Desa CVDR30, CVDR24, CPVSR18, CVSR18, CVDR18 User Manual

...
NATURAL GAS LOG
VENTED DECORATIVE APPLIANCES
OWNER’S OPERATION AND INSTALLATION MANUAL
RGA 2-72
APPROVED
TESTED AND
LISTED BY
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by
a qualified installer, service agency, or the gas supplier.
RADCO Burner Models CVSR18, CVSR24, CPVSR18, CPVSR24, CVDR18, CVDR24, and CVDR30
WARNING: Improper installa­tion, adjustment, alteration, ser­vice, or maintenance can cause injury or property damage. Re­fer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.
WARNING: This appliance is for installation only in a solid­fuel burning masonry or UL127 factory-built fireplace, con­structed of noncombustible material, and connected to a working flue. (See page 7 for minimum flue opening.)
WARNING: This is a gas-fired appliance. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to
This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state or local codes.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Air for Combustion and Ventilation
Save this manual for future reference.
section on page 4 of this manual.
RADCO BURNERS
FOR VENTED NATURAL GAS LOGS
SAFETY INFORMATION
WARNINGS
WARNING ICON G 001
WARNING: Keep flue open
when operating unit.
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, oper­ate, or service this log set. Im­proper use of this log set can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early
signs of carbon monoxide poisoning re­semble the flu, with headaches, dizziness, or nausea. If you have these signs, the log set may not be working properly. Get fresh air at once! Have log set serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Natural Gas: Natural gas is odorless. An odor-making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all Warnings. Keep this manual for reference. It is your guide to safe and proper operation of this log set.
WARNING: Any change to this log set or its controls can be dangerous.
1. This appliance, as supplied, is only for use with the type of gas indicated on the rating plate. This appliance is con­vertible for use with propane/LP, using the GA9000 or GA9100 pilot kit.
2. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use any phone in your building
• immediately call your gas supplier from a neighbor’s phone. F ollow the gas supplier’s instructions
• if you cannot reach your gas supplier , call the fire department
3. Never install the log set
• in a recreational vehicle
• where curtains, furniture, clothing, or other flammable objects are less than 42 inches from the front, top, or sides of the log set
• in high traffic areas
• in windy or drafty areas
4. Before installing in a solid fuel burn­ing fireplace, the chimney flue and fire­box must be cleaned of soot, creosote, ashes and loose paint by a qualified chimney cleaner. Creosote will ignite if highly heated. Inspect chimney flue for damage.
5. Y ou must operate this log set with a fire­place screen in place. Make sure fireplace screen is closed before running log set.
6. This log set is designed to be smoke­less. If logs ever appear to smoke, turn off appliance and call a qualified ser­vice person. eration, slight smoking could occur due to log curing and the burning of manu­facturing residues. You may wish to add more ventalation by opening a window .
7. To reduce the creation of soot, follow the instructions in Cleaning and Main- tenance, page 20.
8. Do not allow fans to blow directly into the fireplace. Avoid any drafts that al­ter burner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can increase sooting.
9. Do not use a blower insert, heat ex­changer insert or other accessory not approved for use with this log set.
10. This log set needs fresh, outside air ven­tilation to run properly. See Air for Combustion and Ventilation, pages 4 through 6.
Note:
During initial op-
11. Do not run log set
• where flammable liquids or vapors are used or stored
• under dusty conditions
12. Do not burn solid fuel in the fireplace after installing the log set. Do not use this log set to cook food or burn paper or other objects.
13. Log set becomes v ery hot when in use. Keep children and adults away from hot surface to avoid burns or clothing igni­tion. Log set will remain hot for a time after shut-down. Allow surface to cool before touching.
14. Carefully supervise young children when they are in the room with log set.
15. Do not use appliance if any part has been exposed to or under water . Immediately call a qualified service technician to in­spect the room appliance and to replace any part of the control system (if using GA9000 or GA9100) and any gas con­trol which has been under water.
