Variable Manually-Controlled Models Also Design-Certified As Vented Decorative Appliances
Echo Valley Oak Log Design
24" Variable Manually-Controlled Models
LSL3124N and LSL3124P
WARNING: If the information in this manual
is not followed exactly, a fire or explosion
may result causing property damage, personal injury, or loss of life.
— Do not store or use gasoline or other
flammable vapors and liquids in the vicinity
of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas
supplier’s instructions.
• If you cannot reach your gas supplier, call
the fire department.
— Installation and service must be performed
by a qualified installer, service agency, or
the gas supplier.
Meadowbrook Oak Log Design
24" Variable Thermostatically-Controlled Models
CDL3924NT and CDL3924PT
WARNING: Improper installation, adjustment, alteration, service, or maintenance
can cause injury or property damage. Refer to this manual for correct installation
and operational procedures. For assistance or additional information consult a
qualified installer, service agency, or the
gas supplier.
WARNING: This appliance is for installation only in a solid-fuel burning masonry
or UL127 factory-built fireplace, or in a
listed ventless firebox enclosure. It i s de sign-certified for these installations in accordance with ANSI Z21.11.2. Exception:
Do not install this appliance in a factorybuilt fireplace that includes instructions
stating it has not been tested or should not
be used with unvented gas logs.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which
it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer
to
Air for Combustion and Ventilation
section on page 4 of this manual.
This appliance may be installed in an aftermarket,* permanently located, manufactured
(mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance
is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Save this manual for future reference.
Save this manual for future reference.
TABLE OF CONTENTS
SAFETY INFORMATION
2
TABLE OF CONTENTS
SAFETY INFORMATION ...................................................................2
LOCAL CODES..................................................................................3
CLEANING AND MAINTENANCE ...................................................18
SAFETY INFORMATION
WARNINGS
WARNING: This product contains and/or generates
chemicals known to the State of California to cause
cancer or birth defects, or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully and
completely before trying to assemble, operate, or service this heater. Improper use of this heater can cause
serious injury or death from burns, fire, explosion,
electrical shock, and carbon monoxide poisoning.
WARRANTY INFORMATION............................................ Back Cover
WARNING: Do not allow fans to blow directly into
the fireplace. Avoid any drafts that alter burner flame
patterns. Ceiling fans can create drafts that alter
burner flame patterns. Altered burner patterns can
cause sooting.
Due to high temperatures, the appliance should be
located out of traffic and away from furniture and
draperies.
DANGER: Carbon monoxide poisoning may lead
to death!
Carbon Monoxide Poisoning: Early signs of carbon monoxide
poisoning resemble the flu, with headaches, dizziness, or nausea.
If you have these signs, the heater may not be working properly.
Get fresh air at once! Have heater serviced. Some people are
more affected by carbon monoxide than others. These include
pregnant women, people with heart or lung disease or anemia,
those under the influence of alcohol, and those at high altitudes.
Natural and Propane/LP Gas: Natural and propane/LP gases are
odorless. An odor-making agent is added to the gas. The odor
helps you detect a gas leak. However, the odor added to the gas can
fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual
for reference. It is your guide to safe and proper operation of this heater.
WARNING: Any change to this heater or its controls
can be dangerous.
WARNING: Do not use a blower insert, heat
exchanger insert, or other accessory not approved
for use with this heater.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Do not place clothing or other flammable material on
or near the appliance. Never place any objects on
the heater.
Heater base assembly becomes very hot when running heater. Keep children and adults away from hot
surface to avoid burns or clothing ignition. Heater
will remain hot for a time after shutdown. Allow
surface to cool before touching.
You must operate this heater with a fireplace screen
in place. Make sure fireplace screen is closed before
running heater.
Keep the appliance area clear and free from combustible materials, gasoline, and other flammable vapors
and liquids.
111347-01B
SAFETY INFORMATION
Continued
SAFETY INFORMATION
LOCAL CODES
UNPACKING
3
3
1.This appliance is only for use with the type of gas indicated on
the rating plate. This appliance is not convertible for use with
other gases.
2.Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors (propane/LP units only).
