Thank you for choosing DELTA’s high-performance VFD-S Series. The VFD-S Series is manufactured with high-quality components and materials and incorporate the latest microprocessor technology available.
To ensure the safety of operators and equipment, only qualified personnel familiar with AC motor drive are to do installation, start-up and maintenance. Always read this manual thoroughly before using VFD-S series AC Motor Drive, especially the WARNING, DANGER and CAUTION notes. Failure to comply may result in personal injury and equipment damage. If you have any questions, please contact your dealer.
PLEASE READ PRIOR TO INSTALLATION FOR SAFETY.
DANGER!
1. AC input power must be disconnected before any wiring to the AC motor drive is made.
2. A charge may still remain in the DC-link capacitors with hazardous voltages, even if the power has been turned off. To prevent personal injury, please ensure that power has been turned off before opening the AC motor drive and wait ten minutes for the capacitors to discharge to safe voltage levels.
3. Never reassemble internal components or wiring.
4. The AC motor drive may be destroyed beyond repair if incorrect cables are connected to the input/output terminals. Never connect the AC motor drive output terminals U/T1, V/T2, and W/T3 directly to the AC mains circuit power supply.
5. Ground the VFD-S using the ground terminal. The grounding method must comply with the laws of the country where the AC motor drive is to be installed. Refer to the Basic Wiring Diagram.
6. VFD-S series is used only to control variable speed of 3-phase induction motors, NOT for 1­phase motors or other purpose.
7. VFD-S series shall NOT be used for life support equipment or any life safety situation.
WARNING!
1. DO NOT use Hi-pot test for internal components. The semi-conductor used in the AC motor
drive is easily damaged by high-pressure.
2. There are highly sensitive MOS components on the printed circuit boards. These components
are especially sensitive to static electricity. To prevent damage to these components, do not touch these components or the circuit boards with metal objects or your bare hands.
3. Only qualified personnel are allowed to install, wire and maintain AC motor drive.
CAUTION!
1. Some parameter settings will cause the motor to run immediately after applying power.
2. DO NOT install the AC motor drive in a place subjected to high temperature, direct sunlight,
high humidity, excessive vibration, corrosive gases or liquids, or airborne dust or metallic particles.
3. Only use AC motor drives within specification. Failure to comply may result in fire, explosion or
electric shock.
4. To prevent personal injury, please keep children and unqualified people away from the
equipment.
5. When the motor cable between the AC motor drive and motor is too long, the layer insulation of
the motor may be damaged. Please use a frequency inverter duty motor or add an AC output reactor to prevent damage to the motor. Refer to appendix B Reactor for details.
6. The rated voltage for the AC motor drive must be 240V ( 480V for 460V models) and the
mains supply current capacity must be 5000A RMS (10000A RMS for the 40hp (30kW) models).

