This manual contains important instructions and warnings that you should follow during
the installation, operation, storage and maintenance of this product. Failure to heed these
instructions and warnings will void the warranty.
Install the UPS in a well ventilated area, away from excess moisture, heat, dust, flammable
z
gas or explosives.
Leave adequate space (at least 15cm) around all sides of the UPS for proper ventilation.
z
Do not mount the UPS with its front or rear panel facing down at any angle.
z
Connection Warnings
The UPS must be well grounded due to a possible risk of current leakage.
z
The installation of upstream and downstream protective devices is highly recommended when
z
the UPS is connected to the mains and the load.
The protective devices connecting to the UPS must be installed near the UPS and must be
z
easily accessible for operation.
Do not use extension cords to connect the UPS to an AC outlet.
z
Usage Warnings
This is a class-A product. In a domestic environment, this product may cause radio interfer-
z
ence, in which case, the user is required to take adequate measures.
The UPS can be used to power computers and associated peripheral devices, such as moni-
z
tors, modems, cartridge tape drives, external hard drives, etc.
The external slits and openings in the UPS are provided for ventilation. To ensure reliable
z
operation of the UPS and to protect the UPS from overheating, these slits and openings must
not be blocked or covered. Do not insert any object into the slits and openings that may hinder
ventilation.
Before usage, you must allow the UPS to adjust to room temperature (20°C~25°C or
z
68°F~77°F) for at least one hour to avoid moisture condensing inside the UPS.
Do not put beverage containers on the UPS, battery pack, cabinet or any other accessory as-
z
sociated with the UPS.
The risk of dangerous high voltage is possible when the batteries are still connected to the
z
UPS even though the UPS is disconnected from the mains. Do not forget to pull out the battery
cable to completely cut off the battery source.
Do not open or mutilate the battery or batteries. The released electrolyte is harmful to the skin
z
and eyes and may be toxic.
1
Do not dispose of the battery or batteries in a re. The batteries may explode.
z
All maintenance services must be performed by quali ed service personnel.
z
removing the cover of the UPS to avoid high voltage electric shock.
You must contact quali ed service personnel if either of the following events occur:
z
1. Liquid is poured or splashed on the UPS.
2. The UPS does not run normally after this User Manual is carefully observed.
NOTE:
If you use the UPS in an area that generates or incurs dust, you should install a dust lter
in the UPS to ensure normal product life and function.
Glossary of Symbols
Symbol DescriptionSymbol Description
The UPS is in on-line mode. Protective earthing conductor
The UPS is in battery mode. Bonded to ground
The UPS is in bypass mode. Positive battery terminal
The UPS has an internal fault. Negative battery terminal
UP buttonPhase
DOWN buttonWarning
Do not connect any computer
to the charger detection port.
DC voltage
Note
Forbid open
ing or
CE
z
IEC62040-1
z
IEC62040-2 C2
z
IEC61000-4-2 (ESD) Level 4
z
IEC61000-4-3 (Radiated Field) Level 3
z
IEC61000-4-4 (EFT) Level 4
z
IEC61000-4-5 (Surge) Level 4
z
Amplon RT Series
Standard Compliance
2
Chapter 2 Introduction
NChapter 2: Introduction
General Overview
This RT series UPS, available in 5kVA, 6kVA, and 10kVA, is a true on-line double-conversion UPS providing reliable and consistent sine-wave quality power to your sensitive electronic equipment. It adopts
the latest technology and the highest quality components providing output power factor up to 0.9, and its
ef ciency in on-line mode and in economy mode can reach at maximum 92% and 96% respectively. With
its outstanding features, the UPS not only provides safe, reliable and uninterrupted power to your
tive electronic equipment at all times, but also produces greater electric power ef ciency at less cost.
Package Contents
The UPS package contains the following items. Please carefully inspect the UPS and check the included
accessories. If there is any damage or anything missing, please immediately contact the dealer from
whom you purchased the unit. If the UPS needs to be returned, carefully repack the UPS and all of the
accessories using the original packing material that came with the unit.
10kVA: 6 PCS
Item Quantity
UPS 1 PC
z
User Manual 1 PC
z
Software CD –SMART2000 1 PC
z
Battery Cable 1 PC
z
RS232 Cable 1 PC
z
Parallel Cable 1 PC
z
Tower Stand 1 SET (4 PCS)
z
Bracket Ear 1 SET (2 PCS)
z
Terminal 5/ 6kVA: 8 PCS
z
sensi-
3
Features
True on-line design UPS protects your sensitive electronic equipment from power interruption.
z
Wide AC input voltage range (100Vac~300Vac) reduces frequent transfer
z
battery mode to save battery consumption and prolong battery life.
Smart battery charger design performs auto-charging and reduces the charging time.
z
Automatic input frequency detection enables operation at 50Hz or 60Hz.
z
The input power factor correction and the high frequency pulse-width-modulated inverter give
z
the UPS excellent performance characteristics in this compact design.