4.If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use any phone in
your building
• immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions
• if you cannot reach your gas supplier, call the fire department
4.This heater shall not be installed in a bedroom or bathroom,
unless installed as a vented appliance. See Installing DamperClamp Accessory for Vented Operation, page 10.
5.Before installing in a solid fuel burning fireplace, the chimney
flue and firebox must be cleaned of soot, creosote, ashes and
loose paint by a qualified chimney cleaner. Creosote will ignite if highly heated. Inspect chimney flue for damage. If damaged, repair flue before operating heater.
6.Do not burn solid-fuel in a masonry or UL127 factory-built
fireplace in which a vent-free room heater is installed.
7.If fireplace has glass doors, never operate this heater with glass
doors closed. If you operate heater with doors closed, heat
buildup inside fireplace will cause glass to burst. Make sure
there are no obstructions across opening of fireplace.
8.To prevent the creation of soot, follow the instructions in Clean-ing and Maintenance, pages 18 and 19.
9.Before using furniture polish, wax, carpet cleaner, or similar
products, turn heater off. If heated, the vapors from these products may create a white powder residue within burner box or
on adjacent walls and furniture.
10. This heater needs fresh, outside air ventilation to run properly .
This heater has an Oxygen Depletion Sensing (ODS) safety
shutoff system. The ODS shuts down the heater if enough fresh
air is not available. See Air for Combustion and Ventilation,
pages 4 through 6. If heater keeps shutting off, see Trouble-shooting, pages 20 through 22.
11. Do not run heater
• where flammable liquids or vapors are used or stored
• under dusty conditions
12. Do not use this heater to cook food or burn paper or other objects.
13. Do not use heater if any part has been exposed to or under
water. Immediately call a qualified service technician to inspect the room heater and to replace any part of the control
system and any gas control which has been under water.
14. Do not operate heater if any log is broken. Do not operate
heater if a log is chipped (dime-sized or larger).
15. Turn heater off and let cool before servicing, installing, or repairing. Only a qualified service person should install, service,
or repair heater.
16. Operating heater above elevations of 4,500 feet may cause pilot outage.
17. T o prevent performance problems, do not use propane/LP fuel
tank of less than 100 lb. capacity (propane/LP units only).
18. Provide adequate clearances around air openings.
LOCAL CODES
Install and use heater with care. Follow all local codes. In the
absence of local codes, use the latest edition of The National FuelGas Code ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
Note:
Where listed vented decorative logs are required, thermostat
operation is not permitted.
UNPACKING
CAUTION: Do not remove the data plates from the
grate assembly. The data plates contain important
warranty and safety information.
1.Remove logs and heater base assembly from carton.
not pick up heater base assembly by burners. This could damage heater. Always handle base assembly by grate.
2.Remove all protective packaging applied to logs and heater
for shipment.
3.Check all items for any shipping damage. If damaged, promptly
inform dealer where you bought heater.
Note:
Do
111347-01B
For more information, visit www.desatech.com
For more information, visit www.desatech.com
PRODUCT IDENTIFICATION
PRODUCT FEATURES
4
AIR FOR COMBUSTION AND VENTILATION
PRODUCT IDENTIFICATION
Control
Cover
Log
Control
Knob
Echo Valley Oak Logs with Manual Control
Piezo Ignitor
(behind log)
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no outside venting. There is no
heat loss out a vent or up a chimney. Heat is generated by realistic
flames. This heater is designed for vent-free operation with flue damper
closed. It has been tested and approved to ANSI Z21.11.2 standard for
unvented heaters. State and local codes in some areas prohibit the use
of vent-free heaters. This heater may also be operated as a vented
decorative (ANSI Z21.60) product by opening the flue damper.
SAFETY DEVICE
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety
shutoff system. The ODS/pilot is a required feature for vent-free room
heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This heater has a piezo ignitor. This system requires no matches,
batteries, or other sources to light heater.
AIR FOR COMBUSTION AND
VENTILATION
WARNING: This heater shall not be installed in a
confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air. Read the following instructions to insure proper fresh air for this and other fuelburning appliances in your home.
