Delfield 18691BUCM Service Manual

18600 Series and CTP-NB
CAUTION
Service and Installation Manual
Please read this manual completely before attempting to install or operate this equipment! Notify carrier of damage! Inspect all components immediately. See page 2.
18600PTL
Pizza Tables with LiquiTec® Rail
18600PDL
Dual LiquiTec® Rail Prep Table
IMPORTANT INFORMATION
18600PTBM
Pizza Tables with Raised Rail
18600BSTM
Work Table with Backsplash
READ BEFORE USE
Work Tables
CTP-NB
Countertop Condiment Rail
PLEASE SAVE THESE INSTRUCTIONS!
July 2011
18600 and CTP-NB Series Service and Installation Manual
Contents
Receiving & Inspecting Equipment ...................................................... 2
Specifications ........................................................................................ 3
Refrigerant Charges .............................................................................. 4
Installation ............................................................................................ 4
Operation
18600PTBM & PTL Series ................................................................ 5
18600BUCM & BSTM Series ............................................................ 5
18600PDL Series ............................................................................... 6
CTP-NB Series ................................................................................... 6
Pressure Control Settings ..................................................................... 7
Temperature Control Settings ............................................................... 7
Care And Cleaning ..............................................................................8-9
Wiring Diagram
18600PTBM & PTL Series .............................................................. 10
18600BUCM & BSTM Series .......................................................... 11
18600PDL ........................................................................................ 11
CTP-NB Series ................................................................................. 12
Replacement Parts ......................................................................... 13-22
Standard Labor Guidelines.................................................................. 23
Standard Warranties ......................................................................24-26
Notes ................................................................................................... 27
Serial Number Information
The serial number on 18600 Series units is located on the electrical specifications tag affixed inside the compressor section next to the pressure control.
The serial number on CTP-NB Series units is located on the front of the unit.
Always have the serial number of your unit available when calling for parts or service.
Warranty may be deemed invalid if other than authorized OEM (original equipment manufacture) replacement parts are used in Delfield equipment.
©2011 The Delfield Company. All rights reserved. Reproduction without written permission is prohibited. “Delfield” is a registered trademark of The Delfield Company.
Receiving And Inspecting The Equipment
Even though most equipment is shipped crated, care should be taken during unloading so the equipment is not damaged while being moved into the building.
1. Visually inspect the exterior of the package and skid or container. Any damage should be noted and reported to the delivering carrier immediately.
2. If damaged, open and inspect the contents with the carrier.
3. In the event that the exterior is not damaged, yet upon opening, there is concealed damage to the equipment notify the carrier. Notification should be made verbally as well as in written form.
4. Request an inspection by the shipping company of the damaged equipment. This should be done within 10 days from receipt of the equipment.
2
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
5. Check the lower portion of the unit to be sure legs or
6. Also open the compressor compartment housing and
7. Freight carriers can supply the necessary damage forms
8. Retain all crating material until an inspection has been
Uncrating the Equipment
First cut and remove the banding from around the crate. Remove the front of the crate material, use of some tools will be required. If the unit is on legs remove the top of the crate and lift the unit off the skid. If the unit is on casters it can be "rolled" off the skid.
casters are not bent.
visually inspect the refrigeration package. Be sure lines are secure and base is still intact.
upon request.
made or waived.
18600 and CTP-NB Series Service and Installation Manual
Specifications
18600PTBM Pizza tables with raised rail
Model
18648PTBM 6 (1) 27” 1 124 3.95 10.23 470/441 2001/952 1/4 115/60/1 10.0 5-15P 520/236
18660PTBM 7 19” & 27” 2 70/124 6.51 15.12 694/617 2409/1208 1/3 115/60/1 12.0 5-15P 575/260
18672PTBM 9 (2) 27” 2 124 7.9 18.10 776/794 2967/1587 1/2 115/60/1 14.0 5-20P 635/288
18691PTBM 11 (2)27” & (1) 19” 3 124/70 10.29 24.48 1062/1058 3537/1865 1/2 115/60/1 14.0 5-20P 770/350
18699PTBM 12 (3) 27” 3 124 11.85 27.46 1144/1147 3537/1945 1/2 115/60/1 14.0 5-20P 805/365
186114PTBM 14 (3) 32” 3 140 14.46 33.05 1297/1323 5169/2433 3/4 115/60/1 16.0 5-20P 927/420
1/3 Pan Size
Capacity # Of Doors
18600BUCM Work tables
Model # Of Doors
18648BUCM (1) 27” 1 124 3.95 10.23 475/NA 1462/NA 1/5 115/60/1 8.0 5-15P 390/177
18660BUCM 19” & 27” 2 70/124 6.51 15.12 686/NA 1462/NA 1/5 115/60/1 8.0 5-15P 435/197
18672BUCM (2) 27” 2 124 7.90 18.10 856/NA 2261/NA 1/4 115/60/1 10.0 5-15P 495/225
18691BUCM (2)27” & (1) 19” 3 124/70 10.29 24.48 1169/NA 2261/NA 1/4 115/60/1 10.0 5-15P 535/243
18699BUCM (3) 27” 3 124 11.85 27.46 1220/NA 2591/NA 1/3 115/60/1 12.0 5-15P 594/269
186114BUCM (3) 32” 3 106 14.46 37.24 1373/NA 2591/NA 1/3 115/60/1 12.0 5-15P 685/310
# Of
Shelves
# Of
Shelves
Shelf Max
Load (LBS)
Shelf Max
Load (LBS)
Shelf Area
2
FT
Shelf Area
2
FT
Storage
Cap. FT
Storage
Cap. FT
3
3
BTU Load
Base/Rail
BTU Load Base/Rail
BTU Sys. Cap.
