Desa VP16, VN18T, VN18IT, VN30, VN30T, VN25IT, VN18, VP26, VP16IT, VP16T, VP26T, VP22IT User Manual
For more information, visit www.desatech.com
For more information, visit www.desatech.com
VN18, VN18T
VP16, VP16T
VP26, VP26T
VN30, VN30T
VP16IT, VN18IT
VP22IT, VN25IT
UNVENTED (VENT-FREE)
INFRARED GAS HEATER
SAFETY INFORMATION AND
®
INSTALLATION MANUAL
Model VN30 Shown
WARNING: If the information in this manual is not
followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
— Installation and service must be performed by a quali-
fied installer, service agency, or the gas supplier.
WARNING: Improper installation,
adjustment, alteration, service, or
maintenance can cause injury or
property damage. Refer to this
manual for correct installation and
operational procedures. For assistance or additional information
consult a qualified installer, service agency, or the gas supplier.
WARNING: This is an unvented
gas-fired heater. It uses air (oxygen) from the room in which it is
installed. Provisions for adequate
combustion and ventilation air
must be provided. Refer to
Combustion and Ventilation
Air for
sec-
tion on page 4 of this manual.
This appliance may be installed in an aftermarket*, permanently located, manufactured
(mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance
is not convertible for use with other gases.
*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Save this manual for future reference.
Save this manual for future reference.
TABLE OF CONTENTS
SAFETY INFORMATION
2
TABLE OF CONTENTS
SAFETY INFORMATION ............................................................ 2
LOCAL CODES........................................................................... 3
CLEANING AND MAINTENANCE ............................................ 17
SAFETY INFORMATION
WARNINGS
IMPORTANT: Read this owner’s manual carefully and
completely before trying to assemble, operate, or service this heater. Improper use of this heater can cause
serious injury or death from burns, fire, explosion,
electrical shock, and carbon monoxide poisoning.
DANGER: Carbon monoxide poisoning may lead
to death!
Carbon Monoxide Poisoning: Early signs of carbon monoxide
poisoning resemble the flu, with headaches, dizziness, or nausea. If
you have these signs, the heater may not be working properly. Getfresh air at once! Have heater serviced. Some people are more
affected by carbon monoxide than others. These include pregnant
women, people with heart or lung disease or anemia, those under the
influence of alcohol, and those at high altitudes.
Natural and Propane/LP Gas: Natural and propane/LP gases are
fuel gases. Fuel gases are odorless. An odor-making agent are added
to fuel gases. The odor helps you detect a fuel gas leak. However,
the odor added to fuel gas can fade. Fuel gas may be present even
though no odor exists.
Make certain you read and understand all warnings. Keep this
manual for reference. It is your guide to safe and proper operation
of this heater.
WARRANTY INFORMATION ...................................... Back Cover
Due to high temperatures, the appliance should be
located out of traffic and away from furniture and
draperies.
Do not place clothing or other flammable material on
or near the appliance. Never place any objects on the
heater.
Surface of heater becomes very hot when running
heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater will
remain hot for a time after shutdown. Allow surface to
cool before touching.
Carefully supervise young children when they are in
the same room with heater.
Make sure grill guard is in place before running
heater.
Keep the appliance area clear and free from combustible materials, gasoline and other flammable vapors
and liquids.
1.This appliance is only for use with the type of gas indicated on
the rating plate. This appliance is not convertible for use with
other gases.
2.Do not place propane/LP supply tank(s) inside any structure.
Locate propane/LP supply tank(s) outdoors.
3.This heater shall not be installed in a bedroom or bathroom.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
107887-01E
SAFETY INFORMATION
LOCAL CODES
PRODUCT IDENTIFICATION
UNPACKING
PRODUCT FEATURES
3
3
SAFETY INFORMATION
Continued
4.If you smell gas
• Shut off gas supply
• Do not try to light any appliance
• Do not touch any electrical switch; do not use any phone in
your building
• Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions
• If you cannot reach your gas supplier , call the fire department
5.Always run heater with plaque control knob at the 1, 2, 3, or 4
locked positions. Never set control knob between locked positions.
Poor combustion and higher levels of carbon monoxide may result.
6.This heater needs fresh, outside air ventilation to run properly .
This heater has an Oxygen Depletion Sensing (ODS) safety
shutoff system. The ODS shuts down the heater if not enough
fresh air is available. See Air for Combustion and Ventilation,
pages 4 through 6.