Table of Contents

Preface ..............................................................................................................i
Table of Contents...........................................................................................iii
Chapter 1 Introduction.................................................................................1-1
1.1 Receiving and Inspection.................................................................... 1-1
1.1.1 Nameplate Information................................................................ 1-1
1.1.2 Model Explanation ...................................................................... 1-1
1.1.3 Series Number Explanation........................................................1-2
1.1.4 Drive Frames .............................................................................. 1-2
1.2 Appearances....................................................................................... 1-2
1.3 Installation Steps ................................................................................ 1-3
1.4 Storage............................................................................................... 1-4
Chapter 2 Installation and Wiring ...............................................................2-1
2.1 Ambient Conditions............................................................................. 2-1
2.2 Installation........................................................................................... 2-1
2.3 Dimensions......................................................................................... 2-3
2.4 Wiring ............................................................................................... 2-16
2.4.1 Basic Wiring.............................................................................. 2-17
2.4.2 External Wiring.......................................................................... 2-21
2.4.3 Main Terminals Connections .................................................... 2-22
2.4.4 Control Terminals...................................................................... 2-24
2.4.5 Main Circuit Terminals..............................................................2-28
Chapter 3 Start Up........................................................................................3-1
3.1 Preparations before Start-up............................................................... 3-1
3.2 Operation Method............................................................................... 3-2
3.3 Trial Run.............................................................................................3-2
Chapter 4 Digital Keypad Operation...........................................................4-1
4.1 Description of the Digital Keypad........................................................ 4-1
4.2 Explanation of LED Indicators............................................................. 4-1
4.3 Explanations of Display Messages.....................................................4-1
4.4 How to Operate the Digital Keypad..................................................... 4-3
Chapter 5 Parameters ..................................................................................5-1
5.1 Summary of Parameter Settings......................................................... 5-2
5.2 Parameter Settings for Applications.................................................. 5-12
5.3 Description of Parameter Settings....................................................5-17
Chapter 6 Fault Code Information...............................................................6-1
6.1 Common Problems and Solutions ...................................................... 6-1
6.2 Reset ..................................................................................................6-4
Chapter 7 Troubleshooting..........................................................................7-1
7.1 Over Current (OC)..............................................................................7-1
7.2 Ground Fault....................................................................................... 7-2
7.3 Over Voltage (OV)..............................................................................7-2
7.4 Low Voltage (Lv).................................................................................7-3
7.5 Over Heat (OH)................................................................................... 7-4
7.6 Overload............................................................................................. 7-4
7.7 Keypad Display is Abnormal............................................................... 7-5
7.8 Phase Loss (PHL)............................................................................... 7-5
7.9 Motor cannot Run...............................................................................7-6
7.10 Motor Speed cannot be Changed..................................................... 7-7
7.11 Motor Stalls during Acceleration.......................................................7-8
7.12 The Motor does not Run as Expected .............................................. 7-8
7.13 Electromagnetic/Induction Noise ...................................................... 7-9
7.14 Environmental Condition................................................................... 7-9
7.15 Affecting Other Machines ............................................................... 7-10
Chapter 8 Maintenance and Inspections....................................................8-1
Appendix A Specifications.........................................................................A-1
Appendix B Accessories ............................................................................B-1
B.1 All Brake Resistors & Brake Units Used in AC Motor Drives..............B-1
B.1.1 Dimensions and Weights for Brake resistors..............................B-2
B.2 EMI Filters..........................................................................................B-3
B.2.1 Dimensions.................................................................................B-6
B.3 AC Reactor.......................................................................................B-10
B.3.1 AC Input Reactor Recommended Value...................................B-10
B.3.2 AC Output Reactor Recommended Value................................B-11
B.3.3 Applications for AC Reactor .....................................................B-11
B.4 DC Choke Recommended Values....................................................B-15
B.5 Zero Phase Reactor (RF220X00A) ..................................................B-16
B.6 Din Rail-DR01 ..................................................................................B-17
B.7 Remote Controller RC-01.................................................................B-18
B.8 Conduit Bracket (BK-S)....................................................................B-19
B.9 Non-fuse Circuit Breaker Chart ........................................................B-20
Appendix C How to Select the Right AC Motor Drive...............................C-1
C.1 Capacity Formulas.............................................................................C-2
C.2 General Precautions ..........................................................................C-4
C.3 How to Choose a Suitable Motor........................................................C-5
Appendix D CE ............................................................................................D-1

Chapter 1 Introduction

A
S

1.1 Receiving and Inspection

This VFD-S AC motor drive has gone through rigorous quality control tests at the factory before shipment. After receiving the AC motor drive, please check for the following:
Check to make sure that the package includes an AC motor drive, the User
Manual/Quick Start and CD, dust covers and rubber bushings. Inspect the unit to assure it was not damaged during shipment.
Make sure that the part number indicated on the nameplate corresponds with the part
number of your order.

1.1.1 Nameplate Information

Example for 1HP/0.75kW 3-phase 230V AC motor drive
AC Drive Model
Input Spec.
Output Frequency Range
Serial Number & Bar Code
Output Spec.
MODEL : VFD007S23A INPUT : 3PH 200-240V 50/60Hz 5.1A OUTPUT : 3PH 0-240V 4.2A 1.6kVA 0.75kW/1HP
Frequency Range : 1-400Hz
007S23A0T70 100 01
DELTA ELECTRONICS INC.
MADE IN XXXXX

1.1.2 Model Explanation

VFD
Version Type
23
007
Input Voltage 11:Single phase 115V 21:Single phase 230V 23:Three phase 230V 43:Three phase 460V
S Series
Applicable motor capacity
002: 0.25HP(0.2kW) 004: 0.5HP (0.4kW) 007: 1 HP(0.7kW)
Series Name
Revision August 2006, SE08, SW V2.61 1-1
022: 3 HP(2.2kW)
Chapter 1 Introduction|VFD-S Series

1.1.3 Series Number Explanation

0160T007S23A
Productio n number Production week Productio n year 2006 Production fa ctory
230V 3-phase 1HP(0.7 5kW)
(Taoyuan) Model
If the nameplate information does not correspond to your purchase order or if there are any problems, please contact your distributor.

