Dell J730N User Manual [en, ru, de, es, fr]

Dellt Online Rack UPS
3750W and 4200W
Getting Started With
Your System
Démarrarer avec Votre Système
Erste Schritte Mit Ihrem System
Начало работы c вашей системой
Inicio de su sistema
사용자의 시스템 시작하기
はじめに システムについて
www.dell.com | support.dell.com
系統使用 入門指南
K804N, H952N, J730N, K805N
J739N
Dellt Online Rack UPS
3750W and 4200W
Getting Started
With Your System
www.dell.com | support.dell.com
K804N, H952N, J730N, K805N
J739N
Notes and Warnings
NOTE: A NOTE indicates important information that helps you make better use of your software.
DANGER: A DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
WARNING: A WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or
injury.
CAUTION: A CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury or in property damage incidents.
DANGER: Observe the following instruction to help prevent an imminently hazardous situation which, if not
avoided, will result in death or serious injury:
S This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY.ThereareNO USER SERVICEABLE PARTS
inside the UPS.
Information in this document is subject to change without notice. E 2009 Dell Inc. All rights reserved.
Reproduction in any manner whatsoever without the written permission of Dell Inc. is strictly forbidden.
Trademarks used in this text: Dell and the DELL logo are trademarks of Dell Inc.
Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Dell Inc. disclaims any proprietary interest in trademarks and trade names other than its own.
July 2009
System Features
Providing outstanding performance and reliability, the UPS's unique benefits include:
S Online UPS design with pure sine wave output. The UPS filters and regulates incoming AC power
and provides consistent power to your equipment without draining the battery.
S True online double-conversion technology with high power density, utility frequency
independence, and generator compatibility.
S Selectable High Efficiency mode of operation. S 4U size that fits any standard 48 cm (19”) rack. S Start-on-battery capability for powering up the UPS even i f utility power is not available. S Extended runtime with an optional Extended Battery Module (EBM). S Emergency shutdown control through the Remote Emergency Power-off (REPO) ports. S Two standard communication ports (USB and DB-9 serial port). S Optional Dell Network Management Card with enhanced communication capabilities for
increased power protection and control.
S Advanced power management with the Dell UPS Management Software for graceful shutdowns
and power monitoring.
S Sequential shutdown and load management through separate receptacle groups called load
segments.
S Firmware that is easily upgradable without a service call. S Backed by worldwide agency approvals.
System Features
|
3
Finding Information
CAUTION: The Safety, Environmental, and Regulatory Information document provides important safety and
regulatory information.
What are You Looking For?
S The user's guide for my UPS S The user's guide for the Dell Network Management
Card
S Dell UPS Management Software
Find It Here
Dell UPS Disc
NOTE: Documentation and software updates can be
found at
S Specifications S How to configure UPS settings S How to troubleshoot and solve problems S How to install REPO control S Safety instructions S Regulatory information S Recycling information
S Warranty information S Terms and Conditions (U.S. only) S End User License Agreement
S Support information Dell Support Website — support.dell.com
Dell UPS User's Guide
The user's guide is available on the Dell UPS disc and on support.dell.com.
Safety, Environmental, and Regulatory Information
Dell Warranty and Support Information
support.dell.com.
NOTE: Select your region or business segment to view
the appropriate support site.
|
4
Finding Information
Installation and Startup
CAUTION: Before performing the procedures in this document, read and follow the safety instructions and
important regulatory information in your Safety, Environmental, and Regulatory Information document.
This section describes the steps to set up your system for the first time.
Unpacking the System
1 Open the outer carton and remove the accessories packaged with the cabinet.
Installation and Startup
|
5
Lifting the Cabinet
CAUTION: The cabinet is heavy (66 kg/145.5 lb). Lifting the cabinets into the rack requires a minimum of two
people.
1 Withonepersononeachside,carefullyliftthecabinet out of the outer carton using the handles
on the cardboard and set it on a flat, stable surface.
2 Discard or recycle the packaging in a responsible manner, or store it for future use.
|
6
Installation and Startup
Identifying the UPS
This section shows a front and rear panel of the Dell Online Rack UPS.
