Delfield KCSC, KHCR, KC, F KCFM, SCSC Service Manual

...
®
®
by Delfield
Shelleyglas
®
by Delfield
CAUTION
Shelleyglas®/Shelleysteel
Service and Installation Manual
Please read this manual completely before attempting to install or operate this equipment! Notify carrier of damage! Inspect all components immediately. See page 2.
Refrigerated, Heated and Non-Electrical Units
IMPORTANT INFORMATION
PLEASE SAVE THESE INSTRUCTIONS!
READ BEFORE USE
September 2010
Shelleyglas®/Shelleysteel™ Service and Installation Manual
Contents Serial Number Information
Receiving & Inspecting Equipment ...........................................2
Shelleyglas Specifications .......................................................3-4
Shelleysteel Specifications ......................................................5-6
Installation: Heated Units ..........................................................7
Operation: Heated Units .............................................................7
Installation: Refrigerated Units ..................................................8
Operation: LiquiTec Units ...........................................................8
Pressure Control Settings ..........................................................9
Maintenance ........................................................................10-11
Food Well Assembly.................................................................12
Wiring Diagrams .................................................................13-16
Replacement Parts List .......................................................17-18
Exploded Views & Replacement Parts ....................................19
Standard Labor Guidelines ......................................................20
Standard Warranties ...........................................................21-22
Notes ........................................................................................23
If your unit is heated, the serial tag is located above the louvered panel near the on/off switch.
Refrigerated units have the serial tag located in the compressor area near the on/off switch.
Understorage units often have the serial tag located on the left inside the storage area.
All purpose counters, utility equipment or delivery carts do not require serial numbers but a model tag is placed at the top of the pylon on the back of the unit.
Always have the serial number of your unit available when calling for parts or service.
This manual covers standard units only. If you have a custom unit, consult the customer service department at the number listed below.
©2010 The Delfield Company. All rights reserved. Reproduction without written permission is prohibited. “Delfield” is a registered trademarks of The Delfield Company.
Receiving And Inspecting The Equipment
Even though most equipment is shipped crated, care should be taken during unloading so the equipment is not damaged while being moved into the building.
1. Visually inspect the exterior of the package and skid or container. Any damage should be noted and reported to the delivering carrier immediately.
2. If damaged, open and inspect the contents with the carrier.
3. In the event that the exterior is not damaged, yet upon opening, there is concealed damage to the equipment notify the carrier. Notification should be made verbally as well as in written form.
4. Request an inspection by the shipping company of the damaged equipment. This should be done within 10 days from receipt of the equipment.
5. Check the lower portion of the unit to be sure legs or casters are not bent.
6. Also open the compressor compartment housing and visually inspect the refrigeration package. Be sure lines are secure and base is still intact.
7. Freight carriers can supply the necessary damage forms upon request.
8. Retain all crating material until an inspection has been made or waived.
Uncrating the Equipment
First cut and remove the banding from around the crate. Remove the front of the crate material, use of some tools will be required. If the unit is on legs remove the top of the crate as well and lift the unit off the skid. If the unit is on casters it can be "rolled" off the skid.
The units with LiquiTec technology cold pans contain a non-toxic eutectic fluid within a sealed inner liner. This fluid may leak if the tank is punctured so care must be taken when uncrating and setting in place. The eutectic fluid is non-toxic and may be flushed down a disposal drain. If the LiquiTec unit cold pans leak, immediately call the Delfield service department directly at 1-800-733-8821 not your local service agent.
2
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Shelleyglas®/Shelleysteel™ Service and Installation Manual
Shelleyglas® Specifications
This manual covers standard units only. If you have a custom unit, consult the customer service department at the number listed below.
Heated Serving Counters
Model V/ Hz/Ph NEMA Plug Amperage
KH-2 120/208-230/60/1 14-20P 15.0
KH-3 120/208-230/60/1 14-30P
KH-4 120/208-230/60/1 14-50P 26.0
KH-5 120/208-230/60/1 14-50P 31.0
KH-6 120/208-230/60/1 14-50P 37.0
KH-2-NU 120/208-230/60/1 14-20P 11.0
KH-3-NU 120/208-230/60/1
KH-4-NU 120/208-230/60/1 14-30P 22.0
KH-5-NU 120/208-230/60/1 14-50P 28.0
KH-6-NU 120/208-230/60/1 14-50P 33.0
Refrigerated Cold Pan Serving Counters
Model V/ Hz/Ph NEMA Plug Amperage H.P. Refrigerant BTU
KCSC-36B 115/60/1 5-15P 7.0 1/4 404a 1102
KCSC-50B 115/60/1 5-15P 7.0 1/4 404a 1240
KCSC-60B 115/60/1 5-15P 7.0 1/4 404a 1343
KCSC-74B 115/60/1 5-15P 7.0 1/4 404a 1423
KCSC-96B 115/60/1 5-15P 7.0 1/4 404a 1487
14-20P 16.0
20.0
Shelleyglas with LiquiTec
Model V/ Hz/Ph NEMA Plug Amperage H.P. Refrigerant BTU
KCSC-36-EF 115/60/1 5-15P 7.0 1/4 404a 1102
KCSC-50-EF 115/60/1 5-15P 7.0 1/4 404a 1240
