WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
— Installation and service must be performed by a quali-
fied installer, service agency or the gas supplier.
Save this manual for future reference.
For more information, visit www.desatech.com
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for correct installation
and operational procedures. For assistance or additional information consult a qualified installer, service
agency or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses
air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must
be provided. Refer to Air for Combustion and Ventilation
section on page 5 of this manual.
This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where
not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the
Commonwealth of Massachusetts.
Sellers of unvented propane or natural gas-fired supplemental room heaters shall provide to each
purchaser a copy of 527 CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for bedroom and bathroom installation in the Common
wealth of Massachusetts.
-
TABLE OF CONTENTS
Safety Information ............................................... 3
Warranty Information ...........................Back Cover
25
29
29
113109-01B
SAFETY INFORMATION
WARNING: This product contains and/or generates chemicals
known to the state of California
to cause cancer or birth defects
or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely
be fore tr ying to assemb le,
operate or service this heater.
Improper use of this heater can
cause serious injury or death
from burns, fire, explosion,
electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of carbon
monoxide poisoning resemble the flu, with head
aches, dizziness or nausea. If you have these signs,
the fireplace may not be working properly. Get fresh air at once! Have fireplace serviced. Some
people are more affected by carbon monoxide than
others. These include pregnant women, people with
heart or lung disease or anemia, those under the
influence of alcohol and those at high altitudes.
Natural and Propane/LP Gas: Natural and Propane/LP
gases are odorless. An odor-making agent is added
to these gases. The odor helps you detect a gas leak.
However, the odor added to the gas can fade. Gas
may be present even though no odor exists.
Make certain you read and understand all warnings.
Keep this manual for reference. It is your guide to
safe and proper operation of this fireplace.
WARNING: Do not allow fans
to blow directly into the fireplace.
Avoid any drafts that alter burner
flame patterns. Ceiling fans can
create drafts that alter burner
flame patterns. Altered burner
patterns can cause sooting.
Due to high temperatures, the
appliance should be located out
of traffic and away from furniture
and draperies.
Do not place clothing or other
flammable material on or near
the appliance. Never place any
objects on the heater.
Fireplace front and screen become very hot when running fire
place. Keep children and adults
-
away from hot surfaces to avoid
burns or clothing ignition. Fire
place will remain hot for a time
after shutdown. Allow surfaces
to cool before touching.
Carefully supervise young children when they are in the room
with fireplace. When using the
optional hand-held remote ac
cessory, keep selector switch
in the OFF position to prevent
children from turning on burners
with remote.
-
-
-
WARNING: Any change to
this heater or its controls can
be dangerous.
You must operate this fireplace
with the fireplace screen and
hood in place. Make sure fireplace screen and hood are in
WARNING: Do not use a
blower insert, heat exchanger
insert or other accessory not approved for use with this heater.
place before running fireplace.
Keep the appliance area clear
and free from combustible materials, gasoline and other flammable vapors and liquids.
113109-01B3
www.desatech.com
O
F
F
P
I
L
O
T
O
N
H
I
L
O
SAFETY INFORMATION
Continued
1. This appliance is only for use with the type of
gas indicated on the rating plate. This appliance
is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) in
side any structure. Locate propane/LP supply
tank(s) outdoors (propane/LP units only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighb orʼs phon e. Foll ow the gas
supplierʼs instructions
• if you cannot reach your gas supplier, call
the fire department
4. This fireplace shall not be installed in a bed
room or bathroom.
5. Do not use this fireplace as a wood-burning
fireplace. Use only the logs provided with the
fireplace.
6. Do not add extra logs or ornaments such as
pine cones, vermiculite or rock wool. Using
these added items can cause sooting. Do not
add lava rock around base. Rock and debris
could fall into the control area of fireplace.
7. To prevent the creation of soot, follow the
instructions in Cleaning and Maintenance,
page 24.
8. Before using furniture polish, wax, carpet
cleaner or similar products, turn heater off. If
heated, the vapors from these products may
create a white powder residue within burner
box or on adjacent walls or furniture.
9.
This fireplace needs fresh air ventilation to run
properly. This fireplace has an Oxygen Depletion
Sensing (ODS) safety shutoff system. The ODS
shuts down the fireplace if enough fresh air is not
available. See Air for Combustion and Ventila
tion, page 5. If fireplace keeps shutting off, see
Troubleshooting,
10. Do not run fireplace
• where flammable liquids or vapors are
used or stored
• under dusty conditions
11. Do not use this fireplace to cook food or burn
paper or other objects.
