Delta HPP-1K5A01KAT User Manual

Page 1
User Manual
PULSED DC Power Supply
Continuous 325 – 1000VDC
Version: Rev.S.00
Page 2
I.
Copyright
All rights reserved. The contents either of manual and design of power supply
may not be reproduced or used in any manner whatsoever without admittance by
Delta Electronics Inc.
Warranty
This product Delta “HPP-1K5A01KAT” Model is been warranted against defect in material and workmanship for a period of “1” year after date of shipment. Delta agrees to repair or replace the fault unit free-of-charge which fails to perform with specification
and under normal use during this period.
This warranty shall not apply to the following items and will be billed of cost:
1. To exceed the warranty period.
2. Subject to misuse, negligence, accident or natural disaster.
3. Used in a hazardous or dangerous manner either alone or in conjunction with other equipment.
4. Repaired or altered by person who was not authorized by Delta.
5. Appearance change with environment factor
Delta will be the sole arbiter for those circumstances
To make a warranty claim please contact Delta at telephone number in the table
or support at delta.com, the fault unit transportation to Delta to be prepaid and
responsibility by purchaser, and Delta will take responsibility for ship it back.
Delta Electronics, Inc.
3 Tungyuan Road, Chungli Industrial Zone Taoyuan County 32063, Taiwan, ROC Tel: 886-3-4526107 Fax: 886-3-4331706 Web Site: www.deltaww.com
Page 3
II.
INDEX ...............................................................
Chapter 1: Safety and Standard ································································· 1
1.1. Important Safety Information ··········································································· 1
1.2. Safety and Warning Symbols ·········································································· 1
1.3. Electromagnetic Compatibility Directives and Standard ········································· 2
1.4. Industry Guideline ························································································ 2
Chapter 2: Introduction ············································································· 3
2.1. Brief Statement ···························································································· 3
2.2. Key Feature ································································································ 4
Chapter 3: Specification ··········································································· 4
3.1. System Block Diagram ·················································································· 4
3.2. Electrical Specification ··················································································· 6
3.3. Ignition Capability ························································································· 7
3.4. Arc Suppression Specification ········································································14
3.5. Ignition Profile ····························································································15
3.6. Process and Monitor Function ········································································15
3.6. Mechanical Specification ···············································································16
3.6. Environment Specification ·············································································18
Chapter 4: System Protection Mechanism ················································ 19
4.1. Input Breaker ·····························································································19
4.2. Protection by MCU ······················································································19
Chapter 5: Installation ············································································ 20
5.1. Cooling Requirements ··················································································21
5.2. Cabinet Design ···························································································21
5.3. Grounding ·································································································22
Chapter 6: Interface ················································································ 23
6.1. Front Panel ································································································23
6.2. Rear Panel ································································································25
6.3. Main Menu Map……………………………………………………………………………….. 26
6.4. Digital Communication Port (Host) ···································································28
6.5. Analog Communication Port (User) ··································································32
Chapter 7: Operation ·············································································· 34
7.1. Panel Operating Steps··················································································34
7.2. D-SUB Operating Steps ················································································35
7.3. RS232 Operating Steps ················································································35
7.4. RS485 Operating Steps ················································································36
Chapter 8: Maintenance ·········································································· 37
Page 4
1.
Chapter1: Safety and Standard
1.1. Important Safety Information
To keep your safety from hazardous and fatal circumstance, please read and realize the content
of this manual before installing and operating Delta “HPP-series” power supply.
1.2. Safety and Warning Symbols
The following advisory symbols as shown in Table 1.1 will be used in the manual for different
level of warning. The meanings of the advisory symbols are explained below.
Table 1.1 Safety and Warning Symbols (1)
This danger symbol advises that improper operation will cause
serious personal injury or death.
This warning symbol advises that improper operation will cause serious personal injury, or catastrophic damage the generator or any electronic devices connected to the
generator, or lose important data.
This caution symbol advises that improper operation will cause personal injury, or damage the power supply or any electronic
devices connected to the power supply, or lose data.
The following advisory symbols as shown in Table 1.2 are used on safety warning labels, and/or
on printed circuit board (only provided with white paint), and/or other part of the generator. The
meanings of these symbols are explained as below.
Table 1.2 Safety and Warning Symbols (2)
Dangerous voltage symbol indicates the presence of high voltage. Access the high voltage will cause serious personal
injury or death.
To protect against electrical shock in case of a fault. This symbol indicates that the terminal must be connected to
ground before operation of equipment.
Residual voltage:
Wait 8 minutes at least for capacitor discharge after power cord is removed and before servicing.
Page 5
2.
Heavy object:
Two persons lifting are recommended to avoid muscle strain or
back injuries.
1.3. Electromagnetic Compatibility Directives and Standard
Disturbance Characteristic: EN55011 - CRSP11 Class A, Group 1 (>20kVA) General Immunity Standard for Industry: EN 61000-6-2 Safety Requirement: IEC-61010-1 (CE and UL certification)
1.4. Industry Guideline
Guideline for Semiconductor manufacturing equipment: SEMI S2 and F47
Page 6
3.
Chapter 2: Introduction
2.1. Brief Statement
Delta “HPP-1K5A01KAT” is a high voltage pulsed DC generator that meets the exciting
requirement in physical vapor deposition technique with a wide range of applications in the
semiconductor, optical and industrial coating, particularly for Reactive Sputtering, like Alumina,
Titania and Silica with high deposition rates.
The reverse voltage here is adjustable from 50V to 100V, which is dependent from the applied
negative voltage and could be adjustable for different targets. Maximum 1.9KV adjustable ignition
voltage could help users to ignite plasma successfully every time for some specific targets, for
example, copper target.
Asymmetric pulsing output makes the arc happening reduced dramatically. With High-speed
MCU based arc detection, Delta power could achieve 1 micro-sec arc detection time. As soon as
the arc is detected, the output will be reversed to positive to reduce arc energy approximately 5
microseconds. When the micro ARC is cleared, normal pulsing resumes.
With Delta’s mutual power supply design technology, efficiency at rated load is higher than
competing products. High efficiency, less temperature stress and highly integrated circuit make it
more stable, reliable and longer product lifetime. DSP-based digital control provides user an
accurate, repeatable and quick pulsed output response. Active front panel, multiple serial and analog
interfaces facilitate user to get an easy and flexible control over power supply.
Figure 2.1 Delta “HPP-1K5A01KAT” Sputtering Power Supply
Page 7
4.
2.2. Key Feature
Advanced SiC mosfets module implement:
The highest power level of pulse DC generator. The widest frequency adjustment.
Lossless Snubber circuit.
Clamp voltage stress of pulse switch.
