Desa HDVF3018P, HDVF3018N User Manual

UNVENTED (VENT-FREE) GAS LOG HEATER
OFF
PILOT
HI
LO
OWNER’S OPERATION AND INSTALLATION MANUAL
Patent Pending
VARIAbLE MANUALLy-
CONTROLLED MODELS
HDVF3018P AND HDVF3018N
Also Design-Certied As Vented Decorative Appliances
WARNING: If the information in this manual is not fol-
— Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
— Installation and service must be performed by a quali-
ed installer, service agency or the gas supplier.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
For more information, visit www.desatech.com
TAbLE OF CONTENTS
Safety Information ............................................... 2
Local Codes......................................................... 4
Product Identication ........................................... 5
Unpacking............................................................ 5
Product Features ................................................. 5
Air for Combustion and Ventilation ...................... 5
Installation ........................................................... 8
Operating Heater ............................................... 17
Inspecting Burners ............................................ 19

SAFETy INFORMATION

Cleaning and Maintenance ................................ 19
Troubleshooting ................................................. 21
Specications .................................................... 24
Technical Service............................................... 24
Service Hints ..................................................... 24
Replacement Parts ............................................ 24
Accessories ....................................................... 25
Illustrated Parts Breakdown and Parts List........ 26
Warranty Information ...........................Back Cover
WARNING: Improper in­stallation, adjustment, al-
teration, service or main­tenance can cause in-
jury or property damage.
Refer to this manual for correct installation and
operational procedures.
For assistance or addi­tional information con-
sult a qualied installer, service agency or the gas supplier.
WARNING: This appliance
is for installation only in a
solid-fuel burning masonry or UL127 factory-built re­place or in a listed vent­less rebox enclosure. It is design-certied for these
installations in accordance with ANSI Z21.11.2. Excep­tion: Do not install this
appliance in a factory-built replace that includes in­structions stating it has not been tested or should not be used with unvented gas logs.
WARNING: This is an
unvented gas-red heat­er. It uses air (oxygen)
from the room in which
it is installed. Provisions for adequate combustion
and ventilation air must
be provided. Refer to Air for Combustion and Ven­tilation section on page 5
of this manual.
This appliance may be in-
stalled in an aftermarket,*
per man ent ly loc ate d, manufactured (mobile) home, where not prohib­ited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
www.desatech.com
119421-01A2
SAFETy INFORMATION
Continued
WARNING: This product con-
tains and/or generates chemicals
known to the state of California
to cause cancer or birth defects or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully and completely be f o r e trying to a s s e mble, operate or service this heater. Improper use of this heater can cause serious injury or death from burns, fire, explosion, electrical shock and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of carbon
monoxide poisoning resemble the u, with head­aches, dizziness or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the inuence of alcohol and those at high altitudes.
Natural and Propane/LP Gas: Natural and pro-
pane/LP gases are odorless. An odor-making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warn­ings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
WARNING: Any change to
this heater or its controls can
be dangerous.
WARNING: Do not allow fans
