blue
Blue
Figure 19 - Wiring Diagram
Fan
Switch
(N.O.)
Blower
Motor
Continued
Loading...
+ 25 hidden pages