Desa VSGF28NVA User Manual

For more information, visit www.desatech.com
For more information, visit www.desatech.com
Variable Manually-
Controlled Model
VSGF28NVA
Thermostatically-
Controlled Model
VSGF28NTC
with
Split Oak Logs
UNVENTED (VENT-FREE) NATURAL GAS FIREPLACE
OWNER’S OPERATION AND
®
INSTALLATION MANUAL
Shown with optional
cabinet mantel,
accessories.
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result caus­ing property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
WARNING: Improper installa­tion, adjustment, alteration, ser­vice, or maintenance can cause injury or property damage. Re­fer to this manual for correct installation and operational pro­cedures. For assistance or ad­ditional information consult a qualified installer, service agency, or the gas supplier.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a
qualified installer, service agency, or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses air (oxy­gen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to
Combustion and Ventilation
Air for
sec-
tion on page 4 of this manual.
This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Save this manual for future reference.
Save this manual for future reference.
TABLE OF CONTENTS SAFETY INFORMATION
2
TABLE OF CONTENTS
SAFETY INFORMATION ............................................................ 2
PRODUCT IDENTIFICATION ..................................................... 3
LOCAL CODES........................................................................... 3
UNPACKING............................................................................... 4
PRODUCT FEATURES .............................................................. 4
AIR FOR COMBUSTION AND VENTILATION ........................... 4
INSTALLATION ........................................................................... 6
OPERA TING FIREPLACE ........................................................ 14
INSPECTING BURNERS.......................................................... 17
CLEANING AND MAINTENANCE ............................................ 18
SAFETY INFORMATION
TROUBLESHOOTING .............................................................. 19
TECHNICAL SERVICE ............................................................. 22
REPLACEMENT PARTS .......................................................... 22
SERVICE HINTS....................................................................... 22
WIRING DIAGRAM ................................................................... 22
SPECIFICATIONS .................................................................... 22
ACCESSORIES ........................................................................ 22
ILLUSTRATED PARTS BREAKDOWN AND PARTS LIST ....... 24
OWNERS REGISTRATION FORM.......................................... 33
WARRANTY INFORMATION ...................................... Back Cover
WARNINGS
IMPORTANT: Read this owners manual carefully and completely before trying to assemble, operate, or ser­vice this fireplace. Improper use of this fireplace can cause serious injury or death from burns, fire, explo­sion, electrical shock, and carbon monoxide poisoning.
DANGER: Carbon monoxide poisoning may lead
to death!
Carbon Monoxide Poisoning: Early signs of carbon monoxide
poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the fireplace may not be working properly. Get fresh air at once! Have fireplace serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Natural Gas: Natural gas is odorless. An odor-making agent is added to
the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this fireplace.
WARNING: Do not use a blower insert, heat exchanger insert, or other accessory not approved for use with this fireplace.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
Fireplace front and screen become very hot when running fireplace. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow surfaces to cool before touching.
Carefully supervise young children when they are in the room with fireplace. When using the hand-held remote accessory, keep selector switch in the OFF position to prevent children from turning on burners with remote.
WARNING: Any change to this heater or its con-
trols can be dangerous.
WARNING: Do not allow fans to blow directly into the fireplace. Avoid any drafts that alter burner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
You must operate this fireplace with the fireplace screen and hood in place. Make sure fireplace screen and hood are in place before running fireplace.
Keep the appliance area clear and free from combus­tible materials, gasoline, and other flammable vapors and liquids.
107157-01F
SAFETY INFORMATION
PRODUCT IDENTIFICATION
LOCAL CODES
3
3
SAFETY INFORMATION
Continued
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. This fireplace shall not be installed in a bedroom or bathroom.
3. Do not use this fireplace as a wood-burning fireplace. Use only the logs provided with the fireplace.
4. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use any phone in
your building
• immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions
• if you cannot reach your gas supplier , call the fire department
5. Do not add extra logs or ornaments such as pine cones, ver­miculite, or rock wool. Using these added items can cause soot­ing. Do not add lava rock around base. Rock and debris could fall into the control area of fireplace.
6. This fireplace is designed to be smokeless. If logs ever appear to smoke, turn off fireplace and call a qualified service person.
Note:
During initial operation, slight smoking could occur due
to log curing and fireplace burning manufacturing residues.