1.1.4 Drive Frames

Frame Power range Models
S1
S2
Please refer to Chapter 2.3 for exact dimensions.
0.25-2hp (0.2-1.5kW)
1-5hp (0.75-3.7kW)
VFD002S11A/11B/21A/21B/21E/23A, VFD004S11A/11B/21A/21B/21E/23A/43A/43B/43E, VFD007S21A/21B/21E/23A/43A/43B/43E, VFD015S23D VFD007S11A/11B, VFD015S21D/21E/21U/43D/43E/43U, VFD022S21D/21E/21U/23D/43D/43E/43U

1.2 Appearances

VFD002S11A/11B/21A/21B/23A, VFD004S11A/11B/21A/21B/23A/43A/43B/43E, VFD007S21A/21B/23A/43A/43B/43E,
1-2 Revision August 2006, SE08, SW V2.61
Frame S1: VFD002S21E, VFD004S21E, VFD007S21E, VFD015S23D, Frame S2: VFD007S11A/11B, VFD015S21D/21E/21U/43D/43E/43U, VFD022S21D/21E/21U/23D/43D/43E/43U

1.3 Installation Steps

T
Chapter 1 Introduction|VFD-S Series
CASE
KNOB
HEAT SINK
DIVISION PLATE
SCREW
COVER
SCREW
SCREW
Installation Steps
1. Remove front cover screw and open.
2. Remove Division Plate. If using optional conduit bracket, please refer to next page.
3. Connect AC Input Power and motor leads. Never connect the AC drive output terminals U/T1, V/T2, W/T3 to main AC Input power.
4. Reinstall Division Plate.
For Optional Conduit Bracket: Make sure to fasten both screws on conduit bracket as shown in the drawing for safety grounding purpose. Bring all the wires out through the conduit bracket. Screw Torque: 5 to 6 kgf-cm (4.3 to 5.2 in-lbf)
CONDUIT BRACKE
Revision August 2006, SE08, SW V2.61 1-3
Chapter 1 Introduction|VFD-S Series
T
DIVISION PLATE
SCREW
Reinstall Division Plate.
CONDUI BRACKET
SCREW
Screw Torque: 5 to 6 kgf-cm (4.3 to 5.2 in-lbf)
SCREW
Install Conduit Bracket cover and tighten screws.

1.4 Storage

The AC motor drive should be kept in the shipping carton or crate before installation. In order to retain the warranty coverage, the AC motor drive should be stored properly when it is not to be used for an extended period of time. Storage conditions are:
Store in a clean and dry location free from direct sunlight or corrosive fumes. Store within an ambient temperature range of -20 °C to +60 °C. Store within a relative humidity range of 0% to 90% and non-condensing environment. Store within an air pressure range of 86kPa to 106kPa.
CAUTION!
1. DO NOT store in an area with rapid changes in temperature. It may cause condensation and frost.
2. DO NOT place on the ground directly. It should be stored properly. Moreover, if the surrounding environment is humid, you should put exsiccator in the package.
1-4 Revision August 2006, SE08, SW V2.61
Chapter 1 Introduction|VFD-S Series
3. If the AC motor drive is stored for more than 3 months, the temperature should not be higher than 30 °C. Storage longer than one year is not recommended, it could result in the degradation of the electrolytic capacitors.
4. When the AC motor drive is not used for a long time after installation on building sites or places with humidity and dust, it’s best to move the AC motor drive to an environment as stated above.
Revision August 2006, SE08, SW V2.61 1-5
Chapter 1 Introduction|VFD-S Series
This page intentionally left blank.
1-6 Revision August 2006, SE08, SW V2.61