Less oscillation. Ultra low arc energy (< 200uJ/KW) Configurable reverse voltage (50V~100V)
Chapter 3: Specification
3.1. System Block Diagram
Taipei rectifier PFC ModuleBreaker
Three phase
AC Input
Full Bridge
module
Output
Measurement
Pulsed DC
module
Pulsed DC
Output
Housekeeping
Supplies
Control Circuit
Front Panel Display Isolated Remote InterfacesAdaptable Fan
Configurable power supply
Figure 3.1 System Block Diagram of Delta “HPP-1K5A01KAT”
Table 3.1 Detail Description for Block Diagram
Taipei rectifier PFC Module
Three phase main voltage is applied while breaker is closed. After Taipei rectifier PFC, soft start mechanism suppresses inrush current to prevent any damage. A good power factor condition back to the mains then is modified through Taipei rectifier PFC and AC voltage
is rectified to DC bus for DC-DC Section.
Full Bridge Module
The converter section converts DC voltage stored in the bulk capacitors to high-frequency voltage by alternating the current through switching power components. In the output side, an isolation transformer steps up the high-frequency voltage from the converter section and delivers it to a full-wave rectifier bridge. The rectified DC power is then passed through a measurement section to the output
connector.
Pulse DC Module
In the pulse section, an inductor and a controlled switch are
responsible for generating pulse output from straight DC.
Output Measurement and
Feedback
The output measurement section measures current and voltage, and feedback the voltage and current information to MCU for voltage,
current and power control and related protection.
Page 8
5.
Housekeeping supplies
The AUX power provides low voltage source to supply the Vcc of
analog OPA, main controller, MCU, fan and LCD display.
Control Circuit
The MCU is responsible for controlling the power supply status and
providing status information to the operator through all interfaces.
Front Panel Display
Control panel shows operating mode, command level, feedback values, set up Arc processing, process control, interface setup,
communication set and system status during power supply working.
Remote Control Interface
The power supply supports three types of interfaces: a User port (analog), a Host port (RS-232, RS-485) and an active front panel. All three interfaces communicate operator-supplied inputs to MCU and
provide the operator with status information.
Configurable power supply
The power supply provide configurable reverse voltage to the output
side in pulse mode and the voltage range is 50V to 100V.
Page 9
6.
3.2. Electrical Specification
Table 3.2 Electrical Specification
Item
Specification
Condition
Input Voltage
208V
AC
± 10% (Three Phase)
50 to 60Hz
Input Current (Per Phase)
5.5A
RMS
nominal per phase
Rated output power
Maximum Output Power
1.5kW
Measured at the DC output
Output Voltage Range
131VDC to 1000V
DC
Measured at the DC output
Output Current Range
0.01A to 4.62A
Measured at the DC output
Power Supply Efficiency
> 90%
Rated output power at DC 1000V
Power Factor
> 0.95
Rated output power
Output Voltage Ripple
< 2% (V
RMS
)
At DC Mode
Output Voltage Accuracy
1% of command setting or 0.25% of full scale voltage between
output and command
Within operation range at 25 ˚C At DC Mode
Output Current Accuracy
1% of command setting or 0.25% of full scale current between
output and command
Within operation range at 25 ˚C At DC Mode
D-sub Monitor/Command
(Analog Interface) Accuracy
1% of full scale rating between
output and D-sub
Operation range
Ignition Capability
1000Vdc to 1900Vdc 100Vdc increments
Temperature Coefficient
< 50ppm/˚C
20˚C to 40˚C Variation in regulated output
Operation Mode
CV, CC, and CP Mode
-
Operation Temperature
0˚C to 40˚C
-
Arc Energy
< 200uJ per 1kW
-
Main Protection
OVP, OCP, OTP, SCP, ARC
Output Frequency
5K~400KHz, 5KHz increments
Reverse Time
0.4us to 10us, 0.1us increments
Allowable reverse time is limited
for a given frequency
Reverse Voltage
50V~100V, 10V increments
Repeatability
Output power repeatability of the DC inverter from run to run at a constant set-point is 0.1% from
10% to 100% of rated power.
Page 10
7.
3.3. Reverse Time as a Function of Voltage Limit (V-Limit)
V-Limit(in Volts)
Corresponding Reverse Time
0-325
10
μs
330
9.8
μs
335
9.7
μs
340
9.5
μs
345
9.4
μs
350
9.2
μs
355
9.1
μs
360
9
μs
365
8.9
μs
370
8.7
μs
375
8.6
μs
380
8.5
μs
385
8.4
μs
390
8.3
μs
395
8.2
μs
400
8.1
μs
405
8
μs
410
7.9
μs
415
7.8
μs
420
7.7
μs
425
7.6
μs
430
7.5
μs
435
7.4
μs
440
7.3
μs
445
7.3
μs
450
7.2
μs
455
7.1
μs
460
7
μs
465
6.9
μs
470
6.9
μs
475
6.8
μs
480
6.7
μs
485
6.7
μs
490
6.6
μs
495
6.5
μs
500
6.5
μs
505
6.4
μs
510
6.3
μs
515
6.3
μs
520
6.2
μs
525
6.1
μs
Page 11
8.
530
6.1
μs
535
6
μs
540
6
μs
545
5.9
μs
550
5.9
μs
555
5.8
μs
560
5.8
μs
565
5.7
μs
570
5.7
μs
575
5.6
μs
580
5.6
μs
585
5.5
μs
590
5.5
μs
595
5.4
μs
600
5.4
μs
605
5.3
μs
610
5.3
μs
615
5.2
μs
620
5.2
μs
625
5.2
μs
630
5.1
μs
635
5.1
μs
640
5
μs
645
5
μs
650
5
μs
655
4.9
μs
660
4.9
μs
665
4.8
μs
670
4.8
μs
675
4.8
μs
680
4.7
μs
685
4.7
μs
690
4.7
μs
695
4.6
μs
700
4.6
μs
705
4.6
μs
710
4.5
μs
715
4.5
μs
720
4.5
μs
725
4.4
μs
730
4.4
μs
735
4.4
μs
740
4.3
μs
745
4.3
μs
Page 12
9.
750
4.3
μs
755
4.3
μs
760
4.2
μs
765
4.2
μs
770
4.2
μs
775
4.1
μs
780
4.1
μs
785
4.1
μs
790
4.1
μs
795
4.0
μs
800
4.0
μs
805
4.0
μs
810
4.0
μs
815
3.9
μs
820
3.9
μs
825
3.9
μs
830
3.9
μs
835
3.8
μs
840
3.8
μs
845
3.8
μs
850
3.8
μs
855
3.7
μs
860
3.7
μs
865
3.7
μs
870
3.7
μs
875
3.7
μs
880
3.6
μs
885
3.6
μs
890
3.6
μs
895
3.6
μs
900
3.6
μs
905
3.5
μs
910
3.5
μs
915
3.5
μs
920
3.5
μs
925
3.5
μs
930
3.4
μs
935
3.4
μs
940
3.4
μs
945
3.4
μs
950
3.4
μs
955
3.3
μs
960
3.3
μs
965
3.3
μs
970
3.3
μs
Page 13
10.
