Delta DTA4848, DTA7272, DTA4896, DTA9648, DTA9696 Instruction Sheet

- 1 -
2013/03/27
Series Temperature Controller
Instruction Sheet
Thank you very much for purchasing DELTA A Series. Please read this instruction sheet before using your A series to ensure proper operation and please keep this instruction sheet handy for quick reference.
Precaution
DANGER! Caution! Electric Shock!
1. Do not touch the AC terminals while the power is supplied to the controller to prevent an electric shock.
2. Make sure power is disconnected while checking the unit inside.
3. The symbol indicates that this Delta A Series Temperature Controller is protected throughout by DOUBLE INSULATION or REINFORCED INSULATION (equivalent to Class II of IEC 536).
WARNI NG!
This controller is an open-type temperature controller. Make sure to evaluate any dangerous application in which a serious human injury or serious property damage may occur.
1. Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, width is 7.0mm, hole diameter 3.2mm). Screw size: M3 x 6.5 (With 6.8 x 6.8 square washer). Recommended tightening torque: 0.4 N.m (4kgf.cm). Applicable wire: Solid/twisted wire of 2 mm
2
, 12AWG to 24AWG.
Please be sure to tighten them properly.
2. Do not allow dust or foreign objects to fall inside the controller to prevent it from malfunctioning.
3. Never modify or disassemble the controller.
4. Do not connect anything to the “No used” terminals.
5. Make sure all wires are connected to the correct polarity of terminals.
6. Do not install and/or use the controller in places subject to:
Dust or corrosive gases and liquid.
High humidity.
High radiation.
Vibration and shock.
High voltage and high frequency
7. Must turn power off when wiring and changing a temperature sensor.
8. Be sure to use compensating wires that match the thermocouple types when extending or connecting the thermocouple wires.
9. Please use wires with resistance when extending or connecting a platinum resistance thermometer (RTD).
10. Please keep the wire as short as possible when wiring a platinum resistance thermometer (RTD) to the controller and please route power wires as far as possible from load wires to prevent interference and induced noise.
11. This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity, dripping water, corrosive materials, airborne dust and electric shock or vibration.
12. Please make sure power cables and signals from instruments are all installed properly before energizing the controller, otherwise serious damage may occur.
13. Please do not touch the terminals in the controller or try to repair the controller when power is applied to prevent an electric shock.
14. Wait at least one minute after power is disconnected to allow capacitors to discharge, and please do not touch any internal circuit within this period.
15. Do not use acid or alkaline liquids for cleaning. Please use a soft, dry cloth to clean the controller.
16. This instrument is not furnished with a power switch or fuse. Therefore, if a fuse or power supply switch is required, install the protection close to the instrument.
Recommended fuse rating: Rated voltage 250 V, Rated current 1 A. Fuse type: Time-lag fuse Note: This controller does not provide overcurrent protection. Use of this product requires that suitable overcurrent protection device(s)
must be added to ensure compliance with all relevant electrical standards and codes. (Rated 250 V, 15 Amps max). A suitable disconnecting device should be provided near the controller in the end-use installation.
- 2 -
Ordering Information
c
Series DTA: Delta A Series Temperature Controller
d
Panel Size (W × H)
4848: 1/16 DIN W48 × H48mm 4896: 1/8 DIN W48 × H96mm 7272: W72 × H72mm
9648: 1/8 DIN W96 x H48 9696: 1/4 DIN W96 × H96mm
e
Output Selection
R: Relay output, SPDT (SPST: 1/16 DIN size), 250VAC, 5A V: Voltage Pulse output, 14V+10% ~ -20% (Max. 40mA) C: Current output, 4 ~ 20mA
f
Communication (Optional)
0: No interface 1: RS-485
g
Current Transformer (CT) Function
(Optional)
None: No CT function (Current transformer is not provided) T: Current transformer is provided (only DTA7272 series support this function)
Display, LED & Pushbuttons
: Function key.
1. Press this key to select the desired function mode.
2. Press this key to confirm a setting value.
: Mode key. Press this key to set parameters within each function mode.
o
C, oF : Temperature unit LEDs. oC LED lights when this parameter is configured for Celsius and oF LED lights if configured for Fahrenheit.
ALM1 / ALM2 : Alarm output LED. The ALM1 / ALM2 LED lights when Alarm 1 or Alarm 2 output is ON.
: Up key. Press this key to increase values displayed on the SV display. Hold down this key to speed up the incremental action.
: Down key. Press this key to decrease values displayed on the SV display. Hold down this key to speed up the decrements.
Specifications
Input voltage 100 ~ 240VAC 50/60Hz
Operation voltage range 85% to 110% of rated voltage
Power consumption 5VA max.
Display method
7-segment digit LED Display Process value (PV): Red color, Set point (SV): Green color
Thermocouple: K, J, T, E, N, R, S, B, U, L, Txk
Sensor type
3-wire Platinum RTD: Pt100, JPt100 Copper resistor: Cu50
Control mode PID, ON/OFF control or Manual tuning
Relay output:(resistive load): SPDT (SPST: 1/16 DIN size), 250VAC, 5A
Voltage Pulse output: DC 14V, Max. load current 40mA
Control output
Current output: 4 to 20mADC (Load resistance: Max. 600Ω)
Display accuracy 0.1% of measuring range
Sampling rate 500 msec/per scan
Vibration resistance 10 to 55Hz, 10m/s2 for 10min, each in X, Y and Z directions
Shock resistance Max. 300m/ s2, 3 times in each 3 axes, 6 directions
Ambient temperature
0
o
C ~ +50oC
PV Display: to display the process value or parameter type.
