Desa EFP33NRB, CGEFP33PRB, CGEFP33NRB, EFP33PRB User Manual

UNVENTED (VENT-FREE) GAS FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
Shown with optional
hearth base accessory.
CGEFP33PRB, CGEFP33NRB
EFP33PRB, EFP33NRB
Gas Fireplace with Total Control System (TCS)
WARNING: If the information in this manual is not fol­lowed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a quali-
fied installer, service agency or the gas supplier.
Save this manual for future reference.
For more information, visit www.desatech.com
WARNING: Improper installation, adjustment, altera­tion, service or maintenance can cause injury or prop­erty damage. Refer to this manual for correct installation and operational procedures. For assistance or addi­tional information consult a qualified installer, service agency or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provi­sions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation section on page 6 of this manual.
This appliance may be installed in an aftermarket,* per­manently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indi­cated on the rating plate. This appliance is not convert­ible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts.
Sellers of unvented propane or natural gas-fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for bedroom and bathroom installation in the Common wealth of Massachusetts.
-
TABLE OF CONTENTS
Safety Information ............................................... 3
Product Identification ...........................................
Local Codes ........................................................ 5
Unpacking ........................................................... 5
Product Features ................................................. 5
Air for Combustion and Ventilation ......................
Installation ........................................................... 8
Operating Fireplace ........................................... 25
Inspecting Burners ............................................ 28
Cleaning and Maintenance ................................ 29
2
www.desatech.com
Troubleshooting .................................................
4
Specifications .................................................... 33
Service Hints ..................................................... 33
Technical
Illustrated Parts Breakdown and Parts List ....... 34
6
Replacement Parts ............................................ 40
Accessories ....................................................... 40
Wiring Diagram .................................................. 42
Templates ..........................................................
Parts Central ..................................................... 45
Service .............................................. 33
30
43
111245-01B

SAFETY INFORMATION

WARNING: This product con­tains and/or generates chemicals known to the state of California to cause cancer or birth defects or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, op­erate or service this fireplace. Improper use of this fireplace can cause serious injury or death from burns, fire, explo­sion, electrical shock and carbon monoxide poisoning.
DANGER: Carbon monoxide poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of carbon
monoxide poisoning resemble the flu, with head aches, dizziness or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol and those at high altitudes.
Natural and Propane/LP Gas: Natural and pro-
pane/LP gases are odorless. An odor-making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warn ings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
WARNING: Any change to this heater or its controls can be dangerous.
WARNING: Do not use a blower insert, heat exchanger insert or other accessory not ap­proved for use with this heater.
WARNING: Do not allow fans to blow directly into the fireplace. Avoid any drafts that alter burner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
Fireplace front and screen be­come very hot when running fire­place. Keep children and adults
-
away from hot surface to avoid burns or clothing ignition. Fire­place will remain hot for a time after shutdown. Allow surfaces to cool before touching.
Carefully supervise young chil­dren when they are in the room with heater. When using the hand­held remote accessory keep se­lector switch in the OFF position to prevent children from turning
-
on burners with remote.
You must operate this fireplace with the fireplace screen and hood in place. Make sure fire­place screen and hood are in place before running heater.
Keep the appliance area clear and free from combustible ma terials, gasoline and other flam mable vapors and liquids.
-
-
111245-01B 3
www.desatech.com
SAFETY INFORMATION
Continued
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) in side any structure. Locate propane/LP supply tank(s) outdoors (propane/LP units only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use
any phone in your building
• immediately call your gas supplier from a
neighborʼs phone. Follow the gas supplierʼs instructions
• if you cannot reach your gas supplier, call
the fire department
4. This fireplace shall not be installed in a bed room or bathroom.
5. Do not use this fireplace as a wood-burning fireplace. Use only the logs provided with the fireplace.
6. Do not add extra logs or ornaments such as pine cones, vermiculite or rock wool. Using these added items can cause sooting. Do not add lava rock around base. Rock and debris could fall into the control area of fireplace.
