WARNING: If the information in this manual is not
followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
— Installation and service must be performed by a quali-
fied installer, service agency, or the gas supplier.
This appliance may be installed in an aftermarket*, permanently located, manufactured
(mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This
appliance is not convertible for use with other gases.
WARNING: Improper installation,
adjustment, alteration, service, or
maintenance can cause injury or
property damage. Refer to this
manual for correct installation and
operational procedures. For assistance or additional information
consult a qualified installer, service agency, or the gas supplier.
WARNING: This is an unvented
gas-fired heater. It uses air (oxygen) from the room in which it is
installed. Provisions for adequate
combustion and ventilation air
must be provided. Refer to
Combustion and Ventilation
tion on page 4 in this manual.
Air for
sec-
*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Save this manual for future reference.
Page 2
VENT-FREE PROPANE/LP GAS HEATER
SAFETY
INFORMATION
WARNINGS
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate, or service this heater. Improper use of this heater can
cause serious injury or death
from burns, fire, explosion, and
carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs
of carbon monoxide poisoning resemble the
flu, with headaches, dizziness, and/or nausea. If you have these signs, the heater may
not be working properly. Get fresh air atonce! Have heater serviced. Some people
are more affected by carbon monoxide than
others. These include pregnant women,
people with heart or lung disease or anemia,
those under the influence of alcohol, and
those at high altitudes.
Propane/LP Gas: Propane/LP gas is odor-
less. An odor-making agent is added to
propane/LP gas. The odor helps you detect
a propane gas leak. However, the odor added
to propane/LP gas can fade. Propane/LP gas
may be present even though no odor exists.
Make certain you read and understand all
Warnings. Keep this manual for reference.
It is your guide to safe and proper operation
of this heater.
WARNING: Any change to this
heater or its controls can be
dangerous.
WARNING: Do not use any
accessory not approved for use
with this heater.
Due to high temperatures, the
appliance should be located out
of traffic and away from furniture
and draperies.
Do not place clothing or other
flammable material on or near
the appliance. Never place any
objects on the heater.
Surface of heater becomes very
hot when running heater. Keep
children and adults away from
hot surface to avoid burns or
clothing ignition. Heater will remain hot for a time after shutdown. Allow surface to cool before touching.
Carefully supervise young children when they are in the same
room with heater.
Make sure grill guard is in place
before running heater.
Keep the appliance area clear and
free from combustible materials,
gasoline, and other flammable
vapors and liquids.
1.This appliance is only for use with the
type of gas indicated on the rating plate.
This appliance is not convertible for use
with other gases.
2.Do not place propane/LP supply tank(s)
inside any structure. Locate propane/
LP supply tank(s) outdoors.
3.If you smell gas
• shut off gas supply
• do not try to light any appliance
•
do not touch any electrical switch; do
not use any phone in your building
• immediately call your gas supplier
from a neighbor’s phone. Follow the
gas supplier’s instructions
• if you cannot reach your gas supplier,
call the fire department
4.Heater shall not be installed in a bathroom.
5.This heater needs fresh, outside air ventilation to run properly. This heater has
an Oxygen Depletion Sensing (ODS)
safety shutoff system. The ODS shuts
down the heater if not enough fresh air
is available. See Air for Combustionand Ventilation, pages 4 through 6.
6.Keep all air openings in the front and
bottom of heater clear and free of debris. This will insure enough air for
proper combustion.
7.If heater shuts off, do not relight until
you provide fresh, outside air. If heater
keeps shutting off, have it serviced.
8.Do not run heater
• where flammable liquids or vapors
are used or stored
• under dusty conditions
9.Before using furniture polish, wax, carpet cleaner, or similar products, turn
heater off. If heated, the vapors from
these products may create a white powder residue within burner box or on
adjacent walls or furniture.
10. Do not use heater if any part has been
under water. Immediately call a qualified service technician to inspect the
room heater and to replace any part of
the control system and any gas control
which has been under water.
11. Turn off heater and let cool before ser vicing. Only a qualified service person
should service and repair heater.
12. Operating heater above elevations of
4,500 feet could cause pilot outage.
13. To prevent performance problems, do
not use propane/LP fuel tank of less
than 100 lbs. capacity.
2
104268
Page 3
OWNER’S MANUAL
PRODUCT
IDENTIFICATION
Front
Panel
Ignitor Button
Control Knob
Grill
Guard
Glass
Panel
Heater
Cabinet
PRODUCT
FEATURES
SAFETY DEVICE
This heater has a pilot with an Oxygen
Depletion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for
vent-free room heaters. The ODS/pilot shuts
off the heater if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This heater has a piezo ignitor. This system
requires no matches, batteries, or other
sources to light heater.
THERMOSTATIC HEAT
CONTROL
This heater has a thermostat sensing bulb
and thermostat control. This results in the
greatest heater comfort. This can also result
in lower gas bills.
Figure 1 - Vent-Free Propane/LP Gas Heater
LOCAL CODES
Install and use heater with care. Follow all
local codes. In the absence of local codes, use
the latest edition of The National Fuel GasCode ANS Z223.1, also known as NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
UNPACKING
1.Remove heater from carton.
2.Remove all protective packaging applied to heater for shipment.
3.Check heater for any shipping damage.
If heater is damaged, promptly inform
dealer where you bought heater.