7.If heater shuts off, do not relight until you provide fresh, outside air. If heater keeps shutting off, have it serviced.
8.Do not run heater
• where flammable liquids or vapors are used or stored
• under dusty conditions
9.Do not use heater if any part has been under water. Immediately call a qualified service technician to inspect the room
heater and to replace any part of the control system and any
gas control which has been under water.
10. Turn off heater, unplug blower and let heater cool before servicing. Only a qualified service person should service and repair heater.
11. Operating heater above elevations of 4,500 feet could cause
pilot outage.
12. To prevent performance problems, do not use propane/LP fuel
tank of less than 100 lbs. capacity.
13. Before using furniture polish, wax, carpet cleaner, or similar
products, turn heater off. If heated, the vapors from these products may create a white powder residue within burner box or
on adjacent walls or furniture.
14. Provide adequate clearances around air openings.
LOCAL CODES
Install and use heater with care. Follow all local codes. In the absence
of local codes, use the latest edition of National Fuel Gas Code, ANSIZ223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
PRODUCT IDENTIFICATION
Ignitor Button
Front
Panel
Figure 1 - Vent-Free Gas Heater
Control Knob
Grill
Guard
Plaque
Heater
Cabinet
UNPACKING
1.Remove heater from carton.
2.Remove all protective packaging applied to heater for shipment.
3.Check heater for any shipping damage. If heater is damaged,
promptly inform dealer where you bought heater.
PRODUCT FEATURES
SAFETY DEVICE
This heater has a pilot with an Oxygen Depletion Sensing (ODS)
safety shutoff system. The ODS/pilot is a required feature for ventfree room heaters. The ODS/pilot shuts off the heater if there is not
enough fresh air.
PIEZO IGNITION SYSTEM
This heater has a piezo ignitor. This system requires no matches,
batteries, or other sources to light heater.
THERMOSTATIC HEAT CONTROL
(Thermostat Models Only)
Thermostat models have a thermostat sensing bulb and a control
valve. This results in the greatest heater comfort. This can also result
in lower gas bills.
107887-01E
For more information, visit www.desatech.com
For more information, visit www.desatech.com
AIR FOR COMBUSTION AND VENTILATION
4
Providing Adequate Ventilation
AIR FOR COMBUSTION AND
VENTILATION
WARNING: This heater shall not be installed in a
confined space or unusually tight construction unless provisions are provided for adequate combustion
and ventilation air. Read the following instructions to
insure proper fresh air for this and other fuel-burning
appliances in your home.
Today’s homes are built more energy efficient than ever. New
materials, increased insulation, and new construction methods help
reduce heat loss in homes. Home owners weather strip and caulk
around windows and doors to keep the cold air out and the warm air
in. During heating months, home owners want their homes as airtight
as possible.
While it is good to make your home energy efficient, your home
needs to breathe. Fresh air must enter your home. All fuel-burning
appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances
draw air from the house to operate. You must provide adequate fresh
air for these appliances. This will insure proper venting of vented
fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation
classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space
The information on pages 4 through 6 will help you classify your
space and provide adequate ventilation.
Unusually tight construction is defined as construction
where:
a.walls and ceilings e xposed to the outside atmosphere
have a continuous water vapor retarder with a rating
of one perm (6x10
openings gasketed or sealed
b. weather stripping has been added on openable win-
dows and doors
c. caulking or sealants are applied to areas such as
joints around window and door frames, between sole
plates and floors, between wall-ceiling joints, between
wall panels, at penetrations for plumbing, electrical,
and gas lines, and at other openings.
If your home meets all of the three criteria above, you
must provide additional fresh air. See
From Outdoors
If your home does not meet all of the three criteria above,
proceed to
tion
, page 5.
, page 6.