12. Do not use fireplace if any part has been
exposed to or under water. Immediately call
a qualified service technician to inspect the
fireplace and to replace any part of the control
4
page 25.
www.desatech.com
system and any gas control which has been
under water.
13. Do not operate fireplace if any log is broken.
Do not operate fireplace if a log is chipped
(dime-sized or larger).
14. Turn fireplace off and let cool before servicing.
Only a qualified service person should service
and repair fireplace.
15. Operating fireplace above elevations of 4,500
feet could cause pilot outage.
16. To pr e v e n t pe r f o r m a n c e pr o b l e m s in
propane/LP units, do not use propane/LP
fuel tanks of less than 100 lbs. capacity
(propane/LP units only).
17. Prov ide adeq ua te clearan ce s around air
openings.
PRODUCT
-
-
IDENTIFICATION
Log Set (VYGF shown)
Optional
Remote
Control
Control
Knobs
Top Outer
Casing
Firebox
Hood
Screen
Assembly
Piezo
Ignitor
Remote Selector
Switch (Optional)
Figure 1 - Log Base Assembly
Louver
Figure 2 - Fireplace
Blower Assembly
(Optional)
113109-01B
Firebox
Support
LOCAL CODES
Install and use fireplace with care. Follow all local
codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
UNPACKING
CAUTION: Do not remove the
data plates attached to the heater
base assembly. The data plates
contain important warranty and
safety information.
1. With utility knife, cut the carton all the way
around above the staples on the bottom tray.
Lift the carton off the heater. Remove packing.
Note: The hood is located in the packing on
the right hand side of the heater front. Lift the
heater off the bottom tray.
2. Locate two screws above top corners of the
fireplace screen. Remove and discard these
screws. Lift fireplace screen up and pull out
to remove.
3. Remove protective packaging applied to logs,
log base assembly and fireplace.
4. Remove fireplace hood from carton insert.
5. Check all items for any shipping damage. If
damaged, promptly inform dealer where you
bought fireplace.
PRODUCT FEATURES
OPERATION
This vent-free fireplace is clean burning. It requires
no outside venting. There is no heat loss out a
vent or up a chimney. Heat is generated by both
realistic flames. When used without the blower, the
fireplace requires no electricity making it ideal for
emergency backup heat. This heater is designed
for vent-free operation. It has been tested and ap
proved to ANSI Z21.11.2 standard for unvented
heaters. State and local codes in some areas pro
hibit the use of vent-free heaters.
SAFETY DEVICE
This fireplace has a pilot with an Oxygen Depletion
Sensing (ODS) safety shutoff system. The ODS/
pilot is a required feature for vent-free room heaters. The ODS/pilot system shuts off the fireplace
if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This fireplace has a piezo ignitor. This system
requires no matches, batteries or other sources to
light fireplace.
OPTIONAL REMOTE CONTROL UNITS
There are four optional remote controls that can be
purchased separately for this log heater:
• wall switch
• wall thermostat
• hand-held ON/OFF remote
• hand-held thermostat remote
See Accessories, page 38.
OPTIONAL BLOWER ASSEMBLY
(GA3700 SERIES & GA3700T
SERIES)
This fireplace accepts an optional blower assembly
(not included). The GA3700T Series blower oper
ates thermostatically and features a variable speed
control. The GA3700 Series blower operates manually and also features a variable speed control.
The blower circulates heated air from the fireplace
into the room. See Accessories, page 38.
AIR FOR COMBUSTION
AND VENTILATION
WARNING: This heater shall
not be installed in a confined
space or unusually tight construction unless provisions are provided for adequate combustion and
ventilation air. Read the following
instructions to insure proper fresh
air for this and other fuel-burning
appliances in your home.
Todayʼs homes are built more energy efficient
than ever. New materials, increased insulation and
new construction methods help reduce heat loss
in homes. Home owners weather strip and caulk
around windows and doors to keep the cold air out
and the warm air in. During heating months, home
owners want their homes as airtight as possible.
