SAFETY INFORMATION
WARNING: Improper installation, adjustment, al-
teration, service or mainte-
nance can cause injury or
property damage. Refer to
this manual for correct in-
stallation and operational
procedures. For assis-
tance or additional infor-
mation consult a qualied
installer, service agency or
the gas supplier.
WARNING: This is an
unvented gas-red heater.
It uses air (oxygen) from the
room in which it is installed.
Provisions for adequate
combustion and ventilation air must be provided.
Refer to Air for Combustion
and Ventilation section on
page 5 of this manual.
This appliance is only for
use with the type of gas
indicated on the rating
plate. This appliance is
not convertible for use
with other gases.
This appliance may be in-
stalled in an aftermarket,*
per man entl y lo cate d,
manufactured (mobile)
home, where not prohibited by local codes.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
WARNING: This product con-
tains and/or generates chemicals
known to the State of California
to cause cancer or birth defects
or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely
be fore trying to assemble,
operate or service this heater.
Improper use of this heater can
cause serious injury or death
from burns, fire, explosion,
electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of carbon
monoxide poisoning resemble the u, with headaches, dizziness or nausea. If you have these signs,
the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people
are more affected by carbon monoxide than others.
These include pregnant women, people with heart
or lung disease or anemia, those under the inuence of alcohol and those at high altitudes.
www.desatech.com
113061-01F2
SAFETY INFORMATION
Continued
Natu ra l an d Prop an e/ LP Gas : Natu ra l and
propane/LP gases are fuel gases. Fuel gases are
odorless. An odor-making agent are added to fuel
gases. The odor helps you detect a fuel gas leak.
However, the odor added to fuel gas can fade. Fuel
gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your
guide to safe and proper operation of this heater.
WARNING: Any change to
this heater or its controls can
be dangerous.
WARNING: Do not use a
blower insert, heat exchanger
insert or other accessory not approved for use with this heater.
Due to high temperatures, the
appliance should be located out
of trafc and away from furniture
and draperies.
Do not place clothing or other
ammable material on or near
the appliance. Never place any
objects on the heater.
Surface of heater becomes very
hot when running heater. Keep
children and adults away from
hot surface to avoid burns or
clothing ignition. Heater will
remain hot for a time after shut-
down. Allow surface to cool
before touching.
Carefully supervise young chil-
dren when they are in the same
room with heater.
Make sure grill guard is in place
before running heater.
Keep the appliance area clear
and free from combustible materials, gasoline and other ammable vapors and liquids.
1. This appliance is only for use with the type of
gas indicated on the rating plate. This appliance
is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply
tank(s) outdoors (propane/LP models only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use
any phone in your building
• immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions
• if you cannot reach your gas supplier, call
the re department
4. This heater shall not be installed in a bedroom
or bathroom.
5. This heater needs fresh, outside air ventilation
to run properly. This heater has an Oxygen
Depletion Sensing (ODS) safety shutoff
system. The ODS shuts down the heater if
not enough fresh air is available. See Air for Combustion and Ventilation, page 5.
6. Keep all air openings in front and bottom of
heater clear and free of debris. This will insure
enough air for proper combustion.
7. If heater shuts off, do not relight until you
provide fresh, outside air. If heater keeps
shutting off, have it serviced.
8. Do not run heater
• where ammable liquids or vapors are used
or stored
• under dusty conditions
9. Do not use heater if any part has been under
water. Immediately call a qualied service
technician to inspect the room heater and to
replace any part of the control system and any
gas control which has been under water.
10. Turn off and let cool before servicing. Only
a qualied service person should service and
repair heater.
11. Operating heater above elevations of 4,500
feet could cause pilot outage.
12. To prevent performance problems, do not use
propane/LP fuel tank of less than 100 lbs.
capacity (propane/LP models only).
113061-01F3
www.desatech.com
SAFETY INFORMATION
Continued
13. Before using furniture polish, wax, carpet
cleaner or similar products, turn heater off. If
heated, the vapors from these products may
create a white powder residue within burner
box or on adjacent walls or furniture.
14. Prov id e adequate clearances around air
openings.
LOCAL CODES
Install and use heater with care. Follow all local codes. In the absence of local codes, use the
latest edition of National Fuel Gas Code, ANSI
Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
State of Massachusetts: The installation must
be made by a licensed plumber or gas tter in
the Commonwealth of Massachusetts.
Sellers of unvented propane or natural gas-red
supplemental room heaters shall provide to
each purchaser a copy of 527 CMR 30 upon
sale of the unit.
Vent-free gas products are prohibited for bed-
room and bathroom installation in the Com-
monwealth of Massachusetts.