7. To prevent the creation of soot, follow the instruc tions in Cleaning and Maintenance, page 29.
8. Before using furniture polish, wax, carpet cleaner or similar products, turn heater off. If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.
9. This fireplace needs fresh air ventilation to run properly. This fireplace has an Oxygen Deple tion Sensing (ODS) safety shutoff system. The ODS shuts down the fireplace if not enough fresh air is available. See Air for Combustion and Ventilation, page 6. If fireplace keeps shutting off, see Troubleshooting, page 30.
10. Do not run fireplace
• where flammable liquids or vapors are used
or stored
• under dusty conditions
11. Do not use this fireplace to cook food or burn paper or other objects.
12. Do not use fireplace if any part has been exposed to or under water. Immediately call a qualified service technician to inspect the fireplace and to replace any part of the control system and any gas control which has been under water.
4
www.desatech.com
13. Do not operate fireplace if any log is broken. Do not operate fireplace if a log is chipped (dime-sized or larger).
14. Turn fireplace off and let cool before servicing. Only a qualified service person should service and repair fireplace.
-
15. Operating fireplace above elevations of 4,500 feet could cause pilot outage.
16. To prevent performance problems with pro pane/LP units, do not use propane/LP fuel tanks of less than 100 lb. capacity.
17. Prov ide adequa te clearance s around air openings.
PRODUCT
IDENTIFICATION
Log Set
-
Manual Override Handle
Remote
-
Control
Figure 1 - Fireplace Floor Assembly
Top Louver Assembly
Firebox
-
Hood
Firebox Support
Screen Assembly
Piezo Ignitor
Wall Switch Assembly
Bottom Louver Assembly
Figure 2 - Fireplace
Manual Ignition Bypass Switch
Blower Assembly (Optional)
Top Outer Casing
111245-01B
-

LOCAL CODES

Install and use fireplace with care. Follow all local codes. In the absence of local codes, use the lat­est edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park Quincy, MA 02269

UNPACKING

CAUTION: Do not remove the data plates attached to the heater base assembly. The data plates contain important warranty and safety information.
1. With utility knife, cut the carton all the way around above the staples on the bottom tray. Lift the carton off the heater. Remove packing. Note: The hood is located in the packing on the right hand side of the heater front. Lift the heater off the bottom tray.
2. Locate two screws above top corners of the fireplace screen. Remove and discard these screws. Lift fireplace screen up and pull out to remove.
3. Remove protective packaging applied to logs, log base assembly and fireplace.
4. Remove fireplace hood from carton insert.
5. Check all items for any shipping damage. If damaged, promptly inform dealer where you bought fireplace.

PRODUCT FEATURES

OPERATION
This vent-free fireplace is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by both realistic flames and glowing embers. When used without the optional blower, the fireplace requires no electricity making it ideal for emergency backup heat.
SAFETY DEVICE
This fireplace has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS/ pilot is a required feature for vent-free room heat ers. The ODS/pilot system shuts off the fireplace if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This fireplace has a piezo ignitor. This system requires no matches, batteries or other sources to light fireplace.
WIRELESS REMOTE CONTROL
This fireplace features an infrared wireless remote control. This control system can be used to auto matically light the pilot and adjust the burner flame height at the push of a button.
WIRED WALL-MOUNTED REMOTE CONTROL
This fireplace features a two-button wall switch as­sembly with glowing LEDʼs. The wall switch per forms the same functions as the wireless hand-held remote control with the added feature of LEDʼs for visual feedback of operation and status.
OPTIONAL BLOWER ASSEMBLY ACCESSORY
This fireplace accepts an optional blower assembly (not included). The GA3650T/GA3700T Series blower operates thermostatically and features a variable speed control. The GA3700/GA3750 Series operates manually and also features a vari­able speed control. The blower circulates heated air from the fireplace into the room. Use of blower is optional. See Accessories, page 40.
