Warranty Information ...........................Back Cover
WARNING: Improper installation, adjustment, al-
teration, service or main-
tenance can cause injury
or property damage. Refer
to this manual for correct
installation and operational procedures. For assis-
tance or additional infor-
mation consult a qualied
installer, service agency
or the gas supplier.
WARNING: This appliance
is for installation only in a
solid-fuel burning masonry or UL127 factory-built
replace or in a listed ventless rebox enclosure. It is
design-certied for these
installations in accordance
with ANSI Z21.11.2. Exception: Do not install this
appliance in a factory-built
fireplace that includes
instructions stating it has
not been tested or should
not be used with unvented
gas logs.
WARNING: This is an
unvented gas-red heater. It uses air (oxygen)
from the room in which
it is installed. Provisions
for adequate combustion
and ventilation air must
be provided. Refer to Air
for Combustion and Ventilation section on page 6
of this manual.
This appliance may be in-
stalled in an aftermarket,*
per man ent ly loc ate d,
manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for
use with the type of gas
indicated on the rating
plate. This appliance is
not convertible for use
with other gases.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
www.desatech.com
119426-01A2
SAFETy INFORMATION
Continued
WARNING: This product con-
tains and/or generates chemicals
known to the state of California
to cause cancer or birth defects
or other reproductive harm.
WARNING: Do not allow fans
to blow directly into the replace.
Avoid any drafts that alter burner
ame patterns. Ceiling fans can
create drafts that alter burner
ame patterns. Altered burner
patterns can cause sooting.
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate or service this replace.
Improper use of this replace
can cause serious injury or
death from burns, re, explosion, electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of carbon
monoxide poisoning resemble the u, with headaches, dizziness or nausea. If you have these signs,
the replace may not be working properly. Get fresh air at once! Have replace serviced. Some
people are more affected by carbon monoxide than
others. These include pregnant women, people with
heart or lung disease or anemia, those under the
inuence of alcohol and those at high altitudes.
Natural and Propane/LP
odor-making agent is added to these gases. The
odor helps you detect a gas leak. However, the odor
added to the gas can fade. Gas may be present even
though no odor exists.
Make certain you read and understand all warnings.
Keep this manual for reference. It is your guide to
safe and proper operation of this replace.
gases are odorless. An
WARNING: Any change to
this heater or its controls can
be dangerous.
Due to high temperatures, the
appliance should be located out
of trafc and away from furniture
and draperies.
Do not place clothing or other
ammable material on or near
the appliance. Never place any
objects on the heater.
Heater base assembly becomes
very hot when running heater.
Keep children and adults away
from hot surface to avoid burns
or clothing ignition. Heater
will remain hot for a time after
shutdown. Allow surface to cool
before touching.
Carefully supervise young chil-
dren when they are in the room
with heater. When using the hand-
held remote accessory (Remote-
Ready Models Only), keep selector switch in the OFF position to
prevent children from turning on
burners with remote.
You must operate this heater
with the replace screen and
hood in place. Make sure replace screen and hood are in
place before running heater.
WARNING: Do not use a
blower insert, heat exchanger
insert or other accessory not approved for use with this heater.
119426-01A3
www.desatech.com
Keep the appliance area clear
and free from combustible materials, gasoline and other ammable vapors and liquids.
SAFETy INFORMATION
Continued
1.
This appliance is only for use with the type of
gas indicated on the rating plate. This appliance
is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply
tank(s) outdoors (propane/LP units only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use
any phone in your building
• immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions
• if you cannot reach your gas supplier, call
the re department
4. This heater shall not be installed in a bedroom
or bathroom, unless installed as a vented appliance. See Installing Damper Clamp Accessory for Vented Operation, page 12 (Remote-Ready
Models Only).
5. Before installing in a solid fuel burning
replace, the chimney ue and rebox must
be cleaned of soot, creosote, ashes and loose
paint by a qualied chimney cleaner. Creosote
will ignite if highly heated. A dirty chimney
ue may create and distribute soot within
the house. Inspect chimney ue for damage.
If damaged, repair ue and rebox before
operating heater.
6. Do not burn solid-fuel in a masonry or UL127
factory-built replace in which a vent-free
room heater is installed.
7. If replace has glass doors, never operate this
heater with glass doors closed. If you operate
heater with doors closed, heat buildup inside
replace will cause glass to burst. Make sure
there are no obstructions across openings of
replace.
8. To prevent the creation of soot, follow the
instructions in Cleaning and Maintenance,
page 26.