UNPACKING
1. Remove heater from carton.
2. Remove all protective packaging applied to
heater for shipment.
3. Check heater for any shipping damage. If
heater is damaged, promptly return to dealer
where you bought heater.
PRODUCT IDENTIFICATION
Heater
Cabinet
Front Panel
Figure 1 - Vent-Free Gas Heater
Ignitor
Button
Glass Panel
Control
Knob
Grill Guard
PRODUCT FEATURES
SAFETY DEVICE
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The
ODS/pilot is a required feature for vent-free room
heaters. The ODS/pilot shuts off the heater if there
is not enough fresh air.
IGNITION SYSTEM
This heater has an electronic ignitor to light heater
fuel supply.
THERMOSTATIC HEAT CONTROL
Thermostat models have a thermostat sensing
bulb and a control valve. This results in the greatest heater comfort. This can also result in lower
gas bills.
www.desatech.com
113061-01F4
AIR FOR COMBUSTION
AND VENTILATION
WARNING: This heater shall
not be installed in a conned
space or unusually tight construction unless provisions are
provided for adequate combustion and ventilation air. Read the
following instructions to insure
proper fresh air for this and
other fuel-burning appliances
in your home.
Today’s homes are built more energy efcient
than ever. New materials, increased insulation and
new construction methods help reduce heat loss
in homes. Home owners weather strip and caulk
around windows and doors to keep the cold air out
and the warm air in. During heating months, home
owners want their homes as airtight as possible.
While it is good to make your home energy efcient, your home needs to breathe. Fresh air must
enter your home. All fuel-burning appliances need
fresh air for proper combustion and ventilation.
Exhaust fans, replaces, clothes dryers and fuel
burning appliances draw air from the house to
operate. You must provide adequate fresh air for
these appliances. This will insure proper venting
of vented fuel-burning appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3,
Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 5 through 7 will help
you classify your space and provide adequate
ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion and
ventilation. However, in buildings of unusually
tight construction, you must provide additional
fresh air.
Unusually tight construction is dened as construction where:
a. walls and ceilings exposed to the outside
atmosphere have a continuous water vapor
retarder with a rating of one perm (6x10
per pa-sec-m2) or less with openings gasketed
or sealed and
b. weather stripping has been added on openable
windows and doors and
c. caulking or sealants are applied to areas such
as joints around window and door frames,
between sole plates and floors, between
wall-ceiling joints, between wall panels, at
penetrations for plumbing, electrical and gas
lines and at other openings.
If your home meets all of the three criteria above,
you must provide additional fresh air. See Ventila-tion Air From Outdoors, page 7.
If your home does not meet all of the three criteria
above, proceed to Determining Fresh-Air Flow For Heater Location, page 6.
Conned and Unconned Space
The National Fuel Gas Code, ANSI Z223.1/NFPA
54 denes a conned space as a space whose
volume is less than 50 cubic feet per 1,000 Btu
per hour (4.8 m3 per kw) of the aggregate input
rating of all appliances installed in that space and
an unconned space as a space whose volume is
not less than 50 cubic feet per 1,000 Btu per hour
(4.8 m3 per kw) of the aggregate input rating of
all appliances installed in that space. Rooms communicating directly with the space in which the
appliances are installed*, through openings not
furnished with doors, are considered a part of the
unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation grills
between them.
-11
kg
113061-01F5
www.desatech.com
AIR FOR COMBUSTION
AND VENTILATION
Continued
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
Determining if You Have a Conned or
Unconned Space
Use this work sheet to determine if you have a conned or unconned space.
Space: Includes the room in which you will install
heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x
width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)
If additional ventilation to adjoining room is
supplied with grills or openings, add the volume
of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
_______ (volume of space) x 20 = (Maximum
Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x 20 =
51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in
the space.
Vent-free heater ______________Btu/Hr
Gas water heater* ______________Btu/Hr
Gas furnace ______________Btu/Hr
Vented gas heater ______________Btu/Hr
Gas replace logs ______________Btu/Hr
Other gas appliances* + _____________Btu/Hr
Total = ____________Btu/Hr
* Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors
and vents to the outdoors.
Example:
Gas water heater ______________Btu/Hr
Vent-free heater + _____________Btu/HrTotal = _____________Btu/Hr
40,000
20,000
60,000
4. Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.
__________ Btu/Hr (maximum the space can
support)
___________Btu/Hr (actual amount of Btu/Hr used)
Example:
51,200 Btu/Hr (maximum the space can support)
60,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the above example is a conned space
because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide
additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoin-
ing room. If the extra space provides an unconned
space, remove door to adjoining room or add
ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.