975
3.3
μs
980
3.3
μs
985
3.2
μs
990
3.2
μs
995
3.2
μs
1000
3.2
μs
Reverse Time Given a Self-Run Frequency
Requested Frequency (kHz)
Actual Frequency (kHz)
Pulse Reversal Time Maximum (μs)
Duty Cycle (min%) Reverse/ Period
Duty Cycle (max%) Reverse/ Period
5
5
10
0.2
5
10
10
10
0.4
10
15
15.004
10
0.6
15
20
20
10
0.8
20
25
25
10 1 25
30
29.985
10
1.2
30
35
35.026
10
1.4
35
40
40
10
1.6
40
45
45.045
9.9
1.8
44.6
50
50 9 2
45
55
54.945
8.1
2.2
44.5
60
60.06
7.4
2.4
44.4
65
64.935
6.9
2.6
44.8
Page 14
11.
70
69.93
6.4
2.8
44.8
75
74.906 6 3
44.9
80
80
5.6
3.2
44.8
85
85.106
5.2
3.4
44.3
90
90.09
4.9
3.6
44.1
95
94.787
4.7
3.79
44.5
100
100
4.5 4 45
105
105.263
4.2
4.21
44.2
110
109.89 4 4.4
44
115
114.943
3.9
4.6
44.8
120
119.76
3.7
4.79
44.3
125
125
3.6 5 45
130
129.87
3.4
5.19
44.2
135
135.135
3.3
5.41
44.6
140
139.86
3.2
5.59
44.8
145
144.928
3.1
5.8
44.9
150
150.376
2.9
6.02
43.6
155
155.039
2.9
6.2
45
160
160
2.8
6.4
44.8
165
165.289
2.7
6.61
44.6
170
169.492
2.6
6.78
44.1
175
175.439
2.5
7.02
43.9
180
180.18
2.4
7.21
43.2
185
183.486
2.4
7.41
44
190
190.476
2.3
7.62
43.8
195
194.175
2.3
7.77
44.7
200
200
2.2 8 44
205
204.082
2.2
8.16
44.9
210
210.526
2.1
8.42
44.2
215
215.054 2 8.6
43
220
219.78 2 8.79
44
225
224.719 2 8.99
44.9
230
229.885
1.9
9.2
43.7
235
235.294
1.9
9.41
44.7
240
240.964
1.8
9.64
43.4
245
243.902
1.8
9.76
43.9
250
250
1.6
10
40
255
256.41
1.5
10.26
38.5
260
259.74
1.5
10.39
39
265
266.667
1.5
10.67
40
270
270.27
1.4
10.81
37.8
275
273.973
1.4
10.96
38.4
280
281.69
1.4
11.27
39.4
285
285.714
1.4
11.43
40
Page 15
12.
290
289.855
1.3
11.59
37.7
295
294.118
1.3
11.76
38.2
300
298.507
1.3
11.94
38.8
305
303.03
1.3
12.12
39.4
310
307.692
1.3
12.31
40
315
312.5
1.2
12.5
37.5
320
317.46
1.2
12.7
38.1
325
322.581
1.2
12.9
38.7
330
327.869
1.2
13.11
39.3
335
333.333
1.2
13.33
40
340
338.983
1.1
13.56
37.3
345
344.828
1.1
13.79
37.9
350
350.877
1.1
14.04
38.6
355
355.877 1 14.2
35.5
360
360.878 1 14.4
36
365
365.788 1 14.6
36.5
370
370.787
0.9
14.8
33.3
375
375.877
0.9
15
33.75
380
380.788
0.9
15.2
34.2
385
385.877
0.9
15.4
34.7
390
390.878
0.9
15.6
35.1
395
395.787
0.9
15.8
35.6
400
400.788
0.9
16
36.0
Page 16
13.
1000V
200V
325V
4.62A
600V
1.2A 1.5A
Power Limit
Current Limit
Voltage Limit
1900V
Operation Range
V
out
I
out
131V
Figure 3.2 Curve of Output V-I Characteristic
1500W
750W
70Ω
Power Limit
Current Limit
Operation Range
Z
out
666Ω 1333Ω
P
out
Voltage Limit
Figure 3.3 Curve of Output Impedance Characteristic
For Delta “HPP-1K5A01KAT” power supply, the maximum output voltage and current level are
1000 V and 4.62 A (Measured at the DC output). The output characteristic is as the figures above.
If the operation point is below 325V, the power supply can provide at most 4.62 A, if the operation
is more than 325V, the maximum output current will decrease to 1.5 A within the output voltage
reaching 1000V.
Page 17
14.
3.4. Arc Suppression Specification
Figure 3.4 shows the waveforms and key parameters under arc condition, and Table 3.3
indicates the arc energy and adjustable parameters for user. As soon as the arc is detected by arc
voltage detection within 1 micro sec, power ON delay after a micro ARC will be approximately 5
microseconds. When the micro ARC is cleared normal pulsing resumes.
Hard Arcs (defined as those micro Arcs which cannot be extinguished with the standard micro
ARC algorithm of a 5 microsecond shutdown) will be detected within low impedance after the initial
micro ARC started. Number of detected arcs is displayed by the front panel display or from
communication interface. If hard arc inside vacuum chamber occur, the hard arc flag will be raised
and the power will shut down for a predetermined time.
Figure 3.4 Arc Suppression Mechanisms
Table 3.3 Arc Energy Specification and Adjustable Parameters for User
Item
Specification
Condition
Reverse Time
5u sec
Voltage Level Recognizing as
Arc
10V to 250V, adjustable
10V Step, 100V Default
Hard Arc Shutdown time
200us to 10000us
After Low Z output, power will
shutdown
Arc Energy
< 200uJ per 1kW
With System
0V
0A
Arc Occurs
Detection Circuit Activated
Arc Detected
Switching on
Detection
Time
Reverse
Time
Arc Voltage
Trip Level
t
1
t
2
Voltage
Current
signal of
switching
t
t
3
t4t5t
6
Recovery
Time
10~250V
-1~-2A
Page 18
15.
3.5. Ignition Profile
Figure 3.5 shows the waveform of output voltage under Ignition condition. When power ON
with ignition function enabled, the output voltage will rise from 0V to ignition voltage within 10ms.
Then the voltage will stay on ignition voltage for 100ms and fall to 1000V for 900ms. This profile
will repeat every 1s. If the chamber is ignited within 10s, the output voltage will change to the set-
point directly. If not, the generator will latch. The Ignition voltage can be set from 1000V to 1900V, 100V increment.
0V
t
Output
Voltage
-1900V
-1000V
10ms 100ms 900ms 900ms 900ms 900ms100ms 100ms 100ms
Figure 3.5 Ignition Profile
3.6. Process and Monitor Function
Table 3.4 Adjustable function parameters for User
Item
Specification
Description
Max. Power
20 to 1.5 kW
Power will be constrained within the value of setting prior to the
set point of regulation.
