Desa Tech CF26PR, NMCF26PT Owner's Manual

For more information, visit www.desatech.com
For more information, visit www.desatech.com
CF26PR
19,000 to 26,000 Btu/Hr
Remote Control Ready
UNVENTED (VENT-FREE) GAS BAY FRONT FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
Patent Pending
Fireplace Shown
A U T O
O F F
O N
With Optional
Bay Front Mantel
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result caus­ing property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
WARNING: Improper installa­tion, adjustment, alteration, ser­vice, or maintenance can cause injury or property damage. Re­fer to this manual for correct installation and operational pro­cedures. For assistance or ad­ditional information consult a qualified installer, service agency, or the gas supplier.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a
qualified installer, service agency, or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses air (oxy­gen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to
Combustion and Ventilation
Air for
sec-
tion on page 4 of this manual.
This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where not prohibited by local codes.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Save this manual for future reference.
Save this manual for future reference.
TABLE OF CONTENTS SAFETY INFORMATION
2
TABLE OF CONTENTS
SAFETY INFORMATION ............................................................ 2
PRODUCT IDENTIFICATION ..................................................... 3
LOCAL CODES........................................................................... 3
UNPACKING............................................................................... 4
PRODUCT FEATURES .............................................................. 4
REMOTE CONTROL ACCESSORIES ....................................... 4
AIR FOR COMBUSTION AND VENTILATION ........................... 4
INSTALLATION ........................................................................... 6
OPERATING FIREPLACE ........................................................ 16
INSPECTING BURNERS.......................................................... 19
CLEANING AND MAINTENANCE ............................................ 19
SAFETY INFORMATION
WARNINGS
WARNING: This product contains and/or generates chemicals known to the State of California to cause cancer or birth defects, or other reproductive harm.
IMPORTANT: Read this owners manual carefully and completely before trying to assemble, operate, or ser­vice this heater. Improper use of this heater can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
DANGER: Carbon monoxide poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of carbon monoxide
poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Propane/LP Gas: Propane/LP gas is odorless. An odor-making
agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
WARNING: Any change to this heater or its controls can be dangerous.
SPECIFICATIONS .................................................................... 20
WIRING DIAGRAM ................................................................... 20
TROUBLESHOOTING .............................................................. 21
ILLUSTRATED PARTS BREAKDOWN AND PARTS LIST ....... 24
REPLACEMENT PARTS .......................................................... 28
PARTS CENTRALS .................................................................. 28
TECHNICAL SERVICE ............................................................. 28
SERVICE HINTS....................................................................... 28
OWNER’S REGISTRATION FORM.......................................... 29
ACCESSORIES ........................................................................ 31
WARRANTY INFORMATION...................................... Back Cover
WARNING: Do not use a blower insert, heat exchanger insert, or other accessory not approved for use with this heater.
WARNING: Do not allow fans to blow directly into the fireplace. Avoid any drafts that alter burner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
Do not place clothing or other flammable material on or near the appliance. Never place any objects in the fireplace or on logs.
Fireplace front and screen become very hot when running fireplace. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow surfaces to cool before touching.
Carefully supervise young children when they are in the room with fireplace. When using the hand-held remote accessory, keep selector switch in the OFF position to prevent children from turning on burners with remote.
You must operate this fireplace with a fireplace screen in place. Make sure fireplace screen is closed before running heater.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
105442-01E
SAFETY INFORMATION
Continued
SAFETY INFORMATION
PRODUCT IDENTIFICATION
LOCAL CODES
3
3
Keep the appliance area clear and free from combus­tible materials, gasoline, and other flammable vapors and liquids.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors.
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use any phone in
your building
• immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions
• if you cannot reach your gas supplier , call the fire department
4. This fireplace shall not be installed in a bedroom or bathroom.
5. Do not use this fireplace as a wood-burning fireplace. Use only the logs provided with the fireplace.
6. Do not add extra logs or ornaments such as pine cones, ver­miculite, or rock wool. Using these added items can cause soot­ing. Do not add lava rock around base. Rock and debris could fall into the control area of fireplace.
7. This fireplace is designed to be smokeless. If logs ever appear to smoke, turn off fireplace and call a qualified service person.
Note:
During initial operation, slight smoking could occur due
to log curing and fireplace burning manufacturing residues.
8. To prevent the creation of soot, follow the instructions in Clean- ing and Maintenance, pages 19 and 20.
9. Before using furniture polish, wax, carpet cleaner, or similar products, turn heater off. If heated, the vapors from these prod­ucts may create a white powder residue within burner box or on adjacent walls or furniture.