104268
3
Page 4
VENT-FREE PROPANE/LP GAS HEATER
AIR FOR
COMBUSTION AND
VENTILATION
WARNING: This heater shall
not be installed in a confined space
or unusually tight construction
unless provisions are provided
for adequate combustion and ventilation air. Read the following instructions to insure proper fresh
air for this and other fuel-burning
appliances in your home
Today’s homes are built more energy efficient than ever. New materials, increased
insulation, and new construction methods
help reduce heat loss in homes. Home owners
weather strip and caulk around windows and
doors to keep the cold air out and the warm air
in. During heating months, home owners
want their homes as airtight as possible.
While it is good to make your home energy
efficient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning
appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and
fuel burning appliances draw air from the
house to operate. You must provide adequate fresh air for these appliances. This
will insure proper venting of vented fuelburning appliances.
.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National
Fuel Gas Code. NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classifications:
1.Unusually Tight Construction
2.Unconfined Space
3.Confined Space
The information on pages 4 through 6 will
help you classify your space and provide
adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for
combustion and ventilation. However, in
buildings of unusually tight construction,
you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings exposed to the
outside atmosphere have a continuous water vapor retarder with
a rating of one perm (6 x 10
per pa-sec-m2) or less with openings gasketed or sealed
b. weather stripping has been
added on openable windows and
doors
c. caulking or sealants are applied
to areas such as joints around
window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and
gas lines, and at other openings.
If your home meets all of the three
criteria above, you must provide additional fresh air. See
From Outdoors
If your home does not meet all of the
three criteria above, proceed to
mining Fresh-Air Flow for Heater Location
and
on page 5.
, page 6
Ventilation Air
.
-11
and
Deter-
kg
Confined and Unconfined
Spaces
The National Fuel Gas Code ANS Z223.1
defines a confined space as a space whose
volume is less than 50 cubic feet per 1000
Btu per hour (4.8 cubic meters per kw) of the
aggregate input rating of all appliances installed in that space and an unconfined space
as a space whose volume is not less than 50
cubic feet per 1000 Btu per hour (4.8 cubic
meters per kw) of the aggregate input rating
of all appliances installed in that space.
Rooms communicating directly with the
space in which the appliances are installed*,
through openings not furnished with doors,
are considered a part of the unconfined
space.
This heater shall not be installed in a confined space or unusually tight construction
unless provisions are provided for adequate
combustion and ventilation air.
*Adjoining rooms are communicating only
if there are doorless passageways or ventilation grills between them.
4
104268
Page 5
OWNER’S MANUAL
AIR FOR
COMBUSTION AND
VENTILATION
Continued
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this worksheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between
the rooms.
1.Determine the volume of the space (length x width x height).
Length x Width x Height = ________________ cu. ft. (volume of space)
Example:
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.
2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.
_______________(volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)
Example:
3.Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free heater_________________ Btu/Hr
Gas water heater*_________________ Btu/Hr
Gas furnace_________________ Btu/Hr
Vented gas heater_________________ Btu/Hr
Gas fireplace logs_________________ Btu/Hr
Other gas appliances* + _________________ Btu/Hr
Total= _________________ Btu/Hr
* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
_________________ Btu/Hr (maximum the space can support)
_________________ Btu/Hr (actual amount of Btu/Hr used)
Example:
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-
ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.
B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.
C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.
Space size 18 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2304 cu. ft. (volume of space)
2304 cu. ft. (volume of space) ÷ 50 cu. ft. = 46.1 or 46,100 (maximum Btu/Hr the space can support)
Example:
Gas water heater40,000Btu/Hr
Vent-free heater+10,000Btu/Hr
Total=50,000Btu/Hr
46,100 Btu/Hr (maximum the space can support)
50,000 Btu/Hr (actual amount of Btu/Hr used)
WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space
or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the
104268
National Fuel Gas Code, ANS Z223.1, Section 5.3
5
or applicable local codes.
Continued
Page 6
VENT-FREE PROPANE/LP GAS HEATER
Or
Remove
Door into
Adjoining
Room,
Option 3
Ventilation Grills
Into Adjoining Room,
Option 2
12"
12"
Ventilation
Grills
into Adjoining
Room,
Option 1
AIR FOR
COMBUSTION AND
VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside
Building
This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconfined space, you must provide two permanent openings: one within
12" of the ceiling and one within 12" of the
floor on the wall connecting the two spaces
(see options 1 and 2, Figure 2). You can also
remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel
Gas Code NFPA 54/ANS Z223.1, Section
5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two permanent openings: one within 12" of the
ceiling and one within 12" of the floor.
Connect these items directly to the outdoors
or spaces open to the outdoors. These spaces
include attics and crawl spaces. Follow the
National Fuel Gas Code NFPA 54/ANS
Z223.1, Section 5.3, Air for Combustion and
Ventilation for required size of ventilation
grills or ducts.
IMPORTANT:
for inlet or outlet air into attic if attic has a
thermostat-controlled power vent. Heated
air entering the attic will activate the power
vent.
WARNING: Rework worksheet, adding the space of the
adjoining unconfined space. The
combined spaces must have
enough fresh air to supply all
appliances in both spaces.
Do not provide openings
Figure 2 - Ventilation Air from Inside Building
Outlet
Air
Outlet
Air
Inlet
Air
Inlet Air
Figure 3 - Ventilation Air from Outdoors
Ventilated
Attic
To Attic
To
Crawl
Space
Ventilated
Crawl Space
6
104268
Page 7
OWNER’S MANUAL
e
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat. Use
this heater along with your primary heating system. Do not install this heater as your primary
heat source. If you have a central
heating system, you may run
system’s circulating blower while
using heater. This will help circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
WARNING: A qualified service person must install heater.
Follow all local codes.
