Desa VMH10TP User Manual

Page 1
®
VENT -FREE PROPANE/LP GAS
COMPACT CLASSIC HEARTH FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
®
Shown with Optional Cabinet Mantel/Hearth
10,000 Btu/Hr with
VMH10TP
Base Accessory
WARNING: If the information in this manual is not fol­lowed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s in­structions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a quali­fied installer, service agency, or the gas supplier.
This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state or local codes. This appliance may be installed in bedroom where not prohibited by state or local codes.
*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer. (I.E. Installation of this product is permitted after the manufactured (mobile) home is sited)
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
Save this manual for future reference.
WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For as­sistance or additional information consult a qualified installer, ser­vice agency, or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses air (oxy­gen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to
Combustion and Ventilation
tion on page 6 of this manual.
Air for
sec-
Page 2
CONTENTS
WARNING ICON G 001
SECTION PAGE
Safety Information...................................................................................2
Product Identification ..............................................................................4
Local Codes ............................................................................................. 4
Product Features ......................................................................................4
Unpacking................................................................................................4
Assembly .................................................................................................5
Air for Combustion and Ventilation........................................................6
Installation ...............................................................................................10
Connecting to Gas Supply ....................................................................... 16
Checking Gas Connections......................................................................18
Operating Fireplace .................................................................................20
Inspecting Burner ....................................................................................22
Cleaning and Maintenance ......................................................................24
Troubleshooting....................................................................................... 24
Technical Service .................................................................................... 28
Specifications ..........................................................................................28
Service Hints ...........................................................................................28
Replacement Parts ...................................................................................28
Illustrated Parts List................................................................................. 30, 31
Accessories ..............................................................................................29
Warranty Information ..............................................................................32
SAFETY
INFORMATION
W ARNINGS
WARNING ICON G 001
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, operate, or service this fireplace. Improper use of this fireplace can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
DANGER
Carbon monoxide poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning
resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the fireplace may not be working properly. Get fresh air at once! Have fireplace serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Propane/LP Gas: Propane/LP gas is odorless. An odor-making agent is added to propane/LP gas. The odor helps you detect a propane/LP gas leak. However, the odor added to propane/LP gas can fade. Propane/LP gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this fireplace.
2
Safety Information continues on next page
103669
Page 3
SAFETY
INFORMATION
Continued
.
WARNINGS
WARNING ICON G 001
WARNING: Any change to this fireplace or its controls can be dangerous.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors.
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use any phone in your building
• immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions
• if you cannot reach your gas supplier, call the fire department
4. This fireplace shall not be installed in a bathroom.
5. Never install the fireplace
• in a recreational vehicle.
• where curtains, furniture, clothing, or other flammable objects are less than 36 inches from the front, top, or sides of the fireplace.
• as a fireplace insert.
• in high traffic areas.
• in windy or drafty areas.
6. Do not use this fireplace as a wood-burning fireplace. Use only the logs provided with the fireplace.
7. Do not add extra logs or ornaments such as pine cones, vermiculite, or rock wool. Using these added items can cause sooting. Do not add lava rock around base. Rock and debris could fall into the control area of fireplace.
8. You must operate this fireplace with the fireplace screen in place. Make sure fireplace screen is in place before running fireplace.
9. This fireplace is designed to be smokeless. If logs ever appear to smoke, turn off fireplace and call a qualified service person. Note: During initial operation, slight smoking could occur due to log curing and fireplace burning manufacturing residues.
10. Do not allow fans to blow directly into the fireplace. Avoid any drafts that alter burner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
11. This fireplace needs fresh air ventilation to run properly. This fireplace has an oxygen depletion sensor (ODS) pilot light safety system. The ODS shuts down the fireplace if not enough fresh air is available. See Air for Combustion and Ventilation, pages 6 through 9. If fireplace keeps shutting off, see Troubleshooting, pages 24 through 27.
12. Do not run fireplace
• where flammable liquids or vapors are used or stored.
• under dusty conditions.
13. Do not use this fireplace to cook food or burn paper or other objects.
14. Never place any objects in the fireplace or on logs.
15. Fireplace front and screen becomes very hot when running fireplace. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Fireplace will remain hot for a time after shut-down. Allow surfaces to cool before touching.
16. Carefully supervise young children when they are in same room with fireplace.
17. Do not use fireplace if any part has been under water. Immediately call a qualified service technician to inspect the room fireplace and to replace any part of the control system and any gas control which has been under water.
18. Turn off and unplug fireplace and let cool before servicing. Only a qualified service person should service and repair fireplace.
19. Operating fireplace above elevations of 4,500 feet could cause pilot outage.
20. Do not use a blower insert, heat exchanger insert, or other accessory not approved for use with this fireplace.
21. Do not operate fireplace if any log is broken. Do not operate fireplace if a log is chipped (dime-sized or larger).
22. To prevent performance problems, do not use propane fuel tank of less than 100 lbs. capacity.
Continued
103669
3
Page 4
PRODUCT
IDENTIFICATION
Fireplace Cabinet
Screen
Logs
Control Knob
Ignitor Button
Figure 1 - Vent-Free Propane/LP Gas Compact Fireplace
LOCAL CODES
PRODUCT
FEATURES
Install and use fireplace with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code ANSI Z223, also known as NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
Safety Pilot
This fireplace has a pilot with an Oxygen Depletion Sensor Shutoff System (ODS). The ODS/pilot is a required feature for vent-free room fireplaces. The ODS/pilot shuts off the fireplace if there is not enough fresh air.
Piezo Ignition System
This fireplace has a piezo ignitor. This system requires no matches, batteries, or other sources to light fireplace.
Thermostatic Heat Control
This fireplace has a thermostat sensing bulb and a control valve.The thermostat will automatically modulate the heat output to maintain a consistent room temperature. This results in greater fireplace comfort. This can also result in lower gas bills.