10. This fireplace needs fresh air ventilation to run properly. This fireplace has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the fireplace if not enough fresh air is available. See Air for Combustion and Ventilation, pages 4 through 6. If fireplace keeps shutting off, see Trouble- shooting, pages 21 through 23.
11. Do not run fireplace
• where flammable liquids or vapors are used or stored.
• under dusty conditions.
12. Do not use this fireplace to cook food or to burn paper or other solid fuels.
13. Do not use fireplace if any part has been under water . Immedi­ately call a qualified service technician to inspect the room fireplace and to replace any part of the control system and any gas control which has been under water.
14. Turn off and unplug fireplace and let cool before servicing. Only a qualified service person should service and repair fireplace.
15. Operating fireplace above elevations of 4,500 feet could cause pilot outage.
16. Do not operate fireplace if any log is broken. Do not operate fireplace if a log is chipped (dime-sized or larger).
17. T o prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. capacity.
18. Provide adequate clearances around air openings.
PRODUCT IDENTIFICATION
Screen
Fireplace Cabinet
Brick Liner
Logs
A U T O
O F F
O N
Heater Controls (Inside Door)
Figure 1 - Vent-Free Propane/LP Gas Compact Fireplace
LOCAL CODES
Install and use fireplace with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code,
ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
105442-01E
For more information, visit www.desatech.com
For more information, visit www.desatech.com
UNPACKING PRODUCT FEATURES
4
REMOTE CONTROL ACCESSORIES AIR FOR COMBUSTION AND VENTILATION
Providing Adequate Ventilation
UNPACKING
1. Remove and fireplace from carton.
2. Remove all protective packaging applied to fireplace for shipment.
3. Make sure your fireplace includes one hardware packet.
4. Check fireplace for any shipping damage. If fireplace is damaged, promptly inform dealer where you bought fireplace.
PRODUCT FEATURES
SAFETY PILOT
This fireplace has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent­free room fireplaces. The ODS/pilot shuts off the fireplace if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This fireplace has a piezo ignitor. This system requires no matches, batteries, or other sources to light fireplace.
REMOTE CONTROL ACCESSORIES
There are two optional remote controls that can be purchased separately for this log heater:
• hand-held ON/OFF remote
• hand-held thermostat remote
See Accessories, page 31.
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall not be installed in a confined space or unusually tight construction un­less provisions are provided for adequate combus­tion and ventilation air. Read the following instruc­tions to insure proper fresh air for this and other fuel­burning appliances in your home.
Today’s homes are built more energy efficient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54 Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on pages 4 through 6 will help you classify your
space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings e xposed to the outside atmosphere
have a continuous water vapor retarder with a rating of one perm (6 x 10 openings gasketed or sealed
b. weather stripping has been added on openable win-
dows and doors
For more information, visit www.desatech.com
For more information, visit www.desatech.com
-11
kg per pa-sec-m2) or less with
and
and
105442-01E
AIR FOR COMBUSTION AND VENTILATION
Continued
AIR FOR COMBUSTION AND VENTILATION
Providing Adequate Ventilation (Cont.)
Determining Fresh-Air Flow For Fireplace Location
5
5
c. caulking or sealants are applied to areas such as
joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations f or plumbing, electrical, and gas lines, and at other openings.
If your home meets all of the three criteria above, you must provide additional fresh air. See
From Outdoors
, page 6
.
Ventilation Air
If your home does not meet all of the three criteria above, proceed to
Location,
Determining Fresh-Air Flow For Fireplace
below
.
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfining space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space. Space: Includes the room in which you will install heater plus any adjoining
rooms with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height). Length x Width x Height =___________ cu. ft. (volume of space)
Example:
height) = 2560 cu. ft. (volume of space) If additional ventilation to adjoining room is supplied with grills or open-
ings, add the volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maximum Btu/Hr the space
Example:
Btu/Hr the space can support)
Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling
can support)
2560 cu. ft. (volume of space) x 20 = 51,200 (maximum
3. Add the Btu/Hr of all fuel burning appliances in the space. Vent-free heater _____________ Btu/Hr Gas water heater* _____________ Btu/Hr Gas furnace _____________ Btu/Hr Vented gas heater _____________ Btu/Hr Gas fireplace logs _____________ Btu/Hr Other gas appliances* + _____________ Btu/Hr Total = _____________ Btu/Hr
* Do not include direct-vent gas appliances. Direct-vent draws com­bustion air from the outdoors and vents to the outdoors.
Example:
Gas water heater _____________ Btu/Hr Vent-free heater + _____________ Btu/Hr Total = _____________ Btu/Hr
4. Compare the maximum Btu/Hr the space can support with the actual
3
amount of Btu/Hr used.