B. Vent room directly to the outdoors. See Ventila-
tion Air From Outdoors, page 7.
C. Install a lower Btu/Hr heater, if lower Btu/Hr size
makes room unconned.
If the actual Btu/Hr used is less than the maximum
Btu/Hr the space can support, the space is an unconned space. You will need no additional fresh air
ventilation.
WARNING: If the area in
which the heater may be operated is smaller than that dened
as an unconned space or if the
building is of unusually tight
construction, provide adequate
combustion and ventilation air
by one of the methods described
in the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 Section 5.3
or applicable local codes.
www.desatech.com
113061-01F6
AIR FOR COMBUSTION
Outlet
Air
Ventilated
Attic
Outlet
A
ir
Inlet
Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
Or
Remove
Door into
Adjoining
Room,
Option 3
Ventilation Grills
Into Adjoining Room,
Option 2
12"
12"
Ventilation
Grills
into Adjoining
Room,
Option 1
AND VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconned space. When ventilating to an adjoining
unconned space, you must provide two permanent openings: one within 12" of the ceiling and
one within 12" of the oor on the wall connecting
the two spaces (see options 1 and 2, Figure 2). You
can also remove door into adjoining room (see
option 3, Figure 2). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for
Combustion and Ventilation for required size of
ventilation grills or ducts.
Figure 3 - Ventilation Air from Outdoors
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your primary heat source. If you have a
central heating system, you may
run system’s circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
WARNING: A qualied service person must install heater.
Follow all local codes.
Figure 2 - Ventilation Air from Inside
Building
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or
ducts. You must provide two permanent openings:
one within 12" of the ceiling and one within 12"
of the oor. Connect these items directly to the
outdoors or spaces open to the outdoors. These
spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54,
Section 5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet
or outlet air into attic if attic has a thermostatcontrolled power vent. Heated air entering the attic
will activate the power vent.
113061-01F7
www.desatech.com
CHECK GAS TYPE
Use only the correct type of gas (natural or propane/LP). If your gas supply is not the correct gas
type, do not install heater. Call dealer where you
bought heater for proper type heater.
This appliance is only for use
with the type of gas indicated on
the rating plate. This appliance
is not convertible for use with
other gases.
WARNING: This appliance
is equipped for (natural or propane/LP) gas. Field conversion
is not permitted.
Minimum
From
Sides Of
Heater
36"
2"
FLOOR
CEILING
Minimum
Minimum To
Top Surface
Of Carpeting,
Tile Or Other
Combustible
Material
6"
Left
Side
Right
Side
INSTALLATION
Continued
INSTALLATION ITEMS
Before installing heater, make sure you have the
items listed below.
• for propane/LP gas, external regulator (supplied
by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• ground joint union
• test gauge connection*
• sediment trap
• tee joint
• pipe wrench
* A CSA design-certied equipment shutoff valve
with 1/8" NPT tap is an acceptable alternative to
test gauge connection. The optional CSA designcertied equipment shutoff valve can be purchased
from your dealer. See Accessories, page 21.
LOCATING HEATER
WARNING: Maintain the
minimum clearances shown
in Figure 4. If you can, provide
greater clearances from oor,
ceiling and joining wall.
You can locate heater on the oor, away from a
wall. A wall mounting bracket and oor base stand
are included with this heater. Determine which
method is best for your application.
WARNING: Never install the
heater
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture,
clothing or other ammable
objects are less than 36" from
the front, top or sides of the
heater
• as a replace insert
• in high trafc areas
• in windy or drafty areas
CAUTION: This heater cre-
ates warm air currents. These
currents move heat to wall sur-
faces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater
where impurities (such as, but
not limited to, tobacco smoke,
aromatic candles, cleaning uids, oil or kerosene lamps, etc.) in
the air exist, may discolor walls
or cause odors.
IMPORTANT: Vent-free heaters add moisture to
the air. Although this is benecial, installing heater
in rooms without enough ventilation air may cause
mildew to form from too much moisture. See Air for Combustion and Ventilation, page 5.
Figure 4 - Mounting Clearances As
Viewed From Front of Heater
www.desatech.com
CAUTION: If you install the
heater in a home garage
• heater pilot and burner must
be at least 18" above oor
• locate heater where moving
vehicle will not hit it
For convenience and efciency, install heater
• where there is easy access for operation, inspection and service
• in coldest part of room
An optional fan kit is available from your dealer.
See Accessories, page 21. If planning to use fan,
locate heater near an electrical outlet.
113061-01F8