16. To help prevent breakage, new logs must be broken-in (see Curing logs page 12).
17. Turn log set off and let cool before ser­vicing, installing, or repairing. Only a qualified service person should install, service, or repair log set.
2
901048
OWNER’S MANUAL
PRODUCT IDENTIFICATION
Grate Steps
Grate
Burner Pan
Burner Clamp
Burner Manifold
Figure 1 - Product Identification (VVDR24 Shown)
Serial Number ________________________________________ Log Set Model ________________________________________
LOCAL CODES
Install and use log set with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code ANS Z223.1, also known as NFPA 54*.
*Available from: American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
UNPACKING
CAUTION: Do not remove the metal data plates from the burner pan. The d ata plates contain im­portant product information.
1. Remove logs, hearth kit, pan materials, and hardware from carton.
2. Remove all protective packaging ap­plied to logs and base for shipment.
3. Check all items for any shipping dam­age. If damaged, promptly inform dealer where you bought the product.
Burner Inlet Fitting
OPTIONAL PRODUCT FEATURES
ON/OFF SAFETY VALVE/ PILOT KIT AND PROPANE/LP CONVERSION
An optional valve/safety pilot kit with a piezo ignitor is available for this appliance. This system requires no matches, batteries, or other sources to light. You must use this optional system for LP conversion. See Ac- cessories, page 20.
REMOTE CONTROL READY (MILLIVOLT) SAFETY VALVE/ PILOT KIT
An optional millivolt valve/safety pilot kit with a piezo ignitor is available for this appliance. This system requires no matches, batteries, or other sources to light. This system may be connected to a wall switch or hand-held wireless remote control. See Ac- cessories, page 20.
REMOTE CONTROL ACCESSORIES
There is an optional hand-held ON/OFF remote control that can be purchased sepa­rately for this log set. You must use the millivolt valve/safety pilot kit to use remote accessories with this appliance. See Acces- sories, page 20.
901048
3
RADCO BURNERS
FOR VENTED NATURAL GAS LOGS
AIR FOR COMBUSTION AND VENTILATION
WARNING: This appliance shall not be installed in a con­fined space or unusually tight construction unless provisions are provided for adequate com­bustion and ventilation air. Read the following instructions to in­sure proper fresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy effi­cient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper com­bustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide ad­equate fresh air for these appliances. This will insure proper venting of vented fuel­burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code. NFPA 54/ANS Z223.1, Sec­tion 5.3, Air for Combustion and Ventila­tion.
All spaces in homes fall into one of the three following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on pages 4 through 6 will
help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and win­dows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is de­fined as construction where:
a. walls and ceilings exposed to the
outside atmosphere have a con­tinuous water vapor retarder with a rating of one perm (6x10 per pa-sec-m2) or less with open­ings gasketed or sealed
b. weather stripping has been
added on openable windows and doors
c. caulking or sealants are applied
to areas such as joints around window and door frames, be­tween sole plates and floors, be­tween wall-ceiling joints, be­tween wall panels, at penetra­tions for plumbing, electrical, and gas lines, and at other openings.
If your home meets all of the three criteria above, you must provide ad­ditional fresh air. See
From Outdoors
If your home does not meet all of the three criteria above, proceed to
termining Fresh-Air Flow For Log Set Location
and
Ventilation Air
, page 6.
, page 5.
and
-11
kg
De-
Confined and Unconfined Space
The National Fuel Gas Code (ANS Z223.1, 1992 Section 5.3) defines a confined space
as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are in­stalled*, through openings not furnished with doors, are considered a part of the unconfined space.
This log set shall not be installed in a con­fined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air.
* Adjoining rooms are communicating only if there are doorless passageways or ventila­tion grills between them.
4
901048
OWNER’S MANUAL
AIR FOR COMBUSTION AND VENTILATION
Continued
DETERMINING FRESH-AIR FLOW FOR APPLIANCE LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space. Space: Includes the room in which you will install appliance plus any adjoining rooms with doorless passageways or ventilation grills
between the rooms.