__________________ Btu/Hr (maximum the space can support) __________________ Btu/Hr (actual amount of Btu/Hr used)
Example:
The space in the example above is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the
extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See V entilation Air Fr om Inside Building, page 6.
B. Vent room directly to the outdoors. See Ventilation Air From Out-
doors, page 6.
C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined. If the actual Btu/Hr used is less than the maximum Btu/Hr the space can
support, the space is an unconfined space. You will need no additional fresh air ventilation.
51,200 Btu/Hr (maximum the space can support) 56,000 Btu/Hr (actual amount of Btu/Hr used)
30,000 26,000 56,000
WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon­fined space or if the building is of unusually tight construction, provide adequate combustion and ven­tilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec­tion 5.3
or applicable local codes.
105442-01E
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Outlet Air
Ventilated Attic
Outlet Air
Inlet Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
AIR FOR COMBUSTION AND VENTILATION
6
Ventilation Air
INSTALLATION
Check Gas Type
AIR FOR COMBUSTION AND VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel
Gas Code ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code ANSI Z223.1/ NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.
IMPORTANT:
attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.
Do not provide openings for inlet or outlet air into
12"
Figure 3 - Ventilation Air from Outdoors Shown with Optional Mantel
INSTALLATION
NOTICE: This heater is intended for use as supple­mental heat. Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a central heating system, you may run systems circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
Ventilation Grills
Ventilation
Grills
into Adjoining
Room,
Option 1
Figure 2 - Ventilation Air from Inside Building Shown with Optional Mantel
Or
Remove
Door into
Adjoining
Room,
Option 3
Into Adjoining Room,
Option 2
12"
For more information, visit www.desatech.com
For more information, visit www.desatech.com
WARNING: A qualified service person must in­stall fireplace. Follow all local codes.
Note:
Your Comfort Glow fireplace is designed to be used in zero clearance installations. Wall or framing material can be placed directly against any exterior surface of your fireplace, except where standoff spacers are integrally attached. If standoff spacers are attached to your fireplace, these spacers can be placed directly against wall or framing materials.
Use the dimensions shown for rough openings to create the easiest installation (see Built-In Fireplace Installation, pages 7 and 8).
CHECK GAS TYPE
Use only propane/LP gas. If your gas supply is not propane/LP, do not install fireplace. Call dealer where you bought fireplace for proper type fireplace.
105442-01E
INSTALLATION
Continued
INSTALLATION
Locating Fireplace
Built-In Fireplace Installation
7
7
LOCATING FIREPLACE
WARNING: Maintain the minimum clearances shown in Figure 4. If you can, provide greater clear­ances from floor, ceiling, and joining wall.
You can recess firebox into the wall. You can also position fireplace in the optional cabinet mantels. cabinet mantels specified in this manual. Purchase the optional mantel from your dealer (see Accessories, page 31).
WARNING: Never install the fireplace
in a bedroom or a bathroom
in a recreational vehicle
where curtains, furniture, clothing, or other flam-
mable objects are less than 42 inches from the front, top, or sides of the fireplace
as a fireplace insert
in high traffic areas
in windy or drafty areas
CAUTION: This fireplace creates warm air cur­rents. These currents move heat to wall surfaces next to fireplace. Installing fireplace next to vinyl or cloth wall coverings or operating fireplace where impuri­ties (such as, but not limited to, tobacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
I
MPORTANT:
Vent-free fireplaces add moisture to the air. Although this is beneficial, installing fireplace in rooms without enough venti­lation air may cause mildew to form from too much moisture. See Air for Combustion and Ventilation, pages 4 through 6.
CAUTION: If you install the fireplace in a home
garage
fireplace pilot and burner must be at least 18 inches above floor.
locate fireplace where moving vehicle will not hit it.
For convenience and efficiency, install fireplace
• where there is easy access for operation, inspection, and service.
• in coldest part of room. An optional blower kit is available from your dealer. See Accesso-
ries, page 31. If planning to use blower, locate fireplace near an electrical outlet.
IMPORTANT:
Only use optional
Minimum Clearances For Side Combustible Material, Side Wall, and Ceiling
A. Clearances from the side of the fireplace cabinet to any com-
bustible material and wall should follow diagram in Figure 4.
Example:
The face of a mantel, bookshelf, etc. is made of combustible material and protrudes 3 1/2" from the wall. This combustible material must be 4" from the side of the fireplace opening (see Figure 4).
B. Clearances from the top of the fireplace opening to the ceiling
should not be less than 42 inches.