CHECK GAS TYPE
Use only propane/LP gas. If your gas supply
is not propane/LP, do not install heater. Call
dealer where you bought heater for proper
type heater.
INSTALLATION ITEMS
Before installing heater, make sure you have
the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• ground joint union
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
* A CSA/AGA design-certified equipment
shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. The optional CSA/AGA design-certified equipment shutoff valve can be purchased from your dealer. See Accessory,
page 13.
LOCATING HEATER
This heater is designed to be mounted on a
wall.
WARNING: Maintain the minimum clearances shown in Figure
4. If you can, provide greater clearances from floor, ceiling, and
joining wall.
WARNING: Never install the
heater
• in a bathroom
• in a recreational vehicle
• where curtains, furniture,
clothing, or other flammable
objects are less than 36 inches
from the front, top, or sides of
the heater
• as a fireplace insert
• in high traffic areas
• in windy or drafty areas
CAUTION: This heater creates warm air currents. These
currents move heat to wall surfaces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater
where impurities (such as tobacco smoke, aromatic candles,
cleaning fluids, oil or kerosene
lamps, etc.) in the air exist, may
discolor walls.
IMPORTANT:
ture to the air. Although this is beneficial,
installing heater in rooms without enough
ventilation air may cause mildew to form
from too much moisture. See Air for Com-bustion and Ventilation, pages 4 through 6.
CAUTION: If you install the
heater in a home garage
• heater pilot and burner must
be at least 18 inches above
floor
• locate heater where moving ve-
hicle will not hit it
Vent-free heaters add mois-
CEILING
36"
6"
Minimum
From
Sides Of
Heater
Left
Side
FLOOR
Figure 4 - Mounting Clearances As Viewed
From Front of Heater
Minimum
Right
Side
Minimum to
Top Surface
of Carpeting,
3"
Minimum To Top Surfac
Tile or Other
Of Carpeting, Tile Or OthCombustible Material
Combustible
Material
THERMOSTAT SENSING
BULB
The thermostat sensing bulb is located inside the heater. Do not move this bulb during installation or operation of the heater.
INSTALLING HEATER TO
WALL
Marking Screw Locations
1.Determine where you will locate heater.
WARNING: Maintain minimum
clearances shown in Figure 5. If
you can, provide greater clearances from floor and joining wall.
2.Mark two mounting screw locations on
wall (see Figure 5).
7
/8"
8
Minimum
To
Maintain 6"
Clearance
From Wall
JOINING WALL
3
/4"
7
Mounting
Screw
Locations
1
/4"
20
Minimum To
Maintain 3"
Clearance
From Floor
104268
For convenience and efficiency, install heater
• where there is easy access for operation,
inspection, and service
• in coldest part of room
7
FLOOR
Figure 5 - Mounting Screw Locations
Continued
Page 8
VENT-FREE PROPANE/LP GAS HEATER
INSTALLATION
Continued
Installing Two Mounting Screws
Note:
Wall anchors and mounting screws
are in hardware package. The hardware package is provided with heater.
Attaching To Wall Stud Method
For attaching mounting screw to wall stud
1.
Drill hole at marked location using 9/64"
drill bit.
2.Insert mounting screw into wall stud.
3.Tighten screw until 1/16" space (thick-
ness of penny) is between screwhead
and wall.
Attaching To Wall Anchor Method
Follow instructions below to attach mounting screws to hollow walls (wall areas between studs) or solid walls (concrete or
masonry).
1.Drill holes at marked locations using
5/16" drill bit. For solid walls (concrete
or masonry), drill at least 1 1/4" deep.
2.Fold wall anchor (see Figure 6).
3. Insert wall anchor (wings first) into
hole. Tap anchor flush to wall.
4.For thin walls (1/2" or less), insert red
key into wall anchor. Push red key to
“pop” open anchor wings (see Figure
7).
IMPORTANT:
For thick walls (over 1/2" thick) or solid
walls, do not pop open wings.
5.Tighten two screws until 1/16" space
(thickness of penny) is between
screwheads and wall (see Figure 8).
Do not hammer key!
Thin or Thick
Wall
(thick wall
shown)
1/16"
Space
Solid Wall
Figure 8 - Tightening Anchors
Placing Heater On Mounting
Screws
1.Locate two keyhole slots on back panel
of heater (see Figure 9).
2. Place large openings of slots over
screwheads. Slide heater down until
screws are in small portion of slots.
Keyhole Slots
Figure 9 - Location Of Keyhole Slots On
Back Panel Of Heater
Removing Front Panel Of Heater
1.Remove two screws near bottom corners of front panel.
2.Lift straight up on grill guard until it stops.
Grill guard will slide up about 1/4".
3.Pull bottom of front panel forward, then
down.
Installing Bottom Mounting
Screw
1. Locate bottom mounting hole. This
hole is near bottom on back panel of
heater (see Figure 11).
2.Mark screw location on wall.
3.Remove heater from wall.
4. If installing bottom mounting screw
into hollow or solid wall, install wall
anchor. Follow steps 1 through 5 under Attaching To Wall Anchor Method,
column 1.
If installing bottom mounting screw
into wall stud, drill hole at marked location using 9/64" drill bit.
5.Replace heater on wall.
6. Insert bottom anchor screw through
back panel into bottom anchor or
drilled hole (see Figure 11).
7. Tighten screw until heater is firmly
secured to wall. Do not over tighten.
Note:
Do not replace front panel at this
time. Replace front panel after making
gas connections and checking for leaks
(see pages 9 and 10 ).