-
-
-
111245-01B 5
www.desatech.com
AIR FOR COMBUSTION
AND VENTILATION
WARNING: This heater shall not be installed in a confined space or unusually tight con­struction unless provisions are provided for adequate combus­tion and ventilation air. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.
Todayʼs homes are built more energy efficient than ever. New materials, increased insulation and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy effi cient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three fol lowing ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on pages 6 through 8 will help
you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings exposed to the out
side atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10 less with openings gasketed or sealed and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines and at other openings.
If your home meets all of these three
criteria, you must provide additional fresh air. See Ventilation Air From Outdoors, page 8.
If your home does not meet all of the three criteria above, proceed to Determining
-
Fresh-Air Flow For Fireplace Location.
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose
volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour
3
(4.8 m
per kw) of the aggregate input rating of all appliances installed in that space. Rooms com municating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.
­* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
-11
kg per pa-sec-m2) or
3
per kw) of the aggregate input
DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install fireplace plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
-
-
6
www.desatech.com
111245-01B
Or
Remove Door into Adjoining
Room, Option
3
Ventilation Grills
Into Adjoining Room,
Option
2
Ve
ntilation Grills
Into Adjoining
Room,
Option 1
12"
12"
AIR FOR COMBUSTION
AND VENTILATION
Continued
1. Determine the volume of the space (length x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 18 ft.
(width) x 8 ft. (ceiling height) = 2880 cu. ft. (volume of space)
If additional ventilation to adjoining room is
supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2880 cu. ft. (volume of space) x 20 =
57,600 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free fireplace ___________ Gas water heater* ___________ Gas furnace ___________ Vented gas heater ___________ Gas fireplace logs ___________ Other gas appliances* + ___________ Total = ___________ * Do not include direct-vent gas appliances. Di
rect-vent draws combustion air from the outdoors and vents to the outdoors.
Example: Gas water heater ________ Vent-free fireplace + ________ Total = ________
40,000
33,000
73,000
Btu/Hr Btu/Hr Btu/Hr Btu/Hr Btu/Hr Btu/Hr Btu/Hr
Btu/Hr Btu/Hr Btu/Hr
C. Install a lower Btu/Hr fireplace, if lower Btu/Hr
size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support,
the space is an un­confined space. You will need no additional fresh air ventilation.
WARNING: If the area in which the fireplace may be oper­ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Section 5.3 or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining un confined space. When ventilating to an adjoining unconfined space, you must provide two perma­nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3). You can also remove door into adjoining room (see
-
option 3, Figure 3). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of
ventilation grills or ducts.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
_________ _________
Btu/Hr (maximum the space can support) Btu/Hr (actual amount of Btu/Hr used)
Example: 57,600 Btu/Hr (maximum the space
can support)
73,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the above example is a confined space because the actual Btu/Hr used is more than the maxi
­mum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoin
ing room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation
Air From Inside Building.
B. Vent room directly to the outdoors. See Ventila
tion Air From Outdoors, page 8.
111245-01B 7
Figure 3 - Ventilation Air from Inside
-
-
www.desatech.com
Building
-
Outlet Air
Ve
ntilated
Attic
Outlet
A
ir
Inlet Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
AIR FOR COMBUSTION
AND VENTILATION
Continued
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts. IMPORTANT: Do not provide openings for inlet
or outlet air into attic if attic has a thermostat­controlled power vent. Heated air entering the attic will activate the power vent.
Figure 4 - Ventilation Air from Outdoors

INSTALLATION

NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your pri mary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
vice person must install fire place. Follow all local codes.