Example
*
*Minimum 16 inches from Side Wall
Figure 4 - Minimum Clearance for Combustible to Wall
BUILT-IN FIREPLACE INSTALLATION
Built-in installation of this fireplace involves installing fireplace into a framed-in enclosure. This makes the front of fireplace flush with wall. Follow the instructions below to install the fireplace in this manner. If installing a built-in mantel above the fireplace, you must follow the clearances shown in Figure 8, page 9.
Note:
If desired, purchase a four-sided brass trim kit for built-in
installations. See Accessories, page 31.
Actual Framing
7
Height 26" 26
Front Width 26
Depth 9
Bottom 3/4" 3/4"
3
/4" 26 7/8"
1
/2" 10 1/2"
1. Frame in rough opening. Use dimensions shown in Figure 5, page 8, for the rough opening.
If installing in a corner, use dimensions shown in Figure 6, page 8, for the rough opening. The height is 26 1/8" which is the same as the wall opening above.
/8"
105442-01E
For more information, visit www.desatech.com
For more information, visit www.desatech.com
INSTALLATION
8
Built-In Fireplace Installation (Cont.)
INSTALLATION
Continued
2. An optional blower accessory is available (see Accessories, page 31). There are two options for connecting blower to elec­trical source.
Option one: Have a licensed electrician install a properly
grounded, three-prong 120-volt electrical outlet at fireplace location. Locate outlet inside the framed enclosure. Blower power cord will plug into this outlet.
Option two: Have a licensed electrician connect blower to elec-
trical source at junction box inside fireplace. If using option one, have electrical outlet installed at this time.
If using option two, do not connect blower to electrical source at junction box until step 6.
3. Install gas piping to fireplace location. This installation includes an approved flexible gas line (if allowed by local codes) after the equipment shutoff valve. The flexible gas line must be the last item installed on the gas piping.
4. Carefully set fireplace in front of rough opening with back of fireplace inside wall opening.
5. Attach flexible gas line to fireplace gas regulator. See Con- necting Fireplace to Gas Supply, page 13.
6. If the optional blower has been installed connect blower to electrical source.
Option one: Route blower electrical cord through side or rear
access door of fireplace. Plug electrical cord into electrical outlet.
Option two: Have a licensed electrician connect blower to elec-
trical source at junction box inside fireplace.
7. Bend four nailing flanges on outer casing with pliers (see Figure 7).
8. Attach fireplace to wall studs using nails or wood screws through holes in nailing flange.
9. Check all gas connections for leaks. See Checking Gas Con- nections, page 14.
IMPORTANT:
When finishing your firebox, combustible materials such as wall board, gypsum board, sheet rock, drywall, plywood, etc. may be butted up next to the sides and top of the firebox. Combustible materials should never overlap the firebox front facing. Firebox should not be placed on top of carpet or other kinds of fibrous material.
WARNING: Do not allow any combustible materi-
als to overlap the firebox front facing.
IMPORTANT:
Noncombustible materials such as brick, tile, etc. may overlap the front facing, but should never cover any necessary openings like louvered slots.
WARNING: Do not allow noncombustible materials
to cover any necessary openings like louvered slots.
WARNING: Never modify or cover the louvered
slots on the front of the firebox.
WARNING: Use only noncombustible mortar or adhesives when overlapping the front facing with noncombustible facing material.
1
10
/2
"
7
/8
"
26
3/4" Off
26
7
/8
"
The Floor Minimum
Figure 5 - Rough Opening for Installing in Wall
5
36
/8
"
7
/8
"
26
3
/4
"
51
25
7
Figure 6 - Rough Opening for Installing in Corner
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Nails or Wood Screws
A U T O
O F F
O N
Nailing Flanges
Figure 7 - Attaching Fireplace to Wall Studs
/8
"
105442-01E
INSTALLATION
Continued
INSTALLATION
Mantel Clearances For Built-In Installation
Removing Brick Liner Retainer
Assembling Brass Trim
Optional Mantel Installation
9
9
MANTEL CLEARANCES FOR BUILT-IN INSTALLATION
NOTICE: Surface temperatures of adjacent walls and mantels become hot during operation. Walls and mantels above the firebox may become hot to the touch. If installed properly, these temperatures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.
If placing mantel above built-in fireplace, you must meet minimum clearance between mantel shelf and top of fireplace opening.
NOTICE: If your installation does not meet the mini­mum clearances shown, you must do one of the following:
raise the mantel to an acceptable height
remove the mantel
Mantel Shelf
Note:
All vertical measurements are from top of fireplace opening to bottom of mantel shelf.
