Desa L32, VL36ZNR, VL36EN, VL36EP, VL32HP User Manual

...
UNVENTED (VENT-FREE) FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
MANUALLY CONTROLLED
MODELS
NATURAL GAS
(V)L32(HN, LHN)
(V)L36(EN, LEN)
PROPANE/LP GAS
(V)L32(HP, LHP)
(V)L36(EP, LEP)
REMOTE CONTROL READY
MODELS
NATURAL GAS (V)L36(ZNR, LZNR) (V)L42(ZNR, LZNR)
PROPANE/LP GAS (V)L36(ZPR, LZPR) (V)L42(ZPR, LZPR)
WARNING: If the information in this manual is not fol­lowed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a quali-
fied installer, service agency or the gas supplier.
Save this manual for future reference.
For more information, visit www.desatech.com
WARNING: Improper installation, adjustment, altera­tion, service or maintenance can cause injury or prop­erty damage. Refer to this manual for correct installation and operational procedures. For assistance or addi­tional information consult a qualified installer, service agency or the gas supplier.
WARNING: FOR USE ONLY WITH A LISTED DECORA­TIVE TYPE UNVENTED ROOM HEATER. DO NOT BUILD A WOOD FIRE.
This appliance may be installed in an aftermarket,* per­manently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indi­cated on the rating plate. This appliance is not convert­ible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts.
Sellers of unvented propane or natural gas-fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for bedroom and bathroom installation in the Common wealth of Massachusetts.
-
TABLE OF CONTENTS
Safety Information ............................................... 3
Local Codes ........................................................ 4
Product Features ................................................. 4
Locating Firebox .................................................. 5
Product Specifications ......................................... 5
Air For Combustion and Ventilation ..................... 7
Installation ........................................................... 9
Operating Fireplace ........................................... 21
Inspecting Burners ............................................ 27
Cleaning and Maintenance ................................ 28
2
www.desatech.com
Troubleshooting .................................................
Specifications ....................................................
Wiring Diagram .................................................. 33
Service Hints ..................................................... 34
Technical Service ..............................................
Replacement Parts ............................................ 34
Accessories ....................................................... 35
Illustrated Parts Breakdown and Pars List ........ 36
Warranty Information ............................ Back Page
115254-01A
29 33
34

SAFETY INFORMATION

WARNING: This product con­tains and/or generates chemicals known to the state of California to cause cancer or birth defects or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully and completely be f o r e tr y i n g to assemb l e , operate or service this heater. Improper use of this heater can cause serious injury or death from burns, fire, explosion, electrical shock and carbon monoxide poisoning.
DANGER: Carbon monoxide poisoning may lead to death!
Carbon Monoxid e Poiso nin g: Early signs of
carbon monoxide poisoning resemble the flu, with headaches, dizziness or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol and those at high altitudes.
Natural and Propane/LP Gas: Natural and pro-
pane/LP gases are odorless. An odor-making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
WARNING: Do not allow fans to blow directly into the fireplace. Avoid any drafts that alter burner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
Fireplace front and screen be come very hot when running fire place. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Fire­place will remain hot for a time after shutdown. Allow surfaces to cool before touching.
Carefully supervise young chil­dren when they are in the room with fireplace. When using the optional hand-held remote ac­cessory, keep selector switch in the OFF position to prevent children from turning on burners with remote.
-
-
WARNING: Any change to this heater or its controls can be dangerous.
You must operate this fireplace with the fireplace screen and hood in place. Make sure fire­place screen and hood are in
WARNING: Do not use a
place before running heater.
blower insert, heat exchanger insert or other accessory not ap proved for use with this heater.
-
Keep the appliance area clear and free from combustible ma­terials, gasoline and other flam­mable vapors and liquids.
115254-01A 3
www.desatech.com
SAFETY INFORMATION
Continued
1.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) in­side any structure. Locate propane/LP supply tank(s) outdoors (propane/LP units only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use
any phone in your building
• immediately call your gas supplier from
a n eighbor ʼs phon e . Follo w the ga s supplierʼs instructions
• if you cannot reach your gas supplier, call
the fire department
4. This fireplace shall not be installed in a bed room or bathroom.
5. Do not use this fireplace as a wood-burning fireplace. Use only the logs provided with the fireplace.
6. Do not add extra logs or ornaments such as pine cones, vermiculite or rock wool. Using these added items can cause sooting. Do not add lava rock around base. Rock and debris could fall into the control area of fireplace.
7. To prevent the creation of soot, follow the instruc tions in Cleaning and Maintenance, page 28.
8. Before using furniture polish, wax, carpet cleaner or similar products, turn heater off. If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.
9. This fireplace needs fresh air ventilation to run properly. This fireplace has an Oxygen Deple tion Sensing (ODS) safety shutoff system. The ODS shuts down the fireplace if enough fresh air is not available. See Air for Combustion and Ventilation, page 7. If fireplace keeps shutting off, see Troubleshooting, page 29.
10. Do not run fireplace
• where flammable liquids or vapors are used
or stored
• under dusty conditions
11. Do not use this fireplace to cook food or burn paper or other objects.
12. Do not use fireplace if any part has been exposed to or under water. Immediately call a qualified service technician to inspect the fireplace and to replace any part of the control system and any gas control which has been under water.
4
www.desatech.com
13. Do not operate fireplace if any log is broken. Do not operate fireplace if a log is chipped (dime-sized or larger).
14. Turn fireplace off and let cool before servicing. Only a qualified service person should service and repair fireplace.
15. Operating fireplace above elevations of 4,500 feet could cause pilot outage.
16.
To prevent performance problems in propane/LP units, do not use propane/LP fuel tanks of less than 100 lbs. capacity (propane/LP units only).
17.
Provide adequate clear ances around a ir openings.