7. To prevent the creation of soot, follow the instructions in Clean- ing and Maintenance, page 18.
8. Before using furniture polish, wax, carpet cleaner, or similar products, turn heater off. If heated, the vapors from these prod­ucts may create a white powder residue within burner box or on adjacent walls or furniture.
9. This fireplace needs fresh air ventilation to run properly . This fireplace has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the fireplace if not enough fresh air is available. See Air for Combustion and Ventilation, pages 4 through 6. If fireplace keeps shutting off, see Trouble- shooting, pages 19 through 21.
10. Do not run fireplace
• where flammable liquids or vapors are used or stored
• under dusty conditions
11. Do not use this fireplace to cook food or burn paper or other objects.
12. Do not use fireplace if any part has been exposed to or under water. Immediately call a qualified service technician to in­spect the fireplace and to replace any part of the control sys­tem and any gas control which has been under water.
13. Do not operate fireplace if any log is broken. Do not operate fireplace if a log is chipped (dime-sized or larger).
14. Turn fireplace off and let cool before servicing. Only a quali­fied service person should service and repair fireplace.
15. Operating fireplace above elevations of 4,500 feet could cause pilot outage.
16. Provide adequate clearances around air openings.
PRODUCT IDENTIFICATION
Middle Log
Front Burner
Front Log
Base Assembly
Figure 1 - Log Base Assembly, Split Oak Set
Top Louver Assembly
Fireplace Hood
Firebox Support
Screen Assembly
Figure 2 - Fireplace
Crossover Log
Rear Log
Rear Burner
Top Outer Casing
Optional Blower Assembly (Not Included)
Bottom Louver Assembly
LOCAL CODES
Install and use fireplace with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel
Gas Code ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
107157-01F
For more information, visit www.desatech.com
For more information, visit www.desatech.com
UNPACKING
4
PRODUCT FEATURES AIR FOR COMBUSTION AND VENTILATION
Providing Adequate Ventilation
UNPACKING
WARNING: Do not remove the data plates at­tached to the heater base assembly. The data plates contain important warranty and safety information.
1. With utility knife, cut the carton all the way around above the staples on the bottom tray. Lift the carton off the heater. Re-
Note:
move packing. the right hand side of the heater front. Lift the heater off the bottom tray.
2. Locate two screws above top corners of the fireplace screen. Remove and discard these screws. Lift fireplace screen up and pull out to remove.
3. Remove protective packaging applied to logs, log base assem­bly, and fireplace.
4. Remove fireplace hood from carton insert.
5. Check all items for any shipping damage. If damaged, promptly inform dealer where you bought fireplace.
The hood is located in the packing on
PRODUCT FEATURES
OPERATION
This vent-free fireplace is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by both realistic flames and glowing embers. When used without the blower, the fireplace requires no electricity making it ideal for emergency backup heat.
SAFETY DEVICE
This fireplace has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent­free room heaters. The ODS system shuts off the fireplace if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This fireplace has a piezo ignitor. This system requires no matches, batteries, or other sources to light fireplace.
THERMOSTAT CONTROL (VSGF28NTC)
This fireplace has a thermostat sensing bulb and a control valve. The thermostat controls the heat output and flame height. This maintains a consistent room temperature. Even the lowest setting provides realistic flames and glowing embers from two burners. Selecting higher comfort settings allows fireplace to run longer, producing greater heat output. At lower comfort settings, the fireplace will run less. This results in increased heating comfort. This can also result in lower gas bills.
VARIABLE MANUAL CONTROL (VSGF28NVA)
This fireplace has a variable manual control valve which allows the user to choose the heat setting that best suits his needs. Any setting between low and high may be selected by simply turning the control knob.
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall not be installed in a confined space or unusually tight construction un­less provisions are provided for adequate combus­tion and ventilation air. Read the following instruc­tions to insure proper fresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy efficient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
BLOWER ASSEMBLY
(VSGF28NTC)
This fireplace has a blower assembly. The blower operates thermo­statically and has a variable speed control. The blower circulates heated air from the fireplace into the room. Use of blower is optional. Optional blower accessories are available for model VSGF28NVA. See Accessories, page 22.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on pages 4 through 6 will help you classify your
space and provide adequate ventilation.