KCSC-60-EF 115/60/1 5-15P 7.0 1/4 404a 1343
KCSC-74-EF 115/60/1 5-15P 7.0 1/4 404a 1423
KCSC-96-EF 115/60/1 5-15P 7.0 1/4 404a 1487
Heated and Refrigerated Combo Counters
Model V/ Hz/Ph NEMA Plug Amperage H.P. Refrigerant BTU
KHCR-50-B 120/60/1 5-20P 16.0 1/4 404a 1102
KHCR-60-B 120/60/1 5-20P 16.0 1/4 404a 1102
KHCR-74-B 120/60/1 5-20P 16.0 1/4 404a 1102
KHCR-96-B 120/60/1 5-20P 16.0 1/4 404a 1240
KH2CR-72-B 120/208-230/60/1 14-30P 18.0 1/4 404a 1102
KH2CR-96-B 120/208-230/60/1 14-30P 18.0 1/4 404a 1343
KH3CR-96-B 120/208-230/60/1 14-30P 23.0
KH4CR-96-B 120/208-230/60/1 14-50P 29.0 1/4 404a 1102
1/4 404a 1240
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
3
Shelleyglas®/Shelleysteel™ Service and Installation Manual
Shelleyglas® Specifications, continued
Heated and Ice Cooled Combo Counters
Model V/ Hz/Ph NEMA Plug Amperage
KHC-50-NU 120/60/1 5-15P 9.0
KHC-60-NU 120/60/1 5-15P 9.0
KHC-74-NU 120/60/1 5-15P 9.0
KHC-96-NU 120/60/1 5-15P 9.0
KH2C-74-NU 120/208-230/60/1 14-20P 11.0
KH2C-96-NU 120/208-230/60/1 14-20P 11.0
KH3C-74-NU 120/208-230/60/1
KH3C-96-NU 120/208-230/60/1
KH4C-96-NU 120/208-230/60/1 14-30P 22.0
Frost Top Serving Counters
Model V/ Hz/Ph NEMA Plug Amperage H.P. Refrigerant BTU
KCFT-36-NU 115/60/1 5-15P 7.0 1/4 404a 435
KCFT-50-NU 115/60/1 5-15P 7.0 1/4 404a 595
KCFT-60-NU 115/60/1 5-15P 7.0 1/4 404a 717
KCFT-74-NU 115/60/1 5-15P 7.0 1/4 404a 827
KCFT-96-NU 115/60/1 5-15P 7.0 1/4 404a 921
14-20P 16.0
14-20P 16.0
Milk Counters
Model V/ Hz/Ph NEMA Plug Amperage H.P. Refrigerant BTU
KCM-36 115/60/1 5-15P 7.0 1/4 404A 1114
KCM-50 115/60/1 5-15P 7.0 1/4 404A 1190
KCM-60 115/60/1 5-15P 7.0 1/4 404A 1329
KCM-74 115/60/1 5-15P 7.0 1/4 404A 1535
Ice Cream Counters
Model V/ Hz/Ph NEMA Plug Amperage H.P. Refrigerant BTU
KCF-36 115/60/1 5-15P 7.0 1/4 404A 915
KCF-50 115/60/1 5-15P 7.0 1/4 404A 1350
KCF-60 115/60/1 5-15P 8.0 1/3 404A 1456
KCF-74 115/60/1 5-15P 8.0 1/3 404A 1609
Milk and Ice Cream Counters
Model V/ Hz/Ph NEMA Plug Amperage H.P. Refrigerant BTU
REF/FRZ
KCFM-50 115/60/1 5-15P 7.0 1/4 404A 789/1580
KCFM-74 115/60/1 5-15P 8.0 1/3 404A 1199/2040
Carving Counter
Model V/ Hz/Ph NEMA Plug Amperage
KRB 115/60/1 5-15P 5.0
4
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Shelleyglas®/Shelleysteel™ Service and Installation Manual
Shelleysteel® Specifications
Heated Serving Counters
Model V/Hz/Ph NEMA Plug Amperage
SH-2 120/208-230/60/1 14-20P 15.0
SH-3 120/208-230/60/1 14-30P
SH-4 120/208-230/60/1 14-50P 26.0
SH-5 120/208-230/60/1 14-50P 31.0
SH-6 120/208-230/60/1 14-50P 37.0
SH-2-NU 120/208-230/60/1 14-20P 11.0
SH-3-NU 120/208-230/60/1
SH-4-NU 120/208-230/60/1 14-30P 22.0
SH-5-NU 120/208-230/60/1 14-50P 28.0
SH-6-NU 120/208-230/60/1 14-50P 33.0
Refrigerated Cold Pan Serving Counters
Model V/Hz/Ph NEMA Plug Amperage H.P. Refrigerant BTU
SCSC-36B
SCSC-50B 115/60/1 5-15P 7.0 1/4 404a 1240
SCSC-60B 115/60/1 5-15P 7.0 1/4 404a 1343
SCSC-74B 115/60/1 5-15P 7.0 1/4 404a 1423
SCSC-96B 115/60/1 5-15P 7.0 1/4 404a 1487
115/60/1 5-15P 7.0 1/4 404a 1102
14-20P 16.0
20.0
Shelleysteel with LiquiTec
Model V/Hz/Ph NEMA Plug Amperage H.P. Refrigerant BTU
SCSC-36-EF
SCSC-50-EF 115/60/1 5-15P 7.0 1/4 404a 1240
SCSC-60-EF 115/60/1 5-15P 7.0 1/4 404a 1343
SCSC-74-EF 115/60/1 5-15P 7.0 1/4 404a 1423
SCSC-96-EF 115/60/1 5-15P 7.0 1/4 404a 1487
Heated and Refrigerated Combo Counters
Model V/Hz/Ph NEMA Plug Amperage H.P. Refrigerant BTU
SHCR-50-B 120/60/1 5-20P 16.0 1/4 404a 1102
SHCR-60-B 120/60/1 5-20P 16.0 1/4 404a 1102
SHCR-74-B 120/60/1 5-20P 16.0 1/4 404a 1102
SHCR-96-B 120/60/1 5-20P 16.0 1/4 404a 1240
SH2CR-62-B 120/208-230/60/1 14-20P 16.0 1/4 404a 1423
SH2CR-72-B 120/208-230/60/1 14-30P 18.0 1/4 404a 1102
SH2CR-96-B 120/208-230/60/1 14-30P 18.0 1/4 404a 1343
SH3CR-96-B 120/208-230/60/1 14-30P 23.0
SH4CR-96-B 120/208-230/60/1 14-50P 29.0 1/4 404a 1102
115/60/1 5-15P 7.0 1/4 404a 1102
1/4 404a 1240
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
5
Shelleyglas®/Shelleysteel™ Service and Installation Manual
Shelleysteel® Specifications, continued
Heated and Ice Cooled Combo Counters
Model V/Hz/Ph NEMA Plug Amperage
SHC-50-NU 120/60/1 5-15P 9.0
SHC-60-NU 120/60/1 5-15P 9.0
SHC-74-NU 120/60/1 5-15P 9.0
SHC-96-NU 120/60/1 5-15P 9.0
SHC2-62-NU 120/208-230/60/1 14-20P 11.0
SH2C-74-NU 120/208-230/60/1 14-20P 11.0
SH2C-96-NU 120/208-230/60/1 14-20P 11.0
SH3C-74-NU 120/208-230/60/1
SH3C-96-NU 120/208-230/60/1
SH4C-96-NU 120/208-230/60/1 14-30P 22.0
Frost Top Serving Counters
Model V/Hz/Ph NEMA Plug Amperage H.P. Refrigerant BTU
SCFT-36-NU
SCFT-50-NU 115/60/1 5-15P 7.0 1/4 404a 595
SCFT-60-NU 115/60/1 5-15P 7.0 1/4 404a 717
SCFT-74-NU 115/60/1 5-15P 7.0 1/4 404a 827
SCFT-96-NU 115/60/1 5-15P 7.0 1/4 404a 921
115/60/1 5-15P 7.0 1/4 404a 435
14-20P 16.0
14-20P 16.0
Milk Counters
Model V/Hz/Ph NEMA Plug Amperage H.P. Refrigerant BTU
SCM-36
SCM-50 115/60/1 5-15P 7.0 1/4 404A 1190
SCM-60 115/60/1 5-15P 7.0 1/4 404A 1328
SCM-74 115/60/1 5-15P 7.0 1/4 404A 1535
Ice Cream Counters
Model V/Hz/Ph NEMA Plug Amperage H.P. Refrigerant BTU
SCF-36
SCF-50 115/60/1 5-15P 7.0 1/4 404A 1350
SCF-60 115/60/1 5-15P 8.0 1/3 404A 1456
SCF-74 115/60/1 5-15P 8.0 1/3 404A 1609
Milk and Ice Cream Counter
Model V/Hz/Ph NEMA Plug Amperage H.P. Refrigerant BTU
SCFM-50 115/60/1 5-15P 7.0 1/4 404A 789/1580
SCFM-74 115/60/1 5-15P 8.0 1/3 404A 1199/2040
Carving Counter
Model V/Hz/Ph NEMA Plug Amperage
SRB 115/60/1 5-15P 5.0
115/60/1 5-15P 7.0 1/4 404A 1114
115/60/1 5-15P 7.0 1/4 404A 915
REF/FRZ
Trimline L-shaped Heated Serving Counter
Model V/Hz/Ph NEMA Plug Amperage
SLT4 (-L OR -R) 208-230/60/1 14-30P 22.0
6
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Installation: Heated Units
Shelleyglas®/Shelleysteel™ Service and Installation Manual
Location
Do not install the unit near combustible objects or surfaces affected by heat or moisture.