Figure 11 - Installing Bottom Mounting
Screw
Figure 6 - Folding Anchor
Thin Walls
(1/4" to 1/2"
thick)
Figure 7 - Popping Open Anchor Wings
For Thin Walls
Figure 10 - Removing Front Panel Of
Heater
8
104268
Page 9
OWNER’S MANUAL
INSTALLATION
Continued
CONNECTING TO GAS
SUPPLY
WARNING: This appliance requires a 3/8" NPT (National Pipe
Thread) inlet connection to the
pressure regulator.
WARNING: A qualified service
person must connect heater to gas
supply. Follow all local codes.
CAUTION: Never connect
heater directly to the propane/LP
supply. This heater requires an
external regulator (not supplied).
Install the external regulator between the heater and propane/LP
supply.
Installation must include an equipment shutoff
valve, ground joint union, and plugged 1/8"
NPT tap. Locate NPT tap within reach for test
gauge hook up. NPT tap must be upstream
from heater (see Figure 13).
IMPORTANT:
Install an equipment shutoff
valve in an accessible location. The equipment shutoff valve is for turning on or
shutting off the gas to the appliance.
Propane/LP
Supply
Tank
Figure 12 - External Regulator With Vent
Pointing Down
External
Regulator
Vent
Pointing
Down
Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged heater valves.
CAUTION: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
Install sediment trap in supply line as shown
in Figure 13. Locate sediment trap where it
is within reach for cleaning. Locate sediment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into heater controls. If sediment trap
is not installed or is installed wrong, heater
may not run properly.
IMPORTANT:
Hold pressure regulator
with wrench when connecting it to gas piping and/or fittings.
The installer must supply an external regulator. The external regulator will reduce
incoming gas pressure. You must reduce
incoming gas pressure between 11 and 14
inches of water. If you do not reduce incoming gas pressure, heater regulator damage
could occur. Install external regulator with
the vent pointing down as shown in Figure
12. Pointing the vent down protects it from
freezing rain or sleet.
CAUTION: Use only new,
black iron or steel pipe. Internally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe 3/8"
diameter or greater to allow
proper gas volume to heater. If
pipe is too small, undue loss of
pressure will occur.
Pressure
Regulator
3/8" NPT
Pipe Nipple
Heater
Cabinet
Ground Joint Union
Tee Joint
Equipment Shutoff
Valve *
From External
Regulator
(11" W.C. to
14" W.C.
Pressure)
3" Minimum
Figure 13 - Gas Connection
Reducer
Bushing to
1/8" NPT
1/8" NPT
Plug Tap
Tee
Joint
Pipe
Nipple
Cap
Test
Gauge
Connection *
Sediment Trap
* A CSA/AGA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the optional CSA/AGA design-certified
equipment shutoff valve from your dealer. See Accessory, page 13.
104268
Continued
9
Page 10
VENT-FREE PROPANE/LP GAS HEATER
INSTALLATION
Continued
CHECKING GAS
CONNECTIONS
WARNING: Test all gas piping and connections for leaks
after installation or servicing.
Correct all leaks at once.
WARNING: Never use an open
flame to check for a leak. Apply a
mixture of liquid soap and water to
all joints. Bubbles forming show a
leak. Correct all leaks at once.
CAUTION: Make sure external regulator has been installed
between propane/LP supply and
heater. See guidelines under
necting to Gas Supply
Pressure Testing Gas Supply
Piping System
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1.Disconnect appliance with its appliance
main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig
will damage heater regulator.
2. Cap off open end of gas pipe where
equipment shutoff valve was connected.
3.Pressurize supply piping system by either using compressed air or opening
propane/LP supply tank valve.
4.Check all joints of gas supply piping
system. Apply mixture of liquid soap
and water to gas joints. Bubbles forming show a leak.
5.Correct all leaks at once.
6. Reconnect heater and equipment
shutoff valve to gas supply. Check reconnected fittings for leaks.
Con-
, page 9.
Test Pressures Equal To or Less Than 1/2
PSIG (3.5 kPa)
1.Close equipment shutoff valve (see Figure 14).
2.Pressurize supply piping system by either using compressed air or opening
propane/LP supply tank valve.
3.Check all joints from propane/LP supply tank to equipment shutoff valve (see
Figure 15). Apply mixture of liquid
soap and water to gas joints. Bubbles
forming show a leak.
4.Correct all leaks at once.
ON
Equipment
Shutoff
Valve
Figure 14 - Equipment Shutoff Valve
Propane/LP
Supply Tank
Figure 15 - Checking Gas Joints
Open
POSITION
OFF
POSITION
Closed
Pressure Testing Heater Gas
Connections
1.Open equipment shutoff valve (see Figure 14).
2.Open propane/LP supply tank valve.
3.Make sure control knob of heater is in
the OFF position.
4.Check all joints from equipment shutoff
valve to control valve (see Figure 15).
Apply mixture of liquid soap and water to gas joints. Bubbles forming show
a leak.
5.Correct all leaks at once.
6. Light heater (see Operating Heater,
pages 11 and 12). Check the rest of the
internal joints for leaks.
7.Turn off heater (see To Turn Off Gas toAppliance, page 12).
8.Replace front panel.
Control
Valve
Location
Equipment
Shutoff
Valve
10
104268
Page 11
OWNER’S MANUAL
OPERATING
HEATER
FOR YOUR SAFETY
READ BEFORE
LIGHTING
WARNING: If you do not follow these instructions exactly, a
fire or explosion may result causing property damage, personal
injury or loss of life.
A. T
his appliance has a pilot which must
be lighted by hand. When lighting the
pilot, follow these instructions exactly .