UNPACKING
4
1. Remove log box and fireplace from carton. The hood is not attached.
2. Remove all protective packaging applied to fireplace for shipment.
3. Make sure your fireplace includes one hardware packet.
4. Check fireplace for any shipping damage. If fireplace is damaged, promptly inform dealer where you bought fireplace.
103669
Page 5
ASSEMBLY
W ARNING
WARNING ICON G 001
Always have branch support and screen in place before operating fireplace. This prevents excessive temperatures on fireplace surfaces.
ASSEMBLING FIREPLACE
Tools Required: Phillips screwdriver, 5/16" hex wrench, and slotted screwdriver
Installing Log
1. Remove back log, branch, and hood from log box. Discard protective packaging.
2. Remove two shipping screws above screen (see Figure 2).
3. Lift screen up and pull out to remove.
4. An optional blower is available. See Accessories, page 29. Install optional blower now. Follow installation instructions provided with blower.
5. Gently place back log on burner support (see Figure 2). The log should fit flat against top of burner support. Place two #10 one-inch-long screws through burner support into the log and tighten. Place branches on branch support (see Figure 2).
6. Reattach screen by placing the notches in the screen frame over the shoulder screws and pushing down.
Back Log
Screw
Screen Shipping Screw
Shoulder Screw
Burner Support
Screen
Screw
Branch
Figure 2 - Assembling Fireplace
W ARNING
WARNING ICON G 001
Branch Support
Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this fireplace may result in property damage or personal injury
Assembling Hood
1. Locate four black phillips sheet metal screws from the hardware packet.
2. Place hood over top edge of firebox wrapper.
3. Attach screws (see Figure 3).
103669
Figure 3 - Assembling Hood
5
Page 6
AIR FOR
W ARNING
COMBUSTION
AND
VENTILATION
This heater shall not be installed in a confined space unless provisions are provided for adequate combustion and ventilation air. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy efficient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following is excerpts from National Fuel Gas Code. NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classifications:
1. Unusually Tight Construction; 2. Unconfined Space; 3. Confined Space. The information on pages 6 through 9 will help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where: a. walls and ceilings exposed to the outside atmosphere have a continu-
ous water vapor retarder with a rating of one perm (10-6 per-pa-m2) or
less with openings gasketed or sealed b. weather stripping has been added on openable windows and doors c. caulking or sealants are applied to areas such as joints around window
and door frames, between sole plates and floors, between wall-ceiling
joints, between wall panels, at penetrations for plumbing, electrical, and
gas lines, and at other openings.
If your home meets all of the three criteria above, you must provide addi­tional fresh air. See
If your home does not meet all of the three criteria above, proceed to page 7.
Ventilation Air From Outdoors
and
, page 9
and
.
Confined and Unconfined Space
The National Fuel Gas Code (ANSIZ223.1, 1992 Section 5.3) defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfining space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are consid­ered a part of the unconfined space. * Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
6
103669
Page 7
AIR FOR
COMBUSTION
AND
VENTILATION
Continued
DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION
Determining if You Have a Confined or Unconfined Space
Use this worksheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install fireplace plus any adjoining rooms
with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height). Length x Width x Height = ___________________ cu. ft. (volume of space)
Example:
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Multiply the space volume by 1000 Btu/Hr per 50 cubic feet to determine the maximum Btu/Hr the space can support.
____________ (volume of space) x
the space can support)
Example:
Btu/Hr the space can support.
3. Add the Btu/Hr of all fuel burning appliances in the space.
Example:
* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
_________________ Btu/Hr (maximum the space can support) _________________ Btu/Hr (actual amount of Btu/Hr used)
Example:
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides
an unconfined space, remove door to adjoining room or add ventilation grills between
rooms. See Ventilation Air From Inside Building, page 8. B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 9. C. Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
Space size 16 ft. (length) x 14 ft. (width) x 8 ft. (ceiling height) =
1792 cu. ft. (volume of space)
1000 Btu/Hr
50 cu. ft.
1792 cu. ft. (space volume) x
Vent-free fireplace ___________________ Btu/Hr Gas water heater* ___________________ Btu/Hr Gas furnace ___________________ Btu/Hr Vented gas heater ___________________ Btu/Hr Gas fireplace logs ___________________ Btu/Hr Other gas appliances* + ___________________ Btu/Hr Total = ___________________ Btu/Hr
Gas water heater 30,000 Btu/Hr Vent-free fireplace + 10,000 Btu/Hr Total = 40,000 Btu/Hr
35,840 Btu/Hr (maximum the space can support) 40,000 Btu/Hr (actual amount of Btu/Hr used)
1000 Btu/Hr
50 cu. ft.
= (Maximum Btu/Hr
= 35,840 Btu/Hr. This is the maximum
103669
Continued
7
Page 8
AIR FOR
Or
Remove Door into Adjoining
Room,
Option 3
Ventilation Grills
Into Adjoining Room,
Option 2
12"
12"
Ventilation
Grills
into Adjoining
Room,
Option 1
COMBUSTION
AND
VENTILATION
Continued
WARNING
If the area in which the heater may be operated is smaller than that defined as an unconfined space, provide adequate combus­tion and ventilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3
or appli-
cable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 4). You can also remove door into adjoining room (see option 3, Figure 4). Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.
WARNING
Rework worksheet, adding the space of the adjoining unconfined space. appliances in both spaces.
The combined spaces must have enough fresh air to supply all
8
Figure 4 - Ventilation Air from Inside Building Shown with Optional Mantel
103669
Page 9
AIR FOR
COMBUSTION
AND
VENTILATION
Continued
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces.
IMPORTANT:
a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.
Do not provide openings for inlet or outlet air into attic if attic has
Outlet Air
Outlet Air
Inlet Air
Inlet Air
Figure 5 - Ventilation Air from Outdoors Shown with Optional Mantel
Ventilated Attic
To Attic
To
Crawl
Space
Ventilated
Crawl Space
103669
9
Page 10
INSTALLATION
NOTICE
A qualified service person must install fireplace. Follow all local codes.