-
113109-01B5
www.desatech.com
AIR FOR COMBUSTION
AND VENTILATION
Continued
While it is good to make your home energy efficient, your home needs to breathe. Fresh air must
enter your home. All fuel-burning appliances need
fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers and fuel
burning appliances draw air from the house to
operate. You must provide adequate fresh air for
these appliances. This will insure proper venting
of vented fuel-burning appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3,
Air for Combustion and Ventilation.
All spaces in homes fall into one of the three fol
lowing ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space
The information on pages 5 through 7 will help you
classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may
provide enough fresh air for combustion and ven
tilation. However, in buildings of unusually tight
construction, you must provide additional fresh air.
Unusually tight construction is defined as
construction where:
a. walls and ceilings exposed to the out
side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6 x 10
less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window
and door frames, between sole plates
and floors, between wall-ceiling joints,
between wall panels, at penetrations
for plumbing, electrical and gas lines
and at other openings.
If your home meets all of these three criteria,
you must provide additional fresh air. See
Ventilation Air From Outdoors, page 7.
If your home does not meet all of the three
criteria above, proceed to Determining Fresh-Air Flow For Heater Location.
6
-11
kg per pa-sec-m2) or
www.desatech.com
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA
54 defines a confined space as a space whose
volume is less than 50 cubic feet per 1,000 Btu
per hour (4.8 m
3
per kw) of the aggregate input
rating of all appliances installed in that space and
an unconfined space as a space whose volume is
not less than 50 cubic feet per 1,000 Btu per hour
3
(4.8 m
per kw) of the aggregate input rating of
all appliances installed in that space. Rooms com
municating directly with the space in which the
appliances are installed*, through openings not
furnished with doors, are considered a part of the
unconfined space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation grills
between them.
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
-
Determining if You Have a Confined or
Unconfined Space
Use this work sheet to determine if you have a
confined or unconfined space.
Space: Includes the room in which you will install
fireplace plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x
width x height).
-
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)
If additional ventilation to adjoining room is
-
supplied with grills or openings, add the volume
of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x 20 =
51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in
the space.
Vent-free fireplace ___________
Gas water heater* ___________
Gas furnace ___________
Vented gas heater ___________
Gas fireplace logs ___________
Other gas appliances* + ___________
Total = ___________
* Do not include direct-vent gas appliances. Di
rect-vent draws combustion air from the outdoors
and vents to the outdoors.
113109-01B
-
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
-
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
Option
2
Ve
ntilation
Grills
Into Adjoining
Room,
Option 1
12"
12"
Outlet
Air
Ve
ntilated
Attic
Outlet
A
ir
Inlet
Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
AIR FOR COMBUSTION
AND VENTILATION
Continued
Example:
Gas water heater ______________
Vent-free fireplace + _____________
Total = _____________
40,000
33,000
73,000
Btu/Hr
Btu/Hr
Btu/Hr
the two spaces (see options 1 and 2, Figure 3). You
can also remove door into adjoining room (see
option 3, Figure 3). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for
Combustion and Ventilation for required size of
ventilation grills or ducts.
4. Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.
_________
_________
Btu/Hr (maximum the space can support)
Btu/Hr (actual amount of Btu/Hr used)
Example: 51,200 Btu/Hr (maximum the space
can support)
73,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the above example is a confined space
because the actual Btu/Hr used is more than the maxi
mum Btu/Hr the space can support. You must provide
additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoin
ing room. If the extra space provides an unconfined
space, remove door to adjoining room or add
ventilation grills between rooms. See Ventilation
Air From Inside Building.
B. Vent room directly to the outdoors. See Ventila
tion Air From Outdoors.
C. Install a lower Btu/Hr fireplace, if lower Btu/Hr
size makes room unconfined.
If the actual Btu/Hr used is less than the maximum
Btu/Hr the space can support,
the space is an uncon-
fined space. You will need no additional fresh air
ventilation.
WARNING: If the area in which
the fireplace may be operated
is smaller than that defined as
Figure 3 - Ventilation Air from Inside
-
Building
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or
ducts. You must provide two permanent openings:
-
one within 12" of the ceiling and one within 12"
of the floor. Connect these items directly to the
outdoors or spaces open to the outdoors. These
spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54,
Section 5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet
or outlet air into attic if attic has a thermostatcontrolled power vent. Heated air entering the attic
will activate the power vent.
an unconfined space or if the
building is of unusually tight
construction, provide adequate
combustion and ventilation air by
one of the methods described in
the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Section 5.3 or
applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining un
confined space. When ventilating to an adjoining
unconfined space, you must provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor on the wall connecting
113109-01B7
Figure 4 - Ventilation Air from Outdoors
-
www.desatech.com
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your pri
mary heat source. If you have a
central heating system, you may
run system’s circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
WARNING: A qualified service person must install fire
place. Follow all local codes.