Base/Rail H.P.
BTU Sys. Cap.
Base/Rail H.P.
Voltz/Hertz/
Phase Amps
Voltz/Hertz/
Phase Amps
NEMA
Plug
NEMA
Plug
Ship Weight
LBS/KG
Ship Weight
LBS/KG
18600BSTM Work table with backsplash
# Of
Model # Of Doors
18648BSTM (1) 27” 1 124 3.95 10.23 475/NA 1462/NA 1/5 115/60/1 8.0 5-15P 390/177
18660BSTM 19” & 27” 2 70/124 6.51 15.12 686/NA 1462/NA 1/5 115/60/1 8.0 5-15P 435/197
18672BSTM (2) 27” 2 124 7.90 18.10 856/NA 2261/NA 1/4 115/60/1 10.0 5-15P 495/225
18691BSTM (2)27” & (1) 19” 3 124/70 10.29 24.48 1169/NA 2261/NA 1/4 115/60/1 10.0 5-15P 535/243
18699BSTM (3) 27” 3 124 11.85 27.46 1220/NA 2591/NA 1/3 115/60/1 12.0 5-15P 594/269
186114BSTM (3) 32” 3 106 14.46 37.24 1373/NA 2591/NA 1/3 115/60/1 12.0 5-15P 685/310
Shelves
Shelf Max
Load (LBS)
Shelf Area
2
FT
Storage
Cap. FT
3
BTU Load Base/Rail
BTU Sys. Cap.
Base/Rail H.P.
Voltz/Hertz/
Phase Amps
NEMA
Plug
Ship Weight
LBS/KG
18600PTL Pizza table with LiquiTec® rail
Model
18648PTL 6 (1) 27” 1 124 3.95 10.23 470/441 2001/952 1/4 115/60/1 10.0 5-15P 520/236
18672PTL 9 (2) 27” 2 124 7.90 18.10 776/794 2967/1587 1/2 115/60/1 14.0 5-20P 635/288
18699PTL 12 (3) 27” 3 124 11.85 27.46 1144/1147 3537/1945 1/2 115/60/1 14.0 5-20P 805/365
1/3 Pan Size
Capacity # Of Doors
# Of
Shelves
Shelf Max
Load (LBS)
Shelf Area
2
FT
Storage
Cap. FT
3
BTU Load Base/Rail
BTU Sys. Cap.
Base/Rail H.P.
Voltz/Hertz/
Phase Amps
NEMA
Plug
Ship Weight
LBS/KG
18600PDL Pizza table with Dual LiquiTec® rails
Model
18648PDL 6 (1) 27” 1 124 3.95 10.23 424/1058 2001/1865 1/5,
18672PDL 9 (2) 27” 2 124 7.90 18.10 703/1588 2001/3174 1/5,
1/3 Pan Size
Capacity # Of Doors
# Of
Shelves
Shelf Max
Load (LBS)
Shelf Area
2
FT
Storage
Cap. FT
3
BTU Load Base/Rail
BTU Sys. Cap.
Base/Rail H.P.
Voltz/Hertz/
Phase Amps
115/60/1 10.1 5-20P 691/313
1/3
115/60/1 12.7 5-20P 873/396
1/2
NEMA
Plug
Ship Weight
LBS/KG
CTP-NB Counter top containment rail
Model
CTP8146-NB 4 5 305 523 1/5 115/60/1 4.0 5-15P 121/54.9
CTP8160-NB 6 7 462 653 1/5 115/60/1 4.0 5-15P 158/71.7
1/3 Pan Size
Capacity # Of Adapter Bars BTU Load
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
BTU System
Capacity H.P.
Voltz/Hertz/
Phase Amps
NEMA
Plug
Ship Weight
LBS/KG
3
18600 and CTP-NB Series Service and Installation Manual
CAUTION
Refrigerant Charges
Refrigerant Charges For 18600 Series Units:
18648-PTBM & PTL ..........16 oz. (454g)
18660-PTBM................24 oz. (680g)
18672-PTBM & PTL ..........32 oz. (907g)
18691-PTBM................32 oz. (907g)
18699-PTBM & PTL ..........32 oz. (907g)
186114-PTBM..............48 oz. (1361g)
18648-BUCM & BSTM ........16 oz. (454g)
Refrigerant Charges For CTP-NB Series Units:
CTP8146-NB .................8 oz. (227g)
CTP8160-NB .................8 oz. (227g)
CTP8175-NB ................16 oz. (454g)
Installation
Location
These units are intended for indoor use only. Be sure the location chosen has a floor strong enough to support the total weight of the cabinet and contents. A fully loaded 72” long model may weigh as much as 1200 pounds. Reinforce the floor as necessary to provide for maximum loading.
