Delta 600 User Manual

Characteristics
DELTA 600 is made up of a receiver unit and a technical control unit.
Installation
Positioning options
The receiver must be placed in a high position. The receiver antenna must be kept away from conductors (electrical cables, electrical switchboard, metallic surface).
Mountings
To mount the unit on the wall, it must be separated from its base.
To do this, unscrew the clamp screw as shown opposite. Once separated from the unit, the base must be fixed to the wall with screws and plugs or on a flush-mounted box (distance between centres 60 mm) using the holes labelled ➊.
To do this:
Unscrew the screw
to remove the terminal box cover ➎.
Temporary partitions, labelled , are provided
to make room for the connection wire if needed.
- Connect the connection wires (see section 3).
- Replace the terminal box cover and secure it with the screw ➋.
Position the unit on the support by first inserting the tabs , then by pushing it until it is securely fastened to the support.
3.5 Mounting the antenna
Slide the flexible wire into the tube, then push the tube in
as far as it will go.
Technical unit
• 230 V, 50 Hz power supply, ±10%
• Class II insulation
• Power consumption: 4 VA
• 6 power-supplied operating contact output, 1A, 250V (valves)
• 1 auxiliary contact output, 5 A, 250 V (burner, circulator, etc.)
• 1 fixed-wire connection bus with the receiver unit (DELTA 600 BR)
• Dimensions: 80 x 230 x 65 mm
Receiver unit
• TBTS 24 Volt power supply provided by the technical unit
• Fixed-wire connection bus with the technical unit (SYT 6/10-type 2 pair telephone cable with shield and continuity wire, 5 metres max.)
• Receiver frequency: 868 MHz (standard 300 220)
• Radio range 100 to 300 metres outside depending on the linked equipment (the range can be altered depending on the installation conditions and the electromagnetic environment)
• Flexible antenna that slides into its support
• 2 buttons to configure outputs
• Wall mounted
• Dimensions: 128 x 85 x 31 mm
• Protection index: IP 30
• Operating temperature: 0 to +40°C
• Storage temperature: -10 to +70°C
1
2
2700621 Rev.3
Connections
Switch off the mains power before handling the device.
3
The diagrams provided are simplified for greater clarity. The protective devices and other accessories required by the standards are not illustrated.
- Standard UTE C15-100 and good practice must be complied with.
- Connected or nearby equipment must not generate excessive interference (directive 89/336/EEC).
Technical unit connecting terminal box
Connection between the receiver unit and the technical unit
l
Fixed-wire connection bus (SYT 6/10-type 2 pair telephone cable with shield and continuity wire, 5 metres max.) The continuity wire is connected to terminal 2 of the technical unit.
Product compliant with the requirements of directives
89/336/EEC (electromagnetic compatibility) and 73/23/EEC
modified 93/68/EEC (low voltage)
DELTA 600
Control receiver for 6-channel
heating/air-conditioning
control system
Receiver
YES
NO
Option 1 Centralized control Delta 600 COM
Programming
zone
Programming
zone
2
Delta 600 TH Transmitters
Delta 600
Programming
zone
3
Programming
zone
456
Programming
zone
Programming
Delta 600 TH Transmitters
zone
pro.deltadore.com
E-mail : deltadore@deltadore.com
DELTA DORE TALCO - Bonnemain - 35270 COMBOURG
Technical unit
1
2
3
456
OK
ZS
....
16
ZS
4
Receiver unit
Solenoid
valve control
5
2
To
8
3
receiver
unit
2721159 Rev. 2
Power supply 230V 4VA
1 2
7
3
6
50Hz / 60 Hz
BUS
24V
N
L
Change-over
power supply
1 A
1 A
1 A
1 A
Max.
Max.
Max.
Max.
1 A
Max.
7854 6 9 10111213141516171819202122
V1 V2 V3 V4 V5 V6
Val ve
24 V to 230 V
1 A
Max.
5 A
Max.
Auxiliary
contact
(Burner,
circulator,
etc.)
Receiver
unit
8 7 6
1 2 3
Technica unit
Starting up
Configuring the technical unit outputs
Remove the receiver unit from its base to access the configuration switches.
SW1: Type of relay control (1A outputs)
ON: Normally closed OFF: Normally open
This selection affects all 6 relay outputs simultaneously.
SW2: Burner or circulator selection (output 5A)
ON: Circulator (activates SW3 function) OFF: Burner
SW3: Anti-seizing function of the circulator (active if the SW2 selection is ON)
ON: Anti-seizing OFF: No anti-seizing
SW4: Keep last valve controlled open
(for constant water circulation in the hydraulic circuit).
ON: Keep last valve controlled open OFF: Authorizes closure of last valve controlled
SW5 to SW8: Solenoid valve opening times
Selection to be made according to the solenoid valves' technical characteristics.
SW9: Control time base
ON: 10 minutes (recommended for air-flow systems)
OFF: 20 minutes (best for hot-water radiant floors)
SW10 to SW11: Limit the cooling operation percentage
Limit according to the installation's cooling over-power.