Leveling
The unit must be level, both front and back and left to right, in order to maintain an equal water depth throughout the wells.
Operation: Heated Units
After plugging in the power supply cord, select desired temperature by rotating the knob on the temperature control panel. Indicator light will come on when the switch is activated. Individual temperature control knobs and indicator lights are provided for each heated food well.
If the same temperature settings for each well are used every day, the temperature knobs can be left in their set position and the wells can be turned off using the ON/OFF switch at the end of the control panel.
Before the unit is used the first time for serving, turn the temperature knob to “10” and heat the well for 15 minutes. Do not be alarmed if smoke appears; this preheat should burn off any residue or dust that has adhered to the food well element.
When serving thick sauces always use the hot food well in “wet” operation. This provides more uniform temperature for the sauce. Product temperature should range from 140˚F to 160˚F
Never place food directly in well. Always use pans.
For most efficient operation, keep covered insets empty in each well during preheating and when the well is not in use.
Always place covers on pans when not serving to prevent food from drying out and to reduce your operating costs.
Wet operation
Fill the food well with about two inches of water and cover with lid or empty pan. To preheat water, set temperature
Electrical Connections
Connections must be made in accordance with all applicable local codes and/or the National Electrical Code. Refer to the amperage data on page 3 and the wiring diagrams on pages 8 and 9. A standard unit is provided with a power cord and 3-prong grounded plug. All units should be plugged into a grounded receptacle with its own circuit protection that matches the amperage of the plug.
control at “High”. With pans in place, wells will boil water. Food temperature will vary depending on type and amount of product. To minimize steam and water usage, set control to lowest setting that will maintain proper food temperature.
To reduce preheating time, use hot water to fill the well.
Steam can cause serious burns. Always wear some type of protective covering on your hands and arms when removing lids from the unit. Lift the lid in a way that will direct escaping steam away from your face and body. Water temperature will average 180˚F.
Dry operation
Wet operation is usually much more efficient and is usually preferred. However, these units may be operated without water with no damage to the unit.
The dry well should never be preheated longer
than 15 minutes. Only 6” deep pans should be used with dry food wells.
When operated dry, the well bottoms become very hot. Do not allow unprotected skin to contact any well surface.
When operated dry, the bottom of the well will discolor. To clean, use a stainless steel cleaner or mild abrasive.
Operation of optional heated understorage
If necessary, preheat the heated understorage to desired temperature. Temperature range of understorage is 100°F to 200°F. The temperature control knob is always the far left knob on the panel. Indicator light is also at the far left.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
7
Shelleyglas®/Shelleysteel™ Service and Installation Manual
CAUTION
Installation: Refrigerated Units
Location
Be sure the location chosen has a floor strong enough to support the total weight of the cabinet and contents. Reinforce the floor as necessary to provide for maximum loading.
For the most efficient refrigeration, be sure to provide good air circulation inside and out.
Inside cabinet: Do not pack unit so full that air cannot circulate. Take care not to block air flow to the fans and allow space along the sides.
Outside cabinet: Be sure the unit has access to ample air; avoid hot corners and locations near stoves and ovens. It is suggested the rear of the unit be no less than two inches from any wall, partition or any other object which will restrict exhaust air flow.
Leveling
A level cabinet looks better and will perform better because the doors will line up with the door frames properly, and the cabinet will not be subject to unnecessary strain.
Stabilizing
Some models are supplied on casters for your convenience, for ease of cleaning underneath and mobility.
The unit must be installed in a stable condition
with the front wheels locked, locking the front casters after installation is the owner’s and operator’s responsibility.
Plumbing
Refrigerated units have a drain that exits the unit on the bottom, and is located on the operator’s left side. Standard units on casters or legs will have a bronze faucet that fits a standard
garden hose. Units on legs with optional remote drain valve handle will have 1” threaded pipe extending from bottom of unit. On standard units, a stainless steel access panel or hinged louver will be provided for access to drain connections.
Moisture collecting from improper drainage can create a slippery surface on the floor and a hazard to employees. It is the owner’s and operator’s responsibility to provide a container or outlet for drainage.
Electrical connection
A standard refrigerated unit is provided with a power cord and 3-prong grounded plug.
The unit should be plugged into a receptacle with its own circuit protection that matches the amperage of the plug.
Refer to the amperage data on page 3 or the serial tag data and your local code or the National Electrical Code to be sure the unit is connected to the proper power source. A protected circuit of the correct voltage and amperage must be run for connection of the supply cord or permanent connection to the unit.
On cord-connected units, an ON/OFF switch is located directly on the face of the compressor section. The switch must be turned to its OFF position and power supply disconnected whenever doing the following:
1. Performing maintenance functions.
2. Cleaning the refrigerated cabinet area.
3. Performing service or repair functions. Under no circumstances should the unit be operated without
the louvered panel in place.