Chapter 2 Installation and Wiring

2.1 Ambient Conditions

Install the AC motor drive in an environment with the following conditions:
Operation Air Temperature: -10 ~ +50°C (14 ~ 122°F)
Storage Transportation
Pollution Degree 2: good for a factory type environment.
-10 ~ +40°C (14 ~ 104°F) for side-by-side Relative Humidity: <90%, no condensation allowed
Atmosphere pressure: 86 ~ 106 kPa Installation Site Altitude: <1000m Vibration: <20Hz: 9.80 m/s
20 ~ 50Hz: 5.88 m/s
Temperature: -20°C ~ +60°C (-4°F ~ 140°F) Relative Humidity: <90%, no condensation allowed Atmosphere pressure: 86 ~ 106 kPa Vibration: <20Hz: 9.80 m/s
20 ~ 50Hz: 5.88 m/s
mounting
2
(1G) max
2
(0.6G) max
2
(1G) max
2
(0.6G) max
CAUTION!
1. Operating, storing or transporting the AC motor drive outside these conditions may cause damage to the AC motor drive.
2. Failure to observe these precautions may void the warranty!

2.2 Installation

1. Mount the AC motor drive vertically on a flat vertical surface by using bolts or screws. Other directions are not allowed.
2. The AC motor drive will generate heat during operation. Allow sufficient space around the unit for heat dissipation.
3. The heat sink temperature may rise to 90°C when running. The material on which the AC motor drive is mounted must be noncombustible and be able to withstand this high temperature.
4. When the AC motor drive is installed in a confined space (e.g. cabinet), the surrounding temperature must be within 10 ~ 40°C with good ventilation. DO NOT install the AC motor drive in a space with bad ventilation.
Revision August 2006, SE08, SW V2.61 2-1
Chapter 2 Installation and Wiring|VFD-S Series
5. When installing multiple AC motor drives in the same cabinet, they should be adjacent in a row with enough space. When installing one AC motor drive below another one, use a metal separation barrier between the AC motor drives to prevent mutual heating. Refer to figure below for details.
6. Prevent fiber particles, scraps of paper, saw dust, metal particles, etc. from adhering to the heatsink.
Mounting Clearances
150mm (6inch)
50mm
(2inch)
150mm (6inch)
50mm
(2inch)
Air Flow
2-2 Revision August 2006, SE08, SW V2.61