B. BEFORE LIGHTING smell all
around the appliance area for gas. Be
sure to smell next to the floor because
some gas is heavier than air and will
settle on the floor.
WHAT TO DO IF YOU SMELL
GAS
• Do not try to light any appliance.
•
Do not touch any electric switch; do
not use any phone in your building .
• Immediately call your gas supplier
from a neighbor’s phone. Follow
the gas supplier’s instructions.
• If you cannot reach your gas sup-
plier, call the fire department.
C. Use only your hand to push in or turn
the gas control knob. Ne ver use tools.
If the knob will not push in or turn
by hand, don’t try to repair it, call a
qualified service technician or gas
supplier. Force or attempted repair
may result in a fire or explosion.
D. Do not use this appliance if any part
has been under water. Immediately
call a qualified service technician to
inspect the appliance and to replace
any part of the control system and
any gas control which has been under water.
LIGHTING
INSTRUCTIONS
1.STOP! Read the safety information,
column 1.
2.Make sure equipment shutoff valve
is fully open.
3.Tur n control knob clockwise
to the OFF position (see Figure 16).
4.Wait f ive (5) minutes to clear out any
gas. Then smell for gas, including
near the floor. If you smell gas,
STOP! Follow “B” in the safety information. If you don’t smell gas, go
to the next step.
5.T urn contr ol knob counterclockwise
to the PILOT position.
C-clockwise
Press in control knob for f ive (5) seconds (see Figure 16).
Note:
You may be running this
heater for the first time after hooking up to gas supply. If so, the control knob may need to be pressed in
for 30 seconds. This will allow air to
bleed from the gas system.
6.With control knob pressed in, push
down and release ignitor button. This
will light pilot. The pilot is attached
to the front of burner. The pilot can
be seen through the glass panel. If
needed, keep pressing ignitor button
until pilot lights.
Note:
If pilot does not stay lit, refer
to Troubleshooting, pages 14 through
16. Also contact a qualified service
person or gas supplier for repairs.
Until repairs are made, light pilot with
match. To light pilot with match, see
Manual Lighting Procedure, page 12.
7.Keep control knob pressed in for 30
seconds after lighting pilot. After 30
seconds, release control knob.
•If control knob does not pop up when
released, contact a qualified service
person or gas supplier for repairs.
Note:
If pilot goes out, repeat steps
3 through 7. This heater has a safety
interlock system. W ait one (1) minute
before lighting pilot again.
Clockwise
8.T urn contr ol knob counterclockwise
C-clockwise
to desired heating level. The
main burner should light. Set control
knob to any heat level between HI
and LO.
CAUTION: Do not try to adjust
heating levels by using the equipment shutoff valve.
Ignitor Button
IGNITOR
Figure 16 - Control Knob In The OFF
Position
Thermocouple
Figure 17 - Pilot
Control Knob
PILOT
OFF
HI
Ignitor Electrode
Pilot Burner
LO
104268
Continued
11
Page 12
VENT-FREE PROPANE/LP GAS HEATER
1/2 GLASS HEIGHT
OPERATING
HEATER
Continued
TO TURN OFF GAS
TO APPLIANCE
Shutting Off Heater
1.Tur n control knob clockwise
to the OFF position.
2.Turn off all electric power to the appliance if service is to be performed.
Shutting Off Burner Only (pilot
stays lit)
Turn control knob clockwise
the PILOT position.
THERMOSTAT
CONTROL
OPERATION
The thermostatic control used on these
models differs from standard thermostats. Standard thermostats simply turn
on and off the burner. The thermostat
used on this heater senses the room temperature. The thermostat adjusts the
amount of gas flow to the burner. This
increases or decreases the burner flame
height. At times the room may exceed the
set temperature. If so, the burner will
shut off. The burner will cycle back on
when room temperature drops below the
set temperature. The control knob can be
set to any heat level between HI and LO.
Note:
The thermostat sensing bulb measures the temperature of air near the
heater cabinet. This may not always agree
with room temperature (depending on
housing construction, installation location, room size, open air temperatures,
etc.). Frequent use of your heater will let
you determine your own comfort levels.
Clockwise
Clockwise
to
MANUAL LIGHTING
PROCEDURE
1.Remove front panel (see Figure 10,
page 8).
2.Follow steps 1 through 5 under Light-ing Instructions, page 11.
3.With control knob pressed in, strike
match. Hold match to pilot until pilot lights.
4.Keep control knob pressed in for 30
seconds after lighting pilot. After 30
seconds, release control knob . Follow
step 8 under Lighting Instructions,
page 11.
5.Replace front panel.
INSPECTING
BURNER
Check pilot flame pattern and burner flame
pattern often.
PILOT FLAME PATTERN
Figure 18 shows a correct pilot flame pattern.
Figure 19 shows an incorrect pilot flame
pattern. The incorrect pilot flame is not touching the thermocouple. This will cause the
thermocouple to cool. When the thermocouple cools, the heater will shut down.
If pilot flame pattern is incorrect, as shown
in Figure 19
• turn heater off (see To Turn Off Gas to
Appliance, column 1)
•
see Troubleshooting, pages 14 through 16
Pilot Burner
Thermocouple
Figure 18 - Correct Pilot Flame Pattern
GRH/OV 007GOOD PILOT/LP
BURNER FLAME PATTERN
Figure 20 shows a correct burner flame
pattern. Figure 21 shows an incorrect burner
flame pattern. The incorrect burner flame
pattern shows yellow tipping of the flame. It
also shows the flame higher than 1/2 the
glass panel height.