8
WARNING: A qualified ser-
-
-
www.desatech.com
WARNING: Never install the
fireplace
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, f urni ture, clothing or other flammable objects are less than 42 inches from the front, top or sides of the fireplace
• in high traffic areas
• in windy or drafty areas
CAUTION: This fireplace cre­ates warm air currents. These currents move heat to wall sur
­faces next to fireplace. Installing fireplace next to vinyl or cloth wall coverings or operating fireplace where impurities (such as, but not limited to, tobacco smoke, aromatic candles, clean
­ing fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
Note: Your fireplace is designed to be used in zero clearance installations. Wall or framing material can be placed directly against any exterior surface on the rear, sides or top of your fireplace, except where standoff spacers are integrally attached. If standoff spacers are attached to your fireplace, these spacers can be placed directly against wall or framing materials.
Use the dimensions shown for rough openings to create the easiest installation (see Built-In Fire place Installation, page 21).
IMPORTANT: Vent-free heaters add moisture to the air. Although this is beneficial, installing fire place in rooms without enough ventilation air may cause mildew to form from too much moisture. See
Air for Combustion and Ventilation
IMPORTANT: Make sure the fireplace is level. If fireplace is not level, log set will not work properly.
CHECK GAS TYPE
Use the correct gas type (natural or propane/LP) for your unit. If your gas supply is not correct, do not install fireplace. Call dealer where you bought fireplace for proper type fireplace.
, page 6.
111245-01B
-
-
INSTALLATION
Continued
WARNING: This appliance is equipped for (natural or pro­pane/LP) gas. Field conversion is not permitted.
ELECTRICAL HOOKUP
Thi s fir ep lace normally operates under 120 VAC/60 Hz line voltage. The electrical cord sup plied with your fireplace is five feet in length. You must locate fireplace within reach of a 120 volt grounded electrical outlet. If not, you must install an electrical outlet within reach of the fireplace power cord. The GA3555 outlet accessory may be used for built-in applications.
INSTALLATION CLEARANCES
WARNING: Maintain the minimum clearances. If you can, provide greater clearances from floor, ceiling and adjoining wall.
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
Top Left and Bottom Right Sides and Rear
0" 16" 0"
Carefully follow the instructions below. This will ensure safe installation.
Minimum Clearances For Side Combustible Material, Side Wall and Ceiling
A. Clearances from the side of the fireplace
cabinet to any combustible material and wall should follow diagram in Figure 5.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and protrudes 3 1/2" from the wall. This combus­tible material must be 4" from the side of the fireplace cabinet (see Figure 5).
B. Clearances from the top of the fireplace open
ing to the ceiling should not be less than 42 inches.
Example
*Minimum 16 inches from Side Wall
-
Figure 5 - Minimum Clearance for
Combustible to Wall
INSTALLATION SEQUENCE
After unpacking fireplace (see Unpacking, page 4), we suggest that you install your fireplace system in the following sequence:
1.
Removal of fireplace floor assembly (required)
2.
Electrical connections for power cord (required)
3. Relocating wall switch (optional)
4. Installing blower accessory (optional)
5.
Connecting fireplace to gas supply (required)
6. Checking gas connections (required)
7. Firebox installation, conventional or built-in (required)
8. Installing brass perimeter trim (optional)
9. Installing fireplace hood (required)
10. Installing logs (required)
11. Installing fireplace screen (required)
Use the following instruction s to comp le te each step.
REMOVING FIREPLACE SCREEN AND FLOOR ASSEMBLY
NOTICE: Shutoff gas supply and disconnect heater from gas supply if installing blower into previously installed fireplace. Contact a qualified service per­son to do this.
1. Remove fireplace screen. Remove two screws
-
that hold fireplace screen in place for shipping. These screws are located near top of screen. Discard screws. Lift fireplace screen up and pull out to remove.
2. If logs are installed, carefully remove the logs and set aside, noting the properly mounted location of each.
*
111245-01B 9
www.desatech.com
INSTALLATION
Continued
3. Remove screws that attach fireplace floor as­sembly to fireplace. Open lower louver door. Carefully lift up fireplace floor assembly and remove from fireplace, taking care to pull flexible gas line through the access holes (see Figure 6). Note: Be careful of all wires on underside of log base.