Control
Cover Log
Meadowbrook Oak Logs with Thermostat Control
Figure 1 - Product Identification
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Control
Knob
Piezo Ignitor
(behind log)
Today’s homes are built more energy efficient than ever. New materials, increased insulation, and new construction methods help reduce
heat loss in homes. Home owners weather strip and caulk around
windows and doors to keep the cold air out and the warm air in. During
heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home
needs to breathe. Fresh air must enter your home. All fuel-burning
appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances
draw air from the house to operate. You must provide adequate fresh
air for these appliances. This will insure proper venting of vented
fuel-burning appliances.
111347-01B
AIR FOR COMBUSTION AND
VENTILATION
Continued
AIR FOR COMBUSTION AND VENTILATION
Providing Adequate Ventilation
Determining Fresh-Air Flow for Heater Location
5
5
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation
classifications:
1.Unusually Tight Construction
2.Unconfined Space
3.Confined Space
The information on pages 4 through 6 will help you classify your
space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough
fresh air for combustion and ventilation. However, in buildings of
unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction
where:
a.walls and ceilings e xposed to the outside atmosphere
have a continuous water vapor retar der with a rating
of one perm (6 x 10
openings gasketed or sealed
b. weather stripping has been added on openable win-
dows and doors
c. caulking or sealants are applied to areas such as
joints around window and door frames, between sole
plates and floors, between wall-ceiling joints, between
wall panels, at penetrations f or plumbing, electrical,
and gas lines, and at other openings.
If your home meets all of the three criteria above,
you must pro vide additional fresh air . See
Air From Outdoors
If your home does not meet all of the three criteria
above, proceed to
Heater Location
.
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a
confined space as a space whose volume is less than 50 cubic feet
per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating
of all appliances installed in that space and an unconfined space as
a space whose volume is not less than 50 cubic feet per 1,000 Btu per
hour (4.8 m3 per kw) of the aggregate input rating of all appliances
installed in that space. Rooms communicating directly with the
space in which the appliances are installed*, through openings not
furnished with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless
passageways or ventilation grills between them.
-11
kg per pa-sec-m2) or less with
and
and
Ventilation
, page 6
.
Determining Fresh-Air Flow For
DETERMINING FRESH-AIR FLOW FOR
HEATER LOCATION
Determining if You Have a Confined or
Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining
rooms with doorless passageways or ventilation grills between the rooms.
1.Determine the volume of the space (length x width x height).
Length x Width x Height =___________ cu. ft. (volume of space)
Example:
height) = 2560 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or open-
ings, add the volume of these rooms to the total volume of the space.
2.Multiply the space volume by 20 to determine the maximum Btu/Hr
the space can support.
__________ (volume of space) x 20 = (Maximum Btu/Hr the space
Example:
Btu/Hr the space can support)
3.Add the Btu/Hr of all fuel burning appliances in the space.
* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
4.Compare the maximum Btu/Hr the space can support with the actual
amount of Btu/Hr used.
__________________ Btu/Hr (maximum the space can support)
__________________ Btu/Hr (actual amount of Btu/Hr used)
Example:
Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling
can support)
2560 cu. ft. (volume of space) x 20 = 51,200 (maximum
Vent-free heater_____________ Btu/Hr
Gas water heater*_____________ Btu/Hr
Gas furnace_____________ Btu/Hr
Vented gas heater_____________ Btu/Hr
Gas fireplace logs_____________ Btu/Hr
Other gas appliances* + _____________ Btu/Hr
Total = _____________ Btu/Hr
Example:
Gas water heater_____________ Btu/Hr
Vent-free heater+ _____________ Btu/Hr
Total= _____________ Btu/Hr
51,200 Btu/Hr (maximum the space can support)
73,000 Btu/Hr (actual amount of Btu/Hr used)
40,000
33,000
73,000
111347-01B
For more information, visit www.desatech.com
For more information, visit www.desatech.com
AIR FOR COMBUSTION AND VENTILATION
6
Determining Fresh-Air Flow for Heater Location (Cont.)