WARNING: If yellow tipping
occurs, your heater could produce increased levels of carbon
monoxide. If burner flame pattern shows yellow tipping, follow
the instructions below.
NOTICE: Do not mistake orange
flames with yellow tipping. Dust
or other fine particles enter the
heater and burn causing brief
patches of orange flame.
If burner flame pattern is incorrect, as shown
in Figure 21
• turn heater off (see To Turn Off Gas toAppliance, column 1)
•
see Troubleshooting, pages 14 through 16
Figure 20 - Correct Burner Flame Pattern
Yellow
Tipping
1/2 GLASS HEIGHT
Figure 21 - Incorrect Burner Flame Pattern
Thermocouple
Figure 19 - Incorrect Pilot Flame Pattern
12
Pilot Burner
GRH/OV 008BAD PILOT/LP
104268
Page 13
OWNER’S MANUAL
CLEANING AND
MAINTENANCE
WARNING: Turn off heater
and let cool before cleaning.
CAUTION: You must keep
control areas, burner, and circulating air passageways of heater
clean. Inspect these areas of
heater before each use. Have
heater inspected yearly by a qualified service person. Heater may
need more frequent cleaning due
to excessive lint from carpeting,
bedding material, pet hair, etc.
ODS/PILOT AND BURNER
ORIFICE
• Use a vacuum cleaner, pressurized air,
or small, soft bristled brush to clean.
CLEANING BURNER
PILOT AIR INLET HOLE
We recommend that you clean the unit every
2,500 hours of operation or every three months.
We also recommend that you keep the burner
tube and pilot assembly clean and free of dust
and dirt. To clean these parts we recommend
using compressed air no greater than 30 PSI.
Your local computer store, hardware store, or
home center may carry compressed air in a
can. You can use a vacuum cleaner in the
blow position. If using compressed air in a
can, please follow the directions on the can.
If you don't follow directions on the can, you
could damage the pilot assembly.
1.Shut off the unit, including the pilot.
Allow the unit to cool for at least thirty
minutes.
2.Inspect burner, pilot for dust and dirt.
3. Blow air through the ports/slots and
holes in the burner.
Clean the pilot assembly also. A yellow tip
on the pilot flame indicates dust and dirt in
the pilot assembly. There is a small pilot air
inlet hole about two inches from where the
pilot flame comes out of the pilot assembly
(see Figure 22). With the unit off, lightly
blow air through the air inlet hole. You may
blow through a drinking straw if compressed
air is not available.
Pilot Air Inlet Hole
SERVICE
HINTS
When Gas Pressure Is Too Low
• pilot will not stay lit
Pilot Assembly
Figure 22 - Pilot Inlet Air Hole
CABINET
Air Passageways
• Use a vacuum cleaner or pressurized air
to clean.
Exterior
• Use a soft cloth dampened with a mild
soap and water mixture. Wipe the cabinet
to remove dust.
• burner will have delayed ignition
• heater will not produce specified heat
• propane/LP gas supply may be low
When Gas Quality Is Bad
• pilot will not stay lit
• burner will produce flames and soot
• heater will backfire when lit
You may feel your gas pressure is too low or
gas quality is bad. If so, contact your local
propane/LP gas supplier.
ACCESSORY
SERVICE
PUBLICATIONS
You can purchase a service manual from the
address listed on the back page of this
manual. Send a check for $5.00 payable to
DESA International.
Purchase these heater accessories from your
local dealer. If they cannot supply this accessories, either contact your nearest Parts
Central or call DESA International’s Parts
Department at 1-800-972-7879 for referral
information. You can also write to the address listed on the back page of this manual.
TECHNICAL
SERVICE
You may have further questions about installation, operation, or troubleshooting. If
so, contact DESA International’s Technical
Service Department at 1-800-323-5190.
You can also visit DESA International’s
technical service web site at
www.desatech.com.
EQUIPMENT SHUTOFF
VALVE - GA5010
Equipment shutoff valve with 1/8" NPT tap.
SPECIFICATIONS
CGP10TA/CGP10TLA
Btu (Variable)5,000/10,000
Type GasPropane/LP Only
IgnitionPiezo
Pressure Regulator Setting8" W.C.
Inlet Gas Pressure (inches of water)
Maximum14"
Minimum11"
Dimensions, Inches (H x W x D)
Heater (Including knobs and grill)21 1/2 x 13 1/2 x 7
Carton25 1/4 x 16 3/4 x 7 1/2
Weight (pounds)
Shipping19
104268
13
Page 14
VENT-FREE PROPANE/LP GAS HEATER
TROUBLESHOOTING
Note:
For additional help, visit DESA
International’s technical service web site
at www.desatech.com.
Note:
All troubleshooting items are listed in
order of operation.
OBSERVED PROBLEM
When ignitor button is pressed, there is no
spark at ODS/pilot
When ignitor button is pressed, there is
spark at ODS/pilot but no ignition
WARNING: Turn off heater
and let cool before servicing.
Only a qualified service person should service and repair
heater.
POSSIBLE CAUSE
1. Ignitor cable pinched or wet
2. Ignitor electrode not connected to ignitor cable
3. Piezo ignitor nut is loose
4. Broken ignitor cable
5. Ignitor electrode broken
6. Bad piezo ignitor
7. Ignitor electrode positioned wrong
1. Gas supply turned off or equipment
shutoff valve closed
2. Control knob not in PILOT position
3. Control knob not pressed in while in
PILOT position
4. Air in gas lines when installed
5. ODS/pilot is clogged
6. Gas regulator setting is not correct
CAUTION: Never use a wire,
needle, or similar object to clean
ODS/pilot. This can damage ODS/
pilot unit.