9. Before using furniture polish, wax, carpet
cleaner or similar products, turn heater off. If
heated, the vapors from these products may
create a white powder residue within burner
box or on adjacent walls and furniture.
10. This heater needs fresh, outside air ventilation
to run properly. This heater has an Oxygen
Depletion Sensing (ODS) safety shutoff system.
The ODS shuts down the heater if enough fresh
air is not available. See Air for Combustion and Ventilation, page 6. If heater keeps shutting off,
see Troubleshooting, page 28.
11. Do not run heater
• where ammable liquids or vapors are used
or stored
• under dusty conditions
12. Do not use this heater to cook food or burn
paper or other objects.
13. Do not use heater if any part has been exposed
to or under water. Immediately call a qualied
service technician to inspect the room heater
and to replace any part of the control system
and any gas control which has been under
water.
14. Do not operate heater if any log is broken. Do
not operate heater if a log is chipped (dimesized or larger).
15. Turn heater off and let cool before servicing,
installing or repairing. Make sure the selector
switch is in the OFF position (Remote-Ready
Models Only). Only a qualied service person
should install, service or repair heater.
16. Make sure the selector switch is in the OFF
position when you are away from home for
long periods of time (Remote-Ready Models
Only).
17. Remote-ready heaters must not be connected
to any external electrical source.
18. Operating heater above elevations of 4,500
feet may cause pilot outage.
19. To prevent performance problems, do not
use propane/LP fuel tank of less than 100 lb.
capacity (propane/LP units only).
20. Prov ide adeq ua te clearan ce s around air
openings.
UNPACkING
CAUTION: Do not remove the
data plates from the grate assembly.
The data plates contain important
warranty and safety information.
1. Remove logs and heater base assembly from
carton. Note: Do not pick up heater base assembly by burners. This could damage heater.
Always handle base assembly by grate.
2. Remove all protective packaging applied to
logs and heater for shipment.
3. Check all items for any shipping damage. If
damaged, promptly inform dealer where you
bought heater.
www.desatech.com
119426-01A4
PRODUCT
IDENTIFICATION
Model CRB and
HRB Series Logs
State of Massachusetts: The installation must be made by a licensed plumber
or gas fitt er in the Common we alth of
Massachusetts.
Sel lers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527
CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for
bedroom and bathroom installation in the
Commonwealth of Massachusetts.
Ignitor
Control Knob
Model VUL
Series Logs
Ignitor
Control
Remote
Control
(Optional)
Knob
Figure 1 - Product Identication
Flame
Adjustment
Knob
Base
Assembly
Rear Burner
Base
Assembly
LOCAL CODES
Install and use heater with care. Follow all local
codes. In the absence of local codes, use the lat-
est edition of The National Fuel Gas Code, ANSI
Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
National Fire Protection Association, Inc.
1430 Broadway
New York, NY 10018
Batterymarch Park
Quincy, MA 02269
OPTIONAL REMOTE
CONTROL ACCESSORIES
There are four optional remote controls that
can be purchased separately for Remote-Ready
Models Only:
• wall switch • hand-held ON/OFF remote
• wall thermostat • hand-held thermostat remote
See Accessories, page 42.
The wall thermostat or hand-held thermostat may not
be used where vented decorative listing is required.
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no outside
venting. There is no heat loss out a vent or up a
chimney. Heat is generated by both realistic ames
and glowing coals. This heater is designed for ventfree operation with ue damper closed. It has been
tested and approved to ANSI Z21.11.2 standard for
unvented heaters. State and local codes in some
areas prohibit the use of vent-free heaters. This
heater may also be operated as a vented decorative
(ANSI Z21.60) product by opening the ue damper
(Non-Thermostat Models Only).
SAFETY DEVICE
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The
ODS/pilot is a required feature for vent-free room
heaters. The ODS/pilot shuts off the heater if there
is not enough fresh air.
ELECTRONIC IGNITION SYSTEM
This heater has an electronic ignitor to light heater
fuel supply.
119426-01A5
www.desatech.com
AIR FOR COMbUSTION
AND VENTILATION
WARNING: This heater shall
not be installed in a conned
space or unusually tight construction unless provisions are provided for adequate combustion and
ventilation air. Read the following
instructions to insure proper fresh
air for this and other fuel-burning
appliances in your home.
Today’s homes are built more energy efcient
than ever. New materials, increased insulation and
new construction methods help reduce heat loss
in homes. Home owners weather strip and caulk
around windows and doors to keep the cold air out
and the warm air in. During heating months, home
owners want their homes as airtight as possible.
