Desa FSVYD18N, FSVYD18NR User Manual

TM
(VENT-FREE) NATURAL G A S STOVE HE AT E R
OWNER’S OPERATION AND INSTALLATION MANUAL
Model (F)SVYD18N Series Variable Manual Control or Model (F)SVYD18NR Series
Remote-Ready Control Gas Log Heater (Burner System For Cast Iron Stoves)
Patent Pending
Amity Sheraton
Townsend
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
— Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas sup­plier, call the fire department.
— Installation and service must be per-
formed by a qualified installer, ser­vice agency, or the gas supplier.
WARNING: The SVYD18N(R) series vent­free gas log heater is only approved for use in the SCIVF(*) series, PSCIVF(*) series, or NSCIVF(*) series cast iron stove models. The FSVYD18N(R) series vent-free gas log heater is only approved for use in the FC(*) and PFC(*) series cast iron stove models.
(* Indicates Color Suffix Designation)
WARNING: Improper installation, adjust­ment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to
Ventilation
section on page 4 of this manual.
Air for Combustion and
This appliance may be installed in an aftermarket*, permanently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Save this manual for future reference.
DESA INTERNATIONAL VENT-FREE NATURAL GAS STOVE HEATER
SAFETY INFORMATION
WARNINGS
WARNING ICON G 001
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, oper­ate, or service this heater. Im­proper use of this heater can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the heater may not be work­ing properly. Get fresh air at once! Have heater serviced. Some people are more af­fected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influ­ence of alcohol, and those at high altitudes.
Natural Gas: Natural gas is odorless. An
odor-making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
WARNING: Any change to this heater or its controls can be dangerous.
WARNING: Do not allow fans to blow directly into the stove. Avoid any drafts that alter burner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
WARNING: Do not use a blower insert, heat exchanger insert or other accessory not ap­proved for use with this heater.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
Stove becomes very hot when running heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater will remain hot for a time after shutdown. Allow surface to cool before touching.
Carefully supervise young chil­dren when they are in the room with fireplace. When using the hand-held remote accessory, keep selector switch in the OFF position to prevent children from turning on burners with remote.
Keep the appliance area clear and free from combustible materials, gasoline, and other flammable vapors and liquids.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do
not use any phone in your building
• immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s instructions
• if you cannot reach your gas supplier ,
call the fire department
3. This heater shall not be installed in a bedroom or bathroom.
4. Do not use this stove as a wood burn­ing fireplace. Use only model SVYD18N(R) series vent-free gas log heater for SCIVF(*), PSCIVF(*), and
VSCIVF(*) series cast iron stove mod­els. Use only FSVYD18N(R) series vent-free gas log heater for FC(*) and PFC(*) series cast iron stove models.
5. Do not add extra logs or ornaments such as pine cones, vermiculite, or rock wool. Using these added items can cause sooting.
6. This log heater is designed to be smoke­less. If logs ever appear to smoke, turn off heater and call a qualified service person.
Note:
During initial operation, slight smoking could occur due to log curing and heater burning manufacturing residues.
7. T o prevent the creation of soot, follow the instructions in Cleaning and Main- tenance, page 18.
8. Before using furniture polish, wax, car­pet cleaners, or similar products, turn heater off. If heated, the vapors from these products may create a white pow­der residue within burner box or on adjacent walls or furniture.
9. This heater needs fresh, outside air ven­tilation to run properly . This heater has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if not enough fresh air is available. See Air for Combustion and Ventilation, pages 4 through 6. If heater keeps shutting off, see Trouble- shooting, pages 19 through 21.
10. Do not run heater
• where flammable liquids or vapors
are used or stored
• under dusty conditions
11. Do not use this stove to cook food or burn paper or other objects.
12. Do not use heater if any part has been exposed to or under water. Immediately call a qualified service technician to in­spect the room heater and to replace any part of the control system and any gas control which has been under water.