1. Determine the volume of the space (length x width x height). Length x Width x Height = _________________cu. ft. (volume of space)
Example:
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.
_____________ (volume of space) ÷ 50 cu. ft. = (maximum Btu/Hr the space can support)
Example:
3. Add the Btu/Hr of all fuel burning appliances in the space. Gas fireplace logs _____________ Btu/Hr
Gas water heater* _____________ Btu/Hr Gas furnace _____________ Btu/Hr Vented gas heater _____________ Btu/Hr Vent-free heater _____________ Btu/Hr Other gas appliances* + _____________ Btu/Hr Total = _____________ Btu/Hr
* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
_____________ Btu/Hr (maximum the space can support) _____________ Btu/Hr (actual amount of Btu/Hr used)
Example:
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-
ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.
B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6. C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)
2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)
Example:
Gas water heater 40,000 Btu/Hr Gas fireplace logs + 55,000 Btu/Hr Total = 95,000 Btu/Hr
51,200 Btu/Hr (maximum the space can support) 95,000 Btu/Hr (actual amount of Btu/Hr used)
WARNING: If the area in which the appliance may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the
901048
National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3
5
or applicable local codes.
Continued
RADCO BURNERS
FOR VENTED NATURAL GAS LOGS
AIR FOR COMBUSTION AND VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro­vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see op­tion 3, Figure 2). Follow the National Fuel
Gas Code NFPA 54/ANS Z223.1, Section
5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
WARNING: Rework work­sheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two per­manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces.
IMPORTANT:
inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.
Do not provide openings for
Ventilation
Grills
Into Adjoining
Room,
Option 1
Figure 2 - Ventilation Air from Inside Building
Or
Remove Door into Adjoining
Room, Option
3
12"
Outlet Air
Ventilation Grills
Into Adjoining Room,
Ventilated Attic
Outlet Air
Inlet Air
Inlet Air
Figure 3 - Ventilation Air from Outdoors
Crawl Space
12"
Option 2
To Attic
To
Crawl
Space
Ventilated
6
901048
OWNER’S MANUAL
INSTALLATION
CAUTION: Do not remove the metal data plates attached to the burner pan. The data plates contain important warranty in­formation.
WARNING: Before installing in a solid fuel burning fireplace, the chimney flue and firebox must be cleaned of soot, creosote, ashes and loose paint by a quali­fied chimney cleaner. Creosote will ignite if highly heated. A dirty chimney flue may create and dis­tribute soot within the house. In­spect chimney flue for damage.
NOTICE: Installation, service, and repair of this appliance must be performed by a qualified installer, service agency, company or gas supplier experienced with this type of gas appliance. Only fac­tory authorized components listed in these instructions may be used in accordance with the manufacturer’s instructions and all codes and requirements of the authority having jurisdiction. Any modifications to this kit, or use of unauthorized components or ac­cessory items will void the manufacturer’s warranty, and may result in a hazardous condition.
FLUE OPENING SPECIFICATIONS
Note:
This vented appliance must be in-
stalled only in a solid-fuel burning fireplace with a working flue and constructed of non­combustible material.
The charts in Figure 4 indicate technical information regarding the installation of your gas log set. Please make sure that all of the specifications shown are applicable be­fore installation is attempted.
The fireplace must include a working flue and venting system with the minimum open­ings shown in the Figure 4.
Btu Input
MODEL DESCRIPTION
CVSR18 18" Single Burner 50,000 40,000 8" dia. CPVSR18 18" Single Burner 50,000 40,000 8" dia. CVSR24 24" Single Burner 60,000 50,000 8" dia. CPVSR24 24" Single Burner 60,000 50,000 8" dia. CVDR18 18" Dual Burner 55,000 45,000 8" dia. CVDR24 24" Dual Burner 65,000 55,000 8" dia. CVDR30 30" Dual Burner 70,000 60,000 8" dia.