Operation: LiquiTec Units
LiquiTec Series cold pans are adjusted at the factory to provide satisfactory operation without any further adjustments. However, if it is necessary to adjust the temperature, the control is located in the machine compartment. Turn the knob clockwise as indicated on the control. Settings are from 1 through 7; 7 being the coldest. Adjustments should be made gradually. Several small adjustments will be more effective than one large adjustment. It may take an hour or longer to realize the temperature change depending on the application and location of the unit.
These units are not designed to cool warm food products. Items should be placed in the unit pre-cooled at least to the desired holding temperature, if not slightly colder. In some applications, a gradual warming of product may occur, particularly at the
8
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
exposed top of the products. Stirring or rotation of the product may be necessary to maintain overall temperature. Warming of food product can occur very quickly outside of the unit. When loading or rotating the product, avoid leaving food items in a non-refrigerated location for any length of time to prevent warming or spoilage.
The cold pan is not intended to be used with ice.
The unit has an ON/OFF switch. Turn the unit ON an hour prior to use to allow for ample cool down time. The unit must be turned off when not in use or overnight for defrosting and cleaning.
Shelleyglas®/Shelleysteel™ Service and Installation Manual
Pressure Control Settings
All Delfield refrigerated models come equipped with 115-volt, 60 cycle, single phase refrigeration units. The refrigeration valves are open and ready to operate as soon as the power supply cord is plugged into the standard 115-volt, grounded electrical outlet.
Pressure Control
The temperature is controlled by an adjustable pressure control located in the machine compartment. An adjustable control has the word COLDER near the knob, with an arrow to indicate the adjustment direction. These controls are field adjustable and do not require a service agent. If you have any questions, feel free to contact the Delfield Service Department.
In attempting to adjust the pressure control, you can do damage to your unit by accidentally adjusting the differential. Please make small incremental adjustments if a temperature adjustment is necessary, please contact the service department at Delfield (800) 733-8821 or your local service agent. Delfield is not responsible for charges incurred while having the pressure control adjusted.
Pressure control settings:
KCSC/SCSC, KHCR/SHCR & KCFT/SCFT 55# cut in 30# cut out KCM/SCM 40# cut in 20# cut out
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
9
Shelleyglas®/Shelleysteel™ Service and Installation Manual
Maintenance
Drain Maintenance - Base
Each unit has a drain located inside the unit that removes the condensation from the evaporator coil and routes it to an external condensate evaporator pan. Each drain can become loose or disconnected during normal use. If you notice water accumulation on the inside of the unit be sure the drain tube is connected to the evaporator drain pan. If water is collecting underneath the unit make sure the end of the drain tube is in the condensate evaporator in the machine compartment. The leveling of the unit is important as the units are designed to drain properly when level. Be sure all drain lines are free of obstructions.
Caster Maintenance
Wipe casters with a damp cloth monthly to prevent corrosion.
The power switch must be turned to OFF and the unit disconnected from the power source whenever performing service, maintenance functions or cleaning the refrigerated area.
Interiors & Exteriors
The interior and exterior can be cleaned using soap and warm water. If this isn’t sufficient, try ammonia and water or a nonabrasive liquid cleaner. When cleaning the exterior, always rub with the “grain” of the stainless steel to avoid marring the finish. Do not use an abrasive cleaner because it will scratch the stainless steel and can damage the breaker strips and gaskets.
For all fiberglass and stainless steel parts, use a mild, non­abrasive soap or detergent and warm water. This may be followed by an application of stainless steel cleaner or polish which will eliminate water spotting, fingerprints and bring out the color of the fiberglass. To maintain the rich, brilliant color of the fiberglass and to remove shallow surface scratches, wax twice a year. This can be done in the same manner in which a car is waxed.
Cleaning solutions need to be alkaline based or non-chloride cleaners. Any cleaner containing chlorides will damage the protective film of the stainless steel. Chlorides are also commonly found in hard water, salts, and household and industrial cleaners. If cleaners containing chlorides are used be sure to rinse repeatedly and dry thoroughly. Routine cleaning of stainless steel can be done with soap and water. Extreme stains or grease should be cleaned with a non-abrasive cleaner and plastic scrub pad. Always rub with the grain of the steel. There are stainless steel cleaners available which can restore and preserve the finish of the steels protective layer. Early signs of stainless steel breakdown are small pits and cracks. If this has begun, clean thoroughly and start to apply stainless steel cleaners in attempt to restore the passivity of the steel.
Never use an acid based cleaning solution! Many food products have an acidic content, which can deteriorate the finish. Be sure to clean the stainless steel surfaces of ALL food products. Common items include, tomatoes, peppers and other vegetables.
Cleaning the Condenser Coil
In order to maintain proper refrigeration performance, the condenser fins must be cleaned of dust, dirt and grease regularly. It is recommended that this be done at least every three months. If conditions are such that the condenser is totally blocked in three months, the frequency of cleaning should be increased. Clean the condenser with a vacuum cleaner or stiff brush. If extremely dirty, a commercially available condenser cleaner may be required.
Failure to maintain a clean condenser coil can initially cause high temperatures and excessive run times. Continuous operation with a dirty or clogged condenser coil can result in compressor failure. Neglecting the condenser coil cleaning procedures will void any warranties associated with the compressor and cost to replace the compressor.
Stainless Steel Care and Cleaning
To prevent discoloration or rust on stainless steel several important steps need to be taken. First, we need to understand the properties of stainless steel. Stainless steel contains 70- 80% iron, which will rust. It also contains 12-30% chromium, which forms an invisible passive film over the steel’s surface, which acts as a shield against corrosion. As long as the protective layer is intact, the metal is still stainless. If the film is broken or contaminated, outside elements can begin to breakdown the steel and begin to form discoloration or rust. Proper cleaning of stainless steel requires soft cloths or plastic scouring pads.
NEVER USE STEEL PADS, WIRE BRUSHES OR SCRAPERS!
10
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Never use a high-pressure water wash for this cleaning procedure as water can damage the electrical components located near or at the condenser coil.
Doors/Hinges
Over time and with heavy use doors the hinges may become loose. If this happens tighten the screws that mount the hinge brackets to the frame of the unit. Loose or sagging doors can cause the hinges to pull out of the frame, which may damage both the doors and the hinges. In some cases this may require qualified service agents or maintenance personnel to perform repairs.
Shelleyglas®/Shelleysteel™ Service and Installation Manual
Maintenance, continued
Do not place hot pans on/against the blue ABS liner. Do not throw items into the storage area. Failure to follow these recommendations could result in damage to the interior of the cabinet or to the blower coil. Overloading the storage area, restricting the airflow, and continuous opening and closing of the doors and drawers will hamper the units ability to maintain operational temperature.