13. Do not operate heater if any log is bro­ken. Do not operate heater if a log is chipped (dime-sized or larger).
14. Turn heater off and let cool before ser­vicing. Only a qualified service person should service and repair heater.
15. Operating heater above elevations of 4,500 feet could cause pilot outage.
16. Provide adequate clearances around air openings.
2
104461
OWNER’S MANUAL
PRODUCT IDENTIFICATION
Stove Body
Piezo Ignitor
Stove Door (Shown in the open position)
Gas Log Heater Base Assembly
N
O
F
F
O
E
T
O
M
E
R
Remote Selector Switch
HI
O
F
F
N
L
O
O
P
I
T
L
O
Flame Adjustment Knob
Control Knob
One Piece Log Set Inside Stove Cavity
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by realistic, dancing yellow flames. This heater is designed for vent-free operation. State and local codes in some areas prohibit the use of vent-free heaters.
SAFETY PILOT
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent-free room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This heater has a piezo ignitor. This system requires no matches, batteries, or other sources to light heater.
Figure 1 - Typical Stove Cabinet Model with Gas Log Heater (Shown is Amity Model with Model SVYD18NR Heater)
LOCAL CODES
Install and use heater with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code ANSI Z223.1/NFPA 54*.
*Available from: American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
104461
3
DESA INTERNATIONAL VENT-FREE NATURAL GAS STOVE HEATER
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall not be installed in a confined space or unusually tight con­struction unless provisions are provided for adequate combus­tion and ventilation air. Read the following instructions to in­sure proper fresh air for this and other fuel-burning appli­ances in your home.
Today’s homes are built more energy effi­cient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper com­bustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide ad­equate fresh air for these appliances. This will insure proper venting of vented fuel­burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from Na­tional Fuel Gas Code, ANSI Z223.1/ NFPA 54, Section 5.3, Air for Combus­tion and Ventilation.
All spaces in homes fall into one of the three following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on pages 4 through 6 will
help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and win­dows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is de­fined as construction where:
a. walls and ceilings exposed to the
outside atmosphere have a con­tinuous water vapor retarder with a rating of one perm (6 x 10 per pa-sec-m2) or less with open­ings gasketed or sealed
b. weather stripping has been
added on openable windows and doors
c. caulking or sealants are applied
to areas such as joints around window and door frames, be­tween sole plates and floors, be­tween wall-ceiling joints, be­tween wall panels, at penetra­tions for plumbing, electrical, and gas lines, and at other openings.
If your home meets all of the three criteria above, you must provide ad­ditional fresh air. See
From Outdoors
If your home does not meet all of the three criteria above, proceed to
termining Fresh-Air Flow For Heater Location,
and
Ventilation Air
, page 6.
page 5.
and
-11
kg
De-
Confined and Unconfined Space
The National Fuel Gas Code ANSI Z223.1/ NFPA 54 defines a confined space as a
space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appli­ances installed in that space and an uncon­fined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are in­stalled*, through openings not furnished with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless passageways or ventila­tion grills between them.
4
104461
OWNER’S MANUAL
AIR FOR COMBUSTION AND VENTILATION
Continued
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space. Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between
the rooms.
1. Determine the volume of the space (length x width x height). Length x Width x Height = ____________________ cu. ft. (volume of space)
Example:
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
_________________ (volume of space) x 20 = (maximum Btu/Hr the space can support)
Example:
3. Add the Btu/Hr of all fuel burning appliances in the space. Vent-free heater ____________________Btu/Hr Gas water heater* ____________________Btu/Hr Gas furnace ____________________Btu/Hr Vented gas heater ____________________Btu/Hr Gas fireplace logs ____________________Btu/Hr Other gas appliances* +___________________Btu/Hr Total =___________________Btu/Hr * Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
_________________ Btu/Hr (maximum the space can support) _________________ Btu/Hr (actual amount of Btu/Hr used)
Example:
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-
ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.