Ventilation Air
AIR FOR COMBUSTION AND
VENTILATION
Continued
The space in the above example is a confined space because the actual Btu/
Hr used is more than the maximum Btu/Hr the space can support. You must
provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the
extra space provides an unconfined space, remove door to adjoining
room or add ventilation grills between rooms. See V entilation Air Fr om
Inside Building.
B.Vent room directly to the outdoors. See V entilation Air F r om Outdoors.
C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can
support, the space is an unconfined space. You will need no additional fresh
air ventilation.
Ventilation
Grills
Into Adjoining
Room,
Option 1
Or
Remove
Door into
Adjoining
Room,
Option
3
12"
Ventilation Grills
Into Adjoining Room,
Option 2
WARNING: If the area in which the heater may be
operated is smaller than that defined as an unconfined space or if the building is of unusually tight
construction, provide adequate combustion and ventilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 Section 5.3
or applicable local codes
.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space.
When ventilating to an adjoining unconfined space, you must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor on the wall connecting the two spaces
(see options 1 and 2, Figure 2). You can also remove door into
adjoining room (see option 3, Figure 2). Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion
and Ventilation for required size of ventilation grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor. Connect these items directly to the
outdoors or spaces open to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation
for required size of ventilation grills or ducts.
IMPORTANT:
attic if attic has a thermostat-controlled power vent. Heated air
entering the attic will activate the power vent.
Do not provide openings for inlet or outlet air into
12"
Figure 2 - Ventilation Air from Inside Building
Outlet
Air
Outlet
Air
Inlet
Air
Inlet Air
Figure 3 - Ventilation Air from Outdoors
Ventilated
Attic
Ventilated
Crawl Space
To Attic
To
Crawl
Space
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111347-01B
INSTALLATION
INSTALLATION
Check Gas Type
Installation and Clearances for Vent-Free Operation
7
7
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary
heating system. Do not install this heater as your
primary heat source. If you have a central heating
system, you may run system’s circulating blower
while using heater. This will help circulate the heat
throughout the house. In the event of a power outage,
you can use this heater as your primary heat source.
WARNING: A qualified service person must install heater. Follow all local codes.
NOTICE: State or local codes may only allow operation of this appliance in a vented configuration. Check
your state or local codes.
WARNING: Before installing in a solid fuel burning fireplace, the chimney flue and firebox must be
cleaned of soot, creosote, ashes and loose paint by
a qualified chimney cleaner. Creosote will ignite if
highly heated. A dirty chimney flue and firebox may
create and distribute soot within the house. Inspect
chimney flue for damage. If damaged, repair flue
before operating heater.
CAUTION: This heater creates warm air currents.
These currents move heat to wall surfaces next to
heater. Installing heater next to vinyl or cloth wall
coverings or operating heater where impurities (such
as, but not limited to, tobacco smoke, aromatic
candles, cleaning fluids, oil or kerosene lamps, etc.)
in the air exist, may discolor walls or cause odors.
IMPORTANT:
this is beneficial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See
Air for Combustion and Ventilation, pages 4 through 6.
Vent-free heaters add moisture to the air. Although
CHECK GAS TYPE
Use the correct gas type (natural or propane/LP) for your unit. If
your gas supply is not correct, do not install log set. Call dealer
where you bought log set for proper type fireplace.
INSTALLATION AND CLEARANCES FOR
VENT-FREE OPERATION
WARNING: Maintain the minimum clearances. If
you can, provide greater clearances from floor, ceiling, and adjoining wall.
WARNING: Seal any fresh air vents or ash cleanout doors located on floor or wall of fireplace. If not,
drafting may cause pilot outage or sooting. Use a heatresistant sealant. Do not seal chimney flue damper.
WARNING: Never install the heater
• in a bedroom or bathroom unless installed as a
vented appliance, see page 10
• in a recreational vehicle
• where curtains, furniture, clothing, or other flam-
mable objects are less than 42 inches from the
front, top, or sides of the heater
• in high traffic areas
• in windy or drafty areas
MINIMUM FIREPLACE
CLEARANCE TO
COMBUSTIBLE MATERIALS
Side WallCeiling
16"42"
LOG SIZING REQUIREMENTS
Minimum Firebox
HeightDepthFrontRear *
WidthWidth
17"14"28"21"
* Measured at 14" depth.