While it is good to make your home energy efcient, your home needs to breathe. Fresh air must
enter your home. All fuel-burning appliances need
fresh air for proper combustion and ventilation.
Exhaust fans, replaces, clothes dryers and fuel
burning appliances draw air from the house to
operate. You must provide adequate fresh air for
these appliances. This will insure proper venting
of vented fuel-burning appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3,
Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 6 through 8 will help
you classify your space and provide adequate
ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion and
ventilation. However, in buildings of unusually
tight construction, you must provide additional
fresh air.
Unusually tight construction is dened as
construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6 x 10
less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window
and door frames, between sole plates
and oors, between wall-ceiling joints,
between wall panels, at penetrations
for plumbing, electrical and gas lines
and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh
air. See Ventilation Air From Outdoors,
page 8.
If your home does not meet all of the
three criteria above, proceed to Determining Fresh-Air Flow For Heater Location,
below.
Conned and Unconned Space
The National Fuel Gas Code, ANSI Z223.1/NFPA
54 denes a conned space as a space whose
volume is less than 50 cubic feet per 1,000 Btu
per hour (4.8 m3 per kw) of the aggregate input
rating of all appliances installed in that space and
an unconned space as a space whose volume is
not less than 50 cubic feet per 1,000 Btu per hour
(4.8 m3 per kw) of the aggregate input rating of
all appliances installed in that space. Rooms communicating directly with the space in which the
appliances are installed*, through openings not
furnished with doors, are considered a part of the
unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation grills
between them.
-11
kg per pa-sec-m2) or
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
Determining if You Have a Conned or
Unconned Space
Use this work sheet to determine if you have a
conned or unconned space.
www.desatech.com
119426-01A6
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills Into
Adjoining
Room,
Option 1
12"
12"
AIR FOR COMbUSTION
AND VENTILATION
Continued
Space: Includes the room in which you will install
replace plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x
width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)
If additional ventilation to adjoining room is
supplied with grills or openings, add the volume
of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x 20 =
51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in
the space.
Vent-free replace ___________ Btu/Hr
Gas water heater* ___________ Btu/Hr
Gas furnace ___________ Btu/Hr
Vented gas heater ___________ Btu/Hr
Gas replace logs ___________ Btu/Hr
Other gas appliances* + __________ Btu/Hr
Total = __________ Btu/Hr
* Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors
and vents to the outdoors.
Example:
Gas water heater ___________ Btu/Hr
Vent-free replace + __________ Btu/Hr
Total = __________ Btu/Hr
4. Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.
__________ Btu/Hr (maximum the space can support)
__________Btu/Hr (actual amount of Btu/Hr used)
Example: 51,200 Btu/Hr (maximum the space
73,000 Btu/Hr (actual amount of
The space in the above example is a conned space
because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide
additional fresh air. Your options are as follows:
119426-01A7
can support)
Btu/Hr used)
40,000
33,000
73,000
www.desatech.com
A. Rework worksheet, adding the space of an adjoin-
ing room. If the extra space provides an unconned
space, remove door to adjoining room or add
ventilation grills between rooms. See Ventilation
Air From Inside Building.
B. Vent room directly to the outdoors. See Ventila-
tion Air From Outdoors, page 8.
C. Install a lower Btu/Hr replace, if lower Btu/Hr
size makes room unconned.
If the actual Btu/Hr used is less than the maximum
Btu/Hr the space can support, the space is an unconned space. You will need no additional fresh
air ventilation.
WARNING: If the area in
which the heater may be operated is smaller than that dened
as an unconned space or if the
building is of unusually tight
construction, provide adequate
combustion and ventilation air
by one of the methods described
in the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 Section 5.3
or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconned space. When ventilating to an adjoining
unconned space, you must provide two permanent openings: one within 12" of the ceiling and
one within 12" of the oor on the wall connecting
the two spaces (see options 1 and 2, Figure 2). You
can also remove door into adjoining room (see
option 3, Figure 2). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for
Combustion and Ventilation for required size of
ventilation grills or ducts.
Figure 2 - Ventilation Air from Inside Building
AIR FOR COMbUSTION
Outlet
Air
Ventilated
Attic
Outlet
A
ir
Inlet
Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
AND VENTILATION
Continued
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or
ducts. You must provide two permanent openings:
one within 12" of the ceiling and one within 12"
of the oor. Connect these items directly to the
outdoors or spaces open to the outdoors. These
spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54,
Section 5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet
or outlet air into attic if attic has a thermostatcontrolled power vent. Heated air entering the attic
will activate the power vent.