Preventing blower coil corrosion
To help prevent corrosion of the blower coil, store all acidic items, such as pickles and tomatoes, in sealable containers. Immediately wipe up all spills.
Units with pans should be operated with pans in place. Operating the unit without all pans in place will lower efficiency and may damage the unit.
Continuous opening and closing of the doors will hamper the unit’s ability to maintain optimum refrigeration temperature. Top section is not intended for overnight storage. Product should be removed from pans. Pans can remain in unit while empty.
Defrosting
Refrigerated cold pans and frost tops should be defrosted daily. Milk or Ice Cream dispensers require defrosting after 3/8 to 1/2 of frost forming. On/Off switch located above louver panel.
Never use sharp objects or tools to clean or scrape ice/frost build up from the refrigerated cold pans or frost tops. A puncture to the pan could cause irreparable damage to the refrigeration system.
Units with a Eutectic Fluid Cold Pan require the same precautions. The fluid is NOT refillable and loss of fluid due to a puncture would cause irreparable damage.
Over shelves and other items mounted to the top of the counters should never be installed in the field due to the potential damage to the refrigeration system.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
11
Shelleyglas®/Shelleysteel™ Service and Installation Manual
6
3
1
5
4
2
208/230V
2
1 FOOD WELL W/STRAPS, ASSY, WO/ DRAIN
2 INSULATION, FIBERGLASS, 9" X 48"
3 PLATE, DEFLECTOR, DFW, W/O DRAIN
4 ELEMENT, HEATING, 208/230V,1000/1222W
ELEMENT, HEATING, 120V/1000W
5 THERMOSTAT, NON-ADJ, 550oF
6 INSULATION, BLANKET
7 KNOB, INFINITE CONTROL
CONTROL, INFINITE, 240V, 13A
CONTROL, INFINITE, 120V, 13A
PLATE, DEFLECTOR, DFW, W/DRAIN
FOOD WELL W/STRAPS, W/ DRAIN
No.
Part Description
7
Food Well Assembly
— KH/SH/-NU Series with Infinite Controls
NOTE: See page 18 for part numbers
12
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Shelleyglas®/Shelleysteel™ Service and Installation Manual
Wiring Diagram
NEUTRAL WIRE FOR 120 VOLT OPTIONS
NEUTRAL
L2
L1
GND
120/208-240V-37A-1PH NEMA #14-50P CORD/PLUG SUPPLIED
HI
6
5
— Units With Infinite and Thermostatic Controls
(DPST SWITCH) MASTER ON/OFF SWITCH 1
INFINITE CONTROL
L2
H2
L1
P
H1
FOOD WELL
INFINITE CONTROL
H2
L2 L1
P
INFINITE CONTROL L2 L1
P
HL
FOOD WELL
H2
H1
FOOD WELL
OFF
LO
1
2
3
4
(DPST SWITCH) MASTER ON/OFF SWITCH 2
LIMIT SWITCH
LIMIT SWITCH
LIMIT SWITCH
PILOT LIGHT
HEATER
PILOT LIGHT
HEATER
PILOT LIGHT
HEATER
INFINITE CONTROL L2 L1
P
H2
H1
PILOT LIGHT
LIMIT SWITCH
HEATER
FOOD WELL
INFINITE CONTROL L2 L1
P
H2
H1
PILOT LIGHT
LIMIT SWITCH
HEATER
FOOD WELL
INFINITE CONTROL L2 L1
P
H2
H1
PILOT LIGHT
LIMIT SWITCH
HEATER
FOOD WELL
OFF
10
1
2
9
8
7
3
6
4
5
L1
THERMOSTAT
L2
PILOT LIGHT
HEATER
HEATED UNDERSTORAGE
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
13
Shelleyglas®/Shelleysteel™ Service and Installation Manual
Wiring Diagram
NEUTRAL WIRE FOR 120 VOLT OPTIONS
NEUTRAL
L2
L1
GND
120/208-240V-33A-1PH NEMA #14-50P CORD/PLUG SUPPLIED
6
— Units With Infinite Controls
(DPST SWITCH) MASTER ON/OFF SWITCH 1
OFF
LO
HI
5
1
2
3
4
(DPST SWITCH) MASTER ON/OFF SWITCH 2
INFINITE CONTROL
L2 L1
P
FOOD WELL
INFINITE CONTROL L2 L1
P
FOOD WELL
INFINITE CONTROL L2 L1
P
FOOD WELL
PILOT LIGHT
H2
H1
H2
HL
H2
H1
LIMIT SWITCH
HEATER
PILOT LIGHT
LIMIT SWITCH
HEATER
PILOT LIGHT
LIMIT SWITCH
HEATER
INFINITE CONTROL
L2
L1 P
FOOD WELL
INFINITE CONTROL L2
L1
P
FOOD WELL
INFINITE CONTROL
L2 L1
P
PILOT LIGHT
H2
H1
H2
H1
H2
H1
LIMIT SWITCH
HEATER
PILOT LIGHT
LIMIT SWITCH
HEATER
PILOT LIGHT
LIMIT SWITCH
HEATER
14
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Shelleyglas®/Shelleysteel™ Service and Installation Manual
PRESSURE CONTROL
CONDENSER FAN
COMPRESSOR
115V
RECEPTACLE FOR OPTIONAL
LOW VOLTAGE COOLING FANS
L1
N
G
S
C
R
GNL1
ON/OFF
SWITCH
CONDENSING UNIT
ON COLD PANS
ONLY. NOT
AVAILABLE ON
FROST TOP
UNITS.
RECEPTACLE FOR OPTIONAL
LOW VOLTAGE COOLING FANS
Wiring Diagram
— Cold Pan Combo
PLEASE REFER TO PAGES 8 AND 9 FOR INFORMATION ON THE HOT PAN SECTION OF COMBINATION MODELS.