LOCAL CODES

Install and use fireplace with care. Follow all local codes. In the absence of local codes, use the lat est edition of The National Fuel Gas Code ANSI Z223.1/NFPA 54*.
-
*Available from:
American National Standards Institute, Inc.
National Fire Protection Association, Inc.
Note: Where listed vented decorative logs are required, thermostat operation is not permitted.
-

PRODUCT FEATURES

OPERATION
This firebox is designed for use with approved ANSI Z21.11.2 decorative type unvented room heaters. (Physical size limitations apply. Refer to minimum firebox requirements supplied with log heater.) It requires no outside venting or chimney making in
-
stallation easy and inexpensive. When used without the blower, the firebox requires no electricity mak­ing it ideal for emergency backup heat.
BLOWER ACCESSORY
The circulating models will accept a rotary type fan (model BK) accessory. The blower circulates heated air from the firebox into the room. Use of blower is optional.
REFRACTORY BRICK LINER
Your firebox may feature a concrete refractory brick liner. As with all concrete liners, this liner may develop slight cracks when exposed to heat. These cracks will not affect the performance of the fireplace or vent-free gas logs.
1430 Broadway
New York, NY 10018
Batterymarch Park
Quincy, MA 02269
115254-01A
-
-
251/8"
291/2"
347/16"
363/8"
Standoffs
221/2"
4"
291/2"
163/4"
187/16"
321/4"
361/2"
1415/16"
65/16"
33/8"
6"
815/16"
93/4"
12 1/4"
19 1/2"
16 11/16"
21/4"
19/16"
29/16"
81/8"
2 13/16"
8 5/8"
41/4"
31/2"
Built-In Side Nailing Flanges
Square Gas Line Access Holes
Electrical Access Hole
5/8"

LOCATING FIREBOX

PLANNING
Plan where you will install the firebox. This will save time and money later when you install the fire box. Before installation, consider the following:
1. Where the firebox will be located. Allow for wall and ceiling clearances (see
Clearances, page 9).
Installation