107157-01F
AIR FOR COMBUSTION AND VENTILATION
Continued
AIR FOR COMBUSTION AND VENTILATION
Providing Adequate Ventilation (Cont.)
Determining Fresh-Air Flow for Heater Location
5
5
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings e xposed to the outside atmosphere
have a continuous water vapor retar der with a rating of one perm (6 x 10 openings gasketed or sealed
-11
kg per pa-sec-m2) or less with
and
b. weather stripping has been added on openable win-
dows and doors
and
c. caulking or sealants are applied to areas such as
joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.
If your home meets all of the three criteria above, you must pro vide additional fresh air . See
Air From Outdoors
, page 6
.
Ventilation
If your home does not meet all of the three criteria above, proceed to
tion,
Determining Fresh-Air Flow For Heater Loca-
column 2.
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space. Space: Includes the room in which you will install heater plus any adjoining
rooms with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height). Length x Width x Height =___________ cu. ft. (volume of space)
Example:
height) = 3168 cu. ft. (volume of space) If additional ventilation to adjoining room is supplied with grills or open-
ings, add the volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maximum Btu/Hr the space
Example:
Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
* Do not include direct-vent gas appliances. Direct-vent draws com­bustion air from the outdoors and vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
__________________ Btu/Hr (maximum the space can support) __________________ Btu/Hr (actual amount of Btu/Hr used)
Example:
The space in the example on page 5 is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the
extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See V entilation Air Fr om Inside Building, page 6.
B. Vent room directly to the outdoors. See Ventilation Air From Out-
doors, page 6.
C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined. If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support,
the space is an unconfined space. You will need no additional fresh air ventilation.
Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling
can support)
3,168 cu. ft. (volume of space) x 20 = 63,360 (maximum
Vent-free heater _____________ Btu/Hr Gas water heater* _____________ Btu/Hr Gas furnace _____________ Btu/Hr Vented gas heater _____________ Btu/Hr Gas fireplace logs _____________ Btu/Hr Other gas appliances* + _____________ Btu/Hr Total = _____________ Btu/Hr
Example:
Gas water heater _____________ Btu/Hr Vent-free heater + _____________ Btu/Hr Total = _____________ Btu/Hr
63,360 Btu/Hr (maximum the space can support) 68,000 Btu/Hr (actual amount of Btu/Hr used)
40,000 28,000 68,000
107157-01F
For more information, visit www.desatech.com
For more information, visit www.desatech.com
AIR FOR COMBUSTION AND VENTILATION
Outlet Air
Ventilated Attic
Outlet Air
Inlet Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
6
Ventilation Air
INSTALLATION
AIR FOR COMBUSTION AND VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3). You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation
for required size of ventilation grills or ducts.
IMPORTANT:
attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.
Do not provide openings for inlet or outlet air into
12"
Figure 4 - Ventilation Air from Outdoors
INSTALLATION
NOTICE: This heater is intended for use as supple­mental heat. Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a central heating system, you may run systems circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
Ventilation
Grills
Into Adjoining
Room,
Option 1
Figure 3 - Ventilation Air from Inside Building
Or
Remove Door into Adjoining
Room, Option
3
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Ventilation Grills
Into Adjoining Room,
12"
Option 2
WARNING: A qualified service person must in-
stall fireplace. Follow all local codes.
WARNING: Never install the fireplace
in a bedroom or bathroom
in a recreational vehicle
where curtains, furniture, clothing, or other flam-
mable objects are less than 42 inches from the front, top, or sides of the heater
in high traffic areas
in windy or drafty areas
WARNING: Model VSGF28NTC has a three-prong, grounded electrical plug. This plug helps protect you against electrical shock. Only connect plug to a properly grounded, three-prong receptacle. Do not cut or remove the grounding prong from this plug.
107157-01F
INSTALLATION
Continued
INSTALLATION
Check Gas Type
Electrical Hookup
Installing Hood
Assembling And Attaching Optional Brass Trim
7
7
CAUTION: This fireplace creates warm air cur­rents. These currents move heat to wall surfaces next to fireplace. Installing fireplace next to vinyl or cloth wall coverings or operating heater where impurities (such as, but not limited to, tobacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
Note:
Your fireplace is designed to be used in zero clearance
installations. Wall or framing material can be placed directly against any exterior surface on the rear, sides, or top of your fireplace, except where standoff spacers are integrally attached. If standoff spacers are attached to your fireplace, these spacers can be placed directly against wall or framing materials.