Wiring Diagram
— KCSC, SCSC, KCFT And SCFT Cold Pans
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
15
Shelleyglas®/Shelleysteel™ Service and Installation Manual
ON/OFF
SWITCH
COMPRESSOR
S
C
R
CONDENSER FAN
THERMOSTAT
LOW PSI
SOL
ON/OFF
SWITCH
COMPRESSOR
S
C
R
CONDENSER FAN
LOW PSI
Wiring Diagram
— KCFM, SCFM
Wiring Diagram
— KCF, SCF, KCM, SCM
16
UNITS SUPPLIED WITH EVAPORATOR PRESSURE REGULATOR
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Shelleyglas®/Shelleysteel™ Service and Installation Manual
Replacement Parts List
Heated Serving Counters
Part Number Description KH/SH-2 KH/SH-3 KH/SH-4 KH/SH-5 KH/SH-6 KH/SH-2-NU KH/SH-3-NU KH/SH-4-NU KH/SH-5-NU KH/SH-6-NU
3234557 Control Knob X X X X X X X X X X
*000-519-0001 Food Warmer, 208V, w/o Drain X X X X X X X X X X
*000-442-0031 Heated Door Assembly X X X X
*000-442-0030 Heated Door Assembly X
6190215 Heating Element X X X X X
2194110 Innite Control 208V X X X X X X X X X X
2194212 On/O Switch X X X X X X X X X X
2194095 Pilot Light X X X X X X X X X X
2194460 Thermostat (Heated Insert) X X X X X
Refrigerated Cold Pans
Part Number Description
3234902 Caster, 5"
3234783 Caster, 5", with brake
*000-BN5-0030 Condensing Unit, 1/4HP
3234242 Drain
3516225 Expansion Valve
*356-411-0001 Louver Panel, End
*356-411-0000 Louver Panel, Front/Rear
2193927 Low Pressure Control
2190154 Rocker Switch
Shelleyglas & Shelleysteel with LiquiTec
Part Number Description
3234902 Caster, 5"
3234783 Caster, 5", with brake
*000-BN5-0030 Condensing Unit, 1/4HP
3516225 Expansion Valve
*356-411-0001 Louver Panel, End
*356-411-0000 Louver Panel, Front/Rear
2193927 Low Pressure Control
2190154 Rocker Switch
Heated and Refrigerated Combo Counters
Part Number Description
3234902 Caster, 5"
3234783 Caster, 5", with brake
*000-BN5-0030 Condensing Unit, 1/4HP
3234557 Control Knob
3234242 Drain
3516225 Expansion Valve
*000-519-0001 Food Warmer, 208V, w/o Drain
2194110 Innite Control 208V
*356-411-0001 Louver Panel, End
*356-411-0000 Louver Panel, Front/Rear
2193927 Low Pressure Control
2194212 On/O Switch
2194095 Pilot Light
2190154 Rocker Switch
* Exploded views and replacement parts shown on page 17.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
17
Shelleyglas®/Shelleysteel™ Service and Installation Manual
Replacement Parts List
Heated and Ice Cooled Combo Counters
Part Number Description
*272-412-0000 Access Panel
*265-102-0030 Bottom, Perforated
3234902 Caster, 5"
3234783 Caster, 5", with brake
3234557 Control Knob
3234242 Drain
*000-519-0001 Food Warmer, 208V, w/o Drain
2194110 Innite Control 208V
2194212 On/O Switch
2194095 Pilot Light
Frost Top Serving Counters
Part Number Description
*000BN50030
3234902 Caster, 5, Plt, Swvl,
3234783 Caster, 5, Plt, Swvl, Brk,
3234242 Drain, Plastic, 1ips, 2.87
3234669 Interlock Assy, Sg
*356-411-0001 Panel, Shy Lvr, End
*356-411-0000 Panel, Shy Lvr, Frt/rear
2190154 Switch, Rocker, 20a/125v,
Assy, 1/4 Hp Cond Unit
Milk Counters
Part Number Description
3234902 Caster, 5, Plt, Swvl,
3234783 Caster, 5, Plt, Swvl, Brk,
3526674 Cond Unit, 1/4hp, Hi, R134a
3234242 Drain, Plastic, 1ips, 2.87
3516101 Drier, Filter, 1/4odf
3234669 Interlock Assy, Sg
3234188 Lid, Large, Ice Cream,
*356-411-0001 Panel, Shy Lvr, End
*356-411-0000 Panel, Shy Lvr, Frt/rear
6150201 Spring, Extension,
2190154 Switch, Rocker, 20a/125v,
Ice Cream Counters
Part Number Description
*000BN50030 Assy, 1/4 Hp Cond Unit
3234902 Caster, 5, Plt, Swvl,
3234783 Caster, 5, Plt, Swvl, Brk,
3234242 Drain, Plastic, 1ips, 2.87
3234669 Interlock Assy, Sg,
3234188 Lid, Large, Ice Cream,
*356-411-0001 Panel, Shy Lvr, End
*356-411-0000 Panel, Shy Lvr, Frt/rear
6150201 Spring, Extension,
2190154 Switch, Rocker, 20a/125v,
Milk And Ice Cream Counters
Part Number Description
*000BN50030 Assy, 1/4 Hp Cond Unit
3234902 Caster, 5, Plt, Swvl,
3234783 Caster, 5, Plt, Swvl, Brk
3234242 Drain, Plastic, 1ips, 2.87
3234669 Interlock Assy, Sg
3234188 Lid, Large, Ice Cream
*356-411-0001 Panel, Shy Lvr, End
*356-411-0000 Panel, Shy Lvr, Frt/rear
6150201 Spring, Extension,
2190154 Switch, Rocker, 20a/125v,
* Exploded views and replacement parts shown on page 17.
18
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Shelleyglas®/Shelleysteel™ Service and Installation Manual
1
2
3
4
1
2
4
5
6
7
3
Exploded Views & Replacement Parts
000-442-0030 Heated Door Assembly
1701249 Door Gasket
3234067 Flag Hinge
000-442-0031 Heated Door Assembly
1701244 Door Gasket
3234067 Flag Hinge
000-BN5-0030
1 3516457
2 2160020
3 2162717
4 3526999
5 3516444
5 2194787
6 3516322
7 3516454
Condensing Unit, 1/4HP
Fan Blade
Fan Guard
Fan Motor
Danfoss Compressor
Compressor Relay
Start Capacitor
Filter Drier
Condenser Coil
000-519-0001 Food Warmer, 208V, w/o Drain
1 2194335 Hi-Limt Safety Switch
2 2194007 Heating Element 208V
3 026-061-0001 Deector Plate
4 0160014 Hot Food Well, 12 x 20
265-102-0030 Bottom, Perforated
272-412-0000 Access Panel
356-411-0000 Louver Panel, Front/Rear
356-411-0001 Louver Panel, End
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
19
Shelleyglas®/Shelleysteel™ Service and Installation Manual
Standard Labor Guidelines To Repair Or Replace Parts On Delfield Equipment
Advice and recommendations given by Delfield Service Technicians do not constitute or guarantee any special coverage.
• A maximum of 1-hour is allowed to diagnose a defective component.
• A maximum of 1-hour is allowed for retrieval of parts not in stock.
• A maximum travel distance of 100 miles round trip and 2-hours will be reimbursed.