PRODUCT SPECIFICATIONS

32" MODELS
Left Side View with Air Kit
2. Everything needed to complete installation.
3. These models CANNOT be installed in a bedroom unless the maximum Btu rating of the installed vent-free log set is less than
-
10,000 Btu/hr.
4. Proper air for combustion and ventilation (page 7).
Outside Air Kit Location (Optional)
Firebox Top View
www.desatech.com
Front View
Right Side
View
Figure 1 - Firebox Dimensions (32" Models)
115254-01A 5
PRODUCT SPECIFICATIONS
Continued
36" AND 42" MODELS
Note: If only one dimension is shown, the dimension is the same for both 36" and 42" models.
Firebox Top View
Left Side View with Air Kit
Outside Air Kit Location (Optional)
Right Side View
6
Front View
Figure 2 - Firebox Dimensions (36" and 42" Models)
www.desatech.com
115254-01A
AIR FOR COMBUSTION
AND VENTILATION
WARNING: This firebox shall not be installed in a confined space or unusually tight con­struction unless provisions are provided for adequate combus­tion and ventilation air. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.
Todayʼs homes are built more energy efficient than ever. New materials, increased insulation and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy effi cient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireboxes, clothes dryers and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three fol lowing ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space
The information on page 7 through 9 will help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings exposed to the out
side atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10 less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors
c. caulking or sealants are applied to
areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines and at other openings.
If your home meets all of the three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors page 9.
If your home does not meet all of the criteria above, proceed to Determin ing
-
Fresh-Air Flow for Firebox Location.
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose
volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour
3
(4.8 m
per kw) of the aggregate input rating of all appliances installed in that space. Rooms com municating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.
­* Adjoining rooms are communicating only if
there are doorless passageways or ventilation grills between them.
-11
kg per pa-sec-m2) or
3
per kw) of the aggregate input
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining rooms with door less passageways or ventilation grills between the rooms.
-
and
,
three
-
-
115254-01A 7
www.desatech.com
Or
Remove Door into Adjoining
Room, Option
3
Ventilation Grills
Into Adjoining Room,
Option
2
Ve
ntilation Grills
Into
Adjoining
Room,
Option 1
12"
12"
AIR FOR COMBUSTION
AND VENTILATION
Continued
1. Determine the volume of the space (length x width x height).
Length x Width x Height = ________ cu . ft.
(volume of space)
Example: Space size 22 ft. (length) x 18 ft.
(width) x 8 ft. (ceiling height) = 3168 cu. ft. (volume of space)
If additional ventilation to adjoining room is
supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
_______(volume of space) x 20 = (Maximum
Btu/Hr the space can support)
Example: 3168 cu. ft. (volume of space) x 20 =
63,360 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free heater
Gas water heater*
Gas furnace
Vented gas heater
Gas fireplace logs
Other gas appliances* + ________
Total = ________
* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the outdoors and vents to the outdoors.
Example:
Gas water heater
Vent-free heater + ________
Total = ________
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
__________ Btu/Hr (maximum the space
can support)
__________ Btu/Hr (actual amount of
Btu/Hr used) Example: 63,360 Btu/Hr (maximum
the space can support)
79,000 Btu/Hr (actual amount
of Btu/Hr used)
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
8
__________ Btu/Hr
__________ Btu/Hr
__________ Btu/Hr
__________ Btu/Hr
__________ Btu/Hr
Btu/Hr
Btu/Hr
40,000
__________ Btu/Hr
39,000
79,000
Btu/Hr
Btu/Hr
www.desatech.com
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building
B. Vent room directly to the outdoors. See Ven
tilation Air From Outdoors, page 9.
C. Install a lower Btu/Hr heater, if lower Btu/Hr
size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un confined space. You will need no additional fresh air ventilation.
WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 Section
5.3 or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining un confined space. When ventilating to an adjoining unconfined space, you must provide two perma nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 4). You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of
ventilation grills or ducts.
Figure 3 - Ventilation Air from Inside
Building
115254-01A
.
-
-
-
-
Outlet Air
Ve
ntilated
Attic
Outlet
A
ir
Inlet Air
Inlet Air
Ve
ntilated
Crawl Space
To
Crawl
Space
To Attic
AIR FOR COMBUSTION
AND VENTILATION
Continued
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts. IMPORTANT: Do not provide openings for inlet
or outlet air into attic if attic has a thermostat­controlled power vent. Heated air entering the attic will activate the power vent.
Figure 4 - Ventilation Air from Outdoors