to blow directly into the replace. Avoid any drafts that alter burner ame patterns. Ceiling fans can create drafts that alter burner ame patterns. Altered burner patterns can cause sooting.
WARNING: Do not use a blow­er insert, heat exchanger insert or other accessory not approved for use with this heater.
Due to high temperatures, the appliance should be located out of trafc and away from furniture and draperies.
Do not place clothing or other ammable material on or near the appliance. Never place any objects on the heater.
Heater base assembly becomes very hot when running heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater
will remain hot for a time after
shutdown. Allow surface to cool before touching.
Carefully supervise young chil-
dren when they are in the room
with heater.
You must operate this heater with a replace screen in place. Make sure replace screen is closed before running heater.
Keep the appliance area clear and free from combustible ma­terials, gasoline and other am­mable vapors and liquids.
1. This appliance is only for use with the type of gas indicated on the rating plate. This ap­pliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors (propane/LP units only).
3. To prevent performance problems, do not use propane/LP fuel tank of less than 100 lb. capacity (propane/LP units only).
119421-01A 3
www.desatech.com
SAFETy INFORMATION
Continued
4. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use any phone in your building
• immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions
• if you cannot reach your gas supplier, call the re department
5. This heater shall not be installed in a bedroom or bathroom unless installed as a vented appli­ance (see Installing Damper Clamp Accessory for Vented Operation, page 11).
6. Before installing in a solid fuel burning replace, the chimney ue and rebox must be cleaned of soot, creosote, ashes and loose paint by a qualied chimney cleaner. Creosote will ignite if highly heated. A dirty chimney ue may create and distribute soot within the house. Inspect chimney ue for damage. If damaged, repair ue and rebox before operating heater.
7. Do not burn solid-fuel in a masonry or UL127 factory-built replace in which a vent-free room heater is installed.
8.
If replace has glass doors, never operate this heater with glass doors closed. If you operate heater with doors closed, heat buildup inside re­place will cause glass to burst. Make sure there are no obstructions across openings of replace.
9.
This log heater is designed to be smokeless. If logs ever appear to smoke, turn off heater and call a qualied service person. Note: During initial operation, slight smoking could occur due to log curing and heater burning manufac­turing residues.
10.
To prevent the creation of soot, follow the instruc­tions in Cleaning and Maintenance, page 19.
11. Before using furniture polish, wax, carpet cleaner or similar products, turn heater off. If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.
12. This heater needs fresh, outside air ventilation to run properly. This heater has an Oxygen De­pletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if not enough fresh air is available. See Air for Combustion and Ventilation, page 5. If heater keeps shutting off, see Troubleshooting, page 21.
13. Do not run heater
• where ammable liquids or vapors are used
or stored
• under dusty conditions
14. Do not use this heater to cook food or burn paper or other objects.
15. Do not use heater if any part has been exposed to or under water. Immediately call a qualied service technician to inspect the room heater
and to replace any part of the control system and
any gas control which has been under water.
16. Do not operate heater if any log is broken. Do not operate heater if a log is chipped (dime­sized or larger).
17. Turn heater off and let cool before servicing. Only a qualied service person should service and repair heater.
18. Operating heater above elevations of 4,500 feet could cause pilot outage.
19.
Provide adequate clear ances around a ir openings.