Determining Fresh-Air Flow For Heater Loca-
-11
kg per pa-sec-m2) or less with
and
and
Ventilation Air
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a
confined space as a space whose volume is less than 50 cubic feet
per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating
of all appliances installed in that space and an unconfined space as
a space whose volume is not less than 50 cubic feet per 1,000 Btu per
hour (4.8 m3 per kw) of the aggregate input rating of all appliances
installed in that space. Rooms communicating directly with the
space in which the appliances are installed*, through openings not
furnished with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless
passageways or ventilation grills between them.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough
fresh air for combustion and ventilation. However, in buildings of
unusually tight construction, you must provide additional fresh air.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
107887-01E
AIR FOR COMBUSTION AND
VENTILATION
Continued
AIR FOR COMBUSTION AND VENTILATION
Determining Fresh-Air Flow For Heater Location
5
5
DETERMINING FRESH-AIR FLOW FOR
HEATER LOCATION
Determining if You Have a Confined or
Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining
rooms with doorless passageways or ventilation grills between the rooms.
1.Determine the volume of the space (length x width x height).
Length x Width x Height =___________ cu. ft. (volume of space)
Example:
height) = 2560 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or open-
ings, add the volume of these rooms to the total volume of the space.
2.Multiply the space volume by 20 to determine the maximum Btu/Hr
the space can support.
__________ (volume of space) x 20 = (Maximum Btu/Hr the space
Example:
Btu/Hr the space can support)
3.Add the Btu/Hr of all fuel burning appliances in the space.
* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling
can support)
2560 cu. ft. (volume of space) x 20 = 51,200 (maximum
Vent-free heater_____________ Btu/Hr
Gas water heater*_____________ Btu/Hr
Gas furnace_____________ Btu/Hr
Vented gas heater_____________ Btu/Hr
Gas fireplace logs_____________ Btu/Hr
Other gas appliances* + _____________ Btu/Hr
Total = _____________ Btu/Hr
Example:
Gas water heater_____________ Btu/Hr
Vent-free heater+ _____________ Btu/Hr
Total= _____________ Btu/Hr
40,000
20,000
60,000
4.Compare the maximum Btu/Hr the space can support with the actual
amount of Btu/Hr used.
__________________ Btu/Hr (maximum the space can support)
__________________ Btu/Hr (actual amount of Btu/Hr used)
Example:
The space in the above example is a confined space because the actual Btu/
Hr used is more than the maximum Btu/Hr the space can support. You must
provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the ex-
tra space provides an unconfined space, remove door to adjoining
room or add ventilation grills between rooms. See V entilation Air Fr omInside Building, page 6.
B. Vent room directly to the outdoors. See Ventilation Air From Out-
doors, page 6.
C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room un-
confined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can
support, the space is an unconfined space. You will need no additional fresh
air ventilation.
51,200 Btu/Hr (maximum the space can support)
60,000 Btu/Hr (actual amount of Btu/Hr used)
WARNING: If the area in which the heater may be
operated is smaller than that defined as an unconfined space or if the building is of unusually tight
construction, provide adequate combustion and ventilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 Section 5.3
or applicable local codes
.
107887-01E
For more information, visit www.desatech.com
For more information, visit www.desatech.com
AIR FOR COMBUSTION AND VENTILATION
6
Ventilation Air
AIR FOR COMBUSTION AND
VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space.
When ventilating to an adjoining unconfined space, you must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor on the wall connecting the two spaces
(see options 1 and 2, Figure 2). You can also remove door into
adjoining room (see option 3, Figure 2). Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion
and Ventilation for required size of ventilation grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor. Connect these items directly to the
outdoors or spaces open to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation
for required size of ventilation grills or ducts.
IMPORTANT:
attic if attic has a thermostat-controlled power vent. Heated air
entering the attic will activate the power vent.
Do not provide openings for inlet or outlet air into
Ventilation Grills
Ventilation
Grills
into Adjoining
Room,
Option 1
Figure 2 - Ventilation Air from Inside Building
Or
Remove
Door into
Adjoining
Room,
Option 3
Into Adjoining Room,
Option 2
12"
12"
Outlet
Air
Outlet
Air
Inlet
Air
Inlet Air
Figure 3 - Ventilation Air from Outdoors
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Ventilated
Attic
Crawl Space
To Attic
To
Crawl
Space
Ventilated
107887-01E
INSTALLATION
INSTALLATION
Check Gas Type
Installation Items
Locating Heater
7
7
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary
heating system. Do not install this heater as your
primary heat source. If you have a central heating
system, you may run system’s circulating blower
while using heater. This will help circulate the heat
throughout the house. In the event of a power outage,
you can use this heater as your primary heat source.
WARNING: A qualified service person must in-
stall heater. Follow all local codes.