Note: Your fireplace is designed to be used in zero
clearance installations. Wall or framing material can be
placed directly against any exterior surface on the rear,
sides or top of your fireplace, except where standoff
spacers are integrally attached. If standoff spacers are
attached to your fireplace, these spacers can be placed
directly against wall or framing materials.
-
Use the dimensions shown for rough openings to
create the easiest installation. See Built-In Fire-place Installation, page 11.
IMPORTANT:
the air. Although this is beneficial, installing fireplace in rooms without enough ventilation air may
cause mildew to form from too much moisture. See
Air for Combustion and Ventilation, page 5.
IMPORTANT: Make sure the fireplace is level. If
fireplace is not level, log set will not work properly.
CHECK GAS TYPE
Use the correct gas type (natural or propane/LP)
for your fireplace. If your gas supply is not correct, do not install fireplace. Call dealer where you
-
bought fireplace for proper type fireplace.
Vent-free heaters add moisture to
WARNING: Make sure the
selector switch is in the OFF po
sition before installing heater
WARNING: Never install the
fireplace
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture, cloth-
ing or other flammable objects
are less than 42 inches from the
front, top or sides of the heater
• in high traffic areas
• in windy or drafty areas
CAUTION: This fireplace creates warm air currents. These
currents move heat to wall surfaces next to fireplace. Installing
fireplace next to vinyl or cloth
wall coverings or operating
heater where impurities (such
as, but not limited, to tobacco
smoke, aromatic candles, clean
ing fluids, oil or kerosene lamps,
etc.) in the air exist, may discolor
walls or cause odors.
8
www.desatech.com
WARNING: This appliance
is equipped for (natural or pro-
-
pane/LP) gas. Field conversion
is not permitted.
ELECTRICAL HOOKUP
(Models GA3700 Series and GA3700T
Series Blower Accessories and GA3555
Internal Duplex Kit)
This fireplace accepts a blower assembly with an
electrical cord. The electrical cord is five feet in
length. You must locate fireplace within reach of
a 120 volt grounded electrical outlet. If not, you
must install an electrical outlet within reach of
fireplace power cord. The GA3555 outlet accessory is used for built-in applications with blower
accessory installed.
INSTALLING HOOD
Install hood to top of firebox as shown in Figure 5.
Use 3 Phillips screws provided.
-
Figure 5 - Installing Hood to Firebox
113109-01B
INSTALLATION
Continued
ASSEMBLING AND ATTACHING
OPTIONAL PERIMETER TRIM
(Included with Mantel Accessory)
IMPORTANT: If you are recessing the firebox in a
wall, do not attach perimeter trim at this time. See
Built-In Fireplace Installation, page 11.
Note: The instructions below show assembling
and attaching perimeter trim to fireplace.
1. Remove packaging from three pieces of pe
rimeter trim.
2. Locate four perimeter screws, two adjusting
plates with set screws and two shims in the
hardware packet.
3. Align shim under adjusting plate as shown in
Figure 6.
4. Slide one end of adjusting plate/shim in slot
on mitered edge of top perimeter trim (see
Figure 6).
5. Slide other end of adjusting plate/shim in slot
on mitered edge of side perimeter trim (see
Figure 6).
6. While firmly holding edges of perimeter trim
together, tighten both set screws on the adjust
ing plate with slotted screwdriver.
7. Repeat steps 1 through 6 for other side.
8. Tighten trim hanging screws (#10 x 6.25
shoulder) into holes in cabinets. Place the
assembled trim onto fireplace cabinet. Align
hanging notches on trim with hanging screws
on side of fireplace (see Figure 7). Push trim
firmly into place, sliding hanging notches over
hanging screws.
Set Screws
Side Trim
Adjusting
Plate
Top
Trim
Trim
Hanging
Screws
-
Assembled
Trim
Figure 7 - Attaching Perimeter Trim to
Fireplace
INSTALLATION CLEARANCES
WARNING: Maintain the
minimum clearances. If you can,
provide greater clearances from
floor, ceiling and adjoining wall.