Max. Current
0.01 to 4.62 A
Current will be constrained within the value of setting prior
to the set point of regulation.
Max. Voltage
500 to 1000 V
Voltage will be constrained within the value of setting prior
to the set point of regulation.
Ignition Mechanism
1000 to 1900 V
A voltage up to 1900 V is adjustable for igniting the
system.
Ramp Time
50 to 2000 ms
A ramp up to set point is adjustable for a soft start
mechanism.
Set Point
1 to 10 s
Monitoring if the output reaches the setting of regulation within
the setting of period.
Energy Mode
1 to 99999 kJ
Monitoring if the output energy
reaches the setting of energy.
Page 19
16.
Target Life Mode
1 to 15000 kWh
Monitoring if the output energy
reaches the setting of kWh.
3.7. Mechanical Specification
The outward appearance, cooling specification for minimum CFM Requirement, and I/O ports
of Delta “HPP-1K5A01KAT” sputtering power supply are described as below:
Table 3.4 Mechanical Specification
Item
Description
Physical Dimension
482.6(W)x132.5(H)x560(L)mm 19"(W)x5.2"(H)x23.6"(L) (19" 3U)
Weight
32kg
Cooling
Fan Cooling
AC Input Connector
Harting Han Q/5 series p/n 09120052633
DC Output Connector
7/16 Connector, Female
User Port
Analog I/O: 15-pin female D-sub
Host Port
Digital I/O: 9-pin female RS232 and RS485 and RJ45
Mechanical Drawing
Unit: mm (inch)
Figure 3.6 Mechanical Drawing of Delta “HPP-1K5A01KAT” sputtering power supply
Page 20
17.
Air cooling
Figure 3.7 Air Flow Schematic Diagram
Delta “HPP-1K5A01KAT” sputtering power supply is the forced air cooling type. Please keep enough
space for air flow cooling capability when it is installing to the cabinet. Air inlet on the front panel and
air outlet on the rear panel is shown in figure 3.7. Air outlet of rear panel is responsible for dissipating
the heat from inside of power supply to outside by internal two fans. The temperature of air inlet
should not exceed 40degree C.
Page 21
18.
3.8. Environment Specification
Table 3.6 Climatic Specification
Item
Temperature
Relative Humidity
Air Pressure
Operating
0˚C to 40˚C (32˚F to 104˚F)
10% to 90% RH (Non-
condensing)
80kPa to 106kPa
(approximately 2000m
above sea level)
Storage
-25˚C to 55˚C (-13˚F to 131˚F)
10% to 95% RH
80kPa to 106kPa
(approximately 2000m
above sea level)
Transportation
-25˚C to 70˚C (-13˚F to 158˚F)
95% RH (Maximum)
66kPa to 106kPa
(approximately 2000m
above sea level)
Table 3.7 Environment Specification
Item
Description
Operating
Category II
Pollution Degree
Pollution Degree 2
Page 22
19.
Chapter 4: System Protection Mechanism
4.1. Input Breaker
The function of this switch is to prevent over current at input side from any malfunction
happening and simultaneously provide a manual switch for user to turn off the power supply.
4.2. Protection by MCU (A: Auto Recovery, L: Latch)
Table 4.1 Definition and description of MCU protection
Alarm Condition
Code
Description
Mode
HW Fault M1
M1F
Hardware error from the left module
A
SW OVP
OV
Output over voltage
A
SW OCP
OC
Output over current
A
SW OPP
OP
Output over power
A
Target Life Monitor
09
Power off while output reaches setting Energy
L
Output Interlock
11
Uninstallation of output cover
L
Contactor Interlock
12
Uninstallation of contactor pin in D-sub connector
L
Communication Loss
15
Error from internal communication
L
Fan1 Error
17
Error from the left fan
L
Fan2 Error
18
Error from the right fan
L
Bus UVP
20
Input voltage is under operation range
L
Bus OVP
21
Input voltage is over operation range
L
Set Point Monitor
23
Error while output fails to reach setting parameter
within setting time
L
Energy Mode Monitor
24
Power off while output reaches setting energy
L
Warning Condition
Code
Description
Mode
Output Limit
limit
Output is over setting parameters of setting
A
Page 23
20.
Chapter 5: Installation
Delta “HPP-1K5A01KAT” power supply is a high voltage power supply. Please read this manual
carefully and follow the instruction before installation and operation, otherwise an electric shock or
a fatal accident might be caused.
Shielding
PE
PE
Chamber
Figure 5.1 Installation diagram
This power supply could only be placed horizontally and connect the protective grounding
to prevent an electric shock before use.
Consideration must be taken not to impede the supply or flow of air to the unit. Please switch off the power supply before touching the case. Before applying power, please verify that the product is set to match with the line voltage. The circumstance temperature should be managed under 40˚C The installation and operation should be only in pollution degree 2 or better environment.
Do not operate this device in a dusty area or in corrosive gas environment. Proper grounding: For safe use, must connect ground cable (Yellow / Green wire) from
ground stud on the power supply rear panel to the pure earth ground. Poor grounding may
cause an electric shock or fatal accident. Output connector must be connected with the attached output cable. (3KV/6AWG/200°C,
with shielding). Do not use other output cables. Before applying power, please verify that the product is set to match with the line voltage.
When emergency, cut-off the circuit breaker, and then removing mains supply cord. Operating personnel must not remove the cover of the instrument. Component
replacement and internal adjustment can be done only by qualified service personnel.
Remove mains cord and output cable before exterior maintenance and service. Use the carrying handle when dismantling it. Avoid drop resulting in hurt.
Page 24
21.
5.1. Cooling Requirements
For the HPP-1K5A01KAT A supply to be sufficiently cooled, the cabinet must be set up to:.
1. Bring in coolant air of the correct temperature(40 ˚C maximum)
2. Distribute coolant air to the power supplies
3. Prevent air exhausted from the cabinet from circulating back and becoming input air
4. Exhaust the hot air from the cabinet with minimal airflow restriction.
5.2. Cabinet Design
The following is a synopsis of the HPP-1K5A01KAT A to follow when designing a cabinet
containing a stack of HPP-1K5A01KAT A power supplies.
Coolant air must be drawn easily into the cabinet; exhaust air must be able to pass
unrestricted out of the cabinet. If some physical constriant restricts the flow of exhaust air out of
the cabinet, we recommend that fans or blowers be mounted so that the hot air is removed from
the cabinet as quickly as possible.
Each HPP-1K5A01KAT A power supply dissipates up to 10% of its maximum power at full
rated output. The minimum air flows in cubic feet per minute(CFM) required by individual HPP-
1K5A01KAT A supplies are shown in table 5.1. The static pressure(inches of water) of the empty
cabinet should not exceed 0.1 inches of water at the CFM level obtained by adding together the
minimum CFM values for all the power supplies that will be placed in the cabinet. For example, if
three HPP-1K5A01KAT A supplies are mounted in a cabinet, the minimum CFM requirement
would be three times the CFM of cabinet air volume compared to an individual supply.