CHECK GAS TYPE
Use only propane/LP gas. If your gas supply is not propane/LP, do not install fire­place. Call the dealer where you bought your fireplace for the proper type fireplace.
INSTALLATION ITEMS
Before installing fireplace, make sure you have the items listed below.
• external regulator (supplied by installer, see page 16)
• piping (check local codes)
* An A.G.A. design-certified manual shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional A.G.A. design-certified manual shutoff valve from your dealer. See Accessories, page 29.
Note:
If desired, purchase a four-sided brass trim kit for built-in installations. See
Accessories, page 29.
• sealant (resistant to propane/LP gas)
• manual shutoff valve *
• ground joint union
LOCATING FIREPLACE
W ARNING
WARNING ICON G 001
Maintain the minimum clearances shown in Figures 6 and 7 (page 11). If you can, provide greater clearances from floor, ceiling, and joining wall.
• sediment trap
• tee joint
• pipe wrench
IMPORTANT:
require that the fireplace/mantel system be secured to (or within) a wall. You can position fireplace in an optional cabinet or corner mantel. You can also recess fireplace into the wall.
If your fireplace is to be used with an optional mantel, the installation instructions included with your mantel shows an AGA approved method of attaching the fireplace/mantel system to a wall. corner mantels specified in this manual. Purchase the optional mantel from your dealer (see Accessories, page 29).
If your fireplace is to be recessed into the wall, see Built-In Fireplace Installation section of this manual to secure your fireplace into the wall.
Never install the fireplace
• in a bathroom
• in a recreational vehicle
• where curtains, furniture, clothing, or other flammable objects are less than 36 inches from the front, top, or sides of the fireplace
• as a fireplace insert
• in high traffic areas
• in windy or drafty areas
If you install the fireplace in a bedroom, some building codes
IMPORTANT:
WARNING
WARNING ICON G 001
Only use optional cabinet or
10
103669
Page 11
INSTALLATION
6" Minimum From Sides Of Fireplace
Left Side
CEILING
36" Minimum
FLOOR
Right Side
Continued
CAUTION
This fireplace creates warm air currents. These currents move heat to wall surfaces next to fireplace. Installing fireplace next to vinyl or cloth wall coverings or operating fireplace where impurities in the air (such as tobacco smoke) exist, may discolor walls.
IMPORTANT:
Vent-free fireplaces add moisture to the air. Although this is beneficial, installing fireplace in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventilation, pages 6 through 9.
CAUTION
WARNING ICON G 001
If you install the fireplace in a home garage
• fireplace pilot and burner must be at least 18 inches above floor.
• locate fireplace where moving vehicle will not hit it.
For convenience and efficiency, install fireplace
• where there is easy access for operation, inspection, and service.
• in coldest part of room.
An optional blower kit is available from your dealer. See Accessories, page 29. If planning to use blower, follow instructions provided with blower for power source.
103669
Figure 6 - Mounting Clearances As Viewed From Front of Fireplace Shown
Built In The Wall
CEILING
36" Minimum
Top Of Mantel Can Be Flush With Wall
Right
Left Side
Side
Figure 7 - Mounting Clearances As Viewed From Front of Fireplace Shown
with Optional Mantel
11
Page 12
INSTALLING
Continued
BUILT-IN FIREPLACE INSTALLATION
Built-in installation of this fireplace involves installing fireplace into a framed-in enclosure. This makes the front of fireplace flush with wall. An optional brass trim kit accessory is available (see Accessories, page 29). Brass trim will extend past sides of fireplace approximately 1/2 inch. This will cover the rough edges of the wall opening. If installing a built-in mantel above the fireplace, but you must follow the clearances shown in Figure 11, page 13. Follow the instructions below to install the fireplace in this manner.
Note:
Your Vanguard fireplace is designed to be used in zero clearance installations. Wall or framing material can be placed directly against any exterior surface on the rear, sides, or top of your fireplace.
Height Front Width Depth Bottom
Actual Framing Actual Framing Actual Framing Actual Framing
7
26" 26
/8" 26 3/4" 26 7/8"9 1/2" 10 1/2"
1. Frame in rough opening. Use dimensions shown in Figure 8 for the rough opening.
10 1/2"
26 7/8"
3
/4"
3
/4"
12
3/4" Off
26 7/8"
The Floor Minimum
Figure 8 - Rough Opening for Installing in Wall
If installing in a corner, use dimensions shown in Figure 9 for the rough opening. The height is 26
1
/8" which is the same as the wall opening above.
36 5/8"
25 7/8"
26 7/8"
51 3/4"
Figure 9 - Rough Opening for Installing in Corner
2. An optional blower accessory is available (see Accessories, page 29). There
are three options for connecting blower to electrical source.
Option one: Install fireplace near an electrical outlet. See blower instruc-
tions for power cord length.
Option two: Have a licensed electrician install a properly grounded, three-
prong 120-volt electrical outlet at fireplace location. Locate outlet inside the
framed enclosure. Blower power cord will plug into this outlet.
Option three: Have a licensed electrician connect blower to electrical source
at junction box inside fireplace.
If using option one, have electrical outlet installed at this time. If using option two, do not connect blower to electrical source at junction box until step 7.
3. Install gas piping to fireplace location. This installation includes an approved
flexible gas line (if allowed by local codes) after the manual shutoff valve. The flexible gas line must be the last item installed on the gas piping.
4. If you have not assembled firebox, follow instructions on page 5.
5. Carefully set fireplace in front of rough opening with back of fireplace inside
wall opening.
103669
Page 13
INSTALLING
Continued
6. Attach flexible gas line to fireplace gas regulator. See Connecting Fireplace to Gas Supply, page 17.
7. If the optional blower has been installed connect blower to electrical source.
Options one and two: Route blower electrical cord through side or rear
access door of fireplace. Plug electrical cord into electrical outlet.
Option three: Have a licensed electrician connect blower to electrical source
at junction box inside fireplace.