• Overtime, installation/start-up, normal control adjustments, general maintenance, glass breakage, freight damage, and/or correcting and end-user installation error will not be reimbursed under warranty unless pre-approved with a Service Work
Authorization from Delfield. You must submit the number with the service claim.
LABOR OF 1-HOUR IS ALLOWED TO REPLACE:
• Thermostat • Contactor/Relay
• Infinite Switch • Transformer
• Door Jamb Switch • Evaporator/Condenser Fan Motor and Blade
• Solenoid Coil • Circulating Fan Motor and Blade
• Hi-limit/Thermal Protector Switch • Microprocessor Control
• Fan Delay/Defrost Termination Switch • Water Level Sensor/Probe
• Compressor Start Components and Overload Protector • Door Hinges, Locks, and Gaskets
• Defrost Timer • Condensate Element
• Thermometer • Springs/Lowerator
• Gear Box
LABOR OF 2 HOURS TO REPLACE:
• Drawer Tracks/Cartridges • Defrost Element
• Pressure Control • Heating Element
• Solenoid Valve • Locate/Repair Leak
LABOR OF 3 HOURS TO REPLACE:
• EPR or CPR Valve • Condenser or Evaporator Coil
• Expansion Valve
LABOR OF 4 HOURS TO REPLACE
• Compressor
This includes recovery of refrigerant and leak check. $55.00 maximum reimbursement for refrigerant recovery (includes recovery machine, pump, torch, oil, flux, minor fittings,
solder, brazing rod, nitrogen, or similar fees.)
REFRIGERANTS
• R22 A maximum of $4.00/lb. or 25¢/oz. will be reimbursed.
• R134A A maximum of $5.00/lb. or 31¢/oz. will be reimbursed.
• R404A A maximum of $15.00/lb. or $1.00/oz. will be reimbursed.
20
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Shelleyglas®/Shelleysteel™ Service and Installation Manual
Standard One Year Limited Warranty One year parts, 90 days labor
The Delfield Company (“Delfield”) warrants to the Original Purchaser of the Delfield product (herein called the “Unit”) that such Unit, and all parts thereof, will be free from defects in material and workmanship under normal use and service for a period of one (1) year from the date of shipment of the Unit to the Original Purchaser or, if the Original
Purchaser returns the warranty card completely filled out including the date of installation within thirty (30) days of receipt of the Unit, one (1) year from the date of installation. During this one year
warranty period, Delfield will repair or replace any defective part or portion there of returned to Delfield by the Original Purchaser which Delfield determines was defective due to faulty material or workmanship. The Original purchaser will pay all labor, crating, freight and related costs incurred in the removal of the Unit of defective component and shipment to Delfield, except that during a period of either ninety (90) days from the date of shipment of the Unit to the Original Purchaser or, if the Original Purchaser returns the warranty card completely filled out including the date of installation within thirty (30) days of receipt of the Unit, ninety (90) days from the date of installation Delfield will pay all related labor costs. Delfield will pay the return costs if the Unit or part thereof was defective.
The term “Original Purchaser” as used herein means that person, firm, association, or corporation for whom the Unit was originally installed.
This warranty does not apply to any Unit or part thereof that has been subjected to misuse, neglect, alteration, or accident, such as accidental damage to the exterior finish, operated contrary to the recommendations specified by Delfield; or repaired or altered by anyone other than Delfield in any way so as to, in Delfield’s sole judgement, affect its quality or efficiency. This warranty does not apply to any Unit that has been moved from the location where it was originally installed. This warranty also does not cover the refrigerator drier or the light bulbs used in the Unit. The warranty is subject to the user’s normal
maintenance and care responsibility as set forth in the Service and Installation Manual, such as cleaning the condenser coil, and is in lieu of all other obligations of Delfield. Delfield neither assumes, nor authorizes any other person to assume for Delfield, any other liability in connection with Delfield’s products.
Removal or defacement of the original Serial Number or Model Number from any Unit shall be deemed to release Delfield from all obligations hereunder or any other obligations, express or implied.
Parts furnished by suppliers to Delfield are guaranteed by Delfield only to the extent of the original manufacturer’s express warranty to Delfield. Failure of the Original Purchaser to receive such manufacturers warranty shall in no way create any warranty, expressed or implied, or any other obligation or liability on Delfield’s part in respect thereof.
IF THE CUSTOMER IS USING A PART THAT RESULTS IN A VOIDED WARRANTY AND A DELFIELD AUTHORIZED REPRESENTATIVE TRAVELS TO THE INSTALLATION ADDRESS TO PERFORM WARRANTY SERVICE, THE SERVICE REPRESENTATIVE WILL ADVISE CUSTOMER THE WARRANTY IS VOID. SUCH SERVICE CALLS WILL BE BILLED TO CUSTOMER AT THE AUTHORIZED SERVICE CENTER’S THEN APPLICABLE TIME AND MATERIALS RATES. CONSIDER: CUSTOMER MAY INITIATE A SERVICE AGREEMENT WITHOUT PARTS COVERAGE.
If shipment of a replacement part is requested prior to the arrival in the Delfield factory of the part claimed to be defective, the Original Purchaser must accept delivery of the replacement part on a C.O.D. basis, with credit being issued after the part has been received and inspected at
Delfield’s plant and determined by Delfield to be within this warranty. Under no condition does this warranty give the Original Purchaser the right to replace the defective Unit with a complete Unit of the same manufacturer or of another make. Unless authorized by Delfield in writing, this warranty does not permit the replacement of any part, including the motor-compressor, to be made with the part of another make or manufacturer.
No claims can be made under this warranty for spoilage of any products for any reason, including system failure.
The installation contractor shall be responsible for building access, entrance and field conditions to insure sufficient clearance to allow any hood(s), vent(s), or Unit(s) if necessary, to be brought into the building. Delfield will not be responsible for structural changes or damages incurred during installation of the Unit or any exhaust system.
Delfield shall not be liable in any manner for any default or delay in performance hereunder caused by or resulting from any contingency beyond Delfield’s control, including, but not limited to, war, governmental restrictions or restraints, strike, lockouts, injunctions, fire, flood, acts of nature, short or reduced supply of raw materials, or discontinuance of the parts by the original part manufacturer.
Except as provided in any Additional Four Year Protection Plan, if applicable, and the Service Labor Contract, if applicable, the foregoing is exclusive and in lieu of all other warranties, whether written or oral, express or implied. This warranty supersedes and excludes any prior oral or written representations or warranties. Delfield expressly disclaims any implied warranties of merchantability, fitness for a particular purpose, or compliance with any law, treaty, rule or regulation relating to the discharge of substances into the environment. The sole and exclusive remedies of any person relating to the Unit, and the full liability of Delfield for any breach of this warranty, will be as provided in this warranty.