CHECK GAS TYPE
Use only the correct type of gas (natural or propane/LP). If your gas
supply is not the correct gas type, do not install heater. Call dealer
where you bought heater for proper type heater.
INSTALLATION ITEMS
Before installing heater, make sure you have the items listed below.
• for propane/LP gas, external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• ground joint union
• sediment trap
• tee joint
• pipe wrench
• for natural gas, test gauge connection*
* A CSA design-certified equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge connection. The
optional CSA design-certified equipment shutoff valve can be
purchased from your dealer. See Accessories, page 30.
WARNING: Never install the heater
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture, clothing, or other flam-
mable objects are less than 36 inches from the
front, top, or sides of the heater
• as a fireplace insert
• in high traffic areas
• in windy or drafty areas
CAUTION: If you install the heater in a home garage
• heater pilot and burner must be at least 18 inches
above floor
• locate heater where moving vehicle will not hit it
CAUTION: This heater creates warm air currents.
These currents move heat to wall surfaces next to heater.
Installing heater next to vinyl or cloth wall coverings or
operating heater where impurities (such as, but not
limited to, tobacco smoke, aromatic candles, cleaning
fluids, oil or kerosene lamps, etc.) in the air exist, may
discolor walls or cause odors.
IMPORTANT:
Vent-free heaters add moisture to the air. Although
this is beneficial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See
Air for Combustion and Ventilation, pages 4 through 6. If high
humidity is experienced, a dehumidifier may be used to help lower
the water vapor content in the air.
For convenience and efficiency, install heater
• where there is easy access for operation, inspection, and service
• in coldest part of room
An optional fan kit is available from your dealer. See Accessories,
page 30. If planning to use fan, locate heater near an electrical outlet.
CEILING
LOCATING HEATER
WARNING: Maintain the minimum clearances
shown in Figure 4. If you can, provide greater clearances from floor, ceiling, and joining wall.
You can locate heater on the floor, away from a wall. A wall
mounting bracket and floor base stand are included with this heater.
Determine which method is best for your application.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
107887-01E
36"
10"
Minimum
From
Sides Of
Heater
Left
Side
FLOOR
Figure 4 - Mounting Clearances As Viewed From Front of Heater
Minimum
Right
Side
2"
Minimum To
Top Surface
Of Carpeting,
Tile Or Other
Combustible
Material
INSTALLATION
8
Thermostat Sensing Bulb
Installing Heater To Wall
INSTALLATION
Continued
THERMOSTAT SENSING BULB
(Thermostat Models Only)
The thermostat sensing bulb has been placed inside the heater for
protection during shipping.
2.Locate thermostat sensing bulb just under burner assembly.
IMPORTANT:
proper operation.
Attach thermostat sensing bulb to back of heater for
Attaching Thermostat Sensing Bulb
1.Remove thermostat sensing bulb from holders inside heater.
Route through slot opening in bottom of heater.
2.Place clamp on thermostat sensing bulb as shown in Figure 5.
Clamp is provided in hardware package.
3.Snap clamp into upper mounting hole as shown in Figure 5.
Mounting hole is located on lower left edge on back of heater.
Make sure the thermostat sensing bulb is pointing up.
Thermostat Sensing Bulb
Clamp
Figure 5 - Attaching Thermostat Sensing Bulb
INSTALLING HEATER TO WALL
Mounting Bracket
Locate mounting bracket in heater carton. Remove mounting bracket
from heater carton.
Removing Front Panel Of Heater
1.Remove the four painted screws, two on each side of front panel.
2.Pull bottom of front panel forward, then out.
3.Remove any remaining packaging materials.
Figure 7 - Removing Front Panel Of Heater
Methods For Attaching Mounting Bracket To Wall
Only use last hole on each end of mounting bracket to attach bracket
to wall. These two holes are 14 inches apart from their centers.
Attach mounting bracket to wall in one of two ways:
1.Attaching to wall stud
2.Attaching to wall anchor
Attaching to Wall Stud: This method provides the strongest hold.
Insert mounting screws through mounting bracket and into wall studs.
Attaching to Wall Anchor: This method allows you to attach
mounting bracket to hollow walls (wall areas between studs) or to
solid walls (concrete or masonry).
Decide which method better suits your needs. Either method will
provide a secure hold for the mounting bracket.
Marking Screw Locations
1.Tape mounting bracket to wall where heater will be located.