CAUTION: Do not pick up fireplace floor assembly by burn­ers. This could damage burners. Only handle base by grates.
Flexible Gas Line
Screws
Fireplace Floor Assembly
Figure 6 - Removing Fireplace Floor
Assembly
ELECTRICAL CONNECTIONS FOR POWER CORD
This fireplace operates on 120 VAC, 60 Hz power. An electrical power cord is supplied with this unit.
For Mantel Installation
1. Determine from which side of the fireplace the power cord will exit. Locate the 1.5" diameter hole near the center of floor support bracket on appropriate side of lower cavity (see Figure 7).
2. Locate power cord. Remove wire tie or tape holding plug end of power cord.
3. Power cord has 2 plastic hole bushings threaded onto it. Route cordʼs 3-prong plug through the 1.5" diameter hole in appropriate floor support bracket.
4. Push first plastic bushing completely through hole. Squeeze bushing as needed to do this.
5. Install the second plastic bushing into the hole in the floor support bracket by snapping into place.
6. Route the 3-prong plug through the 1.5" hole in fireplace outer casing.
7. Install the first plastic bushing into this hole by snapping into place.
8. After you have connected to gas supply and checked your gas connections (see pages 17 through 20), plug power cord into any conve nient 3-prong grounded wall receptacle near fireplace.
For Recessed Installation
If an outlet is not installed in fireplace, install model GA3555 - Outlet Kit with Cover. This kit will supply a convenient 3-prong grounded electrical outlet for power. Refer to installation manual provided with this optional accessory for instructions on wiring. must make all electrical connections.
Hole in Floor Support Bracket
Bushings
Figure 7 - Routing Power Cord
Note: A qualified installer
Hole in Outer Casing
Power Cord
RELOCATING WALL SWITCH ASSEMBLY
Note: The decorative wall switch plate supplied is white. The wall switch plate may be painted to match your decor.
The push-button switch and decorative wall plate assembly supplied with your fireplace is pre-mounted at the factory in the lower cavity of the fireplace. You may relocate this wall switch assembly to a more convenient location such as the side of your mantel or directly onto the wall near the fireplace. To mount the wall switch assembly, you must first cut openings in the mantel or wall where the switch will be located.
-
10
www.desatech.com
111245-01B
INSTALLATION
Continued
Note: If you choose to relocate the wall switch assembly, do so before final installation into a mantel or recessing into a wall. If you are installing an optional blower accessory, install it at the same time you relocate the wall switch assembly.
CAUTION: The wall switch assembly must never be mount­ed directly above the fireplace where heat may damage it. If you relocate wall switch assembly from lower fireplace cavity, it must be mounted either on side wall of mantel or on wall to side of fireplace.
For Recessed Installation
If fireplace is to be recessed into a wall (see Built-In Fireplace Installation, page 21), we recommend mounting wall switch assembly to left side of fireplace. The wall switch assembly should be mounted approximately 12" from left edge of fireplace and less than 60" from the floor. IMPORTANT: Do not locate wall switch assembly directly in front of wall stud - there must be room behind wall board for wires from switch. If you choose to locate wall switch assembly to right side of fireplace, the length of the cord restricts you to less than 6" from right edge of fireplace and less than 48" from floor.
For Mantel Installation
If fireplace is to be installed into a mantel, (see Conventional Fireplace Installation, page 20) the wall switch assembly may be mounted on either side of the mantel, facing to the side. Do not locate wall switch assembly anywhere on the front face of the mantel.
CAUTION: Be careful of gas lines and wiring when moving floor.
1. Determine the new location for the wall switch assembly. The wires attached to switch are six feet long.
2. Remove 2 screws securing plastic wall switch assembly to bracket in fireplace lower cavity. Save screws.
3. Remove wire tie holding coiled wire attached to wall switch assembly (see Figure 8).
111245-01B 11
www.desatech.com
4. Remove wall switch assembly from bracket.
5. Carefully pass wall switch assembly and cord through large elongated hole in rear of either left or right floor support bracket, depending on desired location of switch. Pass wall switch as sembly and cord through 1.5" diameter hole in side of fireplace outer casing (see Figure 9).