Use the dimensions shown for rough openings to create the easiest installation (see Built-In Fireplace Installation, pages 9 and 10).
IMPORTANT:
this is beneficial, installing fireplace in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventilation, pages 4 through 6.
IMPORTANT:
level, log set will not work properly.
Vent-free heaters add moisture to the air. Although
Make sure the fireplace is level. If fireplace is not
CHECK GAS TYPE
Use only natural gas. If your gas supply is not natural gas, do not install fireplace. Call dealer where you bought fireplace for proper type fireplace.
WARNING: Never connect fireplace to pri­vate (non-utility) gas wells. This gas is com­monly known as wellhead gas.
ELECTRICAL HOOKUP
(Model VSGF28NTC or VSGF28NVA with GA3750 or GA3650T Series Blower)
This fireplace has a blower assembly with an electrical cord. The electrical cord is five feet in length. You must locate fireplace within reach of a 120 volt grounded electrical outlet. If not, you must install an electrical outlet within reach of fireplace power cord. The GA3555 outlet accessory may be used for built-in applications with blower installed. This same information applies if installing op­tional blower accessories to Model VSGF28NVA.
Hood
Figure 5 - Installing Hood
Rail
Screw
ASSEMBLING AND ATTACHING OPTIONAL BRASS TRIM (Included with Mantel Accessory)
IMPORTANT:
attach brass trim at this time. See page 9 for built-in fireplace installation.
Note:
The instructions below show assembling and attaching brass
trim to fireplace.
1. Remove packaging from three pieces of brass trim.
2. Locate four brass screws, two adjusting plates with set screws, and two shims in the hardware packet.
3. Align shim under adjusting plate as shown in Figure 6.
4. Slide one end of adjusting plate/shim in slot on mitered edge of top brass trim (see Figure 6).
5. Slide other end of adjusting plate/shim in slot on mitered edge of side brass trim (see Figure 6).
6. While firmly holding edges of brass trim together, tighten both set screws on the adjusting plate with slotted screwdriver.
7. Repeat steps 1 through 6 for other side.
Side Brass Trim
If you are recessing the firebox in a wall, do not
Adjusting Plate
Set Screws
Top Brass Trim
INSTALLING HOOD
Install hood to rail already installed in fireplace as shown in Figure
5. Use 3 Phillips screws provided.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
107157-01F
Slot
Shim
Mitered Edge
Figure 6 - Assembling Brass Trim
Slot
INSTALLATION
8
Assembling and Attaching Optional Brass Trim (Cont.) Installation Clearances Conventional Fireplace Installation
INSTALLATION
Continued
8. Tighten trim hanging screws (#10 x 6.25 shoulder) into holes in cabinets. Place the assembled trim onto fireplace cabinet. Align hanging notches on trim with hanging screws on side of fireplace (see Figure 7). Push trim firmly into place, sliding hanging notches over hanging screws.
Trim Hanging Screws
Hanging Notches on Trim
Assembled Brass Trim
Figure 7 - Attaching Brass Trim to Fireplace
INSTALLATION CLEARANCES
WARNING: Maintain the minimum clearances. If you can, provide greater clearances from floor, ceil­ing, and adjoining wall.
Carefully follow the instructions below. This will ensure safe installation.
Minimum Clearances For Side Combustible Material, Side Wall, and Ceiling
A. Clearances from the side of the fireplace cabinet to any com-
bustible material and wall should follow diagram in Figure 8.
Example:
combustible material and protrudes 3 1/2" from the wall. This combustible material must be 4" from the side of the fireplace opening (see Figure 8).
B. Clearances from the top of the fireplace opening to the ceiling
should not be less than 42 inches.
The face of a mantel, bookshelf, etc. is made of
Example
CONVENTIONAL FIREPLACE INSTALLATION
Conventional installation of this fireplace involves installing fire­place along with the corner or cabinet mantel with hearth base accessories against a wall in your home (see Accessories, page 22 and 23). Follow the instructions below to install the fireplace in this manner.