On/Off Button
Scroll Button (Up or Back)
LCD Panel
Select Button
Figure 1. The Dell Online Rack UPS Front Panel
Two IEC 320-C19 and Two L6-20 Receptacles
(Load Segment 2)
Output Circuit Breaker
Scroll Button (Down or Forward)
RS-232 Port
USB Port
UPS Communication Bay
REPO Ports
Ground Screw
2m, L6-30P Power Cord
Figure 2. 3750W, 208V Rear Panel
One L6-30 Receptacle (Load Segment 1)
EBM Connector
Installation and Startup
|
7
Two IEC 320-C19 Receptacles
(Load Segment 2)
Output Circuit Breaker
USB Port
RS-232 Port
UPS Communication Bay
REPO Ports
Ground Screw
Input Terminal Block
Figure 3. 3750W, 230V Rear Panel
One L6-30 Receptacles
(Load Segment 2)
Output Circuit Breaker
Input Terminal Block
Four IEC 320-C19 and Two L6-20 Receptacles
(Load Segment 1)
Eight IEC 320-C13 Receptacles (Load Segment 1)
RS-232 Port
USB Port
Ground Screw
EBM Connector
UPS Communication Bay
REPO Ports
EBM Connector
Figure 4. 4200W, 208V Rear Panel
|
8
Installation and Startup
Four IEC 320-C19 Receptacles
Output Circuit Breaker
(Load Segment 1)
USB Port
RS-232 Port
UPS Communication Bay
REPO Ports
Input Terminal Block
Figure 5. 4200W, 230V Rear Panel
Six IEC 320-C13 Receptacles (Load Segment 2)
Ground Screw
EBM Connector
Installation and Startup
|
9
Rackmount Setup
CAUTION: The cabinet is heavy (66 kg/145.5 lb): 1) Dell strongly recommends to remove the battery tray from
the UPS before lifting. 2) Lifting the cabinets into the rack requires a minimum of two people.
CAUTION: Removing the batteries should be performed or supervised by personnel knowledgeable about
batteries and the required precautions. Keep unauthorized personnel away from batteries.
Removing the Battery Retaining Bracket
1 Loosen the thumbscrew on the battery retaining bracket and remove.
|
10
Installation and Startup
Removing the Battery Trays
2 Pull the battery trays using the plastic tabs and remove the battery trays.
Installation and Startup
|
11
Installing the Rails
NOTE: The instructions are the same for square-hole racks and unthreaded, round-hole racks. The rails fit both
rack styles. The square-hole rack is shown in the illustrations.
3 Select the proper holes in the rail for positioningtheUPSinthedesiredlocationintherack.
The rails should be located at the bottom of the 4U space allocated for the UPS or 3U for the EBM.
4 Position the end of the left and right rails labeled FRONT facing inward.
|
12
Installation and Startup
5 Attach the rails to the rack:
Engage the back end of the rail until it fully seats on the vertical rack flange and the hook latch locks in place.
Pull the rail toward the front.
Push the front end of the rail until it fully seats on the vertical rack flange and the hook latch locks in place.
Installing the Cabinet
6 Slide the cabinet into the rack. Repeat for any additional cabinets.
Installation and Startup
|
13
Securing the Cabinet
7 Secure the front of the cabinet to the rack using the thumbscrews on the mounting brackets.
Tighten by hand; do not use power tools. Repeat for any additional cabinets.
Installing the Battery Tray
8 Install the UPS battery trays.
|
14
Installation and Startup
Replacing the Battery Retaining Bracket and Connecting the Internal Battery Connectors
9 Replace the battery retaining bracket.
10 Tighten the thumbscrew.
Torque the screw to 0.7 Nm (6.2 lb in).
NOTE:
A small amount of arcing may occur when connecting the batteries. This is normal and does not damage
the unit or present any safety concern.
11 Connect the internal battery connectors and attach to the battery retaining bracket between the
two studs.
|
Installation and Startup
15
Installing the UPS Front Cover
12 Install the UPS front cover.
Connecting the Equipment
13
If you plan to use Dell UPS Management Software, connect your computer to the USB port using the supplied cable.
14 If your rack has conductors for grounding or bonding of ungrounded metal parts, connect the
ground cable (not supplied) to the ground bonding screw.
15 If an emergency power-off (disconnect) switch is required by local codes, see “Installing Remote
Emergency Power-off” (REPO) in the Dell Online Rack UPS 3750W and 4200W User's Guide.
16 Plug the equipment to be protected into the UPS output receptacles, but do not turn on the
protected equipment.
Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm.
NOTE:
|
16
Installation and Startup
Connecting the Power Cord (3750W/208V Models Only)
1 Verify that the power input to the UPS has a minimum of 30A upstream overcurrent protection. 2 Plug the UPS power cord into a power o utlet. 3 Continue to “Starting the UPS” on page 21.