Approximations of this figure, the total power dissipation, and the temperature difference between
coolant air and exhaust air are shown as an example in table 5.2.
Table 5.1 Minimum CFM requirement for HPP-1K5A01KAT unit
Type of PSU
CFM Required
1.5KW
260 CFM (122.7 liters/second)
Page 25
22.
5.3. Grounding
For your convenience, the rear panel of the HPP-1K5A01KAT supply features three
equipotential ground screw: three M6 screw. These are indicated on the rear panel by a ground
symbol.See figure 6.2 for more information.
Page 26
23.
Chapter 6: Interface
6.1. Front Panel
The functions for several buttons on the front panel are described on Table 6.1
Table 6.1 Function description of front panel
“Enter” Button
1. Press the button to change all of adaptive parameters.
2. Press the button to enter the next layer while in menu screen.
“Menu” Button
1. Press the button to menu screen from home screen.
2. Press the button to return to the previous layer while in menu screen.
“P” Button
Press the button to set the output condition in constant power mode. In constant power mode user could adjust output power regulation level by
“enter button” and “knob”.
“I” Button
Press the button to set the output condition in constant current mode. In constant current mode user could adjust output current regulation level by
“enter button” and “knob”.
“V” Button
Press the button to set the output condition in constant voltage mode. In constant voltage mode user could adjust output voltage regulation level by
“enter button” and “knob”.
“ON” Button
Press the button to turn on the output power. While power on, user could
adjust output regulation level by “enter button” and “knob”.
“OFF” Button
Press the button to turn on the output power.
“LOCK” Button
Press the button to lock “Enter”, “Menu”, “P”, “I”, “V”, “ON”, “OFF” button. This function could prevent any unexpected change from panel while PSU
in operation.
Regulation Knob
Rotate the knob to adjust the regulation level.
LCD Display
The display shows command of output regulation level according to control modes of Power/Current/Voltage. It also indicates feedback values of Power/Current/Voltage and system status, such as error conditions for all
protect signals.
Page 27
24.
Display Panel LEDs
POWER ON
Lights green when input power is on
OUTPUT
Lights green if output power is on
SETPOINT
Lights green if the Pulsed DC power supply is operating within set point; accuracy is within 0.4% of full scale or 2% of set point, whichever is greater
INTERLOCK
Lights green if all interlock conditions have been met
BUS FAULT
Lights green when a bus fault occurs
OVERTEMP
Lights green if the Pulsed DC power supply has exceeded the maximum operating temperature
ARC
After the output has been turned off, this LED lights green for a predetermined time if the hard arc count limit was reached during the previous run. You define this limit. The ARC LED will be activated under two different conditions:
1. If the hard arc count limit is non-zero and the number of hard arcs seen exceeded this limit during the last run, the pulse will occur when the output is turned off.
2. If the hard arc count limit is set to zero, this signal will pulse for a predetermined time for every hard arc seen by the unit. If another hard arc is seen before the last pulse is complete, the pulse width will be refreshed to the full width.
Figure 6.1 Front Panel
Page 28
25.
6.2. Rear Panel
1. GND terminal is for chamber grounding, and earth grounding should be performed for safety.
2. Connect output terminal to target and connect UHF to the chamber
3. Your pulsed DC power supply features a host port with a 9-pin, female, RS-232/RS-485 connector for interfacing with a host computer.
4. Your pulsed DC power supply features a user port with a 15-pin, female, D-sub connector for interfacing with a computer.
5. The Contactor Intlk port, located on the rear panel of the pulsed DC power supply, is a 9- pin, male, subminiature-D connector. To enable the pulsed DC power supply to function, pins 3 and 4 of this connector must be shorted together (through a cheater plug, external switch, or relay).
Figure 6.2 Rear Panel
Page 29
26.
6.3. Main Menu Map
Port Selection
Home Screen
Fault Screen
First Layer Second Layer Third Layer
Process Control
Interface Setup
System Information
Delta Service
Limit Setup
Monitor Setup
Arc Setup
Default
Max. Power
Default
1500W
Max. Voltage 1000V
Max. Current 4.62A
Ignition OFF
Ramp Time OFF
Set Point OFF
Energy Mode OFF
Target Life Cnt 1
Default
Default
Arc Function ON
Arc Trip Level 100V
Delay Time OFF Pause Time 250us Arc Density OFF
Arc Number OFF
Communication Setup
Local
Host: RS-485
User : D-sub
User Port Regulation
A / Ri Offset
Local
A / Vo Offset
A / Io Offset
+0.0% +0.0% +0.0%
Default
Parallel Mode Setup Unit State
Master
Parallel Number 01
Termination RES. OFF
Unit Address Depend on 8-Pin Switch
Function Screen
Host : R-S232
Master
Slave
Operation Data
Integral Power Run
Integral Time Run
Power On Count
Output Power Count
After Initializing System
Power On Count
After Initializing System
Output Time Count
After Initializing System
System Life
Total Power Run
Output Power Count
Since Factory
Total Time Run
Output Time Count
After Manufacture
Total On Count
Power On Count
After Manufacture
Software Ver. Panel MCU
System MCU
Arc MCU
S.00 (Depend on Update) S.00 (Depend on Update) S.00 (Depend on Update)
E r r o r O c c u r s
E - 0 0 0
1 OFF
Third Layer Fourth Layer
REG : 1 5.0 W OU T : ON
1 0 0 0 V 4 6. 2 A 1 5 0 W
F : 4 0
M L T : 0 : 0 0 : 0 0S E 0 0sR
0 01uT :
0>
0
0
zHk
REG : 1 0.0 V O U T : O N
1 0 0 0 V 4 6. 2 A 1 5 0 W
F : 4 0
M L T : 0 : 0 0 : 0 0S E 0 0sR
0 01uT :
0>
0
0
zHk
REG : 4 ..6 A O U T : O N
1 0 0 0 V 4 6. 2 A 1 5 0 W
F : 4 0
M L T : 0 : 0 0 : 0 0S E 0 0sR
0 01uT :
2>
0
0
zHk
Reverse Voltage 100V
Page 30
27.
REG : 1 5.0 W OU T : ON
1 0 0 0 V 4 6. 2 A 1 5 0 W
F : 4 0
M L T : 0 : 0 0 : 0 0S E 0 0
s
R
Command Power On/Off
Voltage/Current/Power Reader
Arc NumberArc Density
Set PointEnergyTarget Life Mode
Run Time Hr/Min/SecMaster/Slave
0 01
u
T :
Lock
0>
0
0
zHk
D : 9 9A
9 99AN :
Arc Density Arc Number
Fig 6.3 Front Panel
Page 31
28.