Note:
The instructions below show installation using the cabinet mantel and the G3000F/G3001U/G3004W/G3006F/G3007U se­ries hearth base accessories. The hearth base accessory shown is optional for this installation. You can install fireplace and cabinet/ corner mantel directly on the floor. The corner mantel accessory cannot be installed with the G3000F/G3001U/G3004W/G3006F/ G3007U hearth base. The corner mantel can be paired with the G3008F/G3009U/G3010F corner hearth base. If mounting fire­place and cabinet or corner mantel to the floor, an optional G3005 Slim Base kit may be installed.
1. Assemble cabinet mantel, hearth base, and trim accessories.
Assembly instructions are included with each accessory.
2. When installing blower, install a properly grounded, 120 volt
three-prong electrical outlet at fireplace location if an outlet is not there. If possible, locate outlet so cabinet mantel will cover it when installed (see Figure 9).
3. Install gas piping to fireplace location. This installation includes
an approved flexible gas line (if allowed by local codes) after the equipment shutoff valve. The flexible gas line must be the last item installed on the gas piping. See Installing Gas Piping to Fireplace Location, pages 10 and 11.
4. Place hearth base accessory against wall at installation loca-
tion. Cut an access hole in hearth top to run gas line to fire­place (see Figure 9). Make sure to locate access hole so cabi­net mantel will cover it when installed. base to floor using wood screws. Countersink screw heads and putty over.
5. Route gas line through access hole in hearth base.
6. Center cabinet mantel on hearth base (see Figure 10, page 9).
Make sure mantel is flush against wall.
7. Break off nailing flanges (see Figure 11, page 9) with hammer
or pliers.
Rigid Pipe and Gas Shutoff Valve
Note:
You can secure
Electrical Outlet
*
*Minimum 16 inches from Side Wall
Figure 8 - Minimum Clearance for Combustible to Wall
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Gas Line
Hearth Base
Figure 9 - Placing Hearth Base Accessory Against Wall
Access Hole
107157-01F
8. Place cardboard or other protective material on top of hearth
35 1/2"
17
3
/4"
33"
base. Carefully set fireplace on protective material, with back of fireplace inside mantel opening.
9. If blower is installed, route blower electrical cord through ac­cess holes in either side of fireplace.
Note:
Bushing may be
moved if necessary. Plug electrical cord into electrical outlet.
10. Carefully insert fireplace into cabinet mantel (Figure 12). Be careful not to scratch or damage hearth base, cabinet mantel, or any laminate trim on hearth base. Remove protective mate­rial from top of hearth base and from front of fireplace (if any).
Note:
You can secure fireplace to hearth or floor. Open lower louver. Locate screw holes in bottom of base. Tighten wood screws through these holes and into hearth or floor.
11. Attach gas line from fireplace gas regulator to gas supply. See Connecting Fireplace to Gas Supply, page 11.
12. Check all gas connections for leaks. See Checking Gas Con- nections, page 12.
Cabinet Mantel
Conventional Fireplace Installation (Cont.)
Built-In Fireplace Installation
Figure 12 - Inserting Fireplace Into Cabinet Mantel
INSTALLATION
9
9
BUILT-IN FIREPLACE INSTALLATION
Built-in installation of this fireplace involves installing fireplace into a framed-in enclosure. This makes the front of fireplace flush with wall. If installing a mantel above the fireplace, you must follow the clearances shown in Figure 16, page 10 . Follow the instructions below to install the fireplace in this manner.
Actual Framing
3
Height 32 Front Width 34 Depth 16
/8" 33"
5
/16" 35 1/2"
11
/16" 17 3/4"
Figure 10 - Installing Cabinet Mantel
Figure 11 - Location of Nailing Flanges
For more information, visit www.desatech.com
For more information, visit www.desatech.com
107157-01F
1. Frame in rough opening. Use dimensions shown in Figure 13 for the rough opening.
If installing in a corner, use dimensions shown in Figure 14, page 10 for the rough opening. The height is 33" which is the same as the wall opening above.
2. If using blower, install and properly ground GA3555, three­prong 120 volt electrical outlet, in fireplace. Follow instruc­tions included in kit.