Other than this Delfield Standard One Year Limited Warranty, any applicable Delfield Additional Four Year Protection Plan or applicable Delfield Service Labor Contract, the Original Purchaser agrees and acknowledges that no other warranties are offered or provided in connection with or for the Unit or any other part thereof.
In no event will Delfield be liable for special, incidental or consequential damages, or for damages in the nature of penalties.
IF DURING THE WARRANTY PERIOD, CUSTOMER USES A PART FOR THIS DELFIELD EQUIPMENT OTHER THAN AN UNMODIFIED NEW OR RECYCLED PART PURCHASED DIRECTLY FROM DELFIELD OR ANY OF ITS AUTHORIZED SERVICE CENTERS AND/OR THE PART BEING USED IS MODIFIED FROM ITS ORIGINAL CONFIGURATION, THIS WARRANTY WILL BE VOID. FURTHER, DELFIELD AND ITS AFFILIATES WILL NOT BE LIABLE FOR ANY CLAIMS DAMAGES OR EXPENSES INCURRED BY THE CUSTOMER WHICH ARISE DIRECTLY OR INDIRECTLY, IN WHOLE OR IN PART, DUE TO THE INSTALLATION OF ANY MODIFIED PART AND/OR PART RECEIVED FROM AN UNAUTHORIZED SERVICE CENTER. If the warranty becomes void, Customer may purchase from Delfield, if available, a Service Agreement or service at the then current time and materials rate.
For more information on Delfield warranty’s log on and check out the service section of our web site at www.delfield.com.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
21
Shelleyglas®/Shelleysteel™ Service and Installation Manual
Additional Four Year Protection Plan for Motor-Compressor only
Installation Delfield Model# Serial # Date
General Conditions
Delfield shall not be liable in any manner for any default or delay in performance hereunder caused by or resulting from any contingency
beyond Delfield’s control, including, but not limited to, war, In addition to the Standard One Year Warranty on the Motor­Compressor contained in the above listed Delfield product (the “Unit”), The Delfield Company (“Delfield”) also agrees to repair, or exchange with similar or interchangeable parts in design and capacity at Delfield’s option, the defective Motor-Compressor contained in the Unit (the “Motor-Compressor), or any part thereof, for the Original Purchaser only, at any time during the four (4) years following the initial one (1) year period commencing on the date of installation for the Original Purchaser. Failure of the Original Purchaser to register the
registration card containing the Original Purchasers name, address, date of installation, model number and serial number of the Unit containing the Motor-Compressor within 30 days from the date of installation shall void this warranty. This additional warranty is only
available if the Motor-Compressor is inoperative due to defects in material or factory workmanship, as determined by Delfield in its sole judgement and discretion. The Original Purchaser shall be responsible for returning the defective Motor-Compressor to Delfield prepaid, F.O.B. at the address shown on the back cover of this manual.
The term “Original Purchaser” as used herein means that person, firm, association, or corporation for whom the Unit was originally installed.
The term “Motor-Compressor” as used herein does not include unit base, air or water cooled condenser, receiver, electrical accessories such as relay, capacitors, refrigerant controls, or condenser fan/motor assembly. This warranty does not cover labor charges incidental to the replacement of parts. This warranty further does not include any equipment to which said condensing unit is connected, such as cooling coils, temperature controls or refrigerant metering devices. This warranty shall be void if the Motor-Compressor, in Delfield’s sole judgement, has been subjected to misuse, neglect, alteration or accident, operated contrary to the recommendations specified by the Unit manufacturer, repaired or altered by anyone other than Delfield in any way so as, in Delfield’s sole judgment, to affect its quality or efficiency or if the serial number has been altered, defaced or removed. This Warranty does not apply to a Motor-Compressor in any Unit that has been moved from the location where it was originally installed. The addition of methyl chloride to the condensing unit or refrigeration system shall void this warranty.
governmental restrictions or restraints, strike, lockouts, injunctions,
fire, flood, acts of nature, short or reduced supply of raw materials,
or discontinuance of any part or the Motor-Compressor by the unit
manufacturer.
Replacement of a defective Motor-Compressor is limited to one (1)
Motor-Compressor by us during the four (4) year period. Delfield
shall replace the Motor-Compressor at no charge.
This warranty does not give the Original Purchaser of the Motor-
Compressor the right to purchase a complete replacement Motor-
Compressor of the same make or of another make. It further does
not permit the replacement to be made with a Motor-Compressor
of another kind unless authorized by Delfield. In the event Delfield
authorizes the Original Purchaser to purchase a replacement Motor-
Compressor locally, only the wholesale cost of the Motor-Compressor
is refundable.
Expressly excluded from this warranty are damages resulting from
spoilage of goods.
Except as provided in any applicable Standard One Year Limited
Warranty or applicable Service Labor Contract, the foregoing is
exclusive and in lieu of all other warranties, whether written or
oral, express or implied. This Warranty supersedes and excludes
any prior oral or written representations or warranties. Delfield
expressly disclaims any implied warranties of merchantability,
fitness for a particular purpose or compliance with any law, treaty,
rule or regulation relating to the Motor-Compressor, and the full
liability of Delfield for any breach of this warranty, will be as
provided in this warranty.
Other than any applicable Delfield Standard One year Limited
Warranty, this Delfield Additional Four Year Protection Plan and any
applicable Delfield Service Labor Contract, the Original Purchaser
agrees and acknowledges that no other warranties are offered or
provided in connection with or for the Motor-Compressor or any
part thereof.
In no event will Delfield be liable for special, incidental or consequential
damages, or for damages in the nature of penalties.
22
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Notes
Shelleyglas®/Shelleysteel™ Service and Installation Manual
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
23
Mt. Pleasant, MI Covington, TN
Thank you for choosing Delfield!
Help is a phone call away. Help our team of professional, courteous
customer service reps by having your model number and serial number
available at the time of your call (800) 733-8829
Model: ______________ S/N: _______________________
Installation Date: ____________
For a list of Delfield’s authorized parts depots,
visit our website at www.delfield.com
980 S. Isabella Rd., Mt. Pleasant, MI 48858, U.S.A. • (989) 773-7981 or (800) 733-8829 • Fax (989) 773-3210 • www.delfield.com
Delfield reserves the right to make changes in design or specifications without prior notice. ©2010 The Delfield Company. All rights reserved. Printed in the U.S.A.
DMSG_SS 09/10
Loading...