6.4. Digital Communication Port (Host)
The 9-pin female RS232 connector labeled “Host Port” on the rear of the power supply lets user
connect with computer to control the power supply. Definition of RS232 connector is as follows:
Figure 6.3 Host Port: 9-pin female RS232/RS485 connector
Table6.2 Definition of RS232 RS485 Connector
Pin 1
N/A
Pin 2
RS-232(Tx)
Pin 3
RS-232(Rx)
Pin 4
N/A
Pin 5
GND
Pin 6
RS-485 (+)
Pin 7
RS-485 (-)
Pin 8
N/A
Pin 9
N/A
Page 32
29.
Table 6.3 Protocol of RS232 Definition (1)
Remote to PSU
Byte
0 1 2 3 4 5 6 7 8 9 10
IP
Command
Data1
Data2
Check Sum
Termination
Byte
H-Byte
L-Byte
H-Byte
L-Byte
H-Byte
L-Byte
0x00
Byte
0x00
0x0D
CV Mode
IP
0x11
0x00/01/02
0x00
0x00
Value
0x00
Value
0x00
0x0D
CC Mode
IP
0x12
0x00/01/02
0x00
0x00
Value
0x00
Value
0x00
0x0D
CP Mode
IP
0x13
0x00/01/02
0x00
0x00
Value
0x00
Value
0x00
0x0D
A/Ri Offset
IP
0x15
0x00/01
0x00
0x00
00/01
Value
0x00
Value
0x00
0x0D
A/Vo Offset
IP
0x16
0x00/01
0x00
0x00
00/01
Value
0x00
Value
0x00
0x0D
A/Io Offset
IP
0x17
0x00/01
0x00
0x00
00/01
Value
0x00
Value
0x00
0x0D
Set Point
IP
0x1A
0x00/01/02
0x00
0x00
Value
0x00
Value
0x00
0x0D
Pause Time
IP
0x1C
0x00/01
0x00
0x00
Value
0x00
Value
0x00
0x0D
Energy Mode
IP
0x1D
0x00/01/02
Value
Value
0x00
Value
0x00
0x0D
Arc Function
IP
0x1E
0x00/01
0x00
0x00
Value
0x00
Value
0x00
0x0D
Max Power
IP
0x22
0x00/01
0x00
0x00
Value
0x00
Value
0x00
0x0D
Max Current
IP
0x23
0x00/01
0x00
0x00
Value
0x00
Value
0x00
0x0D
Max Voltage
IP
0x24
0x00/01
0x00
0x00
Value
0x00
Value
0x00
0x0D
Ramp Time
IP
0x25
0x00/01
0x00
0x00
Value
0x00
Value
0x00
0x0D
Target Life
IP
0x26
0x00/01/02
0x00
0x00
Value
0x00
Value
0x00
0x0D
Pulse
reverse time
IP
0x29
0x00/01
0x00
0x00
Value
0x00
Value
0x00
0x0D
Pulse
frequency
IP
0x2A
0x00/01
0x00
0x00
Value
0x00
Value
0x00
0x0D
Arc Voltage
IP
0x30
0x00/01
0x00
0x00
Value
0x00
Value
0x00
0x0D
ARC Density
IP
0x31
0x00/01/02
0x00
0x00
Value
0x00
Value
0x00
0x0D
ARC Number
IP
0x32
0x00/01/02
0x00
0x00
Value
0x00
Value
0x00
0x0D
Ignition
IP
0x33
0x00/01
0x00
0x00
Value
0x00
Value
0x00
0x0D
External On
IP
0x41
0x00/01/02
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
External Off
IP
0x42
0x00/01/02
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
Reset
IP
0x45
0x00
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
Default 1
IP
0x60
0x00
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
Limit setup
Default
IP
0x61
0x00
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
Monitor setup
Default
IP
0x62
0x00
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
ARC setup
Default
IP
0x63
0x00
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
User
Regulation
Default
IP
0x70
0x02
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
Error IP and
Alarm Code
Return
IP
0x71
0x02
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
PSU State
Return
IP
0x80
0x02
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
Page 33
30.
Table 6.4 Protocol of RS232 Definition (2)
PSU to Remote
Byte
0 1 2 3 4 5 6 7 8 9 10
IP
Command
Data1
Data2
Check Sum
Termination
Byte
H-Byte
L-Byte
H-Byte
L-Byte
H-Byte
L-Byte
0x00
Byte
0x00
0x0D
CV Mode
IP
0x11
0x0A
0x00
0x00
Value
0x00
Value
0x00
0x0D
CC Mode
IP
0x12
0x0A
0x00
0x00
Value
0x00
Value
0x00
0x0D
CP Mode
IP
0x13
0x0A
0x00
0x00
Value
0x00
Value
0x00
0x0D
A/Ri Offset
IP
0x15
0x0A
0x00
0x00
00/01
Value
0x00
Value
0x00
0x0D
A/Vo Offset
IP
0x16
0x0A
0x00
0x00
00/01
Value
0x00
Value
0x00
0x0D
A/Io Offset
IP
0x17
0x0A
0x00
0x00
00/01
Value
0x00
Value
0x00
0x0D
Set Point
IP
0x1A
0x0A
0x00
0x00
Value
0x00
Value
0x00
0x0D
Pause Time
IP
0x1C
0x0A
0x00
0x00
Value
0x00
Value
0x00
0x0D
Energy Mode
IP
0x1D
0x0A
Value
Value
0x00
Value
0x00
0x0D
Arc Function
IP
0x1E
0x0A
0x00
0x00
Value
0x00
Value
0x00
0x0D
Max Power
IP
0x22
0x0A
0x00
0x00
Value
0x00
Value
0x00
0x0D
Max Current
IP
0x23
0x0A
0x00
0x00
Value
0x00
Value
0x00
0x0D
Max Voltage
IP
0x24
0x0A
0x00
0x00
Value
0x00
Value
0x00
0x0D
Ramp Time
IP
0x25
0x0A
0x00
0x00
Value
0x00
Value
0x00
0x0D
Target Life
IP
0x26
0x0A
0x00
0x00
Value
0x00
Value
0x00
0x0D
Pulse
reverse time
IP
0x29
0x0A
0x00
0x00
Value
0x00
Value
0x00
0x0D
Pulse
frequency
IP
0x2A
0x0A
0x00
0x00
Value
0x00
Value
0x00
0x0D
Arc Voltage
IP
0x30
0x0A
0x00
0x00
Value
0x00
Value
0x00
0x0D
ARC Density
IP
0x31
0x0A
0x00
0x00
Value
0x00
Value
0x00
0x0D
ARC Number
IP
0x32
0x0A
0x00
0x00
Value
0x00
Value
0x00
0x0D
Ignition
IP
0x33
0x0A
0x00
0x00
Value
0x00
Value
0x00
0x0D
External On
IP
0x41
0x0A
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
External Off
IP
0x42
0x0A
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
Reset
IP
0x45
0x0A
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
Limit setup
Default
IP
0x60
0x0A
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
Monitor setup
Default
IP
0x61
0x0A
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
ARC setup
Default
IP
0x62
0x0A
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
User
Regulation
Default
IP
0x63
0x0A
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
Version
Return
IP
0x70
0x0A
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
Error IP and
Alarm Code
Return
IP
0x71
0x0A
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
Page 34
31.