NOTICE: State or local codes
may only allow operation of this
appliance in a vented conguration. Check your state or local
codes.
WARNING: Make sure the
selector switch is in the OFF
position before installing heater
(Remote-Ready Models Only).
WARNING: Before installing
in a solid fuel burning replace,
the chimney ue and rebox
must be cleaned of soot, creosote, ashes and loose paint by
a qualified chimney cleaner.
Creosote will ignite if highly
heated. A dirty chimney ue may
create and distribute soot within
the house. Inspect chimney and
rebox ue for damage. If damaged, repair ue and rebox
before operating heater.
Figure 3 - Ventilation Air from Outdoors
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your primary heat source. If you have a
central heating system, you may
run system’s circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
vice person must install heater.
Follow all local codes.
WARNING: A qualied ser-
www.desatech.com
WARNING: Seal any fresh
air vents or ash clean-out doors
located on oor or wall of replace. If not, drafting may cause
pilot outage or sooting. Use a
heat-resistant sealant. Do not
seal chimney ue damper.
WARNING: Never install the
heater
• in a bedroom or bathroom
unless installed as a vented
appliance, see page 12 (Remote-Ready Models Only)
• in a recreational vehicle
•
where curtains, furniture, cloth-
ing or other ammable objects
are less than 42" from the front,
top or sides of the heater
• in high trafc areas
• in windy or drafty areas
119426-01A8
INSTALLATION
Continued
CAUTION: This heater cre-
ates warm air currents. These
currents move heat to wall sur-
faces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater
where impurities (such as, but
not limited to, tobacco smoke,
aromatic candles, cleaning uids, oil or kerosene lamps, etc.) in
the air exist, may discolor walls
or cause odors.
IMPORTANT: Vent-free heaters add moisture to
the air. Although this is benecial, installing heater
in rooms without enough ventilation air may cause
mildew to form from too much moisture. See Air for Combustion and Ventilation, page 6.
CHECK GAS TYPE
Use the correct type of gas (natural or propane/LP).
If your gas supply is not the correct gas type, do
not install heater. Call dealer where you bought
heater for proper type heater.
WARNING: This appliance
is equipped for natural or propane/LP gas. Field conversion
is not permitted.
INSTALLATION AND CLEARANCES
FOR VENT-FREE OPERATION
Carefully follow the instructions below. This will
ensure safe installation into a masonry, UL127listed manufactured replace or listed vent-free
rebox.
Minimum Clearances For Side
Combustible Material, Side Wall and
Ceiling
A. Clearances from the side of the fireplace
cabinet to any combustible material and wall
should follow diagram in Figure 4.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and
protrudes 3 1/2" from the wall. This combustible material must be 4" from the side of the
replace cabinet (see Figure 4).
Note: When installing your gas logs into
a man uf actur ed fireb ox , foll ow fir ebox
manufacturer’s instructions for minimum
clearances to combustible materials.
B. Clearances from the top of the fireplace
opening to the ceiling should not be less than
42".
Example
WARNING: Maintain the
minimum clearances. If you
can, provide greater clearances
from oor, ceiling and adjoining
wall.
MINIMUM FIREPLACE CLEARANCE TO
COMBUSTIBLE MATERIALS
Log Size18", 24", 30"
Side Wall16"
Ceiling42"
Floor5"
119426-01A9
www.desatech.com
*Minimum 16" from Side Wall
Figure 4 - Minimum Clearance for
Combustible to Wall
*
Heat Resistant
Material
(A)
INSTALLATION
Continued
NOTICE: Manual control heaters
may be used as a vented product.
If so, you must always run heater
with chimney ue damper open.
If running heater with damper
open, noncombustible material
above replace opening is not
needed. Go to Installing Damper
Clamp Accessory for Vented
Operation, page 12.
Minimum Noncombustible Material
Clearances
If Not Using Mantel
Note: If using a mantel proceed to If Using Mantel.
If not using a mantel, follow the information on
this page.
You must have noncombustible material(s) above
the replace opening. Noncombustible materials
(such as slate, marble, tile, etc.) must be at least
1/2" thick. With sheet metal, you must have noncombustible material behind it. Noncombustible
material must extend at least 8" up (for all models).
If noncombustible material is less than 12", you
must install the replace hood accessory (24" and
30" Models Only). See Figure 5 for minimum
clearances.