B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6. C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) =2560 cu. ft. (volume of space)
2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)
Example:
Gas water heater 40,000 Btu/Hr Vent-free heater + 30,000 Btu/Hr Total = 70,000 Btu/Hr
51,200 Btu/Hr (maximum the space can support) 70,000 Btu/Hr (actual amount of Btu/Hr used)
WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the
104461
National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3
5
or applicable local codes.
Continued
DESA INTERNATIONAL VENT-FREE NATURAL GAS STOVE HEATER
AIR FOR COMBUSTION AND VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro­vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see op­tion 3, Figure 2). Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section
5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two per­manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/ NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventila-
tion grills or ducts.
IMPORTANT:
inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.
Do not provide openings for
12"
Ventilation
Grills
Into Adjoining
Room,
Option 1
Figure 2 - Ventilation Air from Inside Building (Amity Stove Model Shown)
Or
Remove
Door into
Adjoining
Room, Option
3
12"
Outlet Air
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilated Attic
Outlet Air
To Attic
To
Crawl
Space Inlet Air
Inlet Air
Ventilated
Crawl Space
Figure 3 - Ventilation Air from Outdoors (Amity Stove Model Shown)
6
104461
OWNER’S MANUAL
INSTALLATION
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your pri­mary heating system. Do not in­stall this heater as your primary heat source. If you have a central heating system, you may run systems circulating blower while using heater. This will help circu­late the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualified ser­vice person must install heater. Follow all local codes.
WARNING: Never install the heater
in a bedroom or bathroom
in a recreational vehicle
where curtains, furniture,
clothing, or other flammable objects are less than 42 inches from the front, top, or sides of the heater
in high traffic areas
in windy or drafty areas
IMPORTANT:
Vent-free heaters add mois­ture to the air. Although this is beneficial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Com- bustion and Ventilation, pages 4 through 6.
CHECK GAS TYPE
Use only natural gas. If your gas supply is not natural gas, do not install heater. Call dealer where you bought heater for proper type heater.
CLEARANCES TO COMBUSTIBLES
(Vent-Free Operation Only)
WARNING: Maintain the mini­mum clearances. If you can, pro­vide greater clearances from floor, ceiling, and adjoining side and back walls.
Front View
Side Wall Side Wall
12"
Minimum
Carefully follow the instructions below. This stove is a freestanding unit designed to set directly on the floor.
IMPORTANT:
must maintain minimum wall and ceiling clearances during installation. The mini­mum clearances are shown in Figure 4. Measure from outermost point of stove top.
Minimum Wall and Ceiling Clearances (see Figure 4)
A. Clearances from outermost point of
stove top to any combustible side wall should not be less than 12 inches.
B. Clearances from outermost point of
stove top to any combustible back wall should not be less than 6 inches (In­cludes Corner Installations).
C. Clearances from the stove top to the
ceiling should not be less than 48 inches.
Ceiling
48"
Minimum
12"
Minimum
You
CAUTION: This heater cre­ates warm air currents. These currents move heat to wall sur­faces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as, but not limited to, tobacco smoke, aromatic candles, cleaning flu­ids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
104461
Top View
Back Wall
"
6
Minimum
12
"
Minimum
Side Wall Side Wall
Corner
Wall
6
"
Minimum
12
"
Minimum
Front of
Stove Unit
6
Wall
"
Minimum
Figure 4 - Minimum Clearance to Walls and Ceiling (Stove May Vary Depending on Model)
7
Side View
Ceiling
48"
Minimum
Floor
6"
Minimum
Back Wall
Continued
DESA INTERNATIONAL VENT-FREE NATURAL GAS STOVE HEATER
INSTALLATION
Continued
STOVE CAVITY ASSEMBLY
1. Lift off corrugated box enclosing stove body crating.
2. Remove all screws fastening the wood frame enclosure. Spread wood frame open and lift away from plastic­bagged stove body . The bottom pieces of pallet wood will remain bolted to the stove body.
3. Remove plastic bag from stove body.
4. Remove back panel from stove (see Figure 5). Use an adjustable wrench or a 10 mm socket. Remove six (6) bolts and washers. Keep bolts and washers to reattach back panel later.