Installation and Startup
|
17
Hardwiring the UPS Input
WARNING: Only qualified service personnel (such as a licensed electrician) shall perform the electrical
installation. Risk of electrical shock.
The Dell Online Rack hardwired models require a dedicated branch circuit that meets the following requirements:
S 250V/30A, 2-pole circuit breaker (25A for 3750W/230V UPS models) to provide short circuit and
overcurrent protection
S The protection device requires a two-pole disconnection device between the UPS output and the
load (see Figure 6)
S The breaker must be wall-mounted and be readily accessible to the operator S For Europe, the breaker must meet the IEC/EN 60934 standard and have a contact air gap of at
least 3 mm
S 200–240 Vac S Single-phase (4200W/208V model is split-phase) S 50/60 Hz S Flexible metal conduit (recommended for ease of service and maintenance)
Wall
AC Mains
Figure 6. Circuit Breaker Diagram
|
18
Installation and Startup
2-pole
Breaker
Line
UPS
Neutral
Removing the Terminal Block Cover
1 Switch off utility power at the distribution point where the UPS will be connected. Be absolutely
sure there is no power.
2 Remove the terminal block cover (four screws) and retain.
Installation and Startup
|
19
Installing the Input and Ground Wires
3 Punch a hole in the terminal block cover for the input conduit using a Greenlee
®
punch or similar
device. The hole accommodates 3/4or 1IMC conduit.
4 Pull the input wire through the conduit, leaving approximately 2 ft (0.5m) of exposed wire. Attach
a flexible metal fitting to the end of the conduit.
5 Insert the conduit through the wiring access entry and attach the conduit fitting to the panel.
Strip 0.5(1.5 cm) of insulation from the end of each incoming wire.
6 Connect the input and ground wires to the terminal block according to Table 1.
Table 1. UPS Wiring Specifications
Wire
Function
Input
* Use 5.26 mm2(10 AWG) 75_C copper wire minimum.
Terminal
Position
1 Input Ground 2 L2/Neutral In 3 L1 In
UPS Wire Function
Terminal Wire
Size Rating*
5.26–16 mm (10–6 AWG)
Tightening
Torque
2
2.26 Nm (20 lb in)
7 Replace the terminal block cover.
20
|
Installation and Startup
Starting the UPS
1 Verify that all load segment circuit breakers are in the ON position. 2 For 3750W/208V models only. Verify that the power input to the UPS has a minimum of 30A
upstream overcurrent protection.
3 For hardwired input models only. Switch the main utility breaker on. 4 Press the button on the UPS front panel.
Installation and Startup
|
21
Completing the Startup
1 Verify that the Normal icon appears on the UPS status summary screen, indicating that the
UPS is operating normally and any loads are powered.
2 On the UPS status summary screen, press the button to check for active alarms or notices.
Resolve any active alarms before continuing. See “Troubleshooting” in the Dell Network Management Card User's Guide.
If there are no active alarms, a “No Active Alarms” message appears.
3 To change other factory-set defaults, see “Operation” in the Dell Network Management Card
User's Guide.
22
|
Installation and Startup
Onduleur en Baie En Ligne Dellt
3750W et 4200W
Démarrer
avec Votre Système
www.dell.com | support.dell.com
K804N, H952N, J730N, K805N
J739N
Remarques et avertissements
REMARQUE : Une REMARQUE indique des informations importantes qui vous aident à mieux utiliser votre logiciel.
DANGER : Un DANGER indique une situation dangereuse imminente qui, si elle n'est pas évitée, provoquera la
mort ou une blessure grave.
AVERTISSEMENT : Un AVERTISSEMENT indique une situation dangereuse potentielle qui, si elle n'est pas évitée,
pourrait provoquer la mort ou une blessure.
MISE EN GARDE : Une MISE E N GARDE indique une situation dangereuse potentielle qui, si elle n'est pas évitée,
peut provoquer une blessure mineure ou modérée ou des dommages matériels.
DANGER : Respectez les instructions suivantes pour aider à empêcher une situation dangereuse imminente qui, si
elle n'est pas évitée, peut provoquer la mort ou des blessures graves :
S Cet onduleur contient des TENSIONS MORTELLES. Toutes les réparations et tous les entretiens
devront être effectués UNIQUEMENT PAR UN PERSONNEL D’ENTRETIEN AGRÉÉ. Aucune pièce à l’intérieur de cet onduleur NE PEUT ÊTRE ENTRETENUE PAR L’UTILISATEUR.
Les informations figurant dans ce document sont soumises à modification sans préavis. E 2009 Dell Inc. Tous droits réservés.