6. Pull wall switch assembly and cord from fireplace making sure wall switch assembly will reach desired mounting location without straining cord assembly.
If you are mounting wall switch assembly to a wall, continue reading. If you are mounting your wall switch assembly to the side of the mantel, see page 12.
Burner Outlet Tube
Figure 8 - Relocating Wall Switch
Hole in Outer Casing
Wall Switch Assembly
Figure 9 - Routing Wall Switch Assembly
Through Fireplace for Relocation
Mounting Wall Switch Assembly to Wall for Recessed Fireplace
7. Create three openings on wall according to Template 1, page 41. This is best done by making a pattern to work with on your wall. Carefully cut page 41/42 from manual and tape paper template vertically onto wall at preferred location. Pierce the paper at the cen­ters of the 2 holes with a nail or sharp pencil, leaving a mark on the wall. Do the same at centers of the four circles near the corners of the rectangle.
Firebox Bottom
Wire Tie
Gas Control Valve
Assembly
Wall Switch Assembly
Hole in Floor Support Bracket
-
4 3/4"
3 3/4"
3/8"
3/16"
3/4"
3/8" Diameter 2 Holes
INSTALLATION
Continued
8. Remove paper template from wall.
9. Drill 3/8" holes at each mark.
10. Using a straight edge and pencil, connect the outer edges of the 4 holes for the rectangle (see Figure 10). This will give you cutting lines for the rectangle you will cut in the wall.
11. Using a keyhole saw, hack saw blade, drill, file or other suitable tool, carefully cut out the rectangular opening. Note: The corners of the rectangle may be round. IMPORTANT: Do not exceed the size of the rectangle on template.
12. From inside the recessed opening for the fireplace, carefully pass wall switch assembly through the rectangular opening to the outside of the wall.
13. Using wall anchors supplied in hardware pack age, fold wall anchor as shown in Figure 11.
14. Insert wall anchor, wings first, into hole. Tap anchor flush to wall.
15. For thin walls (1/2" or less), insert red key into wall anchor. Push red key to “pop” open anchor wings. See Figure 12. IMPORTANT: Do not hammer key! For thick walls (over 1/2" thick), do not pop open wings.
Make Marks at Centers of Holes
Template from This Manual
Figure 10 - Using Template for Wall
Switch Assembly Installation
Figure 11 - Folding
Anchor
12
Figure 12 - Popping
Open Anchor Wings
for Thin Walls
16. Position wall switch assembly vertically over wall openings with decal lettering upright (see Figure 13).
17. Insert mounting screws, removed in step 2 of Relocating Wall Switch Assembly on page 10, through holes in wall plate and into wall anchors.
18. Tighten screws until wall plate is firmly at tached to wall. Do not overtighten.
-
Figure 13 - Securing Wall Switch
Mounting Wall Switch Assembly to Side of Mantel
7. Create three openings in the mantel wall ac­cording to Template 2, page 41. This is best done by making a pattern to work with on the
Cutting Lines
mantel. Carefully cut page 39/40 from manual and tape paper template vertically onto mantel wall at preferred location. Pierce the paper at the centers of the 2 holes with a nail or sharp pencil, leaving a mark on the wall. Do the same at centers of the four circles near the corners of the rectangle.
8. Remove paper template from mantel wall.
9. Drill 1/8" pilot holes at each mark for top and bottom screw holes. Drill 3/8" holes at each mark for centers of four circles near corners of rectangle.
10. Using a straight edge and pencil, connect the outer edges of the 4 holes for the rectangle (see Figure 10). This will give you cutting lines for
Tape
the rectangle you will cut in the mantel wall.