INSTALLATION

WARNING: A qualified ser­vice person must install firebox. Follow all local codes.
WARNING: Never install the firebox
• in a bedroom or bathroom*
• in a recreational vehicle
• where curtains, furniture,
clothing or other flammable objects are less than 42 inches from the front, top or sides of the firebox
• in high traffic areas
• in windy or drafty areas * Unless the installed log set is
rated at 10,000 Btu/Hr or less.
115254-01A 9
www.desatech.com
CAUTION: Log heaters in­stalled in this firebox create warm air currents. These currents move heat to wall surfaces next to fire­box. Installing firebox next to vinyl or cloth wall coverings or operat­ing firebox where impurities (such as, but not limited to, tobacco smoke, aromatic candles, clean­ing fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
IMPORTANT: Vent-free gas log heaters add mois­ture to the air. Although this is beneficial, installing firebox in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventilation, page 7.
IMPORTANT: Make sure the firebox is level. If firebox is not level, log set will not work properly.
Note: Your firebox is designed to be used in zero clearance installations. Wall or framing material can be placed against any exterior surface on the rear, sides, top or bottom of your firebox, except where standoff spacers are integrally attached. If standoff spacers are attached to your firebox, these spacers can be placed directly against wall or fram ing materials. Use the dimensions shown for rough opening to create the easiest installation.
Use dimensions shown for rough openings to create the easiest installation (see Built-In Firebox Installation, page 11).
INSTALLATION CLEARANCES
WARNING: Maintain the minimum clearances. If you can, provide greater clearances from floor, ceiling and adjoining wall.
Carefully follow these instructions. This will ensure safe installation.
Minimum Wall and Ceiling Clearances (see Figure 5, page 10)
A. Clearances from the side of the fireplace
cabinet to any combustible material and wall should follow diagram in Figure 5, page 10.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and protrudes 3 1/2" from the wall. This combus­tible material must be 4" from the side of the fireplace cabinet (see Figure 5, page 10).
-
INSTALLATION
Supplied Firebox Hood Must Be Used at All Times
Wire-mesh Screen
Firebox
Noncombustible Material May Project Off this Surface above the Firebox Hood
Mantel Shelf Note: Any portion of the mantel shelf must NOT extend beyond this profile.
12"
16"
20"
1
1
/2
"
6
3
/4
"
12"
Note: All vertical measurements are from top of fireplace hood opening to bottom of mantel shelf. These minimum clearances replace any other recommended clearances supplied with your ANSI Z21.11.2 approved gas logs.
Wa
ll board or facing material (above firebox) may be of combustible material, including decorative mantel ornaments or other similar projec­tions off of the facing material.
Framing Material
Continued
B. Clearances from the top of the firebox opening to
the ceiling should not be less than 42 inches.
C. When the firebox is installed on carpeting or
other combustible material, other than wood flooring, the firebox should be installed on a metal or wood panel extending the full width and depth of the enclosure.
D. Clearances from the bottom of firebox to the
floor is 0 inches.
These fireboxes can be installed as freestanding units against a wall with the approved, optional cabinet mantels (see built-in unit. The clearances are the same for either installation method.
CAUTION: Do not install the firebox directly on carpet or vinyl.
Accessories, page 35) or as a
Example
NOTICE: Surface temperatures of adjacent walls and mantels be­come hot during operation. Walls and mantels above the firebox may become hot to the touch. If installed properly, these tem­peratures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.
NOTICE: If your installation does not meet the minimum clearances shown, you must do one of the following:
• raise the mantel to an accept­able height
• remove the mantel
*Minimum 16 inches from Side Wall
Figure 5 - Minimum Clearance for
Combustible to Wall
Mantel Clearances for Built-In Installation
If placing custom mantel above built-in firebox, you must meet the minimum allowable clearance between mantel shelf and top of firebox opening shown in Figure 6. These are the minimum allow able mantel clearances for a safe installation. Use larger clearances wherever possible to minimize the heating of objects and materials placed on the mantel.
CAUTION: Do not allow the vent-free gas log heater to touch or extend beyond the fireplace screen.
10
www.desatech.com
*
Figure 6 - Minimum Mantel Clearances
for Built-In Installation
-
BUILT-IN FIREBOX INSTALLATION