If Using Mantel
You must have noncombustible material(s) above
the replace opening. Noncombustible materials
(such as slate, marble, tile, etc.) must be at least
1/2" thick. With sheet metal, you must have noncombustible material behind it. Noncombustible
material must extend at least 8" up (for all models).
If noncombustible material is less than 12", you
must install the replace hood accessory (24"
and 30" Models Only). Even if noncombustible
material is more than 12", you may need the hood
accessory to deect heat away from your mantel
shelf. See Figure 5 and Figures 6 and 7, page 9,
for minimum clearances.
IMPORTANT: If you cannot meet these minimum
clearances, you must operate heater with chimney
ue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 12.
Noncombustible
Material Requirements for
Distance (A) Safe Installation
1
2" or more Noncombustible mate-
Between 8" and 12"
18" Model: Noncombus-
Less than 8"
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
rial OK.
24" or 30" Models:
Install fireplace hood
ac ces sor y (GA 605 0,
GA6052 or GA6053 see
Accessories, page 42).
tible material OK.
Noncombustible mate-
rial must be extended to
at least 8". See Between
8" and 12", above. If you
cannot extend material,
you must operate heater
with ue damper open.
MANTEL CLEARANCES
In addition to meeting noncombustible material
clearances, you must also meet required clearances
between replace opening and mantel shelf. If
you do not meet the clearances listed below, you
will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between mantel
shelf and top of replace opening, a hood is not
required (see Figure 6, page 11).
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6, page 11, are
not met, you must have a hood. When using a hood
there are still certain minimum mantel clearances
required. Follow minimum clearances shown in
Figure 7, page 11, when using hood.
www.desatech.com
119426-01A10
INSTALLATION
14"
Min.
Combustible
Material
Noncombustible Material
Minimum NonCombustible
Material
Minimum NonCombustible
Material Height
Distances to
Underside of
Mantel
Top of
Fireplace
Opening
Underside of
Mantel Shelf
12"
8"
(A)
18"
14"
20"
17"
22"
19"
24"
20"
All minimum
distances are
in inches
Log Set
24"/30"/36"
Models
18" Model
2
1
/2
"
6"
8"
10"
Mantel Shelf
Minimum
Noncombustible
Material
8"
Min.
12" 15" 18"
All minimum
distances are
in inches
Log Sets
18", 24",
& 30"
Models
20"
2
1
/2
"
6"
8"
10"
12"
Distances to
Underside of
Mantel
Hood
(GA6050,
GA6052,
or GA6053)
Top of
Fireplace
Opening
Underside of
Mantel Shelf
Mantel Shelf
Hearth
5"
Min.
Combustible
Material
Continued
NOTICE: Surface temperatures
of adjacent walls and mantels become hot during operation. Walls
and mantels above the rebox
may become hot to the touch.
If installed properly, these temperatures meet the requirement
of the national product standard.
Follow all minimum clearances
shown in this manual.
NOTICE: If your installation does
not meet the minimum clearances shown, you must do one
of the following:
• operate the logs only with the
ue damper open
• raise the mantel to an acceptable height
• remove the mantel
Figure 7 - Minimum Mantel Clearances
When Using Hood
FLOOR CLEARANCES
A. If installing appliance on the oor level, you
must maintain the minimum distance of 14"
to combustibles (see Figure 8).
B. If combustible materials are less than 14" to
the replace, you must install appliance at
least 5" above the combustible ooring (see
Figure 9).
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
Figure 6 - Minimum Mantel Clearances
119426-01A11
Without Using Hood
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
www.desatech.com
INSTALLATION
Continued
INSTALLING DAMPER CLAMP
ACCESSORY FOR VENTED
OPERATION
Note: When used as a vented heater, appliance
must be installed only in a solid-fuel burning
replace with a working ue and constructed of
noncombustible material.
If your heater is a manually-controlled model, you
may use this heater as a vented product. There
are three reasons for operating your heater in the
vented mode.
1. The replace does not meet the clearance
to combustibles requirements for vent-free
operation.
2. State or local codes do not permit vent-free
operation.
3. You prefer vented operation.
If reasons number 1 or 2 above apply to you, you
must permanently open chimney ue damper. You
must install the damper clamp accessory (to order,
see Accessories, page 42). This will insure vented
operation (see Figure 10). The damper clamp will
keep damper open. Installation instructions are
included with clamp accessory.
See chart below for minimum permanent ue
opening you must provide. Attach damper clamp
so the minimum permanent ue opening will be
maintained at all times.
adjust controls. Moving heater
may cause a gas leak.