LOCAL CODES

Install and use heater with care. Follow all local codes. In the absence of local codes, use the lat-
est edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
National Fire Protection Association, Inc.
State of Massachusetts: The installa-
tion must be made by a licensed plumber or gas fitt er in the Common we alth of Massachusetts.
Sel lers of unvented propane or natural gas-red supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for
bedroom and bathroom installation in the
Commonwealth of Massachusetts.
1430 Broadway
New York, NY 10018
Batterymarch Park
Quincy, MA 02269
www.desatech.com
119421-01A4
PRODUCT
IDENTIFICATION
Log Set
Piezo Ignitor
Control Knob
Figure 1 - Vent-Free Gas Log Heater
Base Grate
Burner

UNPACkING

CAUTION: Do not remove
the data plates from the grate as­sembly. The data plates contain important product information.
1. Remove logs and heater base assembly from
carton. Note: Do not pick up heater base as­sembly by burners. This could damage heater. Always handle base assembly by grate.
2. Remove all protective packaging applied to logs and heater for shipment.
3. Check all items for any shipping damage. If damaged, promptly inform dealer where you bought heater.

PRODUCT FEATURES

OpERATION
This heater is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by realistic dancing, yellow ames. This heater is designed for vent-free operation with ue damper closed. It has been tested and approved to ANSI Z21.11.2 standard for unvented heaters. State and local codes in some areas prohibit the use of vent-free heaters. This heater may also be operated as a vented decorative (ANSI Z21.60) product by opening the ue damper.
SAFETY pILOT
This heater has a pilot with an Oxygen Deple­tion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent-free room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.
pIEzO IGNITION SYSTEM
This heater has a piezo ignitor. This system re­quires no matches, batteries or other sources to light heater.
AIR FOR COMbUSTION
AND VENTILATION
WARNING: This heater shall
not be installed in a conned space or unusually tight con­struction unless provisions are provided for adequate combus­tion and ventilation air. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy efcient than ever. New materials, increased insulation and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy ef­cient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.
119421-01A 5
www.desatech.com
AIR FOR COMbUSTION
AND VENTILATION
Continued
Exhaust fans, replaces, clothes dryers and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
pROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three fol­lowing ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 5 through 7 will help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is dened
as construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous water vapor retarder with a rating of one perm (6x10 less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window and door frames, between sole plates and oors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh air. See Ventilation Air From Outdoors, page 7.
If your home does not meet all of the three
criteria above, proceed to Determining Fresh-Air Flow for Heater Location.
-11
kg per pa-sec-m2) or
www.desatech.com
Conned and Unconned Space
National Fuel Gas Code, ANSI Z223.1/NFPA 54 denes a conned space as a space whose
volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input
rating of all appliances installed in that space and
an unconned space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms com­municating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconned space.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Conned or Unconned Space
Use this work sheet to determine if you have a conned or unconned space.
Space: Includes the room in which you will install replace plus any adjoining rooms with doorless pas­sageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2,560 cu. ft. (volume of space)
If additional ventilation to adjoining room is
supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2,560 cu. ft. (volume of space) x 20 =
51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free replace __________ Btu/Hr
Gas water heater* __________ Btu/Hr
Gas furnace __________ Btu/Hr
Vented gas heater __________ Btu/Hr
Gas replace logs __________ Btu/Hr
Other gas appliances* + ________ Btu/Hr
Total = ________ Btu/Hr
* Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors and vents to the outdoors.
119421-01A6
AIR FOR COMbUSTION
Outlet Air
Ventilated Attic
Outlet A
ir
Inlet Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
Or
Remove Door into Adjoining
Room, Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills
Into Adjoining
Room,
Option 1
12"
12"
AND VENTILATION
Continued
Example:
Gas water heater ____________ Btu/Hr
Vent-free replace + ___________ Btu/Hr
Total = ___________ Btu/Hr
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
_________
_________
Btu/Hr (maximum the space can support)
Btu/Hr (actual amount of Btu/Hr used)
Example: 51,200 Btu/Hr (maximum the space
can support)
79,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the example is a conned space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide ad­ditional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoin-
ing room. If the extra space provides an unconned space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation
Air From Inside Building.
B. Vent room directly to the outdoors. See Ventila-
tion Air From Outdoors.
C. Install a lower Btu/Hr replace, if lower Btu/Hr
size makes room unconned.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un­conned space. You will need no additional fresh air ventilation.
WARNING: If the area in
which the heater may be oper­ated is smaller than that dened as an unconned space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described
in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Section 5.3
or applicable local codes.
40,000
39,000
79,000
the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of
ventilation grills or ducts.
Figure 2 - Ventilation Air from Inside
Building
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the oor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts. IMPORTANT: Do not provide openings for inlet
or outlet air into attic if attic has a thermostat­controlled power vent. Heated air entering the attic will activate the power vent.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining un­conned space. When ventilating to an adjoining unconned space, you must provide two perma­nent openings: one within 12" of the ceiling and one within 12" of the oor on the wall connecting
119421-01A 7
Figure 3 - Ventilation Air from Outdoors
www.desatech.com