Byte
0 1 2 3 4 5 6 7 8 9 10
11 IP
0x90
Status1
Status2
Warning
Alarm
Voltage(V)
Current(.0A)
Power(.0Kw)
Byte
12
13
14
15
16
17
18
19
20
21
22
23
User
Command
Arc Counter(/s)
Arc Counter 0x00
Check
Sum
0x00
0x0D
Note: Check Sum Value is the summation of “1” signal calculated by byte 0 to 6.
Note: Use 9600bps, 8 data bits, no parity, 1 stop bit (9600 8-N-1)
Bit 0 1 2 3 4 5 6 7
Status1
CV MODE
CC MODE
CP MODE
HV ON
Setpoint MODE
Ignition MODE
System Warning
System
Shutdown
Bit 0 1 2 3 4 5 6 7
Status2
System Ready
OVP
OCP
OTP
OPP
Interlock
Arc Protect
AC Bus
Protect
Table 6.5 Value definition (Translate decimal to hexadecimal for utilizing)
Command
Byte3
Byte4
Byte5
Byte6
CV Mode
0 to 1000 for 0 to 1000V
CC Mode
0 to 462 for 0~4.62A
CP Mode
20 to 1500 for 10w to 1500W
A/Ri Offset
Plus: 00, Minus: 01
0 to 99 for 0 to 9.9%
A/Vo Offset
Plus: 00, Minus: 01
0 to 99 for 0 to 9.9%
A/Io Offset
Plus: 00, Minus: 01
0 to 99 for 0 to 9.9%
Set Point
1 to 10 for 1 to 10s
pause Time
2 to 100 for 200 to 10000us, Scale: 100us
Pulse frequency
0 to 80 for DC to 400k Scale:5kHz
Pulse reverse time
4 to 100 for 0.4us to 10us Scale:0.1us
Energy Mode
1 to 99999 for 1 to 99999kJ, 0: OFF
Arc Function
OFF: 0, ON: 1
Max Power
20 to 1500 for 20 to 1500W
Max Current
10 to 462 for 0.01 to 4.62A
Max Voltage
325 to 1000 for 325 to 1000V
Ramp Time
5 to 200 for 50 to 2000ms
Target Life
0 to 9999kWh for OFF to 9999kWh, 0: OFF
Arc Voltage
10 to 250 for 10 to 250
Arc Density
0 to 99 for 0 to 99 times/s
Arc Number
0 to 999 for 0 to 999 times
Ignition
10 to 19 for 1000V to 1900V
Note: Please use hexadecimal
Page 35
32.
6.5. Analog Communication Port (User)
The 15-pin female subminiature-D connector labeled “User Port” on the rear of the power supply
lets you connect with control box to control the power supply in analog signal. Definition of 15-pin
female subminiature-D connector is as follows:
Figure 6.4 Connector of user port, 15pin female subminiature-D
Table 6.6 Definition of subminiature-D connector
Pin Define
I/O
Description
1
+24V
I
External 24V is connected to the collector of photo
coupler
2
VOUT_A
O
Pin 2 shows the reader of output voltage 0 to 10 V for V = 0 to 1000 V
3
POUT_A
O
Pin 3 shows the reader of output Power 0 to 10 V for P = 0 to 1.5 kW
4
OUTPUT_ENABLE_D
I
Turn on the output power by pulling the pin low
5
XPROG_A
I
User could adjust regulation by Pin 5 0 to 10 V for P = 0 to 1.5 kW
6
COM_A
-
The return pin for VOUT_A, POUT_A, XPROG_A
7
PWRON_D
O
Pin 7 shows the on/off state of output
8
PWRON COM_D
-
The return pin for PWRON_D
9
OUTPUT_ENABLE_COM_D
-
The return pin for OUTPUT_ENABLE_D
PSU
Digital Signal Output
Digital Signal Input
Vcc
Vcc
+15V_ISO
Analog Signal Input
Vcc
+15V_ISO
Analog Signal Output
15-pin D-sub
+15V_ISO
Page 36
33.
10
MOD GREEN
O
Pin 10 is connected to the emitter of photo coupler
for MOD GREEN function
11
INTERLOCK_D
I
Pin 11 indicates the disconnection of interlock
12
INTLK COM_D
-
The return pin for INTERLOCK_D
13
NET GREEN
O
Pin 13 is connected to the emitter of photo coupler
for NET GREEN function
14
MOD AMBER
O
Pin 14 is connected to the emitter of photo coupler
for MOD AMBER function
15
NET AMBER
O
Pin 15 is connected to the emitter of photo coupler
for NET AMBER function
Note 6.5: Precaution for external connection
Port of Digital Signal Input
To control the input signal, a switch is utilized between the ports and isolated ground. Open Floating Close Grounding
Port of digital Signal output
The internal resistance of the ports is 5.1 kohm, and a pull-up power supply V
pull-up
is
required with a 5.1 kohm resistor. Initial > 0.9 * V
pull-up
Trigger < 0.5 * V
pull-up
+ 1 V
If V
pull-up
is connected to “+15V_ISO” supplied by pin18 with a 5.1 kohm resistor, initial state
would be high than 13.5 V and trigger state would be lower than 8.5 V.
Analog Signal Input Port
An isolated amplifier is utilized in the ports. The voltage level is 0 to 10 V for user to enter
the command and shall not greater than 12 V.
Analog Signal output Port
An isolated amplifier is utilized in the ports. The voltage level is 0 to 10 V for users to read
out the output values of voltage, current, and power.
Page 37
34.
Chapter 7: Operation
7.1. Local Operating Steps
Step A
Import AC voltage to input connector on rear panel. The mains voltage level should be 208±
10% V
AC
.
Step B
Turn on the breaker to start the power supply. Now, you can see “LCD Display” is working and
shows the default setting of the power supply.
Step C
Choose one operating mode from “P”, “I”, “V” button, and “LCD Display” will show the mode
you selected and change the command unit mode by mode.
Operating mode cannot be changed during power on period. It only can select while power off.
Step D
Rotate the knob to adjust the regulation level. The command (P, I or V) will change by different
mode selection in step B. The reverse time can be adjusted from 0.4us to 10.0us. The frequency
can be adjusted from 5kHz to 400kHz. When in Power mode, the command can be adjusted from 0
to 1.5 kW; when in Current mode, command can be adjusted from 0.01 to 4.62 A; when in Voltage
mode, and command can be adjusted from 131 to 1000 V
Step E
Press the “On” button to turn on the output power. While power on, user could adjust output
regulation level by “Enter” button and “knob”. “LCD Display” will show the feedback values once the
output is on.