SV Display: to display set point, parameter operation read value, manipulated
variable or set value of the parameter.
AT: flashes when the Auto-tuning operation is ON.
OUT: lights when the output is ON.
- 3 -
Storage temperature
-20
o
C ~ +65oC
Relative humidity 35% ~ 80% (non-condensing)
Altitude 2,000m or less
Installation environment Installation Category 33, Pollution Degree 2. Conforming to EN61010-1
Panel protection level IP65
Parameters List
1. Operation Mode: Perform per the settings of related control parameters
LED Display Explanation Default
RUN/STOP: Control setting begins. Run (
) or Stop ( ) mode on the SV display.
RUN
ALARM1 HIGH: Upper-limit alarm 1
4.0
o
C
ALARM1 LOW: Lower-limit alarm 1
4.0
o
C
ALARM2 HIGH: Upper-limit alarm 2
4.0
o
C
ALARM2 LOW: Lower-limit alarm 2
4.0
o
C
Setting lock: Lock 1 (
), Lock 2 ( ) or OFF ( ) on the SV display. Lock 1 mode can lock all
settings and Lock 2 mode only can lock others than SV value. When OFF mode is selected, the Lock
function will be OFF. If you press
and key simultaneously, the “Lock” status can be released and
the controller will be back to the previous display.
OFF
OUT: Output value display and output value adjustment in manual tuning control (This function is not available in ON/OFF control or Auto-tuning setting)
0
CT: In case of using an external current transformer (CT), the controller displays the current value being measured by CT, if the control output is ON
Read only
2. Regulation Mode: Set the control parameters
LED Display Explanation Default
AT: Auto-tuning setting. When AT key is set to ON (
), the execution of the PID auto-tuning function is
automatically started. (PID control)
OFF
P: Proportional Band (PID control) 47.6
I: Integral Time (PID control) 260
D: Derivative Time (PID control) 41
PdoF: Offset output when P or PD control function is ON. (PID control and Ki=0) 0
ioF: Default value of integral volume when PID control function is ON and integral time constant is not equal to 0(zero). AT can automatically set this parameter. (PID control and Ki≠0)
0
HTS: Set Heating hysteresis when ON/OFF control function is ON. 0
CTS: Set Cooling hysteresis when ON/OFF control function is ON. 0
HTPD: PID heating control cycle setting (PID control)
CLPD: PID cooling control cycle setting (PID control)
Output
Selection:
V: 4 sec.
R: 20 sec.
TPOF: Regulate temperature deviation value 0
CRHI: Regulate 20mA output deviation value (1unit = 0.1mA) 0
CRLO: Regulate 4mA output deviation value (1unit = 0.1mA) 0
3. Initial Setting Mode: Initial settings of the controller and communication parameters
LED Display Explanation Default
INPUT: Select input temperature sensor type (Please refer to the contents of the “Temperature Sensor Type and Temperature Range” for detail)
PT2
UNIT: Temperature display unit,
o
C ( ) and oF ( )
o
C
T-HIGH: Upper limit for temperature range 500.0
- 4 -
LED Display Explanation Default
T-LOW: Lower limit for temperature range -20.0
CONTROL: Control method setting on the SV display: PID (
), ON/OFF control ( ), or manual
tuning (
)
PID
SWITCH: Select Heating (
) or Cooling ( ) action
HEAT
AL1 SET: Alarm 1 setting (See explanations in “Alarm Outputs” section.) 0
AL2 SET: Alarm 2 setting (See explanations in “Alarm Outputs” section.) 0
C SELECT : ASCII, RTU communication formats selection (Displayed when using serial communication)
ASCII
C WE: Write-in function disable/enable (Displayed when using serial communication)
OFF
C NO: Address setting (Displayed when using serial communication)
1
BPS: Baud rate setting (Displayed when using serial communication)
9,600
LENGTH: Data length setting (Displayed when using serial communication)
7
PARITY: Parity bit setting (Displayed when using serial communication)
E
STOP BIT: Stop bit setting (Displayed when using serial communication)
1
Note: Alarm values should be set in the initial setting mode so AL1H, AL1L, AL2H and AL2L would display in operation mode.
Operation
There are three modes of operation: operation, regulation and initial setting. When power is applied, controller gets into the operation mode.
Press the
key to switch to regulation mode. If the key is pressed for more than 3 seconds, controller will switch to the initial setting
mode. Pressing the
key while in the regulation mode or initial setting mode, forces the controller to return to the operation mode.
PV/SV: Sets the temperature set point and displays the temperature process value. Use the
and keys to set the temperature set
point.
Setting method: While in any function mode, press the
key to select the desired function and use the and keys to change
settings. Press
key to save the changes.
The next flow chart shows how to switch for settings and internal functions:
Regulation Mode Operation Mode Initial Setting Mode
Auto-tuning
(In PID control and RUN mode)
Press
V
Use to set temperature of
target
Press
V
Set input type
Press
V
Set PID PB
(In PID control)
Press
V
Control setting RUN or STOP
Press
V
Set temperature unit
Press
V
Set PID Ti
(In PID control)
Press
V
Upper-limit alarm 1
(This parameter is available only when ALA1 function enables)
Press
V
Set upper-limit of temperature range
Press
V
Set PID Td
(In PID control)
Press
V
Lower-limit alarm 1
(The parameter is available only when ALA1 function enables)
Press
V
Set lower-limit of temperature range
Press
V