Desa V50S, VFB50NC, V50SH User Manual

UNVENTED (VENT-FREE) UNIVERSAL FIREBOX
TM
OWNER’S OPERATION AND INSTALLATION MANUAL
For more information, visit www.desatech.com
For more information, visit www.desatech.com
V50S, V50SH, and VFB50NC Vent-Free Fireboxes
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result caus­ing property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a
qualified installer, service agency, or the gas supplier.
WARNING: Improper installation, ad­justment, alteration, service, or main­tenance can cause injury or property damage. Refer to this manual for cor­rect installation and operational pro­cedures. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.
WARNING: FOR USE ONLY WITH A LISTED DECORATIVE TYPE UNVENTED ROOM HEATER. DO NOT BUILD A WOOD FIRE.
This firebox has been tested and ap­proved by CSA International under Z21.91-2001 for use with approved ANSI Z21.11.2 decorative type unvented room heater.
This appliance may be installed in an aftermarket*, permanently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Save this manual for future reference.
Save this manual for future reference.
TABLE OF CONTENTS SAFETY INFORMATION
2
TABLE OF CONTENTS
SAFETY INFORMATION ............................................................ 2
LOCAL CODES........................................................................... 3
PRODUCT FEATURES .............................................................. 3
LOCATING FIREBOX ................................................................. 3
PRODUCT SPECIFICATIONS.................................................... 4
AIR FOR COMBUSTION AND VENTILATION ........................... 5
INSTALLATION ........................................................................... 8
SAFETY INFORMATION
WARNINGS
IMPORTANT: Read this owners manual carefully and completely before trying to assemble, operate, or service this firebox. Improper use of this firebox can cause serious injury or death from burns, fire, explo­sion, electrical shock, or carbon monoxide poisoning.
WARNING: Carefully review the instructions sup­plied with the decorative type unvented room heater for the minimum fireplace size requirement.
DO NOT INSTALL THE APPLIANCE IN THIS FIRE­BOX, UNLESS THIS FIREBOX MEETS THE MINIMUM DIMENSIONS REQUIRED FOR THE INSTALLATION.
ILLUSTRATED PARTS BREAKDOWN AND PARTS LIST ....... 12
TECHNICAL SERVICE ............................................................. 14
REPLACEMENT PARTS .......................................................... 14
ACCESSORIES ........................................................................ 14
OWNER'S REGISTRATION FORM .......................................... 15
WARRANTY INFORMATION...................................... Back Cover
Do not place clothing or other flammable material on or near the appliance. Never place any objects in the firebox or on logs.
Firebox front and screen becomes very hot when running firebox. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Firebox will remain hot for a time after shutdown. Allow surfaces to cool before touching.
Carefully supervise young children when they are in the room with firebox.
WARNING: Any change to this firebox or its
controls can be dangerous.
WARNING: Do not allow fans to blow directly into the firebox. Avoid any drafts that alter burner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
WARNING: Do not use a blower insert, heat exchanger insert, or other accessory not approved for use with this firebox.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
You must operate this fireplace with the provided fireplace screen, hood, if provided, in place. Make sure these parts are in place and screens are closed before running firebox. The supplied hood may not be replaced with a hood which may be provided with a log heater.
Keep the fireplace area clear and free from combus­tible materials, gasoline, and other flammable vapors and liquids.
110749-01A
SAFETY INFORMATION
LOCAL CODES
PRODUCT FEATURES
LOCATING FIREBOX
3
3
SAFETY INFORMATION
Continued
1. Do not use this firebox as a wood-burning fireplace. Use only decorative unvented room heaters (log sets).
2. Do not add extra logs or ornaments such as pine cones, vermicu­lite, or rock wool. Using these added items can cause sooting.
3. Use only the provided hood, or appropriate hood accessory. See Accessories, page 14.
4. Vent-free gas log heaters installed in these fireboxes require fresh air ventilation to run properly. See Air for Combustion and Ventilation, pages 5 through 7.
5. Do not run vent-free heaters installed in these fireboxes
• where flammable liquids or vapors are used or stored
• under dusty conditions
6. Do not use this firebox to cook food or burn paper or other objects.
7. Turn unit off and let cool before servicing. Only a qualified service person should service and repair firebox.
8. Operating vent-free heaters installed in these fireboxes above elevations of 4,500 feet could cause pilot outage.
9. Do not use the firebox if it has been under water.
LOCAL CODES
Install and use fireplace with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code ANSI Z223.1/NFPA 54*. Firebox must be electrically grounded in accordance with the National Electrical Code, ANSI/NFPA70 (latest edition).