8. Bend four nailing flanges on outer casing with pliers (see Figure 10).
9. Attach fireplace to wall studs using nails or wood screws through holes in nailing flange.
Nails or Wood Screws
Nailing Flanges
Figure 10 - Attaching Fireplace to Wall Studs
10. Check all gas connections for leaks. See Checking Gas Connections, page 18.
11. If using optional brass trim kit, install the trim after final finishing and/or painting of wall. See instructions included with brass trim accessory for attach­ing brass trim.
Mantel Clearances for Built-In Installation
If placing mantel above built-in fireplace, you must meet minimum clearance between mantel shelf and top of fireplace opening.
Mantel Shelf
Side of Firebox
10" 8" 6" 2
1
"
/2
20" 24
Distances to Underside of Built-in Mantel
1
/2
" 27
1
/2
" 30"
Underside of Mantel Shelf
All minimum distances are in inches
Top of Fireplace Opening
103669
Figure 11 - Minimum Mantel Clearances for Built-In Installation
If your installation does not meet the above minimum clearances, you must:
• raise the mantel to an acceptable height, OR
• remove the mantel.
Continued
13
Page 14
INSTALLING
Continued
OPTIONAL MANTEL INSTALLATION
Note:
Refer to instructions provided with the mantel for assembly instructions. Refer to instructions below for system installation. Refer to instructions on page 5 for firebox assembly. Blower accessory should be installed if it is being used (see Accessories, page 29).
1. Unscrew four brass screws that attach top louver to fireplace. Remove louvre
from fireplace and set aside.
2. Place fireplace on wood base.
3. Place mantel around fireplace/base assembly.
4. Assemble brass trim kit. See Assembling Brass Trim, page 15.
5. Firmly snap brass trim kit on shoulder screws. Shoulder screws are located on
fireplace cabinet (see Figure 12).
6. Align brass trim kit for flush fit around opening.
7. Use two 3" wood screws provided and attach fireplace base to wooden base (see
Figure 12).
Shoulder Screws
Hole for 3" wood screw for attaching fireplace to mantel
14
Hole for 3" wood screw
Assembled Brass Trim
Figure 12 - Attaching Brass Trim to Fireplace
for attaching fireplace to wooden base
8. Place assembly next to wall at installation location.
9. Remove brass trim kit and mantel. Be careful not to damage wall or mantel.
10. Attach wood base to floor with two 1 3/4" black screws provided (see Figure 13).
If the floor is concrete use anchor method (see Attaching Wood Base to Solid Floor, page 15).
1 3/4" Screw
Wood Base
Figure 13 - Attaching Wood Base to Floor
11. Install gas line. See Connecting To Gas Supply, pages 16-18.
12. Check for leaks. See Checking Gas Connections, page 18.
13. Place mantel around fireplace. Be careful not to damage wall or mantel.
14. Place brass trim kit on the shoulder screws located on the side and top of the fireplace.
Firmly snap the brass trim over the shoulder screws on fireplace (see Figure 12).
15. Adjust assembly to remove any gaps. Attach remaining two 3" wood screws from
hardware pack through openings inside of fireplace sides into the mantel. The openings are located at top behind the area for the brass louvers (see Figure 13).
16. Reinstall top brass louvers.
103669
Page 15
INSTALLING
Continued
Assembling Brass Trim (Brass trim shipped with mantel)
1. Remove packaging from three remaining pieces of brass trim.
2. Locate two adjusting plates with set screws, and two shims in the hardware packet.
3. Align shim under adjusting plate as shown in Figure 14.
4. Slide one end of adjusting plate/shim in slot on mitered edge of top brass trim (see Figure 14).
5. Slide other end of adjusting plate/shim in slot on mitered edge of side brass trim (see Figure 14).
6. While firmly holding edges of brass trim together, tighten both set screws on the adjusting plate with slotted screwdriver.
7. Repeat steps 1 through 6 for other corner.
8. Set Brass Assembly aside for later installation.
Top Brass Trim
Set Screws
Adjusting Plate
Slot
Shim
Slot
Figure 14 - Assembling Brass Trim
Mitered Edge
Side Brass Trim
Attaching Wood Base to Solid Floor
For attaching base to solid floors (concrete or masonry)
Note:
Floor anchors and mounting screws are in hardware package. The hardware
package is provided with fireplace.
1. Drill holes at marked locations using 5/16" drill bit. For solid floors (concrete or masonry), drill at least 1" deep.
2. Fold floor anchor as shown in Figure 15.
103669
Figure 15 - Folding Anchor
3. Insert floor anchor (wings first) into hole. Tap anchor flush to floor.
4. Insert mounting screws through base and into floor anchors.
5. Tighten screws until base is firmly fastened to floor.
15
Page 16
CONNECTING
NOTICE
TO GAS
SUPPLY
A qualified service person must connect fireplace to gas supply. Follow all local codes.
CAUTION
WARNING ICON G 001
Never connect fireplace directly to the propane/LP supply. This fireplace requires an external regulator (not supplied). Install the external regulator between the fireplace and propane/LP supply.
The installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, fireplace regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 16. Pointing the vent down protects it from freezing rain or sleet.
Propane/LP Supply Tank
External Regulator
Vent Pointing Down
Figure 16 - External Regulator with Vent Pointing Down
CAUTION
WARNING ICON G 001
Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" or greater diameter to allow proper gas volume to fireplace. If pipe is too small, undue loss of pressure will occur.
Installation must include a manual shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 17, page 17).
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves.
Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
Install sediment trap in supply line as shown in Figure 17, page 17. Locate sedi­ment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into fireplace controls. If sediment trap is not installed or is installed wrong, fireplace may not run properly.
CAUTION
WARNING ICON G 001
16
103669
Page 17
CONNECTING
TO GAS
SUPPLY
A.G.A. Design-Certified Manual Shutoff Valve With 1/8" NPT Tap*
Continued
Approved Flexible Gas Line
From External Regulator
3" Minimum
Figure 17 - Gas Connection
* Purchase the optional A.G.A. design-certified manual shutoff valve from your dealer. See Accessories, page 29.