Battery-Start powers on the UPS to provide stable AC power when there is no AC line avail-
z
able.
Remote Control Port: Use this port to either shut down the UPS completely (REPO) or switch
z
off the inverter only (ROO).
Built-in RS232 communication port allows the monitoring and management of the UPS via
z
SMART2000 software.
from on-line mode
to
Optional accessories include
z
TVSS
cation and surge protection.
State-of-the-art microprocessor technology performs self-detection and displays the UPS sta-
z
tus on LCD.
Surge protection and EMI lter functions.
z
Automatic restart:
z
1) The UPS will restart in on-line mode automatically right after the AC line resumes following
a low battery shutdown.
2) The UPS returns automatically to on-line mode from bypass mode after the overload condition is cleared.
External battery pack connector is provided to connect an external battery pack to extend the
z
backup time.
Optional ECO Mode: When the utility input voltage and frequency are
z
voltage ±10% and rating frequency ±6%, the UPS will transfer to bypass mode; otherwise, the
UPS will transfer to on-line mode to reach higher ef ciency.
Auto-detect the bypass mode voltage: Automatically detects whether the bypass voltage is out of
z
rating voltage (240Vac output: 156~276Vac; 200/ 208/ 220/ 230Vac output: 156~264Vac). If yes,
the UPS will stop the supply to the load to protect your electronic equipment.
Automatically detects and shows whether the fan(s) is operating normally.
z
Amplon RT Series
cards for
network communication
Mini SNMP, Mini Relay I/O, Mini USB, Mini ModBus
and
, dry contact, USB communication, ModBus communi-
within the range of rating
4
Mini
Chapter 2 Introduction
Normal start-up function even when the UPS is not connected to the batteries.
z
WARNING:
Please note that when the UPS is not connected to the batteries, it will not protect your
equipment if the utility power is lost.
Enables set up of “1+1” parallel redundant system (with optional manual bypass box) to in-
z
crease the system availability and reliability.
The fan(s) automatically adjusts the fan speed to prolong fan life.
z
Storage
Prior to installation:
z
If the UPS needs to be stored prior to installation, it should be placed in a dry area. The allowable storage temperature is between -15°C and +50°C (5°F~122°F).
After usage:
z
Press the ‘OFF’ button, make sure the UPS is shutdown, disconnect the UPS from the utility
power, remove all equipment from the UPS, and store the UPS in a dry and well-ventilated
area at a temperature between -15°C and +50°C (5°F~122°F). Idle batteries must be recharged fully approximately every three months if the UPS needs to be stored for an extended
period of time. The charging time must not be less than 24 hours each time.
NOTE: After storage and before start-up of the UPS, you must allow the UPS to adjust to
room temperature (20°C~25°C or 68°F~77°F) for at least one hour to avoid moisture condensing inside the UPS.
5
Front Panel
(Figure 2-a) Front Panel
No.ItemDescription
1
On-line LEDIndicates that the UPS is in on-line mode.
2
Battery LED
3
Fault LEDIndicates that the UPS has an internal fault.
4
Bypass LEDIndicates that the UPS is in bypass mode.
5
Backlight LCD Display
ON Button
6
OFF Button
7
8
and Buttons
Indicates that the UPS is currently in battery mode and the external
battery is discharging now.
The LCD display shows the status of the UPS and relevant information.
Press this button for 3~5 seconds to start up the UPS. In on-line
mode with utility power available, press this button for 3 seconds to
execute the 10-second battery discharge test.
Press this button for over 3 seconds to shut down the inverter of
the UPS.
Use these two buttons to set up the output frequency, voltage, operation mode and the LCD. Press either
than 3 seconds to disable ‘BEEP’.
or button for more
Amplon RT Series
6
Chapter 2 Introduction
Rear Panel
(Figure 2-b)
5kVA/ 6kVA
Rear Panel
(Figure 2-c)
10kVA Rear Panel
No. ItemDescription
Input BreakerProtects the utility power from further damage when the UPS fails.
1
Input Terminal BlockConnects the UPS to the mains.
2
Output Terminal BlockConnects to the load.
3
Fan Cools and ventilates the UPS.
4
Parallel ConnectorFor UPS parallel communication, please see Chapter 5 for detailed
5
Remote Control PortShuts down the UPS completely or switches off the inverter only.
6
Charger Detection Connects to the charger box and detects the charger status.
7
SNMP Slot Accepts SNMP/ Relay I/O/ ModBus card. Please see Chapter 5 for
8
RS232 PortCommunication interface port. Please see Chapter 5 for detailed
9
Smart Slot Accepts Mini SNMP/ Mini Relay I/O/ Mini USB/ Mini ModBus/ Mini
10
11
External Battery Pack
Connector
information.
Please see Chapter 5 for detailed information.
detailed information.
information.
TVSS card. Please see Chapter 5 for detailed information.
Connects to the external battery pack. Please see Chapter 5 for
detailed information.
7