REMEDY
1. Free ignitor cable if pinched by any
metal or tubing. Keep ignitor cable dry
2. Reconnect ignitor cable
3. Tighten nut holding piezo ignitor to
heater cabinet. Nut is located inside
heater cabinet at top
4. Replace ignitor cable
5. Replace ignitor
6. Replace piezo ignitor
7. Replace ignitor
1. Turn on gas supply or open equipment
shutoff valve
2. Turn control knob to PILOT position
3. Press in control knob while in PILOT
position
4. Continue holding down control knob
Repeat igniting operation until air is removed
5. Clean ODS/pilot (see Cleaning andMaintenance, page 13) or replace ODS/
pilot assembly
6. Replace gas regulator
ODS/pilot lights but flame goes out when
control knob is released
1. Control knob not fully pressed in
2. Control knob not pressed in long enough
3. Safety interlock system has been triggered
4. Equipment shutoff valve not fully open
5. Thermocouple connection loose at control valve
6. Pilot flame not touching thermocouple,
which allows thermocouple to cool,
causing pilot flame to go out. This problem could be caused by one or both of
the following:
A) Low gas pressure
B) Dirty or partially clogged ODS/pilot
7. Thermocouple damaged
8. Control valve damaged
www.desatech.com
14
1. Press in control knob fully
2. After ODS/pilot lights, keep control
knob pressed in 30 seconds
3. W ait one minute for safety interlock system to reset. Repeat ignition operation.
4. Fully open equipment shutoff valve
5.
Hand tighten until snug, then tighten 1/4
turn more
6.
A) Contact local propane/LP gas company
B) Clean ODS/pilot (see Cleaning andMaintenance, page 13) or replace ODS/
pilot assembly
7. Replace thermocouple
8. Replace control valve
104268
Page 15
TROUBLESHOOTING
Continued
OWNER’S MANUAL
OBSERVED PROBLEM
Burner does not light after ODS/pilot is lit
Delayed ignition of burner
Burner backfiring during combustion
Yellow flame during burner combustion
Slight smoke or odor during initial operation
POSSIBLE CAUSE
1. Burner orifice is clogged
2. Burner orifice diameter is too small
3. Inlet gas pressure is too low
1. Manifold pressure is too low
2. Burner orifice is clogged
1. Burner orifice is clogged or damaged
2. Inlet gas pressure is too low
3. Burner damaged
4. Gas regulator defective
1. Not enough air
2. Inlet gas pressure is too low
3. Gas regulator defective
1. Residues from manufacturing processes
REMEDY
1. Clean burner orifice (see Cleaning and
Maintenance, page 13) or replace burner
orifice
2. Replace burner orifice
3. Contact local propane/LP gas company
1. Contact local propane/LP gas company
2. Clean burner orifice (see Cleaning andMaintenance, page 13) or replace burner
orifice
1. Clean burner orifice (see Cleaning andMaintenance, page 13) or replace burner
orifice
2. Contact local propane/LP gas company
3. Replace burner
4. Replace gas regulator
1. Check burner for dirt and debris. If
found, clean burner (see Cleaning andMaintenance, page 13)
2. Contact local propane/LP gas company
3. Replace gas regulator
1. Problem will stop after a few hours of
operation
Heater produces a whistling noise when
burner is lit
White powder residue forming within burner
box or on adjacent walls or furniture
104268
1. Turn control knob to HI position when
burner is cold
2. Air in gas line
3. Air passageways on heater blocked
4. Dirty or partially clogged burner orifice
1. When heated, vapors from furniture polish, wax, carpet cleaners, etc. turn into
white powder residue
www.desatech.com
15
1. Turn control knob to LO position and
let warm up for a minute
2. Operate burner until air is removed from
line. Have gas checked by local propane/
LP gas company
3. Observe minimum installation clearances (see Figure 4, page 7)
4.
Clean burner (see Cleaning and Mainte-nance, page 13) or replace burner orifice
1. Turn heater off when using furniture
polish, wax, carpet cleaners, or similar
products
Continued
Page 16
VENT-FREE PROPANE/LP GAS HEATER
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your
building.
• Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
IMPORTANT:
Cleaning supplies, paint, paint remover, cigarette smoke, cements and glues, new
carpet or textiles, etc., create fumes. These fumes may mix with combustion air and
create odors.
OBSERVED PROBLEM
Heater produces a clicking/ticking noise
just after burner is lit or shut off
Heater produces unwanted odors
Heater shuts off in use (ODS operates)
Gas odor even when control knob is in OFF
position
Operating heater where impurities in air exist may create odors.
POSSIBLE CAUSE
1. Metal expanding while heating or contracting while cooling
1. Heater burning vapors from paint, hair
spray, glues, etc. See
statement above
2. Low fuel supply
3. Gas leak. See W arning statement at
top of page
1. Not enough fresh air is available
2. Low line pressure
3. ODS/pilot is partially clogged
1. Gas leak. See W arning statement at
top of page
2. Control valve defective
IMPORTANT
REMEDY
1. This is common with most heaters. If
noise is excessive, contact qualified service person
1. Ventilate room. Stop using odor -causing
products while heater is running
2. Refill supply tank
3. Locate and correct all leaks (see Check-ing Gas Connections, page 10)
1.