(11" W.C. to 14" W.C.
Pressure)
Sediment
Tee Joint Pipe Nipple Cap
Trap
CONNECTING FIREPLACE TO GAS SUPPLY
Installation Items Needed
• Phillips screwdriver
• sealant (resistant to propane gas, not provided)
1. Remove fireplace screen. Remove two screws that hold fireplace screen in place
for shipping. These screws are located near top of screen. Discard screws. Lift fireplace screen up and pull out to remove.
2. Remove screws that attach branch support to fireplace (see Figure 18). Care-
fully lift up branch support and remove from fireplace (see Figure 18).
103669
Figure 18 - Removing Branch Support From Fireplace
3. Route flexible gas line from manual shutoff valve into fireplace through side or rear
access holes in outer casing. Route flexible gas supply line through fireplace access holes in outer casing.
NOTICE
Most building codes do not permit concealed gas connections. A flexible gas line is provided to allow accessibility from the fireplace. The flexible gas supply line connection to the manual shutoff valve should be accessible.
Continued
17
Page 18
CONNECTING
TO GAS
SUPPLY
Continued
4. Apply pipe joint sealant lightly to male threads of gas connector attached to flexible gas line (see Figure 18). Connect flexible gas line to flexible gas line attached to gas regulator of fireplace (see Figure 18).
5. Check all gas connections for leaks. See Checking Gas Connections, below.
6. Replace branch support back into fireplace. Feed flexible gas line into fireplace base area while replacing branch support. Make sure the entire flexible gas line is in fireplace base area. Reattach branch support to fireplace with screws removed in step 3.
CHECKING
GAS
CONNECTIONS
To Fireplace Gas Regulator
Flexible Gas Line from Fireplace Gas Regulator
Test all gas piping and connections for leaks after installing or servicing. Correct all leaks at once.
Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.
Gas Connector
Flexible Gas Line from Manual Shutoff Valve
Figure 19 - Attaching Flexible Gas Lines Together
WARNING
WARNING ICON G 001
WARNING
WARNING ICON G 001
Manual Shutoff Valve
To Gas Supply
18
CAUTION
WARNING ICON G 001
Make sure external regulator has been installed between propane/ LP supply and fireplace. See guidelines under
Supply
, page 16.
Connecting to Gas
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
1. Disconnect fireplace and its individual manual shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage fireplace regulator.
2. Cap off open end of gas pipe where manual shutoff valve was connected.
3. Pressurize supply piping system by either using compressed air or opening propane/LP supply tank valve.
4. Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
5. Correct all leaks at once.
103669
Page 19
CHECKING
GAS
CONNECTIONS
Continued
Test Pressures Equal To or Less Than 1/2 PSIG
1. Close manual shutoff valve (see Figure 20).
2. Pressurize supply piping system by either using compressed air or opening propane/LP supply tank valve.
3. Check all joints from propane/LP supply tank to manual shutoff valve (see Figure 21). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
4. Correct all leaks at once.
PRESSURE TESTING FIREPLACE GAS CONNECTIONS
1. Open manual shutoff valve (see Figure 20).
2. Open propane/LP supply tank valve.
3. Make sure control knob of fireplace is in the OFF position.
4. Check all joints from manual shutoff valve to thermostat gas valve (see Figure
20). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light fireplace (see Operating Fireplace, pages 20 through 22). Check all other internal joints for leaks.
7. Turn off fireplace (see To Turn Off Gas to Appliance, page 22).
8. Replace front panel.
Manual Shutoff Valve
Propane/LP Supply Tank
ON
Open
POSITION
OFF
POSITION
Closed
Figure 20 - Manual Shutoff Valve
Manual Shutoff Valve
103669
Figure 21 - Checking Gas Joints Shown with Optional Mantel
19
Page 20
OPERATING
Clockwise
FOR YOUR SAFETY READ BEFORE LIGHTING
FIREPLACE
W ARNING
WARNING ICON G 001
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by hand. When lighting
the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure
to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use
tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician or gas supplier. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately call
a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
LIGHTING INSTRUCTIONS
W ARNING
You must operate this fireplace with the fireplace screen in place. Make sure fireplace screen is installed before running fireplace.
NOTICE
During initial operation of new fireplace, burning logs will give off a paper-burning smell. Open window to vent smell. Operate fireplace on HI position to burn off odor. This will only last a few hours.
1. STOP! Read the safety information above.
2. Make sure manual shutoff valve is fully open.
3. Turn control knob clockwise
Ignitor Button
to the OFF position.
Control Knob
20
Figure 22 - Control Knob In The OFF Position
Continued
103669
Page 21
OPERATING
FIREPLACE
4. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety information at the top of page 20. If you don’t smell gas, go to the next step.
Continued
5. Turn control knob counterclockwise
to the PILOT position. Press
C-clockwise
in control knob for five (5) seconds (see Figure 22, page 20).
Note:
You may be running this fireplace for the first time after hooking up
to gas supply. If so, the control knob may need to be pressed in for 30 seconds. This will allow air to bleed from the gas system.
• If control knob does not pop up when released, contact a qualified service person or gas supplier for repairs.
6. With control knob pressed in, push down and release ignitor button. This will light pilot. The pilot is attached to the front of burner. If needed, keep pressing ignitor button until pilot lights.
Note:
If pilot does not stay lit, refer to Troubleshooting, pages 24 through
27. Also contact a qualified service person or gas supplier for repairs. Until repairs are made, light pilot with match. To light pilot with match, see Manual Lighting Procedure, page 22.
7. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob.
Ignitor Electrode
Thermocouple
Pilot Burner
103669
Figure 23 - Pilot
Note:
If pilot goes out, repeat steps 3 through 7. This fireplace has a safety
interlock system. Wait one (1) minute before lighting pilot again.