Carefully follow the instructions below. This will
ensure safe installation.
-
Minimum Clearances For Side Combustible
Material, Side Wall and Ceiling
A. Clearances from the side of the fireplace
cabinet to any combustible material and wall
should follow diagram in Figure 8.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and
protrudes 3
tible material must be 4" from the side of the
fireplace opening (see Figure 8).
Clearances from the top of the fireplace opening
B.
to the ceiling should not be less than 42 inches.
Minimum Clearance to Combustible Materials
Top: 42", Left and Right Sides: 16"
1
/2" from the wall. This combus-
Bottom and Rear: 0"
Hanging
Notches
on Trim
Shim
Mitered
Slot
Figure 6 - Assembling Perimeter Trim
113109-01B9
Edge
Slot
www.desatech.com
Example
*
*Minimum 16 inches from Side Wall
Figure 8 - Minimum Clearance for
Combustible to Wall
INSTALLATION
Continued
CONVENTIONAL FIREPLACE
INSTALLATION
Conventional installation of this fireplace involves
installing fireplace along with the corner, face or
cabinet mantel with hearth base accessories against
a wall in your home. Follow the instructions below
to install the fireplace in this manner.
Note: The instructions in this section show installation using the cabinet mantel and hearth base
accessories. The hearth base accessory shown
is optional for this installation. You can install
fireplace and cabinet mantel directly on the floor.
The corner mantel accessory (VYGF models only)
can only be paired with the corner hearth base. If
mounting fireplace and cabinet or corner mantel
to the floor, an optional G3005 Series Slim Base
kit may be installed.
1. Assemble cabinet mantel, hearth base and
trim accessories. Assembly instructions are
included with each accessory.
2. When installing blower, install a properly
grounded, 120 volt three-prong electrical out
let at fireplace location if an outlet is not there.
If possible, locate outlet so cabinet mantel will
cover it when installed (see Figure 9).
3.
Install gas piping to fireplace location. This installation includes an approved flexible gas line
(if allowed by local codes) after the equipment
shutoff valve. The flexible gas line must be the
last item installed on the gas piping. See Install-ing Gas Piping to Fireplace Location, page 13.
4. Place hearth base accessory against wall at
installation location. Cut an access hole in
hearth top to run flexible gas line to fireplace
(see Figure 9). Make sure to locate access hole
so cabinet mantel will cover it when installed.
Note: You can secure base to floor using wood
screws. Countersink screw heads and putty over.
5. Route flexible gas line through access hole in
hearth base.
6. Center cabinet mantel on hearth base (see Figure
10). Make sure mantel is flush against wall.
7. Break off nailing flanges (see Figure 11) with
hammer or pliers.
8. Place cardboard or other protective material
on top of hearth base. Carefully set fireplace
on protective material, with back of fireplace
inside mantel opening.
9. Attach flexible gas line from fireplace gas
regulato r to gas supply. See Conne cting
Fireplace to Gas Supply,
10
page 14.
www.desatech.com
Electrical
Rigid
Hearth
Base
Figure 9 - Placing Hearth Base
Accessory Against Wall
-
Figure 10 - Installing Cabinet Mantel
Figure 11 - Location of Nailing Flanges
Figure 12 - Inserting Fireplace Into
Cabinet Mantel
Gas
Line
Outlet
Gas
Line
Access
Hole
Cabinet
Mantel
Nailing
Flanges
113109-01B
INSTALLATION
35 1/2"
17 3/4"
33"
39
3
/8
"
27
7
/8
"
55
5
/8
"
35
1
/2
"
Continued
10. If blower is installed, route blower electrical cord
through access holes in either side of fireplace.
Note: Bushing may be moved if necessary. Plug
electrical cord into electrical outlet.
11. Carefully insert fireplace into cabinet mantel.
Be careful not to scratch or damage hearth
base, cabinet mantel or any laminate trim on
hearth base (VYGF models only). Remove
6. Carefully insert fireplace into rough opening.
7. Attach flexible gas line to gas supply. See Connecting Fireplace to Gas Supply, page 14.
8. Attach fireplace to wall studs using nails or
wood screws through holes in nailing flange
(see Figure 15).
9. Check all gas connections for leaks. See
Checking Gas Connections, page 15.
10. Install perimeter trim after final finishing and/or
painting of wall (see Figure 7, page 9).
protective material from top of hearth base and
from front of fireplace (if any). Note: You can
secure fireplace to hearth or floor. Open lower
louver. Locate screw holes in bottom of base.