WARNING: If installing in a
sunken replace, special care
is needed. You must raise the
replace oor to allow access to
heater control panel. This will insure adequate air ow and guard
against sooting and controls being damaged. Raise replace oor
with noncombustible material.
Make sure material is secure.
Chimney Minimum Permanent
Height Flue Opening
6' to 15' 39 sq. inches
15' to 30' 29 sq. inches
www.desatech.com
CAUTION: Do not pick up
heater base assembly by burners. This could damage heater.
Only handle base assembly by
grates.
119426-01A12
INSTALLATION
Continued
IMPORTANT: Make sure the heater burners are
level. If heater is not level, heater will not work
properly. For thermostat models, avoid damage
to thermostat bulb. Avoid nicks or sharp bends
in thermostat bulb wire. Keep thermostat bulb
in mounting bracket until ready to mount base
to oor. See Optional Positioning Of Thermostat Sensing Bulb, page 32.
Installation Items Needed
• hardware package (provided with heater)
• approved exible gas hose and ttings (not
provided) (if allowed by local codes)
• sealant (resistant to propane/LP gas, not provided)
• electric drill with 3/16” masonry drill bit
Note: Install optional GHRCTB Receiver and
Hand-Held Remote Control Kit (see Accessories,
page 42) before installing gas log heater (RemoteReady Models Only). See installation instructions
included with the kit.
1. Apply pipe joint sealant lightly to male threads
of gas tting (not provided). For Thermostatically-Controlled Models connect approved
exible gas hose to gas regulator of heater
(see Figure 11). For Remote-Ready models
connect approved exible gas hose to inlet
side of gas control (see Figure 12). IMPOR-TANT: Hold gas regulator with wrench when
connecting exible gas hose (Thermostatically-Controlled Models Only).
2. Position heater base assembly in replace.
3. Mark screw locations through holes in front
panel of base (see Figure 13). If installing in a
brick-bottom replace, mark screw locations
in mortar joint of bricks.
4. Remove heater base from replace.
5. Drill holes at marked locations using 3/16"
drill bit.
6.
Attach base, through holes in front panel of base,
to replace oor using masonry screws provided
in hardware package (see Figure 13).
7. Connect to gas supply. See Connecting To Gas
Supply, page 14.
Heater Gas
Regulator
Flexible Gas Hose (if
allowed by local codes)
Figure 11 - Attaching Flexible Gas Hose to
Heater Gas Regulator (Thermostatically-
Controlled Models Only)
Gas Control
Flexible Gas Hose
(if allowed by local
codes)
Figure 12 - Attaching Flexible Gas Hose
to Heater Gas Regulator
(Remote-Ready Models Only)
Masonry Screw
Figure 13 - Attaching Base to Fireplace
Floor (Remote-Ready Models Only)
119426-01A13
www.desatech.com
INSTALLATION
Continued
CONNECTING TO GAS SUPPLY
WARNING: This appliance
requires a 1/2" NPT (National
Pipe Thread) inlet connection to
the pressure regulator.
For propane/LP units, the installer must supply
an external regulator. The external regulator will
reduce incoming gas pressure. You must reduce
incoming gas pressure to between 11" and 14" of
water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install
external regulator with the vent pointing down
as shown in Figure 14. Pointing the vent down
protects it from freezing rain or sleet.
WARNING: A qualied service person must connect heater
to gas supply. Follow all local
codes.
CAUTION: Never connect
propane/LP replace directly
to the propane/LP supply. This
heater requires an external regulator (not supplied). Install the
external regulator between the
heater and propane/LP supply.
WARNING: Never connect
natural gas replace to private
(non-utility) gas wells. This
gas is commonly known as
wellhead gas.
Installation Items Needed
Before installing heater, make sure you have the
items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved exible gas line with gas connector
(if allowed by local codes) (not provided)
* A CSA design-certied equipment shutoff valve
with 1/8" NPT tap is an acceptable alternative to
test gauge connection. Purchase the optional CSA
design-certied equipment shutoff valve from your
dealer. See Accessories, page 42.
CAUTION: Use only new,
black iron or steel pipe. Internally-tinned copper tubing
may be used in certain areas.
Check your local codes. Use
pipe of 1/2" diameter or greater
to allow proper gas volume to
heater. If pipe is too small, undue
loss of volume will occur.
Propane/LP
Supply Tank
Figure 14 - External Regulator With Vent
Pointing Down
External
Regulator
Vent
Pointing
Down
www.desatech.com
119426-01A14
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.