111347-01B
For more information, visit www.desatech.com
For more information, visit www.desatech.com
INSTALLATION
8
Installation and Clearances for Vent-Free Operation (Cont.)
INSTALLATION
Continued
Carefully follow the instructions below. This will ensure safe
installation into a masonry, UL127-listed manufactured fireplace,
or listed vent-free firebox.
Minimum Clearances For Side Combustible
Material, Side Wall, and Ceiling
A. Clearances from the side of the fireplace cabinet to any com-
bustible material and wall should follow diagram in Figure 4.
Example:
combustible material and protrudes 3 1/2" from the wall. This
combustible material must be 4" from the side of the fireplace
cabinet (see Figure 4).
Note:
follow firebox manufacturer’s instructions for minimum clearances to combustible materials.
B. Clearances from the top of the fireplace opening to the ceiling
should not be less than 42 inches.
*Minimum 16 inches from Side Wall
Figure 4 - Minimum Clearance for Combustible to Wall
NOTICE: Manual control heaters may be used as a
vented product. If so, you must always run heater with
chimney flue damper open. If running heater with
damper open, noncombustible material above fireplace opening is not needed. Go to
Clamp Accessory for Vented Operation,
The face of a mantel, bookshelf, etc. is made of
When installing your gas logs into a manufactured firebox,
Example
*
Installing Damper
page 10.
noncombustible material behind it. Noncombustible material must
extend at least 8" up (for all models). If noncombustible material is
less than 12", you must install the fireplace hood accessory. See
Figure 5 for minimum clearances.
If Using Mantel
You must have noncombustible material(s) above the fireplace
opening. Noncombustible materials (such as slate, marble, tile, etc.)
must be at least 1/2 inch thick. With sheet metal, you must have
noncombustible material behind it. Noncombustible material must
extend at least 8 inches up). If noncombustible material is less than
12", you must install the fireplace hood accessory. Even if noncombustible material is more than 12", you may need the hood accessory
to deflect heat away from your mantel shelf. See Figure 5 and
Figures 6 and 7, page 9, for minimum clearances.
IMPORTANT:
If you cannot meet these minimum clearances, you
must operate heater with chimney flue damper open. Go to Install-ing Damper Clamp Accessory for Vented Operation, page 10.
NoncombustibleRequirements for
Material Distance (A) Safe Installation
12" or moreNoncombustible material OK.
Between 8" and 12"Install fireplace hood accessory
(GA6050, GA6052, or GA6053 see
Accessories
Less than 8"Noncombustible material must be
extended to at least 8". See
8" and 12"
extend material, you must operate
heater with flue damper open.
Heat Resistant
Material
, page 28).
Between
, above. If you cannot
(A)
Minimum Noncombustible Material Clearances
If Not Using Mantel
Note:
If using a mantel proceed to If Using Mantel. If not using a
mantel, follow the information on this page.
You must have noncombustible material(s) above the fireplace
opening. Noncombustible materials (such as slate, marble, tile, etc.)
must be at least 1/2 inch thick. With sheet metal, you must have
In addition to meeting noncombustible material clearances, you must
also meet required clearances between fireplace opening and mantel
shelf. If you do not meet the clearances listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between mantel shelf and top of
fireplace opening, a hood is not required (see Figure 6).
Determining Minimum Mantel Clearance When
Using a Hood
If minimum clearances in Figure 6 are not met, you must have
a hood. When using a hood there are still certain minimum
mantel clearances required. Follow minimum clearances shown
in Figure 7 when using hood.
NOTICE: Surface temperatures of adjacent walls and
mantels become hot during operation. Walls and
mantels above the firebox may become hot to the
touch. If installed properly, these temperatures meet
the requirement of the national product standard.
Follow all minimum clearances shown in this manual.
NOTICE: If your installation does not meet the minimum
clearances shown, you must do one of the following:
• operate the logs only with the flue damper open
• raise the mantel to an acceptable height
• remove the mantel
8"
Min.