Minimum Non­Combustible Material
Figure 8 - Minimum Mantel Clearances for Built-In Installation
10" 8" 6" 2 1/2"
13"
16"
19"
21"
ASSEMBLING BRASS TRIM
(Brass trim shipped with mantel)
1. Remove packaging from three pieces of brass trim.
2. Locate two adjusting plates with set screws, and two shims in the hardware packet.
3. Align shim under adjusting plate as shown in Figure 9.
4. Slide one end of adjusting plate/shim in slot on mitered edge of top brass trim (see Figure 9).
5. Slide other end of adjusting plate/shim in slot on mitered edge of side brass trim (see Figure 9).
6. While firmly holding edges of brass trim together, tighten both set screws on the adjusting plate with slotted screwdriver.
7. Repeat steps 1 through 6 for other corner.
8. Set brass assembly aside for later installation.
Slot
Slot
Shim
Mitered Edge
Top Brass Trim
Side Brass Trim
Set Screws
Adjusting Plate
Figure 9 - Assembling Brass Trim
OPTIONAL MANTEL INSTALLATION
Note:
Refer to instructions provided with the mantel for assembly instructions. Refer to instructions below for system installation. If using blower accessory (see Accessories, page 31), see installation instructions on pages 10 and 11.
1. Choose location for fireplace and install gas supply line.
2. Remove screen from fireplace by removing screws in each
end of screen rod (see Figure 10). Hold screen rod cover while removing five hex head screws underneath hood (see Figure 11, page 10). Carefully lift and pull out hood (see Figure 12, page 10).
REMOVING BRICK LINER RETAINER
1. Using Phillips screw driver, remove 2 screws attaching brick liner retainers to vertical sides.
2. Remove brick liner retainers and discard. Replace 2 screws into vertical sides.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
105442-01E
Figure 10 - Removing Screen
INSTALLATION
10
Optional Mantel Installation (Cont.) Installing Blower Assembly - GA3450T
INSTALLATION
Continued
3. Assemble brass trim kit. See Assembling Brass Trim, column 2.
4. Place brass trim on the shoulder screws located on the side and top of the fireplace. Firmly snap the brass trim over the shoulder screws on fireplace (see Figure 13).
5. Place mantel base close to wall in desired fireplace location.
6. Install gas line. See Connecting To Gas Supply, page 12
7. Carefully place fireplace on mantel base and center left to right. Check for gas leaks. See Checking Gas Connections, page 14.
8. Refer to instructions provided with the mantel for permanent attachment to wall.
9. Slide mantel around fireplace. Be careful not to damage wall or mantel.
10. Adjust assembly to remove any gaps. From back side of fire­place, attach two 2" wood screws through base mounting blocks attached to bottom sides of mantel into base (see instructions provided with mantel).
11. Attach remaining two 3" wood screws from hardware pack through openings inside of fireplace sides into the mantel. See Figure 12, for screw hole location.
Hood
Screen Rod Cover
Screw
Figure 11 - Removing Hood Screws
Mantel Screw Location
Figure 12 - Removing Hood
Shoulder Screws
INSTALLING BLOWER ASSEMBLY - GA3450T
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
CAUTION: Verify proper operation after servicing.
Note:
If you are using a mantel with your heater, use the following
instructions. If your heater is built-in, see For Built-In Installation on page 11.
1. Screen and hood should be removed from fireplace (see page
9). Remove log set and set aside.
2. Install snap bushings found in hardware kit into both holes in rear of blower control shield (see Figure 14).
3. Make sure the wire harness is firmly connected to the termi­nals on the blower bracket assembly.
4. Note the wire locations on back of AUTO/OFF/ON switch. Carefully remove red wire from the AUTO terminal and blue wire from the ON terminal. Black wire can remain on the middle or OFF terminal (see Figure 15, page 11).
5. Carefully disconnect green and white wires from power cord harness at their insulated connectors.
6. In top of the heater cabinet, locate the four mounting holes on the outer casing. Align these four holes with those on the blower bracket assembly. Attach blower bracket assembly to the outer casing with 4 - #10 screws provided (see Figure 15, page 11).
7. Route the wire harness through the hole to the left side of heat deflector. Pull wire harness through lower opening to the left of the blower control shield. (see Figure 15, page 11).
8. Insert the 4 wire harness into one of the round holes in the rear of the blower control shield and through the rectangular hole in the front of shield (see Figure 15, page 11).
9. Reconnect red wire to the AUTO switch position. Reconnect blue wire to the ON switch position. Reconnect green and white wires to the power cord.
Blower Control Shield
Snap Bushing
A U T O
O F F
O N
Assembled Brass Trim
Figure 13 - Attaching Brass Trim to Fireplace
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Figure 14 - Installing Snap Bushings
105442-01E
Loading...
+ 22 hidden pages