Tighten wood screws through these holes and
into hearth or floor.
12. Check all gas connections for leaks. See
Checking Gas Connections, page 15.
BUILT-IN FIREPLACE INSTALLATION
Built-in installation of this fireplace involves
installing fireplace into a framed-in enclosure.
This makes the front of fireplace flush with wall.
If installing a mantel above the fireplace, you
must follow the clearances shown in Figure 20,
page 13. Follow the instructions below to install
the fireplace in this manner.
Actual Framing
Height 32
Front Width 34
Depth 16
3
/8" 33"
5
/16" 35 1/2"
11
/16" 17 3/4"
Models VYGF33PRB and VYGF33NRB
1. Frame in rough opening. Use dimensions shown
in Figure 13 for the rough opening. If installing
in a corner, use dimensions shown in Figure 14
for the rough opening. The height is 33" which
is the same as the wall opening above.
2. If using blower, install and properly ground
GA3555, three-prong 120 volt electrical out
let, in fireplace. Follow instructions included
in kit (see Accessories, page 38).
3.
Install gas piping to fireplace location. This installation includes an approved flexible gas line
(if allowed by local codes) after the equipment
shutoff valve. The flexible gas line must be the
last item installed on the gas piping. See Installing Gas Piping to Fireplace Location, page 13.
4. Carefully set fireplace in front of rough opening
with back of fireplace inside wall opening.
5. Plug electrical cord into electrical outlet
installed in step 2.
113109-01B11
www.desatech.com
Figure 13 - Rough Opening for Installing
in Wall
Figure 14 - Rough Opening for Installing
in Corner
Nails or
Wood
Screws
-
-
Nailing
Flanges
Figure 15 - Attaching Fireplace to Wall
Studs
-
INSTALLATION
35 1/2"
17 3/4"
33"
Continued
Models FPVF33PRA and FPVF33NRA
WARNING: A qualified electrician must connect electrical wiring
to duplex outlet for built-in instal
lation. Follow all local codes.
1. Frame in rough opening. Use dimensions
shown in Figure 16 for the rough opening.
2. If using blower, install wiring and properly
ground the three-prong, 120 volt electrical
outlet in fireplace.
3. Before replacing bottom of firebox, install
duplex outlet to the right support bracket in
the bottom of firebox (see Figure 17).
4. Route wire s from electrical box through
smallest hole in outer casing using strain relief
fitting provided (see Figure 17).
5. Connect wires from the electrical box to
duplex outlet. Match wire colors to those
indicated on duplex outlet. Be sure to connect
ground wire.
6. Install shield to end of right support bracket
and behind the firebox wrapper with 2 screws
provided (see Figure 18).
7. Plug blower cord into duplex outlet. Note:
On thermostat model fireplaces, route power
cord to the back of the fireplace to clear
thermostat valve.
8. Replace bottom of firebox.
9. Install gas piping to fireplace location. This
installation includes an approved flexible
gas line (if allowed by local codes) after the
equipment shutoff valve. The flexible gas line
must be the last item installed on the gas piping. See Installing Gas Piping to Fireplace Location, page 13.
10. Carefully set fireplace in front of rough opening
with back of fireplace inside wall opening.
11. Attach flexible gas line to gas supply. See Con-necting Fireplace to Gas Supply, page 14.
12. Plug electrical cord into electrical outlet
installed in step 2.
13. Carefully insert fireplace into rough opening.
14. Attach fireplace to wall studs using nails or
wood screws through holes in nailing flange
(see Figure 19).
15. Check all gas connections for leaks. See
Checking Gas Connections, page 15.
16. Install brass trim after final finishing and/or
painting of wall (see Figure 7, page 6).
12
-
Figure 16 - Rough Opening for Installing
Blower
Blower
Power
Cord
Figure 17 - Connecting Duplex Outlet
Figure 18 - Attaching Fireplace to Wall Studs
Nails or
Wood
Screws
Figure 19 - Attaching Fireplace to Wall Studs
www.desatech.com
Screw
Power
Cord
in Wall
Support
Bracket
Strain
Relief Fitting
Screws
Nailing
Flanges
Cable from
Electrical
Source
Duplex
Outlet
Support Bracket
Firebox
Wrapper
113109-01B
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.