Make sure mounting bracket is level.
WARNING: Maintain minimum clearances shown
in Figure 8, page 9. If you can, provide greater clearances from floor and joining wall.
Figure 6 - Mounting Bracket
For more information, visit www.desatech.com
For more information, visit www.desatech.com
107887-01E
INSTALLATION
Continued
INSTALLATION
Installing Heater To Wall (Cont.)
9
9
2.Mark screw locations on wall (see Figure 8).
Note:
Only mark last hole on each end of mounting bracket.
Insert mounting screws through these holes only.
3.Remove tape and mounting bracket from wall.
16"
Min.
Only Insert Mounting
Screws Through Last
Adjoining Wall
12"
Min.
Adjoining Wall
Figure 8 - Mounting Bracket Clearances
Hole On Each End
4 and 5 Plaque Heaters
Only Insert Mounting
Screws Through Last
Hole On Each End
3 Plaque Heater
Floor
14"
Floor
14"
25 3/4"
Optional
19 3/4"
Min.
25 3/4"
Optional
19 3/4"
Min.
Attaching Mounting Bracket To Wall
Note:
Wall anchors, mounting screws, and spacers are in hardware
package. The hardware package is provided with heater.
Attaching To Wall Anchor Method
For attaching mounting bracket to hollow walls (wall areas between
studs) or solid walls (concrete or masonry)
1.Drill holes at marked locations using 5/16" drill bit. For solid
walls (concrete or masonry), drill at least 1" deep.
2.Fold wall anchor as shown in Figure 9.
3.Insert wall anchor (wings first) into hole. Tap anchor flush to wall.
4.For thin walls (1/2" or less), insert red key into wall anchor.
Push red key to “pop” open anchor wings.
IMPORTANT:
Do not hammer key!
For thick walls (over 1/2" thick) or solid walls, do not pop
open wings.
5.Place mounting bracket onto wall. Line up last hole on each
end of bracket with wall anchors.
6.Insert mounting screws through bracket and into wall anchors.
7.Tighten screws until mounting bracket is firmly fastened to wall.
Figure 9 - Folding Anchor
Figure 10 - Popping Open
Anchor Wings For Thin Walls
Placing Heater On Mounting Bracket
1.Locate two horizontal slots on back panel of heater.
1.Drill holes at marked locations using 9/64" drill bit.
2.Place mounting bracket onto wall. Line up last hole on each
end of bracket with holes drilled in wall.
3.Insert mounting screws through bracket and into wall studs.
4.Tighten screws until mounting bracket is firmly fastened to
wall studs.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
107887-01E
Stand-Out Tab
Figure 11 - Mounting Heater Onto Mounting Bracket
Mounting Bracket
(attached to wall)
INSTALLATION
10
Installing Heater To Wall (Cont.)
Mounting Heater To Floor
INSTALLATION
Continued
Installing Bottom Mounting Screws
1.Locate two bottom mounting holes. These holes are near bottom on back panel of heater (see Figure 12).
2.Mark screw locations on wall.
3.Remove heater from mounting bracket.
4.If installing bottom mounting screws into hollow or solid wall,
install wall anchors. Follow steps 1 through 4 under Attaching T oW all Anc hor Method, page 9.
If installing bottom mounting screw into wall stud, drill holes
at marked locations using 9/64" drill bit.
5.Replace heater onto mounting bracket.
6.Place spacers between bottom mounting holes and wall anchor
or drilled hole.
7.Hold spacer in place with one hand. With other hand, insert
mounting screw through bottom mounting hole and spacer.
Place tip of screw in opening of wall anchor or drilled hole.
8.Tighten both screws until heater is firmly secured to wall. Do
not over tighten.
Note:
Do not replace front panel at this time. Replace front
panel after making gas connections and checking for leaks (see
pages 11 and 12).
MOUNTING HEATER TO FLOOR
Mounting Base Feet to Heater
1.Lay heater cabinet on its back on a table with the heater bottom overhanging the table edge.
2.Align holes in base foot with mounting holes on bottom of
cabinet (see Figure 13).
3.Secure base foot to heater using sheet metal screws.
4.Repeat for other side.
Mounting Base Feet to Floor (Where required by
local code)
1.Remove front cover (see Removing Front Panel of Heater , page 8).
2.Position heater with base feet in desired location. Mark holes
for drilling. Remove heater with base.