Nailing Flanges
Figure 13 - Rough Opening for Installing in Wall
INSTALLATION
10
Built-In Fireplace Installation (Cont.) Installing Gas Piping To Fireplace Location
INSTALLATION
Continued
3. Install gas piping into fireplace location. This installation in­cludes an approved flexible gas line (if allowed by local codes) after the equipment shutoff valve. The flexible gas line must be the last item installed on the gas piping. See Installing Gas Piping to Fireplace Location.
4. Carefully set fireplace in front of rough opening with back of fireplace inside wall opening.
5. Carefully insert fireplace into rough opening.
6. Attach flexible gas line to gas supply. See Connecting Fire- place to Gas Supply, page 11.
7. Attach fireplace to wall studs using nails or wood screws through holes in nailing flange (see Figure 15).
8. Check all gas connections for leaks. See Checking Gas Con- nections, page 12.
9. Plug electrical cord into electrical outlet installed in step 2, page 9.
10. Install brass trim after final finishing and/or painting of wall (see Figure 7, page 8).
3
39
/8
"
1
/2
"
35
5
/8
"
55
27
7
/8
"
Mantel
19"
Shelf
21"
Note:
All Vertical measurements are from top of fireplace opening to bottom of mantel shelf.
10" 8" 6" 2
1
"
/2
13"
16"
Figure 16 - Minimum Mantel Clearances for Built-In Installation
INSTALLING GAS PIPING TO FIREPLACE LOCATION
WARNING: This appliance requires a 1/2" NPT (National Pipe Thread) inlet connection to the pres­sure regulator.
Figure 14 - Rough Opening for Installing in Corner
Nails or Wood Screws
Nailing Flanges
Figure 15 - Attaching Fireplace to Wall Studs
Mantel Clearances for Built-In Installation
If placing mantel above built-in fireplace, you must meet minimum clearance between mantel shelf and top of fireplace opening.
If your installation does not meet the below minimum clearances, you must:
• raise the mantel to an acceptable height, OR
• remove the mantel.
WARNING: A qualified service person must con­nect fireplace to gas supply. Follow all local codes.
Installation Items Needed
Before installing fireplace, make sure you have the items listed below.
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench * A CSA design-certified equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge connection. Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, pages 22 through 23.
WARNING: Never connect fireplace to private (non-utility) gas wells. This gas is commonly known as wellhead gas.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
107157-01F
INSTALLATION
Continued
Installing Gas Piping to Fireplace Location (Cont.)
INSTALLATION
Connecting Fireplace To Gas Supply
11
11
CAUTION: Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diam­eter or greater to allow proper gas volume to fireplace. If pipe is too small, undue loss of volume will occur.
Installation must include an equipment shutoff valve, and a plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 17).
IMPORTANT:
location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.
Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves. Never use thread sealant on flare threads.
CAUTION: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
Install equipment shutoff valve in an accessible
CSA Design-Certified Equipment Shutoff Valve With 1/8" NPT Tap*
CONNECTING FIREPLACE TO GAS SUPPLY
Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• Phillips screwdriver
• sealant (resistant to propane/LP gas, not provided)
1. Remove fireplace screen. Remove two screws that hold fire­place screen in place for shipping. These screws are located near top of screen. Discard screws. Lift fireplace screen up and pull out to remove.
2. Remove screws that attach log base assembly to fireplace (see Figure 18). Carefully lift up log base assembly and remove from fireplace (see Figure 18).
Note:
If adding the G8000 series brick liner accessory, install it
now. Follow instructions in G8000 accessory kit.
CAUTION: Do not pick up log base assembly by burners. This could damage burners. Only handle base by grates.
3. Route gas line (provided by installer) from equipment shutoff through one of the access holes.
NOTICE: Most building codes do not permit con­cealed gas connections. A flexible gas line is pro­vided to allow accessibility from the fireplace (see Figure 19). The flexible gas supply line connection to the equipment shutoff valve should be accessible.
3" Minimum
Cap Pipe Tee
Nipple Joint
Sediment Trap
Figure 17 - Gas Connection
* Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, pages 22 and 23
We recommend that you install a sediment trap in supply line as shown in Figure 17. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and fireplace. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into fireplace gas controls. If sediment trap is not installed or is installed wrong, fireplace may not run properly.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
107157-01F
Natural Gas
From Gas Meter (5" W.C.** to 10.5" W.C. Pressure)
Figure 18 - Removing Log Base Assembly From Fireplace
Loading...
+ 25 hidden pages