Delta 20-120kVA User Manual

NH Plus series
Three phase 20-120kVA
Uninterruptible Power Supply
NH Plus belongs to “Delta High UPS” product series. Based on the patented technology, It is designed for high efficiency, high reliability and cost-effectiveness requirement.
As fast changing in the data center and IT frame, you need more flexibility for future power needs. NH Plus combines scalability, hot-swappable and manageability as your business grows.
Features and benefits
• Double conversion and IGBT topology.
• High input power factor (pf > 0.99) and low harmonic distortion (iTHD < 3%).
• Overall high efficiency (> 94%), savings in the operating cost.
• N+X parallel redundancy and expansion.
• Easy parallel link (up to 4 units) without extra hardware needed.
• Modular design provides easy and fast maintenance.
• Dual mains input increasing the availability by two separate power source.
• Smart fan speed control to reduce the noise.
• Built-in manual and static bypass switch for maintenance.
• Compatible with generator installation.
Data Center
Security
T elecom
Labs
Industry
Medical
Industry
Network
Metro
Scalable And Hot-swappable
NH Plus series
Three phase 20-120kVA
Technical Specifications
Model NHP20 NHP40 NHP60 NHP80 NHP100 NHP120
Power Rating – kVA 20 40 60 80 100 120
Power Rating - kW 16 32 48 64 80 96
Rating Voltage V 380/220 , 400/230 , 415/240 (3phase, 4-wire plus gr ound)
Voltage Range V 208~477(line-line) / 120 ~276 (line-neutral) *
Input
Input Current Harmonic
Power Factor > 0.99
Frequency Hz 50 or 60 ± 5
Voltage V 380/220 , 400/230 , 415/240 (3phase, 4-w ire plus ground)
Voltage Harmonic < 3 (linear load)
Output
Voltage Regulation Static : ± 1 ; Dynamic : ± 7 (10% ~ 90% linear load)
Frequency Hz 50 or 60
Frequency Regulation
Overload
Display
LED UPS status : Normal、Bypass、Backup、Fault
LCD
Interface
Stand ard
Optional Accessories
Confor-
mance
Safety & EMC CE, EN62040-1-1, EN62040-2 (Class A)
< 3 (full load)
Hz ± 0.05 (interior oscillator)
Hz ± 5 (synchronized), adjustable
Input/OutputBypassInverterFrequencyLoading and battery voltageCurrent
RS232 x 1, Smart Slot x 2, Dry contact output x 6, Contact input x 2, Parallel port x 1,
SNMP card, Modbus card, R elay I/O control card, Environmental monitoring box,
Battery cabinet temperature kit (For Delta battery cabinet), Battery cabinet status cable
125% : 10m inutes ; ≤150% : 1minute
UPS abnormal message and intelligent self diagnosis
Battery cabinet temperature x 4
SNMP+ 5 ports hub, Batter y cabinet temperature sensor,
Mimic LCD Display
20-80kVA + Battery Cabinet
Parallel Redundancy Up to 4 cabinets
Emergency Power Off Local and remote
Others
SRAM Event Log 500 records
Battery Temperature Compensation
AC-Start Yes
Battery-Start Yes
Efficiency
Transfer Time ms 0
Overall
Temperature 0 ~ 40
Relative Humidity 90 (non-condensing)
Noise (at one meter) dBA 65 68 70 70 72 73
Dimension
(WxD xH)
Weight kg 170 200 230 260 320 350
* Lower range 208~300 / 120~173Vac is acceptable under 70~100% loading condition. ** EBC: External battery cabinet. All specifications are subject to change without prior notice.
Normal 94
ECO 97
UPS 520x910x1165 520x975x1695
EBC**
Optional
mm
520x850x1165 (26Ahx40pcs) 520x975x1695 (40A hx40pcs)
100-120kVA +
Battery Cabinet
Delta delivers 0.6~4000kVA full-scale UPS
solutions to fulfill all your needs