5. Remove all contents from inside stove cavity. Contents include:
(1) - Stove bottom (4) - Legs (Amity and Townsend
models include leg leveler bolts) (1) - Bottom door (1) - Top grate (1) - Hardware kit bag with fasteners
6. Carefully lay stove body on back to attach bottom components to stove body (see Figure 6). Rest stove on drop cloth or blanket to avoid scratching stove edges.
7. Remove remaining pallet wood at­tached to bottom of stove body (see Figure 7). Use an adjustable wrench to remove bolts.
Bolt
Product Identification Label
Figure 5 - Removing Back Panel
Top of Stove Unit
Front of Stove Unit
Drop Cloth/ Blanket
Figure 6 - Laying Down Stove On Side (Stove Style May Vary Depending on Model)
Bolt
Pallet Wood
Back Stove Panel
Front of Stove Unit
Pallet Wood Bolted to Stove Body Bottom
Front
Pallet Wood
Bottom Of Stove Unit
Top of Stove Unit
Figure 7 - Removing Pallet Wood From The Bottom of The Stove
8
104461
OWNER’S MANUAL
INSTALLATION
Continued
Amity and Townsend Models
8. Fasten each leg to stove with four (4) M8 x 1.25 - 20mm bolts. Use a flat washer and lock washer with each bolt. Tighten bolts into threaded holes on stove body (see Figures 8 and 9). Use an adjustable wrench or a 12mm socket.
9. Fasten stove bottom to stove with four (4) M6 x 1 - 25mm bolts. Use a flat washer and lock washer with each bolt. Tighten bolts into threaded holes on stove body (see Figures 8 and 10). Use an adjustable wrench or a 10mm socket.
Sheraton Models
8. Fasten each leg to stove with four (4) bolts. Use a flat screw driver to tighten bolt to leg. Insert bolt in threaded holes on stove body (see Figures 8 and 11).
9. Fasten stove bottom to stove with four (4) M6 x 1 - 25mm bolts. Use a flat washer and lock washer with each bolt. Tighten bolts into threaded holes on stove body (see Figures 8 and 12). Use an adjustable wrench or a 10mm socket.
Door Hinge Step Bolt Hole
Leg Hole
Leg Hole
Figure 8 - Locating Threaded Holes for Stove Bottom, Legs, and Door Attachment (Appearance May Vary Depending on Model)
Washers
Bolt
Figure 9 - Attaching Stove Legs (Amity Model Shown)
Bottom Of Stove Unit
Leg
Front
Stove Bottom Hole
Bolt
Figure 11 - Attaching Stove Legs (Sheraton Model)
Door Catch Bolt With Adjustable Hex Nuts Hole
Leg Hole
Bottom Of Stove Unit
Leg Hole
Bottom Of Stove Unit
Leg
104461
Washers
Bolt
Stove Bottom
Figure 10 - Attaching Stove Bottom (Amity Model Shown)
9
Bottom Of Stove Unit
Washers
Bolt
Stove Bottom
Figure 12 - Attaching Stove Bottom (Sheraton Model)
Bottom Of Stove Unit
Continued
DESA INTERNATIONAL VENT-FREE NATURAL GAS STOVE HEATER
INSTALLATION
Continued
10. Attach stove door by inserting step bolt through door hinge pivot hole and into threaded hole in stove body (see Fig­ures 8 and 13). Use an adjustable wrench or a 12mm socket to fasten step bolt. Tighten step bolt until snug. Make sure door moves freely.
11. Install door catch bolt (M8 x 1.25­55mm with two M8 hex nuts) into threaded hole on stove body (see Fig­ure 8, page 9). Use an adjustable wrench or a 12mm socket. The catch bolt has two hex nuts attached to it (see Figure 14). The top nut is a bolt stop and the bottom nut is for door leveling adjustment.
12. Check general catch bolt alignment with door claw. Make final adjustment and door leveling after stove is in nor­mal standing position.