SSW12: Not used
Technical control unit operation
LThe auxiliary contact is closed when one of the transmitters is in need of heat or cold.
Cooling mode operation (air-flow system)
When change-over is activated (Cooling mode), the Economy set-point temperature
on the thermostats must be higher than the Comfort set-point temperature .
Radio receiver operation
The 2 Heating and Cooling controls are calculated simultaneously. The LEDs on the receiver unit's front side allow either Heating or Cooling controls to be viewed.
Selection method:
from normal display, press the 2 buttons for 5 sec. (the 6 LEDs flash quickly
indicating "control view selection" mode):
• for heating periods (change-over open), use the browsing button “1...6, COM” to select the red LED
(Com).
The unit displays the Heating control.
• for cooling periods (change-over closed), use the browsing button “1...6, COM” to select the green
LED (OK).
The unit displays the Cooling control.
Use the button to exit this mode (automatic exit after 2 min. of inactivity).
Radio configuration / reconfiguration
Configuration mode lets you couple a transmitter (Thermostat Delta 600 TH, Delta 600 COM centralized control) with the Delta 600 BT receiver (no conflict possible with neighbouring installations). It is also used to check the radio transmission.
On the transmitter, turn the knob to the position. Press (~3 sec.) until CnF is displayed.
The transmitter sends its information to the receiver.
On the receiver, push “1...6, COM” repeatedly until the LED of the relative channel flashes.
If the green LED (OK) is on steady, the receiver channel is already configured. To reconfigure it (with another transmitter, for example), press the button for 10 sec. until the green "OK" LED flashes slowly, then release it. Press the button again.
The green "OK" LED comes on steady; the receiver channel has been "reconfigured".
• If the green LED (OK) is flashing slowly, the receiver channel is not configured.
Press the button.
The green "OK" LED comes on steady. The receiver channel is configured.
On the transmitter, press to exit configuration mode.
Radio transmission check
On the transmitter, turn the knob to the position. Press (~3 sec.) until tESt is displayed.
The transmitter sends its information to the receiver.
Transmission is correct if, on the receiver, the "OK" LED andthe LED of the relative channel” flash together.
Press the button to exit the radio transmission test mode.
Problems?
A channel's red LED flashes (the receiver has not received information from the transmitter of the relevant channel for more than an hour).
1) Check the transmitter batteries.
2) Go to transmission test mode.
- If the "OK" LED and "the LED of the relative channel" are not flashing together each time information is received, move the transmitter.
- If the problem persists, reconfigure the units.
Note:
In the event of malfunction, pressing the button on the receiver changes the status of the selected channel (exemption) until the next transmission from the thermostat (which continues to have priority). For an override, the red LED flashes.
5.7
5.6
5.5
5.4
5.3
5.2
5.1
5
Description
The
Delta 600
control receiver is made up of 2
units:
- a receiver unit that receives information from the transmitters (Delta 600 TH programmable thermostats, Delta 600 COM centralized control) by radio waves
- a technical unit, connected to the receiver unit by a fixed-wire bus, which acts as a power interface for controlling the installation's valves.
Delta 600
will manage up to 6 hot-water heating or
air-conditioning outputs.
Delta 600
is designed for:
hot-water heating (underfloor or radiators)
• air-flow air-conditioning
• cooling floors equipped with dewpoint control
2 operating modes:
Current mode:
- Channel status display
- Display of the presence or absence of a
centralized control
Configuration mode:
- Display of whether or not a channel is configured
- Manual activation of the channels in case of
a fault
Because of changes in standards and equipment, the characteristics given in the text and the illustrations of this document are not binding unless confirmed by Delta Dore.
4
Unconfiguring a channel
To select a channel to unconfigure, press “1...6, COM” repeatedly on the receiver until the LED of the relevant
channel flashes. Hold the button down until the green "OK"
LED flashes (~30 sec.). Press the “1...6, COM” repeatedly until you exit
the mode.
Unconfiguring all channels
On the receiver, from the current operating
mode, press the button and hold it down until the green "OK" LED flashes (~60 sec.). The unit is now unconfigured.
Normal operation LED
Control status of the programmable radio thermostats (Delta 600 TH)
Presence of the Delta 600 COM control unit
Scrolling button
Configuration button
ON
123456789101112
Valve opening delay
ON
0 sec.
123456789101112
ON
30 sec.
123456789101112
ON
1min.
123456789101112
1min. 30s.
2min. sec.
ON
123456789101112
ON
2min.
123456789101112
ON
123456789101112
3min.
3min. 30sec.
4min.
4min. 30sec.
5min.
5min. 30sec.
ON
123456789101112
ON
123456789101112
ON
123456789101112
ON
123456789101112
ON
123456789101112
ON
123456789101112
6min. 30sec.
7min. 30sec.
ON
6min.
123456789101112
ON
123456789101112
ON
7min.
123456789101112
ON
123456789101112
56789101112
No limit
75% limit
ON
12345678910 11 12
ON
12345678910 11 12
50% limit
25% limit
ON
12345678910 11 12
ON
12345678910 11 12
Loading...
+ 4 hidden pages