La reproduction de quelque manière que ce soit sans l’autorisation écrite de Dell Inc. est strictement interdite.
Marques commerciales utilisées dans ce texte : Dell et le logo DELL sont des marques commerciales de Dell Inc.
D’autres marques commerciales et noms commerciaux peuvent être utilisés dans ce document pour se référer à des entités revendiquant les marques et les noms ou à leurs produits. Dell Inc. nie tout intérêt propriétaire dans les marques commerciales et les noms commerciaux qui ne lui appartenant pas.
Juillet 2009
Caractéristiques du système
Offrant une fiabilité et des performances remarquables, les avantages uniques de l'onduleur comprennent :
S Conception en ligne avec sortie sinusoïdale pure. L'onduleur filtre et régule le courant AC entrant
et fournit un courant constant à votre équipement sans vider la batterie.
S Véritable technologie en ligne double-conversion avec haute densité de puissance, indépendance
de la fréquence du secteur, et compatibilité avec les groupes électrogènes.
S Mode de fonctionnement sélectionnable haute performance. S Taille4Uquiconvientàtoutebaiestandardde48cm(19"). S La capacité de démarrage-sur-batterie pour alimenter l'onduleur même si le courant du secteur
n'est pas disponible.
S Autonomie étendue avec un Module de batterie e xterne(EBM) optionnel. S Commande d'arrêt d'urgence par les ports d'arrêt d'urgence à distance (REPO). S Deux ports de communication standards (port série DB-9 et USB). S Dell Carte de gestion de réseau optionnelle avec capacités de communication améliorées pour une
protection et un contrôle accrus de l'alimentation électrique.
S Gestion avancée de l'alimentation électrique avec l e Logiciel de gestion d'onduleur Dell pour des
coupures progressives et une surveillance de l'alimentation.
S Arrêt séquentiel et gestion de charge par des groupes de prises séparés appelés « segments de
charge ».
S Micrologiciel qui peut être facilement mis à niveau sans appeler le service technique. S Certifié par des approbations d'organismes mondiales.
Caractéristiques du système
|
25
Trouver des informations
ATTENTION : Le document Informations sur la sécurité, l'environnement et la réglementation fournit des
informations importantes sur la sécurité et la réglementation.
Que recherchez-vous ?
S Le guide d'utilisation de mon onduleur S Le guide d'utilisation pour la Dell Carte de gestion
de réseau
S Logiciel de gestion d'onduleur Dell
Trouvez-le ici
Disque de l'onduleur Dell
REMARQUE : Les mises à jour des documents e t des
logiciels se trouvent sur
S Spécifications S Comment configurer les paramètres de l'onduleur S Comment identifier et résoudre les problèmes S Comment installer un contrôle REPO S Instructions de sécurité S Informations sur la réglementation S Informations sur le recyclage
S Informations sur la garantie S Termes et conditions (États-Unis uniquement) S Contrat de licence de l'utilisateur final
S Informations sur l'assistance Site Internet d'Assistance Dell — support.dell.com
Guide d'utilisation de l'onduleur Dell
Le guide d'utilisation est disponible sur le disque de l'onduleur Dell et sur support.dell.com.
Informations sur la sécurité, l'environnement et la réglementation
Informations sur l'assistance et la garantie Dell
support.dell.com.
REMARQUE : Sélectionnez votre région ou votre
segment commercial pour voir le site d'assistance approprié.
26
|
Trouver des informations
Installation et démarrage
ATTENTION : Avant de réaliser les procédures de ce document, lisez et suivez les instructions de sécurité et
les informations importantes sur la réglementation qui figurent dans votre document Informations sur la sécurité, l'environnement et la réglementation.
Cette section décrit les étapes de configuration de votre système pour la première fois.
Déballage du système
1 Ouvrez le carton extérieur et retirez les accessoires emballés avec le module.
Installation et démarrage
|
27
Levage du Module
ATTENTION : Le module est lourd (66 kg/66,00 kg). Le levage des modules dans la baie exige deux personnes
au minimum.
1 Avec une personne de chaque côté, levez soigneusement le module hors du carton extérieur en
utilisant les poignées du carton et posez-le sur une surface plane et stable.
2 Jetez ou recyclez l'emballage d'une façon responsable, ou conservez-le pour une utilisation
ultérieure.
Identification de l'onduleur
Cette section montre un panneau avant et arrière de l'onduleur Baie En Ligne Dell.
|
28
Installation et démarrage
Loading...
+ 172 hidden pages