2.3 Dimensions

(Dimensions are in millimeter and [inch]) Frame S1: VFD002S11A, VFD002S21A, VFD002S23A
85.0 [3.35]
74.0 [2.92]
]
]
1
3
2
8
.
.
5
5
[
[
2
0
.
.
2
8
3
4
1
1
Chapter 2 Installation and Wiring|VFD-S Series
88.0 [3.47]5.8 [0.23]
13.0 [0.51]
]
2
1
.
0
[ 0
.
3
5.0 [0.20]
Revision August 2006, SE08, SW V2.61 2-3
5.0 [0.20]
]
4
4
.
0
[ 1
.
1
1
]
2
3
.
0
[ 1
.
8
Chapter 2 Installation and Wiring|VFD-S Series
Frame S1: VFD002S11B, VFD002S21B
85 .0 [3.3 5]
74 .0 [2.9 2]
]
]
3
1
.8
.2
5
5
[
[
0
2
.
.
8
2
4
3
1
1
88 .0 [3.4 7]5.8 [0.23 ]
13 .0 [0.5 1]
73 .0 [2.8 8]
]
3 .6 0
[ 0
. 6 1
5.0 [0.20]
2-4 Revision August 2006, SE08, SW V2.61
]
2 .1 0
[ 0
. 3
67 .8 [2.6 7]
5.0 [0.20 ]
]
4 .4 0
[ 1
. 1 1
13 .0 [0.5 1]
]
2 .3 0
[ 1
. 8
Frame S1: VFD004S11A, VFD004S21A, VFD004S23A
5.8 [0. 23]
74 .0 [2.92 ]
]
]
3
1
.8
.2
5
5
[
[
0
2
.
.
8
2
4
3
1
1
5.0 [0.20]
Chapter 2 Installation and Wiring|VFD-S Series
10 2. 0 [4. 02]85 .0 [3.35 ]
2.8 [0. 11]
]
2
5.0 [0.20]
.1
0
[ 0
.
3
]
4 .4
0
[ 1
.
1 1
]
2 .3
0
[ 1
.
8
Revision August 2006, SE08, SW V2.61 2-5
Chapter 2 Installation and Wiring|VFD-S Series
Frame S1: VFD004S11B, VFD004S21B
85 .0 [3.3 5]
74.0 [2.92 ]
74.0 [2.92 ]
5.8 [0.23]
]
]
1
3
.2
.8
5
5
[
[
2
0
.
.
2
8
3
4
1
1
10 2. 0 [4.02]
2.8 [0.11]
73 .0 [2.8 8]
]
3 .6
0
[ 0
.
6
1
5.0 [0.20 ]
2-6 Revision August 2006, SE08, SW V2.61
]
2 .1
0
[ 0
.
3
67 .8 [2.67]
5.0 [0.20]
]
4 .4
0
[ 1
.
1
1
27 .0 [1.0 6]
]
2 .3
0
[ 1
.
8
Frame S1: VFD007S21A, VFD007S23A
85 .0 [3.3 5]
5.8 [0. 23]
74 .0 [2.9 2]
]
1 .2
5
[ 2
. 2 3 1
]
3 .8
5
[ 0
. 8 4 1
5.0 [0.20]
Chapter 2 Installation and Wiring|VFD-S Series
12 4. 0 [4.89]
2.8 [0. 11]
]
2
5.0 [0.20]
.1 0
[ 0
. 3
]
4 .4 0
[ 1
. 1 1
]
2 .3 0
[ 1
. 8
Revision August 2006, SE08, SW V2.61 2-7
Chapter 2 Installation and Wiring|VFD-S Series
Frame S1: VFD007S21B
85 .0 [3.3 5] 74 .0 [2.9 2]
74 .0 [2.9 2]
5.8 [0.23]
]
]
3
1
.8
.2
5
5
[
[
0
2
.
.
8
2
4
3
1
1
12 4. 0 [4.89]
2.8 [0.11]
]
2 .1
0
[ 0
. 3
67 .8 [2.6 7]
5.0 [0.20]
73 .0 [2 .88 ]
] 3 .6 0
[ 0
. 6 1
5.0 [0.20]
2-8 Revision August 2006, SE08, SW V2.61
]
4
4
. 0
[ 1
. 1 1
50 .0 [1.9 7]
] 2 .3 0
[ 1
. 8
Chapter 2 Installation and Wiring|VFD-S Series
Frame S1: VFD004S43A, VFD004S43E, VFD007S43A, VFD007S43E
85 .0 [3.3 5 ]
5.8 [0.23]
12 6. 0 [4.96]
74 .0 [2.9 2 ]
]
]
1
3
.2
.8
5
5
[
[
2
0
.
.
2
8
3
4
1
1
]
2
5.0 [0.20]
.1 0
[ 0
. 3
5.0 [0.20]
]
4 .4 0
[ 1
. 1 1
3.0 [0.12]
] 2 .3 0
[ 1
. 8
Revision August 2006, SE08, SW V2.61 2-9
Chapter 2 Installation and Wiring|VFD-S Series
Frame S1: VFD004S43B, VFD007S43B
85.0 [3.35]
5.8 [0.23 ]
74.0 [2.92]
]
]
3
1
.8
.2
5
5
[
[
0
2
.
.
8
2
4
3
1
1
12 6. 0 [4. 96]
3.0 [0.1 2]
73 .0 [2 .88]
] 3 .6 0
[ 0
. 6 1
5.0 [0.20]
2-10 Revision August 2006, SE08, SW V2.61
]
2 .1
0
[ 0
. 3
67 .8 [2 .67]
5.0 [0.2 0]
]
4 .4 0
[ 1
. 1 1
51.0 [2.01]
]
2 .3 0
[ 1
. 8
Chapter 2 Installation and Wiring|VFD-S Series
Frame S1: VFD002S21E, VFD004S21E, VFD007S21E, VFD015S23D
85 .0 [3.35]
5.8 [0.23] 12 7. 0 [5.00]
74 .0 [2.92]
]
]
7
3
.2
.8
5
5
[
[
7
0
.
.
3
8
3
4
1
1
5.0 [0 .2 0]
8.5 [0.33]
]
3 .3 0
[ 3
. 8
Revision August 2006, SE08, SW V2.61 2-11
Chapter 2 Installation and Wiring|VFD-S Series
Frame S2: VFD007S11A
10 0. 0 [3.94]
86 .5 [3.4 1]
5.4 [0.21]
]
1 .8
6
[ 0
. 3 7 1
12 9. 0 [5.08]
]
3 .3
7
[ 0
. 6 8 1
5.5 [0.22]
]
4 .0 0
[ 0
. 1
5.5 [0.22]
2-12 Revision August 2006, SE08, SW V2.61
]
8 .3 0
[ 5
. 9
]
6 .2 0
[ 5
. 6
Frame S2: VFD007S11B
100.0 [3.94]
86.5 [3.41]
5.4 [0. 21]
]
]
3
2
.3
.8
7
6
[
[
0
0
.
.
6
3
8
7
1
1
Chapter 2 Installation and Wiring|VFD-S Series
129.0 [5.08]
73.0 [2.88]
]
3 .6 0
[ 0
. 6 1
5.5 [0.22]
Revision August 2006, SE08, SW V2.61 2-13
67 .8 [2.67]
5.5 [0.22]
]
4 .0 0
[ 0
. 1
53 .5 [2.1 1 ]
]
8 .3 0
[ 5
. 9
] 6 .2 0
[ 5
. 6
Chapter 2 Installation and Wiring|VFD-S Series
Frame S2: VFD015S21D, VFD015S21E, VFD015S43D, VFD015S43E, VFD022S21D, VFD022S21E, VFD022S23D, VFD022S43D, VFD022S43E
100.0 [3.94]
86.5 [3.41 ]
5.4 [0.21] 12 9. 3 [5. 09]
8.5 [0.33]
]
]
3
2
.3
.8
7
6
[
[
0
0
.
.
6
3
8
7
1
1
] 4 .0 0
[ 0
. 1
5.5 [0.22]
2-14 Revision August 2006, SE08, SW V2.61
5.5 [0.22]
]
7 .3 0
[ 5
. 9
] 6 .2 0
[ 5
. 6
Chapter 2 Installation and Wiring|VFD-S Series
Frame S2: VFD015S21U, VFD015S43U, VFD022S21U, VFD022S43U
100.0 [3.94]
129.3 [5.09]5.4 [0.21]
86.5 [3 .41]
173.0 [6.82]
186.0 [7.33]
8.5 [0.33]
73.0 [2.88]
67.8 [2.67] 53.9 [2 .12]
16.0 [0.63] 5 .5 [0.22]
1.0 [0.04]
6.5 [0.26]
5.5 [0.22]
9.5 [0.37]
Revision August 2006, SE08, SW V2.61 2-15
Chapter 2 Installation and Wiring|VFD-S Series