8. Turn control knob counterclockwise
to desired heating level. The
C-clockwise
main burner should light. Set control knob to any heat level between HI and LO.
CAUTION
WARNING ICON G 001
Do not try to adjust heating levels by using the manual shutoff valve.
21
Page 22
Clockwise
Clockwise
OPERATING
TO TURN OFF GAS TO APPLIANCE
FIREPLACE
Continued
Shutting Off Fireplace
1. Turn control knob clockwise
2. Turn off all electric power to the appliance if service is to be performed.
Shutting Off Burner Only (pilot stays lit)
1. Turn control knob clockwise
to the OFF position.
to the PILOT position.
THERMOSTAT CONTROL OPERATION
The thermostat used on this fireplace senses the room temperature. At times the room may exceed the set temperature. If so, the burner will shut off. The burner will cycle back on when room temperature drops below the set temperature. The control knob can be set to any heat level between HI and LO.
Note:
The thermostat sensing bulb measures the temperature of air near the fireplace cabinet. This may not always agree with room temperature (depend­ing on housing construction, installation location, room size, open air tempera­tures, etc.). Frequent use of your fireplace will let you determine your own comfort levels.
INSPECTING
BURNER
MANUAL LIGHTING PROCEDURE
1. Follow steps 1 through 5 under Lighting Instructions, pages 20 and 21.
2. With control knob pressed in, strike match. Hold match to pilot until pilot lights.
3. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob.
Check pilot flame pattern and burner flame pattern often.
PILOT FLAME PATTERN
Figure 24 shows a correct pilot flame pattern. Figure 25 shows an incorrect pilot flame pattern. The incorrect pilot flame is not touching the thermocouple. This will cause the thermocouple to cool. When the thermocouple cools, the fireplace will shut down.
Thermocouple
Pilot Burner
22
Figure 24 - Correct Pilot Flame Pattern
103669
Page 23
INSPECTING
BURNER
Continued
Thermocouple
Figure 25 - Incorrect Pilot Flame Pattern
Pilot Burner
If pilot flame pattern is incorrect, as shown in Figure 25
• turn fireplace off (see To Turn Off Gas to Appliance, page 22).
• see Troubleshooting, pages 24 through 27.
BURNER FLAME PATTERN
Figure 26 shows a correct burner flame pattern. Figure 27 shows an incorrect burner flame pattern. The incorrect burner flame pattern shows the flame consistantly higher than one inch above the log.
Note:
When using the fireplace the first time, the flame will be yellow for approxi-
mately one hour until the log cures.
CORRECT FLAME PATTERN
AT HIGH POSITION
Figure 26 - Correct Burner Flame Pattern
INCORRECT FLAME PATTERN
AT HIGH POSITION
Figure 27 - Incorrect Burner Flame Pattern
Top of Flame About One Inch Below Logs
Top of Flame Consistantly About One Inch Higher Than Logs
103669
If burner flame pattern is incorrect, as shown in Figure 27
• turn fireplace off (see To Turn Off Gas to Appliance, page 22).
• see Troubleshooting, pages 24 through 27.
23
Page 24
CLEANING
AND
MAINTENANCE
W ARNING
WARNING ICON G 001
Turn off fireplace and let cool before cleaning.
CAUTION
WARNING ICON G 001
You must keep control areas, burner, and circulating air passage­ways of fireplace clean. Inspect these areas of fireplace before each use. Have fireplace inspected yearly by a qualified service person. Fireplace may need more frequent cleaning due to excessive lint from carpeting, bedding material, etc.
ODS/PILOT AND BURNER
• Use a vacuum cleaner, pressurized air, or small, soft bristled brush to clean.
CABINET
Air Passageways
• Use a vacuum cleaner or pressurized air to clean.
Exterior
• Use a soft cloth dampened with a mild soap and water mixture. Wipe the cabinet to remove dust.
TROUBLE-
SHOOTING
Note:
All troubleshooting items are listed in order of operation.
W ARNING
WARNING ICON G 001
Turn off and unplug fireplace and let cool before servicing. Only a qualified service person should service and repair fireplace.
CAUTION
WARNING ICON G 001
Never use a wire, needle, or similar object to clean ODS/pilot. This can damage ODS/pilot unit.