3.For carpeted floors, make a small cut with a sharp knife at
marked locations prior to drilling. If mounting base to a wood
floor, drill 1/8 inch diameter hole, 3/4 inch deep. (Do not use
anchors in wood floors).
If mounting base to a concrete floor, drill with 1/4 inch diameter concrete drill bit, 13/8 inches into floor. Insert anchors completely into holes.
4.Reposition heater with base feet over holes. Secure base to floor
with wood screws. See Figure 13.
Front View
Heater
Spacer
Side View
Figure 12 - Installing Bottom Mounting Screws
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Wood
Screw
Wall
Base Foot
Sheet Metal Screw
Figure 13 - Installing Base Feet
107887-01E
INSTALLATION
Continued
INSTALLATION
Connecting To Gas Supply
11
11
CONNECTING TO GAS SUPPLY
WARNING: This appliance requires a 3/8" NPT
(National Pipe Thread) inlet connection to the pressure regulator.
WARNING: A qualified service person must connect heater to gas supply. Follow all local codes.
WARNING: For natural gas, never connect heater
to private (non-utility) gas wells. This gas is commonly known as wellhead gas.
IMPORTANT
connecting heater to gas line. Gas line pressure must be no greater
than 14 inches of water. If gas line pressure is higher, heater
regulator damage could occur.
CAUTION: For propane/LP gas, never connect
heater directly to the propane/LP supply. This heater
requires an external regulator (not supplied). Install
the external regulator between the heater and propane/LP supply.
For propane/LP gas, the installer must supply an external regulator.
The external regulator will reduce incoming gas pressure. You must
reduce incoming gas pressure to between 11 and 14 inches of water.
If you do not reduce incoming gas pressure, heater regulator damage
could occur. Install the external regulator with the vent pointing
down as shown in Figure 14. Pointing the vent down protects it from
freezing rain or sleet.
: For natural gas, check gas line pressure before
Typical Inlet Pipe Diameters
VN18(T), VP16(T), VN18IT, and VP16IT - 3/8" or greater
VN30(T), VP26(T), VN25IT, and VP22IT - 1/2" or greater
Installation must include equipment shutoff valve, union, and
plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from heater (see Figure 15).
IMPORTANT:
Install an equipment shutoff valve in an accessible
location. The equipment shutoff valve is for turning on or shutting
off the gas to the appliance.
Apply pipe joint sealant lightly to male NPT threads. This will
prevent excess sealant from going into pipe. Excess sealant in pipe
could result in clogged heater valves.
WARNING: Use pipe joint sealant that is resistant
to liquid petroleum (LP) gas.
We recommend that you install a sediment trap in supply line as
shown in Figure 15. Locate sediment trap where it is within reach for
cleaning. Install in piping system between fuel supply and heater.
Locate sediment trap where trapped matter is not likely to freeze. A
sediment trap traps moisture and contaminants. This keeps them
from going into heater controls. If sediment trap is not installed or
is installed wrong, heater may not run properly.
IMPORTANT:
Hold the pressure regulator with wrench when
connecting it to gas piping and/or fittings. Do not over tighten pipe
connection to regulator. The regulator body could be damaged.
Pressure Regulator
Regulator Bracket
Propane/LP
Supply
Tank
Figure 14 - External Regulator With Vent Pointing Down
External
Regulator
Vent
Pointing
Down
CAUTION: Use only new, black iron or steel pipe.
Internally-tinned copper tubing may be used in certain
areas. Check your local codes. Use pipe of large
enough diameter to allow proper gas volume to heater.
If pipe is too small, undue loss of volume will occur.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
107887-01E
Heater Cabinet
3/8" NPT Pipe Nipple
Test
Gauge
Connection*
Sediment
Trap
Figure 15 - Gas Connection
Tee Joint
Reducer
Bushing to
1/8" NPT
1/8" NPT
Plug Tap
Tee Joint
Pipe Nipple
Cap
3"
Minimum
Ground Joint Union
Equipment
Shutoff Valve *
Natural Gas
From Gas Meter
(7" W.C. to 10.5" W.C.
Pressure)
Propane/LP
From External
Regulator
(11" W.C. to 14" W.C.
Pressure)
* A CSA design-certified equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge connection. Purchase
the optional CSA design-certified equipment shutoff valve from
your dealer. See Accessories, page 30.