Built-in installation of this firebox involves install­ing firebox into a framed-in enclosure. This makes the front of firebox flush with wall. Optional brass trim accessories are available (see Accessories, page 35). The brass trim will extend past sides of firebox approximately 1/2 inch. This will cover the rough edges of the wall opening. If installing a mantel above the firebox, you must follow the clearances shown in Figure 6. Follow these instruc­tions to install the firebox in this manner.
115254-01A
INSTALLATION
Depth
(Minimum)
Widt
h
(Inside to Inside)
Height
37"
411/2"
5
2
11
/
32
"
74"
TOP
VIEW
FOR 36" MODELS
30"
347/8"
42
7
/
16
"
60"
TOP VIEW
FOR 32" MODELS
43"
485/8"
6
0
13
/
1
6
"
86"
TOP
VIEW
FOR 42" MODELS
Continued
1. Frame in rough opening. The firebox fram­ing should be constructed of 2 x 4 lumber or heavier. Use dimensions in Table 1 and rough opening layout in Figure 7a. Adjust framing so that firebox flushes with finished wall surface. If installing in a corner, use dimensions in Figures 7b, 7c and 7d for rough opening.
2. Install gas piping to firebox location (see
Connecting to Gas Supply, page 16.) IM PORTANT:
(circulating models with louvers only), see
Hard-Wiring Firebox,
3. Carefully set firebox in front of rough open ing with back of firebox inside wall opening. IMPORTANT: If installing a perimeter trim kit, see instructions included with trim accessory. You must install shoulder screws from trim kit now.
4. Carefully insert firebox into rough opening.
5. Attach firebox to wall studs using nails or wood screws through holes in nailing flange (see Figure 8).
6. If using an optional perimeter trim kit, install the trim after final finishing and/or painting of wall. See instructions included with trim accessory for attaching trim.
7. Install and properly test gas log heater. Follow installation instructions included with the vent­free gas log heater that is being installed.
IMPORTANT:
tible materials such as wall board, gypsum board, sheet rock, drywall, plywood, etc. may be butted up next to the sides and top of the firebox. Combustible materials should never overlap the firebox front facing.
If installing blower accessory
page 15.
When finishing your firebox, combus-
WARNING: Do not allow noncombustible materials to cover any necessary openings like louvered slots.
WARNING: Use only non­combustible mortar or adhe­sives when overlapping the front
-
facing with noncombustible facing material.
-
Figure 7a
Figure 7b
Figure 7c
WARNING: Do not allow any combustible materials to overlap the firebox front facing.
IMPORTANT: Noncombustible materials such as brick, tile, etc. may overlap the front facing, but should never cover any necessary openings like louvered slots.
Table 1
Rough Opening Dimensions for
Built-in Installation
Front Width Depth
Model (Inside to Inside) Height (Min.)
32" 34 7/8" 36 3/4" 16 1/4"
1
36" 41 42" 48
115254-01A 11
/2" 40 1/2" 20 3/4"
5
/8" 44 1/2" 22 5/8"
www.desatech.com
Figure 7 - Rough Opening for Installing
in Wall
Nails or Wood Screws
Nailing Flanges
Figure 8 - Attaching Firebox to Wall Studs
Figure 7d
INSTALLATION
Continued
INSTALLING FIREBOX USING OPTIONAL ACCESSORY MANTELS
WARNING: A qualified ser­vice person must install firebox. Follow all local codes.
This firebox may be installed using a cabinet mantel accessory against a wall in your home. The firebox and cabinet mantel can be installed directly on the floor. A trim kit is included with the mantel accessories.
1. Assemble cabinet mantel accessory and the trim kit. Assembly instructions are included with each accessory.
2. If using an optional blower accessory (circulat ing models only), install a properly grounded, 120 volt three-prong electrical outlet at firebox location if an outlet is not there. If possible, locate outlet so cabinet mantel will cover it when installed (see Figure 9).
3. Install gas piping to firebox location. See Connecting to Gas Supply, page 15. You may have to cut an access hole in the floor or wall to run gas line to firebox. Make sure to locate access hole so cabinet mantel will cover it when installed (see Figure 9).
4. Place cabinet mantel on floor in desired loca tion. Make sure mantel is flush against wall.
5. Break off nailing flanges with hammer or pliers (32" models only, see Figure 10).
6. Install the trim kit furnished with mantel. See in­struction sheet included with the mantel now.
7. If installing an optional blower accessory (cir culating models only), see Installing Optional Blower Accessories, page 13.
8. Carefully insert firebox into cabinet mantel. Be careful not to scratch firebox, cabinet mantel, flooring, etc. when installing (see Figure 11).
9. Install and properly test gas log heater. Follow installation instructions included with the vent­free gas log heater that is being installed.
-
Nailing Flanges
Figure 10 - Location of Nailing Flanges