OBSERVED PROBLEM
When ignitor button is pressed, there is no spark at ODS/pilot
POSSIBLE CAUSE
1. Ignitor cable pinched or wet
2. Ignitor electrode not con­nected to ignitor cable
3. Broken ignitor cable
4. Bad piezo ignitor
5. Ignitor electrode broken
6. Ignitor electrode posi­tioned wrong
REMEDY
1. Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry
2. Reconnect ignitor cable
3. Replace ignitor cable
4. Replace piezo ignitor
5. Replace ignitor
6. Replace ignitor
24
103669
Page 25
TROUBLE-
SHOOTING
Continued
OBSERVED PROBLEM
When ignitor button is pressed, there is spark at ODS/pilot but no ignition
POSSIBLE CAUSE
1. Gas supply turned off or manual shutoff valve closed
2. Control knob not in PILOT position
3. Control knob not pressed in while in PILOT position
4. Air in gas lines when installed
5. Depleted gas supply
6. ODS/pilot is clogged
7. Gas regulator setting is not correct
REMEDY
1. Turn on gas supply or open manual shutoff valve
2. Turn control knob to PILOT position
3. Press in control knob while in PILOT position
4. Continue holding down control knob. Repeat ig­niting operation until air is removed
5. Contact local propane/ LP gas company
6. Clean ODS/pilot (see
Cleaning and Mainte­nance, page 24) or
replace ODS/pilot assembly
7. Replace gas regulator
ODS/pilot lights but flame goes out when control knob is released
1. Control knob not fully pressed in
2. Control knob not pressed in long enough
3. Safety interlock system has been triggered
4. Manual shutoff valve not fully open
5. Thermocouple connec­tion loose at control valve
6. Pilot flame not touch­ing thermocouple, which allows thermo­couple to cool, causing pilot flame to go out. This problem could be caused by one or both of the following: A) Low gas pressure B) Dirty or partially clogged ODS/pilot
7. Thermocouple damaged
8. Control valve damaged
1. Press in control knob fully
2. After ODS/pilot lights, keep control knob pressed in 30 seconds
3. Wait one minute for safety interlock system to reset. Repeat ignition operation
4. Fully open manual shut-off valve
5. Hand tighten until snug, then tighten 1/4 turn more
6. A) Contact local pro­pane/LP gas company
B) Clean ODS/pilot (see Cleaning and Maintenance, page 24) or replace ODS/pilot assembly
7. Replace thermocouple
8. Replace control valve
103669
Continued
25
Page 26
TROUBLE-
SHOOTING
Continued
OBSERVED PROBLEM
Burner does not light after ODS/pilot is lit
POSSIBLE CAUSE
1. Burner orifice is clogged
2. Burner orifice diameter is too small
3. Inlet gas pressure is too low
REMEDY
1. Clean burner (see
Cleaning and Mainte­nance, page 24) or
replace burner orifice
2. Replace burner orifice
3. Contact local propane/ LP gas company
Delayed ignition of burner
Burner backfiring during combustion
Slight smoke or odor during initial operation
Fireplace produces a whistling noise when burner is lit
1. Manifold pressure is too low
2. Burner orifice is clogged
1. Burner orifice is clogged or damaged
2. Burner damaged
3. Low inlet gas pressure
4. Gas regulator defective
1. Residues from manu­facturing processes
1. Air in gas line
2. Air passageways on fireplace blocked
3. Dirty or partially clogged burner orifice
1. Contact local propane/ LP gas company
2. Clean burner (see
Cleaning and Mainte­nance, page 24) or
replace burner orifice
1. Clean burner (see
Cleaning and Mainte­nance, page 24) or
replace burner orifice
2. Replace burner pressure
3. Contact local propane/ LP gas company
4. Replace gas regulator
1. Problem will stop after a few hours of operation
1. Operate burner until air is removed from line. Have gas line checked by local propane/LP gas company
2. Observe minimum installation clearances (see Figures 6 and 7 page 11)
3. Clean burner (see
Cleaning and Mainte­nance, page 24) or
replace burner orifice
26
103669
Page 27
TROUBLE-
SHOOTING
Continued
WARNING
WARNING ICON G 001
If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
IMPORTANT:
Operating fireplace where impurities in air exist may create odors. Clean­ing supplies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc., create fumes. These fumes may mix with combustion air and create odors.
OBSERVED PROBLEM
Fireplace produces a clicking/ticking noise just after burner is lit or shut off
Fireplace produces unwanted odors
Fireplace shuts off in use (ODS operates)
POSSIBLE CAUSE
1. Metal expanding while heating or contracting while cooling
1. Fireplace burning vapors from paint, hair spray, glues, etc. (See
statement above)
TANT
IMPOR-
2. Low fuel supply
3. Gas leak. See Warn-
ing statement at top of page
1. Not enough fresh air is available
2. Low line pressure
REMEDY
1. This is common with most fireplaces. If noise is excessive, contact qualified service person
1. Ventilate room. Stop using odor causing products while fire­place is running
2. Refill supply tank
3. Locate and correct all leaks (see Checking Gas Connections, page 18)
1. Open window and/or door for ventilation
2. Contact local propane/ LP gas company
3. ODS/pilot is partially clogged
3. Clean ODS/pilot (see
Cleaning and Mainte­nance, page 24)
103669
Gas odor even when control knob is in OFF position
Gas odor during combustion
Moisture/condensa­tion noticed on windows
1. Gas leak. See Warn-
ing statement at top of page
2. Control valve defective
1. Foreign matter be­tween control valve and burner
2. Gas leak. See Warn-
ing statement at top of page
1. Not enough combus­tion/ventilation air.
1. Locate and correct all leaks (see Checking Gas Connections, page 18)
2. Replace control valve
1. Take apart gas tubing and remove foreign matter
2. Locate and correct all leaks (see Checking Gas Connections, page 18)
1. Refer to Air for Combus-
tion and Ventilation
requirements (page 6)
27
Page 28
TECHNICAL
SERVICE
You may have further questions about installation, operation, or troubleshooting. If so, contact DESA International’s Technical Service Department at 1-800-323-5190.
SPECIFICA TIONS
SERVICE
HINTS
Input Rate 10,000 Btu/Hr Type Gas Propane/LP Only Ignition Piezo Pressure Regulator Setting 8.5" W.C. Inlet Gas Pressure (in. of water) *
Maximum 14" Minimum 11"
Dimensions, Inches (H x W x D)
Fireplace (including hood and screws) 25 Carton 325/8 x 273/16 x 115/8
Weight, pounds
Fireplace 44 Shipping 48 lbs.
* For purposes of input adjustment
When gas pressure is too low
• pilot will not stay lit
• burner will have delayed ignition
• fireplace will not produce specified heat
• propane/LP gas supply may be low
When gas quality is bad
• pilot will not stay lit
• burner will produce flames and soot
• fireplace will backfire when lit
7
/8 x 2613/16 x 93/8
1
/2 lbs.
REPLACEMENT
P ARTS
You may feel your gas pressure is too low or gas quality is bad. If so, contact your local propane/LP gas supplier.
Note:
Use only original replacement parts. This will protect your warranty coverage
for parts replaced under warranty.
Parts Under Warranty
Contact authorized dealers of this product. If they can’t supply original replacement part(s) call DESA International’s Technical Service Department at 1-800-323-5190 for referral information.
When calling DESA International, have ready
• your name
• your address
• model number of your fireplace
• how fireplace was malfunctioning
• type of gas used (propane/LP or natural gas)
• purchase date
Usually, we will ask you to return the defective part to the factory.