2.4 Wiring

After removing the front cover, check if the power and control terminals are clear of debris. Be sure to observe the following precautions when wiring.
General Wiring Information
Applicable Codes
All VFD-S series are Underwriters Laboratories, Inc. (UL) and Canadian Underwriters Laboratories (cUL) listed, and therefore comply with the requirements of the National Electrical Code (NEC) and the Canadian Electrical Code (CEC).
Installation intended to meet the UL and cUL requirements must follow the instructions provided in “Wiring Notes” as a minimum standard. Follow all local codes that exceed UL and cUL requirements. Refer to the technical data label affixed to the AC motor drive and the motor nameplate for electrical data.
The "Line Fuse Specification" in Appendix B, lists the recommended fuse part number for each S-Series part number. These fuses (or equivalent) must be used on all installations where compliance with U.L. standards is a required.
2-16 Revision August 2006, SE08, SW V2.61
Chapter 2 Installation and Wiring|VFD-S Series
2.4.1 Basic Wiring
Make sure that power is only applied to the R/L1, S/L2, T/L3 terminals. Failure to comply
may result in damage to the equipment. The voltage and current should lie within the range as indicated on the nameplate. Check the following items after completing the wiring:
1. Are all connections correct?
2. No loose wires?
3. No short-circuits between terminals or to ground?
A charge may still remain in the DC bus capacitors with hazardous voltages even if the power has been turned off. To prevent personal injury, please ensure that the power is turned off and wait ten minutes for the capacitors to discharge to safe voltage levels before opening the AC motor drive.
DANGER!
1. All the units must be grounded directly to a common ground terminal to prevent electric shock, fire and interference.
2. Only qualified personnel familiar with AC motor drives are allowed to perform installation, wiring and commissioning.
3. Make sure that the power is off before doing any wiring to prevent electric shocks.
Basic Wiring Diagrams
Users must connect wires according to the circuit diagrams on the following pages. Do not plug a modem or telephone line to the RS-485 communication port or permanent damage may result. Terminals 1 & 2 are the power supply for the optional copy keypad only and should not be used for RS-485 communication.
Revision August 2006, SE08, SW V2.61 2-17
Loading...