After power on, the electric shock may lead to death or serious injury. Please read this manual
carefully and follow the instruction steps before installation and operation, otherwise an electric
shock or a fatal accident might be caused.
Step F
Press the “Off” button to turn off the output power.
Page 38
35.
Step G
If the power supply is kept off for a while, please remove AC power cord.
Don’t touch the load before grounding it. And make sure the electricity is fully discharged by meter.
7.2. D-sub Operating Steps
Example : CP mode 1.5 kW output
Operating steps:
1. Set the front panel => Interface Setup => Communnication Setup => D-sub.
2. Command Level: Set +10 V input to pin 5 for 1.5 kW Command.
3. Enable On: Connect pin 4 to pin 9
4. Enable Off: Remove pin4 from pin 9.
7.3. RS-232 Operating Steps
1. Set the front panel => Interface Setup => Communnication Setup => RS-232.
2. Follow the protocol defined in chapter 6.4 to operating.
3. Set Pulse reverse time and Pulse frequency
Remote to PSU
Byte
0 1 2 3 4 5 6 7 8 9 10
IP
Command
Data1
Data2
Check Sum
Termination
Byte
H-Byte
L-Byte
H-Byte
L-Byte
H-Byte
L-Byte
0x00
Byte
0x00
0x0D
Pulse
reverse time
IP
0x29
0x00/01
0x00
0x00
Value
0x00
Value
0x00
0x0D
Pulse
frequency
IP
0x2A
0x00/01
0x00
0x00
Value
0x00
Value
0x00
0x0D
4. Set Operating mode
Remote to PSU
Byte
0 1 2 3 4 5 6 7 8 9 10
IP
Command
Data1
Data2
Check Sum
Termination
Byte
H-Byte
L-Byte
H-Byte
L-Byte
H-Byte
L-Byte
0x00
Byte
0x00
0x0D
CV Mode
IP
0x11
0x00/01/02
0x00
0x00
Value
0x00
Value
0x00
0x0D
CC Mode
IP
0x12
0x00/01/02
0x00
0x00
Value
0x00
Value
0x00
0x0D
CP Mode
IP
0x13
0x00/01/02
0x00
0x00
Value
0x00
Value
0x00
0x0D
5. Power on and power off
Page 39
36.
Remote to PSU
Byte
0 1 2 3 4 5 6 7 8 9 10
IP
Command
Data1
Data2
Check Sum
Termination
Byte
H-Byte
L-Byte
H-Byte
L-Byte
H-Byte
L-Byte
0x00
Byte
0x00
0x0D
External On
IP
0x41
0x00/01/02
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
External Off
IP
0x42
0x00/01/02
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
7.4. RS-485 Operating Steps
1. Set the front panel => Interface Setup => Communnication Setup => RS-485.
2. Follow the protocol defined in chapter 6.4 to operating.
3. Set Pulse reverse time and Pulse frequency
Remote to PSU
Byte
0 1 2 3 4 5 6 7 8 9 10
IP
Command
Data1
Data2
Check Sum
Termination
Byte
H-Byte
L-Byte
H-Byte
L-Byte
H-Byte
L-Byte
0x00
Byte
0x00
0x0D
Pulse
reverse time
IP
0x29
0x00/01
0x00
0x00
Value
0x00
Value
0x00
0x0D
Pulse
frequency
IP
0x2A
0x00/01
0x00
0x00
Value
0x00
Value
0x00
0x0D
4. Set Operating mode
Remote to PSU
Byte
0 1 2 3 4 5 6 7 8 9 10
IP
Command
Data1
Data2
Check Sum
Termination
Byte
H-Byte
L-Byte
H-Byte
L-Byte
H-Byte
L-Byte
0x00
Byte
0x00
0x0D
CV Mode
IP
0x11
0x00/01/02
0x00
0x00
Value
0x00
Value
0x00
0x0D
CC Mode
IP
0x12
0x00/01/02
0x00
0x00
Value
0x00
Value
0x00
0x0D
CP Mode
IP
0x13
0x00/01/02
0x00
0x00
Value
0x00
Value
0x00
0x0D
5. Power on and power off
Remote to PSU
Byte
0 1 2 3 4 5 6 7 8 9 10
IP
Command
Data1
Data2
Check Sum
Termination
Byte
H-Byte
L-Byte
H-Byte
L-Byte
H-Byte
L-Byte
0x00
Byte
0x00
0x0D
External On
IP
0x41
0x00/01/02
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
External Off
IP
0x42
0x00/01/02
0x00
0x00
0x00
0x00
0x00
Value
0x00
0x0D
Page 40
37.
Chapter 8: Maintenance
Alarm Condition
Code
Description
Suggested Action
HW Fault M1
M1F
Hardware error from the left module
Take all safety precaution, and then check if the mains voltage that is in specification. Turn on the output power with a dummy load to ensure if it is under
normal operation.
HW Fault M2
M2F
Hardware error from the right
module
Take all safety precaution, and then check if the mains voltage that is in specification. Turn on the output power with a dummy load to ensure if it is under
normal operation.
SW OVP
OV
Output over voltage
Take all safety precaution, and then check if the mains voltage that is in specification. Turn on the output power with a dummy load to ensure if it is under
normal operation.
SW OCP
OC
Output over current
Take all safety precaution, and then check if the mains voltage that is in specification. Turn on the output power with a dummy load to ensure if it is under
normal operation
SW OPP
OP
Output over power
Take all safety precaution, and then check if the mains voltage that is in specification. Turn on the output power with a dummy load to ensure if it is under
normal operation.
Contactor Interlock
10
Uninstallation of contactor pin in D-
sub connector
Check if contactor pin in D-sub
connector is short.
Output Interlock
11
Uninstallation of output cover
Check if output cover is
correctly installed.
Communication Loss
15
Error from internal communication
Check if the bus between panel and control card is correctly
connected.
Fan1 Error
17
Error from the left fan
Check if the cable between fan in the left module 1 and control
card is correctly connected.
Fan2 Error
18
Error from the right fan
Check if the cable between fan in the right module 2 and control
card is correctly connected.
Bus UVP
20
Input voltage is under operation
range
Take all safety precaution, and then check if the mains voltage
that is in specification.
Bus OVP
21
Input voltage is over operation range
Take all safety precaution, and then check if the mains voltage
that is in specification.
Set Point Monitor
23
Error while output fails to reach
setting parameter within setting time
Take all safety precaution, and then turn on the output power with a dummy load to ensure if
it is under normal operation.
Page 41
38.
Energy Mode Monitor
24
Power off while output reaches
setting Energy
Monitor Setting is end. Press and hold “OFF” button with 10
second to clear error.
Warning Condition
Code
Description
Suggested Action
Output Limit
Limit
Output is over setting parameter
N/A
Loading...