Parts Not Under Warranty
Contact authorized dealers of this product. If they can’t supply original replacement part(s) call DESA International’s Parts Department at 1-800-972-7879 for referral information.
When calling DESA International, have ready
• model number of your fireplace
• the replacement part number
28
103669
Page 29
ACCESSORIES
Purchase these fireplace accessories from your local dealer. If they cannot supply these accessories call DESA International’s Sales Department at 1-800-458-2472 for referral information. You can also write to the address listed on the back page of this manual.
MANUAL SHUTOFF VALVE - GA5010
Manual shutoff valve with 1/8" NPT tap.
BRASS TRIM KIT - GA6095
Optional four-sided brass trim kit for built-in installations. Provides a finished appearance covering rough edges of wall opening.
THERMOSTATICALLY CONTROLLED BLOWER KIT ­GA3400T
Provides better heat distribution. Makes fireplace more efficient. Automatically turns off and on as needed.
CABINET MANTEL WITH BUILT-IN HEARTH BASE Unfinished - GM921U Finished - GM920F
For use with fireplace. A hardwood mantel and hearth base offers compact styling and completes the fireplace look. Available in a walnut finished or an unfinished hardwood, ready to stain or paint. Complete assembly instructions included. Three-sided brass trim kit included.
103669
CORNER MANTEL WITH BUILT-IN HEARTH BASE Unfinished - GM721U Finished - GM720F
For use with fireplace. Space-saving mantel and hearth base corner design features clean, classic lines. Available in a walnut finish or an unfinished hardwood, ready to stain or paint. Complete assembly instructions in­cluded. Three-sided brass trim kit included.
29
Page 30
3
17
20
42
9
7
10
1
30
8
8
4
11
7
33
14
25
23
29
24
12-1
2
12-1 12-2
34
38
25
41
28
16
39
12
15
35
24
13
5
38
26
27
18
32
19
37
6
36
22
21
40
31
30
VMH10TP
103669
Page 31
PARTS LIST
KEY VMH10TP NO. PART NO. DESCRIPTION QTY.
1 102633-01 Outer Casing Top 1 2 102624-02 Outer Casing 1 3 099230-02 Shoulder Screw 4 4 098304-01 Screw, #10 x 3/8" 40 5 103591-02 Burner 1 6 103209-02 Louvered Door 1 7 102635-01CJ Left and Right Side Front 2 8 102458-01CJ Top and Middle Front 2 9 103209-01 Brass Top Louver 1 10 102730-01CJ Firebox Hood 1 11 102638-01 Firebox Top 1 12 099059-02 ODS/Pilot Assembly 1 12-1 098514-01 Thermocouple 1 12-2 098594-01 Ignitor Electrode 1 13 102460-01CJ Firebox Wrapper 1 14 099211-01 Control Bracket Screw 2 15 103963-01 Inlet Tube 1 16 103671-01 Burner Tube 1 17 100587-01 Brass Screw, #6 x 3/8 4 18 098303-02 Regulator Screw 2 19 102634-01CJ Outer Shell Base 1 20 102649-01CJ Branch Support 1 21 099415-04 Gas Regulator 1 22 102875-01 Regulator Bracket 1 23 101381-01 Valve Cover and Piezo 1 24 099387-03 Pilot Tube 1 25 098271-06 Ignitor Cable 1 26 M11084-38 Screw #8 x 3/8" 1 27 101004-13 Injector 1 28 M11084-26 Screw #10 x 3/8" 6 29 098522-15 Gas Valve 1 30 102639-01 Baffle 1 31 101628-01 Flexible Connector 1 32 102869-01 Control Bracket 1 33 102731-01 Control Shield 1 34 103295-01CJ Screen Assembly 1 35 104078-01 Main Log 1 36 102032-01 Hinge 2 37 102807-01 Hinge Screws 8 38 103734-01 Burner Support 2 39 101006-01 Pilot Bracket 1 40 097809-03 3/8 NPT x 3/8" Flare Brass Fitting 1 41 098249-01 Nut, M5 2 42 104058-01 Twig 1
This list contains replaceable parts used in your fireplace. When ordering parts, follow the instructions listed under Replacement Parts on page 28 of this manual.
Model: VMH10TP
103669
PARTS AVAILABLE — NOT SHOWN
101416-32 Instructional Video 1 101054-01 Lighting Instructions Plate 1 100563-01 Warning Plate 1 103470-01 Hardware Package 1
31
Page 32
WARRANTY INFORMATION
KEEP THIS WARRANTY
Model Serial No. Date Purchased
Always specify model and serial numbers when communicating with the factory. We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our
standard written warranty. We make no other warranty, expressed or implied.
LIMITED WARRANTY
VENT-FREE PROPANE/LP GAS COMPACT CLASSIC HEARTH FIREPLACE
DESA International warrants this product to be free from defects in materials and components for three (3) years and five (5) years on stainless steel burners from the date of first purchase, provided that the product has been properly installed, operated and maintained in accordance with all applicable instructions. To make a claim under this warranty the Bill of Sale or cancelled check must be presented.
This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s) required to restore this fireplace to proper operating condition and an allowance for labor when provided by a DESA Authorized Service Center. Warranty part(s) MUST be obtained through authorized dealers of this product and/or DESA International who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty. The fireplace MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail or become damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation. Travel, diagnostic cost, labor, transportation and any and all such other costs related to repairing a defective fireplace will be the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURATION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO THREE (3) YEARS ON ALL COMPONENTS AND FIVE (5) YEARS ON STAINLESS STEEL BURNERS FROM THE DATE OF FIRST PURCHASE; AND DESA INTERNATIONAL’S LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE PRODUCT AND DESA INTERNATIONAL SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAM­AGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or consequential damages, so the above limitation on implied warranties, or exclusion or limitation on damages may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights that vary from state to state. For information about this warranty write:
2701 Industrial Drive P.O. Box 90004 Bowling Green, KY 42102-9004
103669-01 REV. B
08/97