Open window and/or door for ventilation
2. Contact local propane/LP gas company
3. Clean ODS/pilot (see Cleaning andMaintenance, page 13)
1. Locate and correct all leaks (see Check-ing Gas Connections, page 10)
2. Replace control valve
Gas odor during combustion
Moisture/condensation noticed on windows
1. Foreign matter between control valve
and burner
2. Gas leak. See W arning statement at
top of page
1. Not enough combustion/ventilation air
www.desatech.com
16
1. Take apart gas tubing and remove foreign matter
2. Locate and correct all leaks (see Check-ing Gas Connections, page 10)
1. Refer to Air for Combustion and Venti-lation requirements (page 4)
104268
Page 17
OWNER’S MANUAL
REPLACEMENT
PARTS
Note:
Use only original replacement parts.
This will protect your warranty coverage for
parts replaced under warranty.
PARTS UNDER WARRANTY
Contact authorized dealer from whom you
purchased this product. If they cannot supply
original replacement part(s), call DESA
International’s Technical Service Department
at 1-800-323-5190 for referral information.
When contacting your dealer or DESA International, have ready:
• your name
• your address
• model and serial numbers of your heater
• how heater was malfunctioning
•
type of gas used (propane/LP or natural gas)
• purchase date
Usually, we will ask you to return the defec-
tive part to the factory.
PARTS NOT UNDER
WARRANTY
Contact authorized dealers of this product.
If they cannot supply original replacement
part(s), either contact your nearest Parts
Central or call DESA International’s Parts
Department at 1-800-972-7879 for referral
information.
When calling DESA International, have
ready:
• model number of your heater
• the replacement part number
PARTS CENTRAL
These Parts Centrals are privately-owned
businesses. They have agreed to support our
customer’s needs by providing original replacement parts and accessories.
Baltimore Electric
1348 Dixwell Avenue
Hamden, CT 06514-0322
1-800-397-7553
203-248-7553
Parts Department
Portable Heater Parts
342 N. County Rd. 400 East
Valparaiso, IN 46383-9704
All States
219-462-7441
1-800-362-6951
sales@portableheaterparts.com
techservice@portableheaterparts.com
FBD
1349 Adams Street
Bowling Green, KY 42103-3414
270-846-1199
1-800-654-8534
Fax: 1-800-846-0090
franktalk@aol.com
Master Parts Dist.
1251 Mound Ave. NW
Grand Rapids, MI 49504-2672
616-791-0505
1-800-446-1446
Fax: 616-791-8270
www.nbmc.com
Washer Equipment Co.
1715 Main Street
Kansas City, MO 64108-2195
KS, MO, AR
816-842-3911
www.washerparts.com
East Coast Energy Products
707 Broadway
W. Long Branch, NJ 07764-1542
732-870-8809
1-800-755-8809
www.njplaza.com/ecep
58 Halbe Lane
Cape May Court, NJ 08210-1110
609-390-9774
Parts Department
Dayton Hardware
P.O. Box 275
North Dayton Station
Dayton, OH 45404-0275
All States
937-258-3721
OH 1-800-762-3426
Halco Enterprises
208 Carter Drive, Unit 21
West Chester, PA 19382-4500
610-430-7717
1-800-368-0803
www.halcoenterprises.com
LA Porte’s Parts & Service
2444 N. 5th Street
Hartsville, SC 29550-7704
803-332-0191
Parts Department
Cans Unlimited, Inc.
P.O. Box 645
Taylor, SC 29687-0013
All States
803-879-3009
1-800-845-5301
cuisales@aol.com
104268
17
Page 18
VENT-FREE PROPANE/LP GAS HEATER
ILLUSTRATED
PARTS
BREAKDOWN
CGP10TA
CGP10TLA
3
21
20
14
13
23
12
10
4
11
7
6
5
9
8
14
15
19
22
10
16
24
18
17
2
1
12-1
12-2
ODS/PILOT
18
104268
Page 19
OWNER’S MANUAL
PARTS LIST
CGP10TA
CGP10TLA
This list contains replaceable parts used in your heater. When ordering parts, follow the
instructions listed under Replacement Parts on page 17 of this manual.
KEYPART
NO.NUMBERDESCRIPTIONQTY.
1098304-01Screw, #10 x 3/8"2
2099467-02Front Panel Assembly (CGP10TA)1
Always specify model and serial numbers when communicating with the factory.
We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our standard written warranty.
We make no other warranty, expressed or implied.
LIMITED WARRANTY
COMFORT GLOW VENT-FREE RESIDENTIAL GAS HEATERS
DESA International warrants this product to be free from defects in materials and components for two (2) years from the date of first
purchase, provided that the product has been properly installed, operated and maintained in accordance with all applicable instructions.
To make a claim under this warranty the Bill of Sale or cancelled check must be presented.
This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s) required to restore this heater
to proper operating condition and an allowance for labor when provided by a DESA Authorized Service Center. Warranty part(s) MUST
be obtained through authorized dealers of this product and/or DESA International who will provide original factory replacement parts.
Failure to use original factory replacement parts voids this warranty. The heater MUST be installed by a qualified installer in accordance
with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail or become
damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation. Travel, diagnostic cost,
labor, transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT;
THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE
DURATION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE TO TWO (2) YEARS ON ALL COMPONENTS FROM THE DATE OF FIRST
PURCHASE; AND DESA INTERNATIONAL’S LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE
PRODUCT AND DESA INTERNATIONAL SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER
INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or consequential
damages, so the above limitation on implied warranties, or exclusion or limitation on damages may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights that vary from state to state.
For information about this warranty write:
INTERNATIONAL
2701 Industrial Drive
P.O. Box 90004
Bowling Green, KY 42102-9004
www.desatech.com
104268 01
NOT A UPC
104268-01
REV. C
02/00
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.