11. Using a keyhole saw, hack saw blade, drill, file or other suitable tool, carefully cut out the rectangular opening. Note: The corners of the rectangle may be round. IMPORTANT: Do not exceed the size of the rectangle on template.
12. Carefully pass wall switch assembly through rectangular opening from inside mantel (see Figure 13).
www.desatech.com
-
Opening in Wall or Mantel Wall
Wall Switch Assembly
Screws
Assembly
111245-01B
INSTALLATION
Continued
13. Position wall switch assembly vertically over opening with decal lettering upright. Make sure wires freely pass through wall without binding. Align holes in wall plate with 1/8" pilot holes in mantel wall.
14. Drive mounting screws, removed in step 2 of Relocating Wall Switch Assembly on page 10, through wall plate holes and into pilot holes in mantel wall.
15. Tighten screws until wall switch assembly is firmly attached to mantel. Do not overtighten.
INSTALLING VARIABLE SPEED BLOWER ACCESSORY
NOTICE: Shut off gas supply and disconnect heater from gas supply if installing blower into previously
on the exit side (see Figure 16). Install the second plastic bushing provided into the
1.5" hole in the outer casing through which the power cord will exit. Route power cord through both plastic bushings and plug the power cord into a properly grounded 3-prong wall receptacle near the firebox.
b. If your fireplace system installation is
recessed and if an outlet is not installed in your fireplace, you must install the
GA3555 Outlet kit with cover in your fireplace which will supply a convenient 3-prong grounded electrical outlet for your blower. Refer to the installation manual provided with the model GA3555 accessory for instructions on wiring the duplex outlet. must make all electrical connections.
Blower
Note: A qualified installer
installed fireplace. Contact a quali­fied service person to do this.
1. If fireplace screen and floor are still installed, see Removing Fireplace Screen and Floor Assembly, page 9.
2. Attach the power cord to the blower motor by firmly pushing the two female terminals at the end of the power cord onto the two spade terminals on the blower motor.
3. Attach green ground wire from power cord to blower housing using screw provided (see Figure 14). Tighten screws securely.
4. Place the blower against lower rear wall of firebox outer wrapper with the exhaust port directed upward. Align the holes in top mount ing tabs of blower with holes in wall of wrap per (see Figure 14). Using 2 screws provided, mount blower and tighten screws securely.
5. Be certain that all wire terminals are securely at tached to terminals on blower motor and that the screw retaining the green ground wire is tight.
6. Place control knob provided on plastic control shaft of speed control.
7. Mount the speed control on the front leg of the left floor support bracket using 2 screws provided (see Figure 15).
8. Plug in blower power cord. a. If your fireplace system is installed as a
freestanding unit with an accessory man tel, determine whether the power cord will
exit the left side or the right side of the fire box. Install 1 plastic bushing provided into the 1.5" hole in the floor support bracket
111245-01B 13
www.desatech.com
Screws
Exhaust Port
Screw
Green Ground Wire
-
-
Figure 14 - Mounting Blower to Firebox
Left Floor Support Bracket
-
Screws
Speed
Control
-
Knob
-
Figure 15 - Attaching Speed Control to
Control
Control Shaft
Firebox
Lower Rear Wall of Firebox
Top Mounting Tab
INSTALLATION
V
a
r
i
a
b
l
e
F
a
n
S
w
i
t
c
h
W
h
it
e
W
h
it
e
B
l
a
c
k
G
r
e
e
n
O
n
1
1
0
/
1
1
5
V
.A
.
C
.
Bl
ower Moto
r
B
l
a
c
k
B
l
a
c
k
B
l
a
c
k
O
f
f
Variable
Fan Switch
White
White
Black
Green
On
11
0/115
V.
A.C.
Blower
Motor
Black
Black
Black
Off
Continued
9. Check to make sure that all electrical cords are completely clear of the blower wheel and that there are no other foreign objects in blower wheel. Turn blower on and check for operation. Turn blower off by rotating knob fully counterclockwise before continuing.