INSTALLATION

NOTICE: This heater is intended
for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your pri­mary heat source. If you have a central heating system, you may run system’s circulating blower while using log heater. This will help circulate the heat from your log heater throughout the house. In the event of a power outage,
you can use this heater as your
primary heat source.
WARNING: A qualied ser­vice person must install heater. Follow all local codes.
NOTICE: State or local codes may
only allow operation of this appli­ance in a vented conguration. Check your state or local codes.
WARNING: Before installing in a solid fuel burning replace, the chimney ue and rebox must be cleaned of soot, creo­sote, ashes and loose paint by a qualified chimney cleaner. Creosote will ignite if highly heated. A dirty chimney ue may create and distribute soot within house. Inspect chimney ue and rebox for damage. If damaged, repair ue and rebox before operating heater.
WARNING: Seal any fresh air vents or ash clean-out doors
located on oor or wall of re­place. If not, drafting may cause pilot outage or sooting. Use a heat-resistant sealant. Do not seal chimney ue damper.
WARNING: Never install the
heater
• in a bedroom or bathroom
unless installed as a vented
appliance (see page 11)
• in a recreational vehicle
• where curtains, furniture,
clothing or other ammable objects are less than 42" from the front, top or sides of the
heater
• in high trafc areas
• in windy or drafty areas
CAUTION: This heater cre-
ates warm air currents. These
currents move heat to wall sur-
faces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater where impurities (such as, but not limited to, tobacco smoke, aromatic candles, cleaning u­ids, oil or kerosene lamps, etc.) in
the air exist, may discolor walls
or cause odors.
IMPORTANT: Vent-free heaters add moisture to the air. Although this is benecial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventilation, page 5.
CHECK GAS TYpE
Use the correct gas type (natural or propane/LP) for your unit. If your gas supply is not correct, do not install heater. Call dealer where you bought heater for proper type heater.
WARNING: This appliance is equipped for natural or pro­pane/LP gas. Field conversion is not permitted.
www.desatech.com
119421-01A8
INSTALLATION
Continued
INSTALLATION AND CLEARANCES
(Vent-Free Operation Only)
WARNING: Maintain the
minimum clearances. If you can, provide greater clearances from oor, ceiling and adjoining wall.
MINIMUM FIREpLACE CLEARANCE
TO COMBUSTIBLE MATERIALS
Log Size Side Wall Ceiling
18" 16" 42"
LOG SIzING REQUIREMENTS
Minimum Firebox Log Front Rear *
Size Height Depth Width Width
18" 17" 14" 24" 20"
* Measured at 14" depth.
Carefully follow the instructions below. This will ensure safe installation into a masonry, UL127­listed manufactured replace or certied vent-free rebox.
Minimum Clearances For Side
Combustible Material, Side Wall and Ceiling
A. Clearances from the side of the fireplace
cabinet to any combustible material and wall should follow diagram in Figure 4.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and protrudes 3 1/2" from the wall. This combus­tible material must be 4" from the side of the replace opening (see Figure 4).
Note: When installing your gas logs into
a man uf actur ed fireb ox , foll ow fir ebox manufacturer’s instructions for minimum clearances to combustible materials.
B. Clearances from the top of the replace open-
ing to the ceiling should not be less than 42".
Example
*
*Minimum 16" from Side Wall
Figure 4 - Minimum Clearance for
Combustible to Wall
NOTICE: Manual control heaters
may be used as a vented product.
If so, you must always run heater
with chimney ue damper open. If running heater with damper open, noncombustible material above replace opening is not needed. Go to Installing Damper
Clamp Accessory for Vented Operation, page 11.
Minimum Noncombustible Material
Clearances
If Not Using Mantel
Note: If using a mantel, proceed to If Using Mantel, page 10. If not using a mantel, follow the
information below.
You must have noncombustible material(s) above the replace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2" thick. With sheet metal, you must have non­combustible material behind it. Noncombustible material must extend at least 8" up (for all mod­els). If noncombustible material is less than 12", you must install the replace hood accessory (24" and 30" models only). See Figure 5, page 10 for minimum clearances.
IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney ue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 11.
119421-01A 9
www.desatech.com