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
PRODUCT FEATURES
OPERATION
This firebox is designed for use with approved ANSI Z21.11.2 decorative type unvented room heaters. (Physical size limitations apply. Refer to minimum firebox requirements supplied with log heater.) It requires no outside venting or chimney making installation easy and inexpensive. When used without the blower, the firebox requires no electricity making it ideal for emergency backup heat.
REFRACTORY BRICK LINER
Your firebox features a concrete refractory brick liner. As with all concrete liners, this liner may develop slight cracks when exposed to heat. These cracks will not affect the performance of the fireplace or vent-free gas logs.
LOCATING FIREBOX
PLANNING
Plan where you will install the firebox. This will save time and money later when you install the firebox. Before installation, consider the following:
1. Where the firebox will be located. Allow for wall and ceiling clearances (see Installation Clearances, pages 8 and 9).
2. Everything needed to complete installation.
3. These models CANNOT be installed in a bedroom unless the maximum Btu rating of the installed vent-free log set is less than 10,000 Btu/hr.
4. Proper air for combustion and ventilation (page 5).
110749-01A
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
For more information, visit www.desatech.com
For more information, visit www.desatech.com
PRODUCT SPECIFICATIONS
4
PRODUCT SPECIFICATIONS
Firebox Top View
Figure 1 - Firebox Dimensions
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Front View
Side View
110749-01A
AIR FOR COMBUSTION AND VENTILATION
WARNING: This firebox shall not be installed in a confined space or unusually tight construction un­less provisions are provided for adequate combus­tion and ventilation air. Read the following instruc­tions to insure proper fresh air for this and other fuel­burning appliances in your home.
Today’s homes are built more energy efficient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireboxes, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on pages 5 through 7 will help you classify your
space and provide adequate ventilation.
AIR FOR COMBUSTION AND VENTILATION
Unusually tight construction is defined as construction where:
a. walls and ceilings e xposed to the outside atmosphere
have a continuous water vapor retar der with a rating of one perm (6 x 10 openings gasketed or sealed
b. weather stripping has been added on openable win-
dows and doors
c. caulking or sealants are applied to areas such as
joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.
If your home meets all of the three criteria above, you must provide additional fresh air. See
From Outdoors
If your home does not meet all of the proceed to
tion,
page 6.
Providing Adequate Ventilation
-11
kg per pa-sec-m2) or less with
and
and
Ventilation Air
, page 7.
three criteria above,
Determining Fresh-Air Flow for Firebox Loca-
5
5
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
110749-01A
AIR FOR COMBUSTION AND VENTILATION
6
Determining Fresh-Air Flow For Heater Location
AIR FOR COMBUSTION AND VENTILATION
Continued
DETERMINING FRESH-AIR FLOW FOR FIREBOX LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space. Space: Includes the room in which you will install heater plus any adjoining
rooms with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height). Length x Width x Height =___________ cu. ft. (volume of space)
Example:
height) = 3168 cu. ft. (volume of space) If additional ventilation to adjoining room is supplied with grills or open-
ings, add the volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maximum Btu/Hr the space
Example:
Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
* Do not include direct-vent gas appliances. Direct-vent draws com­bustion air from the outdoors and vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
__________________ Btu/Hr (maximum the space can support) __________________ Btu/Hr (actual amount of Btu/Hr used)
Example:
Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling
can support)
3168 cu. ft. (volume of space) x 20 = 63,360 (maximum
Vent-free heater _____________ Btu/Hr Gas water heater* _____________ Btu/Hr Gas furnace _____________ Btu/Hr Vented gas heater _____________ Btu/Hr Gas fireplace logs _____________ Btu/Hr Other gas appliances* + _____________ Btu/Hr Total = _____________ Btu/Hr
Example:
Gas water heater _____________ Btu/Hr Vent-free heater + _____________ Btu/Hr Total = _____________ Btu/Hr
63,360 Btu/Hr (maximum the space can support) 79,000 Btu/Hr (actual amount of Btu/Hr used)
40,000 39,000 79,000
The space in the above example is a confined space because the actual Btu/ Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the
extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See V entilation Air Fr om Inside Building, page 7.
B. Vent room directly to the outdoors. See Ventilation Air From Out-
doors, page 7.
C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room un-
confined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon­fined space or if the building is of unusually tight construction, provide adequate combustion and ven­tilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec­tion 5.3
or applicable local codes
.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
110749-01A