MINIMUM FIREBOX SIZES
LOG FRONT BACK SIZE WIDTH* WIDTH** DEPTH HEIGHT
18" 28" 16" 14" 18" 24" 29 3/4" 17" 15 1/2" 18" 30" 36" 27" 18" 18"
*Add 6" if safety valve/pilot is used **At depth indicated
FUEL INLET PRESSURE
SPECIFICATIONS ("W.C.)
Min. Max. NG 5.5 10.5 LP 11 13
Figure 4 - Technical Information Charts
CHECK GAS TYPE
Use only natural gas. If your gas supply is not natural gas, you must install ON/OFF Safety Valve/Pilot Kit (see Accessories, page 20). Call dealer where you bought log set.
If the fireplace does not have a gas supply shut-off valve, one must be installed.
Natural Gas
VENTING SPECIFICATIONS FOR INSTALLATION
The fireplace chimney flue and vent must be drafting properly. To check the vent for proper drafting: Light a tightly rolled news­paper on one end and place it at the inside front edge of the fireplace. Observe the smoke and be sure the vent is properly drawing it up the chimney. If the smoke spills out into the room, extinguish the flame and remove any obstruction until proper venting is achieved.
The chimney flue must remain open a mini­mum of 3" at all times during the operation of this log set.
Btu Input
Propane Gas
BURNER ORIFICE
LOG NATURAL PROPANE/LP SIZE IN. NUM. IN. NUM.
18" .1285 30 .076 48 24" .144 27 .086 44 30" .154 23 .089 43
Minimum
Vent Opening
Continued
901048
7
RADCO BURNERS
FOR VENTED NATURAL GAS LOGS
INSTALLATION
Continued
INSTALLING DAMPER CLAMP
Secure the damper stop clamp provided to the leading edge of the damper as shown in Figure 5. If for any reason this clamp doesn't work on your fireplace, another suitable clamp or permanent stop must be installed, or the damper blade must be cut or removed.
Damper Clamp
Damper
Masonry Fireplace
Damper Clamp
Figure 5 - Attaching Damper Clamp
Manufactured Fireplace
CONNECTING TO GAS SUPPLY
Damper
Damper
CAUTION: Use only new, black iron or steel pipe. Inter­nally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to log set. If pipe is too small, undue loss of pressure will occur.
Installation must include a manual shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from log set (see Figure 6).
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in a clogged burner injector.
CAUTION: Use pipe joint seal­ant that is resistant to liquid pe­troleum (LP) gas.
Install sediment trap in supply line as shown in Figure 6. Locate sediment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into log set controls. If sediment trap is not installed or is installed wrong, log set may not run properly.
Approved Flexible Gas Hose (if allowed by local codes)
CHECKING GAS CONNECTIONS
WARNING: Test all gas pip­ing and connections for leaks after installing or servicing. Cor­rect all leaks at once.
WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.
Pressure Testing Gas Supply Piping System
Test Pressures In Excess Of 1/2 PSIG
1. Disconnect log set and its individual manual shutoff valve from gas supply piping system.
2. Cap off open end of gas pipe where manual shutoff valve was connected.
3. Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.
4. Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles form­ing show a leak.
5. Correct all leaks at once.
6. Reconnect log set and manual shutoff valve to gas supply . Check reconnected fittings for leaks.
WARNING: A qualified ser­vice person must connect log set to gas supply. Follow all local codes.
Installation Items Needed
Before installing log set, make sure you have the items listed below.
• piping (check local codes)
• sealant (resistant to LP gas)
• manual shutoff valve
• test gauge connection
• adjustable (crescent) wrench or pliers
• sediment trap
• tee joint
• pipe wrench
A.G.A. Design-Certified Manual Shutoff Valve With 1/8" NPT Tap*
3" Minimum
Cap
Pipe Nipple
Figure 9 - Gas Connection
* Purchase the optional A.G.A. design-certified manual shutoff valve from your dealer. See Accessories, page 20.
** Minimum inlet pressure for purpose of input adjustment.
8
Sediment Trap
From Gas Meter (5" W.C.** to 10.5" W.C. Pressure)
Tee Joint
901048
Loading...
+ 16 hidden pages