CAUTION: Never touch the
blower wheel while in operation.
10. Peel off backing paper and stick supplied wiring diagram decal near center of firebox bottom (Figure 17).
11. If gas connection s have been made and checked, replace fireplace floor assembly. Feed flexible gas supply line into fireplace base area while replacing fireplace floor as sembly. Make sure the entire flexible gas line is in fireplace base area.
IMPORTANT: Do not pick up fireplace floor
assembly by burners. This could damage burners. Only handle base by grates. Note: Be careful of all wires and components on underside of floor assembly.
12. Reattac h firepla ce floor asse mbly with screws removed in step 3 of Removing Fire place Screen and Floor Assembly, page 9. Note: Discard the remaining hardware items. After assembly, make sure all wires are com pletely clear of blower wheel.
13. Install logs (see Installing Logs, page 24 and fireplace screen (see Installing Screen, page
25).
WARNING: Failure to position the parts in accordance with sup­plied diagrams or failure to use only parts specifically approved with this heater may result in damage or personal injury.
WARNING: A qualified service person must connect fireplace to gas supply. Follow all local codes.
-
Wiring Diagram
-
-
Figure 17 - Location of Wiring Diagram
Decal 3" from Blower
Operating the Blower
Light your gas appliance with the blower off. After about 15 minutes, turn the blower on to deliver heated air at the top louvers. The blower features a variable control which allows you to select the speed you desire. Note: Periodically check the louvers of the firebox and remove any dust, dirt
Right Floor Support Bracket
Figure 16 - Installing Plastic Bushing for
14
Power Cord
Plastic Bushing
www.desatech.com
or other obstructions.
111245-01B
INSTALLATION
Continued
INSTALLING THERMOSTATIC BLOWER ACCESSORY
NOTICE: Shut off gas supply and disconnect heater from gas supply if installing blower in previously installed fireplace. Contact a qualified service per­son to do this.
1. If fireplace screen and floor are still installed, see Removing Fireplace Screen and Floor Assembly, page 9.
2. Using screw provided, attach green ground wire from speed control cord to blower hous ing. Tighten screw securely (see Figure 18).
3. Place the blower against lower rear wall of firebox outer wrapper with the exhaust port directed upward. Align the holes in top mount ing tabs of blower with holes in wall of wrapper (see Figure 19). Using two #8 screws provided, mount blower and tighten screws firmly.
4. Remove the three screws (do not discard) and cover plate from center of firebox wrapper rear wall. Discard this cover plate (see Figure 18).
Thermostatic Switch and Cover Assembly
5. Mount the supplied thermostatic switch and cover assembly into firebox wrapper wall. Do this by feeding terminal ends of wire harness into the hole. Allow wires to fall to bottom of firebox cavity (see Figure 18).
6. Using three screws from step 7, attach switch and cover assembly to firebox wrapper rear wall. Tighten screws firmly (see Figure 18).
7. Firmly attach red wire from the thermostatic switch and cover assembly to either of the ter minals on the blower motor (see Figure 18).
8. Firmly attach black wire from speed control cord to blue wire from thermostatic switch and cover assembly (see Figure 18).
9. Firmly attach white wire from speed control cord to remaining terminal on blower motor (see Figure 18).
-
10. Place control knob provided on plastic control shaft of speed control (see Figure 20).
11. Mount the speed control onto the front leg of the left floor support bracket using 2 screws
-
provided (see Figure 20).
Lower Rear Wall of
Blower
Firebox
-
#8 Screws
Exhaust Port
Top
Blue Wire
Black Wire
White Wire
Speed Control
Green Wire
Figure 18 - Installing Switch and Cover
Assembly and Speed Control
111245-01B 15
Red Wire
Figure 19 - Mounting Blower to Firebox
Floor Support Bracket
Screws
Figure 20 - Attaching Speed Control
www.desatech.com