Mantel Shelf
12"15"18"
Distances to
Underside of
Mantel
Underside of
Mantel Shelf
All minimum
distances are
in inches
20"
Top of Fireplace
Opening
Minimum NonCombustible
Material
12"
10"
8"
6"
1
2
/2
"
Hood
Hood
(GA6050, GA6052,
(GA6050, GA6052)
or GA6053)
Figure 7 - Minimum Mantel Clearances When Using Hood
FLOOR CLEARANCES
A. If installing appliance on the floor level, you must maintain
the minimum distance of 14" to combustibles (see Figure 8).
B. If combustible materials are less than 14" to the fireplace, you
must install appliance at least 5" above the combustible flooring (see Figure 9).
"
Mantel Shelf
18"8"20"
14"
Distances to
Underside of
Mantel
22"
17"
Underside of
Mantel Shelf
24"
20"
Top of Fireplace
Opening
All minimum
distances are
in inches
Log Set
24"/30"/36" Models
18" Model
Minimum NonCombustible
Material
10"
8"
6"
1
/2
2
(A)
12"
8"
Minimum NonCombustible
Material Height
Figure 6 - Minimum Mantel Clearances Without Using Hood
111347-01B
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Noncombustible Material
Figure 8 - Minimum Fireplace Clearances If Installed at Floor Level
Installing Damper Clamp Accessory for Vented Operation
Installing Heater Base Assembly
INSTALLATION
Continued
INSTALLING DAMPER CLAMP ACCESSORY
FOR VENTED OPERATION
Note:
When used as a vented heater, appliance must be installed
only in a solid-fuel burning fireplace with a working flue and
constructed of noncombustible material.
If your heater is a manually-controlled model, you may use this
heater as a vented product. There are three reasons for operating
your heater in the vented mode.
1.The fireplace does not meet the clearance to combustibles re-
quirements for vent-free operation.
2.State or local codes do not permit vent-free operation.
3.You prefer vented operation.
If reasons number 1 or 2 above apply to you, you must permanently
open chimney flue damper. You must install the damper clamp
accessory (to order, see Accessories, page 28). This will insure vented
operation (see Figure 10). The damper clamp will keep damper open.
Installation instructions are included with clamp accessory.
See chart below for minimum permanent flue opening you must
provide. Attach damper clamp so the minimum permanent flue
opening will be maintained at all times.
WARNING: You must secure this heater to fireplace floor. If not, heater will move when you adjust
controls. Moving heater may cause a gas leak or log
misplacement.
WARNING: If installing in a sunken fireplace, special care is needed. You must raise the fireplace floor to
allow access to heater control panel. This will insure
adequate air flow and guard against sooting and controls being damaged. Raise fireplace floor with noncombustible material. Make sure material is secure.
CAUTION: Do not pick up heater base assembly by
burners. This could damage heater. Only handle base
assembly by grates.
IMPORTANT:
not level, heater will not work properly. For thermostat models,
avoid damage to thermostat bulb. Avoid nicks or sharp bends in
thermostat bulb wire. Keep thermostat bulb in mounting bracket
until ready to mount base to floor. See Optional Positioning OfThermostat Sensing Bulb, page 23.
Installation Items Needed
• hardware package (provided with heater)
• approved flexible gas hose and fittings (not provided) (if allowed
by local codes)
• sealant (resistant to propane/LP gas, not provided)
• electric drill with 3/16" drill bit (metal or masonry as applicable)
• flathead screwdriver
• pipe wrench
1.Apply pipe joint sealant lightly to male threads of gas fitting
(not provided). Connect approved flexible gas hose to gas regulator of heater (see Figure 11).
tor with wrench when connecting flexible gas hose.
2.Locate two masonry screws in hardware package.
3.Place heater base in fireplace.
4.Place logs in their proper position on heater base (see Installing
Logs, pages 13 and 14).
Make sure the heater burners are level. If heater is
IMPORTANT:
Heater Gas Regulator
Flexible Gas Hose (if
Fitting
allowed by local codes)
Hold gas regula-
Masonry Fireplace
Figure 10 - Attaching Damper Clamp
Manufactured Fireplace
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Figure 11 - Attaching Flexible Gas Hose to Heater Gas Regulator
111347-01B
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.