13. Carefully lift stove back up on its four attached legs.
14. Set top grate into stove top.
15. If available, install gas log heater in­side stove cavity before installing the back panel (see Installing Gas Log Heater Into Stove, page 11).
16. Fasten back panel to stove with six (6) M6 x 1 - 20mm bolts and washers. Make sure product identification label is located on the outside in lower left­hand corner.
Stove Door
Threaded Hole
Door Hinge
Step Bolt
Bolt Shoulder
Figure 13 - Attaching Stove Door (Appearance May Vary Depending on Model)
Door
Figure 14 - Catch Bolt and Door Claw Orientation
Door Claw
Stove Bottom
Bolt Stop
Adjusting Nut
Catch Bolt
Stove Door
Bolt Shoulder
Door Hinge
Step Bolt
10
104461
OWNER’S MANUAL
H
I
L
O
O
F
F
P
I
L
O
T
O
N
INSTALLATION
Continued
CAUTION: Do not remove the data plates attached to the heater base assembly. The data plates contain important warranty and safety information.
WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this heater may result in property damage or personal injury.
CAUTION: After installation and periodically thereafter, check to en­sure that no flame comes in contact with any log. With the heater set to High, check to see if flames contact any log. If so, reposition logs ac­cording to the log installation in­structions in this manual. Flames contacting logs will create soot.
INSTALLING GAS LOG HEATER INTO STOVE
1. Remove log and gas log heater from carton. heater by the burner itself. This could damage heater. Always handle the gas log heater by the heater base only.
2. Remove all protective packaging ap­plied to log and gas log heater for ship­ment.
3. Check all items for any shipping dam­age. If damaged, promptly inform dealer where you bought heater.
4. If not already removed, remove back panel from assembled stove body (see Figure 5, page 8). Use an adjustable wrench or a 10 mm socket. Remove six (6) bolts and washers. Keep bolts and washers to reattach back panel later.
5. Set gas log heater inside stove. Make sure control knob extension passes through bottom front opening (see Fig­ure 15).
6. Align outside holes on heater base with four (4) mounting holes on the stove bottom (see Figure 15).
Note:
Do not pick up gas log
7. Fasten heater base to stove bottom with #10-24 x .50 bolts and hex nuts pro­vided with gas log heater (see Figure
16). Attachment hardware is factory packed inside plastic bag with installa­tion manual and owner’s registration card. Push bolt through heater base mounting hole and through stove bot­tom. Connect hex nut to bolt on under­side of stove bottom. The bolt hex head is for a 5/16" socket and the hex nuts are for a 3/8" socket. If sockets are not available, use adjustable wrenches.
8. Set one-piece log on heater base as shown in Figure 17. Make sure middle section at bottom of log is seated into "U" shaped cutout in center of heater base. Log will fit securely on base.
IMPORTANT:
Make sure log does not cover any burner ports and does not touch the stove cavity (see Figure 18).
9. Fasten back panel to stove with six (6) M6 x 1.20mm bolts and washers. Make sure product identification label is lo­cated on the outside lower left-hand corner.
10. Place freestanding stove in desired po­sition in room. Be sure to maintain clearances to combustibles as outlined on page 7.
Bottom Front Opening
Bolt
Heater Base
Stove Bottom
Figure 15 - Placing Heater Base In Stove Cavity (Appearance May Vary Depending on Model)
Burner
Heater
Bolt
Base
Stove
Hex Nut
Bottom
Figure 16 - Fastening Heater Base to Stove Drop Bottom
One-Piece Log Set
Middle Section at Bottom of Log Set
Burner
"U" Shaped Cutout in Chassis
Heater Base
Figure 17 - Installing One-Piece Stove Log Set (Remote-Ready Log Heater Shown)
Burner Porting Areas (double slotted rectangular openings
Safety Pilot Location
One-Piece Log Set
Figure 18 - Top View of One-Piece Log Set on Gas Log Heater
Continued
104461
11
Loading...
+ 23 hidden pages