(Two on Each Side), 32" Model Shown
(Model May Vary From Illustration)
-
-
Cabinet Mantel
Gas Line Access Hole (Either Side of Firebox)
Figure 9 - Installing Cabinet Mantel
12
Gas Piping
Electrical Outlet
www.desatech.com
Figure 11 - Inserting Firebox Into
Cabinet Mantel (Model May Vary From
Illustration)
115254-01A
INSTALLATION
Continued
INSTALLING OPTIONAL BLOWER ACCESSORIES
NOTICE: The firebox identifica­tion label (including model num­ber, serial number, clearances, etc.) is located in the right side screen pocket area on the front of the firebox. See Figure 25, page 15.
Lower Louver Panel
NOTICE: If a log set is installed in the firebox, disconnect log set from gas supply and remove from firebox. Contact a qualified service person to do this.
Note: Appearance of firebox may vary depending on model.
The blower accessory option for use in the vent­free fireboxes is model BK. Model BK is a rotary squirrel cage type blower with magnetic attach ment and variable speed control.
The blower is installed by removing the lower face panel. To remove the lower face panel, pull the left and right latches toward the center of the appliance until they are disengaged from their locator holes (see Figure 12).
Models with louvered front panels can also be removed by inserting fingertips between slots and gently pulling out. DO NOT FORCE. The panels are actually held in place by means of a retention dimple embossed on the edge of remov able panels.
WARNING: If there is a duplex electrical outlet installed in the right side of the bottom of the fireplace base area (see Figure
13), be sure that the electrical power to the outlet is turned off before proceeding with blower installation. Failure to do this may result in serious injury.
1. Attach the power cord to the blower motor by firmly pushing the two female terminals at the end of the power cord onto the two spade ter­minals on the blower motor (see Figure 14).
Figure 12 - Accessing Blower
Compartment (Controls Not Shown
-
Figure 13 - Accessing Duplex Electrical Outlet Installed in Bottom Right Side of
-
Spade Terminals
Green Ground Wire
Blower Installed After Lower Panel Removed
Figure 14 - Blower Model BK
for Clarity)
Duplex Electrical Outlet
Firebox
Magnetic Strips
Exhaust Port
Screw
Side View Firebox Bottom
Blower Location
Air Flow Direction
Magnets
115254-01A 13
www.desatech.com
INSTALLATION
Red
Va
riable
Fan Switch
Fan Switch
(N.O.)
Green
White
On
11
0/115
V.
A.C.
Blower
Motor
Black
Off
1
2
Black
Blue
Continued
2. Attach green ground wire from power cord to blower housing using screw provided (see Figure 14, page 13). Tighten screws securely with a phillips screwdriver.
3. Place the blower against the lower rear wall of the firebox outer wrapper with the exhaust port directed upward. Depending on your model, you may have to carefully route the blower assembly past the controls and brackets and position the blower inside the back opening. The blower will be held in position against the back wall by the magnets incorporated onto the blower housing (see Figure 14, page 13).
4. Be certain that all wire terminals are securely at tached to terminals on blower motor and that the screw retaining the green ground wire is tight.
5. Mount speed control box by placing plastic con trol shaft through bottom hole on speed control bracket. Top screw head on control box will fit inside top hole on bracket (see Figure 15). Secure speed control to bracket with lock nut by pushing and turning lock nut with pliers clockwise until it is tight against bracket.
6. Place control knob, provided, onto control shaft (see Figure 15).
7. Check to make sure power cord is completely clear of blower wheel and there are no foreign objects in blower wheel. Also, double check all wire leads and make sure wire routing is not pinched or in a precarious position. Cor rect accordingly.
CAUTION: Never touch the
blower wheel while in operation.
8. Turn on power to duplex outlet if previously turned off per warning on page 13.
9. Plug in blower power cord to duplex outlet (see Figure 15, page 13).
10. Turn blower on and check for operation. Turn blower off by turning knob fully counterclock wise before continuing.
11. Peel off backing paper and stick supplied wiring diagram decal on firebox bottom approximately 12" in from of blower (see Figure 16).
12. Replace all panels and/or brick bottom panel if previously removed.
-
-
(BKT Model Only)
-
-
Speed Control
Control Shaft
Locknut
Duplex Outlet (Located under firebox floor against lower
Control Knob
Figure 15 - Attaching Speed Control to
14
Firebox with Panel Louvers
right outside wall)
Blower Plug-In
Wiring Diagram Decal 12" in Front of Blower
Figure 16 - Location of Wiring Diagram
Decal (Model May Vary From Illustration)
www.desatech.com
115254-01A
Loading...
+ 30 hidden pages