For the most efficient refrigeration, be sure to provide good air circulation inside and out.
Inside cabinet: Do not pack refrigerator so full that air cannot circulate. Outside cabinet: Be sure that the unit has access to ample air. Avoid hot corners and locations near stoves and ovens. It is recommended that the unit be installed no closer than 1” from any wall. PDL models also require 14” (36cm) clearance at the top and 6” (15cm) clearance at the bottom (casters).
18660-BUCM & BSTM ........16 oz. (454g)
18672-BUCM & BSTM ........16 oz. (454g)
18691-BUCM & BSTM ........16 oz. (454g)
18699-BUCM & BSTM ........24 oz. (680g)
186114-BUCM & BSTM .......24 oz. (680g)
18648PDL.................40 oz. (1134g)
18672PDL.................56 oz. (1588g)
Plumbing
Self-contained models are standard with a condensate evaporator. If, for some reason, a unit does not have a condensate evaporator, or the evaporator fails, the unit’s drain must have an outlet to an appropriate drainage area or container.
Moisture collecting from improper drainage can create a slippery surface on the floor and a hazard to employees. It is the owner’s responsibility to provide a container or outlet for drainage.
Electrical connection
Refer to the amperage data on page 3, the serial tag, your local code or the National Electrical Code to be sure the unit is connected to the proper power source. A protected circuit of the correct voltage and amperage must be run for con nec tion of the line cord, or permanent connection to the unit.
Leveling
A level cabinet looks better and will perform better because the drain pan will drain properly, the doors will line up with the frames properly, and the cabinet will not be subject to undue strain. Some models have casters for your convenience, for ease of cleaning underneath and for mobility. It is important that the unit be installed in a stable condition with the front casters locked before operating.
4
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
The power switch must be turned to OFF and the unit disconnected from the power source whenever performing service or maintenance functions. Never operate the unit without the louvered panel in place!
Operation: 18600PTBM & PTL Series
18600 and CTP-NB Series Service and Installation Manual
Product should be loaded into the unit with care. Failure to heed these recommendations could result in damage to the interior of the cabinet or the blower coil.
This unit is equipped with two ON/OFF switches located behind the louvered machine compartment panel. The unit’s com pres sor and all evaporator fans will begin op er at ing when the main power switch is turned to the ON position. Tem per a ture ranges for the base are 36°F to 40°F.
The switch labeled rail is for the raised rail. The rail switch is accessible through a 1.5” diameter hole in the louvered panel. Turning this switch to the ON position will activate the refrigeration for the rail. Temperature ranges for the raised rail are 33°F to 41°F.
Product located in the rail must be removed at the end of day. This allows you to turn the rail off at night to save energy and the rail will have time to defrost as needed.
A minimum of one hour of off time per day with the pans removed from the rail is required to properly defrost the rail.
The power must be turned to OFF and the unit disconnected from the power source whenever performing service or maintenance functions. Never operate the unit without the louvered panel in place!
All R404A models have a high pressure limiting device. Under severe overloading conditions, or in the event of a condenser fan failure or a plugged or blocked condenser, this device may shut down the refrigeration system. This device will automatically reset, but determining the cause of the high pressure condition should be investigated by a qualified refrigeration technician.
Refrigerator Evaporator Fan Operation
When the refrigerator is initially powered up or immediately following a power outage the unit will begin cooling after a 3-6 minute delay. During normal operation the evaporator fan pulses independently of the compressor as dictated by the controller as follows:
1. During the cooling mode, compressor and evaporator fan run simultaneously.
2. During the compressor off mode, evaporator fan pulses three minutes on and three minutes off.
3. During an actual defrost event other than the off-cycle defrost, compressor stays off but the evaporator fan runs continuously.
Cooling Cycle Defrost Cycle
Compressor On Compressor Off Compressor Off
Evap Fan OnEvap Fan
Off
X
Evap Fan OnEvap Fan
Off
Cycles On 3-Min, Off
3-Min
Evap Fan OnEvap Fan
Off
X
Operation: 18600BUCM & BSTM Series
After turning the ON/OFF switch to ON, the units compressor will begin operating. Delfield refrigerated bases are designed to maintain an operational temperature of 36°F to 40°F.
Product should be loaded into the unit with care. Failure to heed these recommendations could result in damage to the interior of the cabinet or the blower coil.
Overloading the storage area, restricting the air flow and continuous opening and closing of the doors and drawers will hamper the units ability to maintain operational temperature.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Refrigerator Evaporator Fan Operation
When the refrigerator is initially powered up or immediately following a power outage the unit will begin cooling after a 3-6 minute delay. During normal operation the evaporator fan pulses independently of the compressor as dictated by the controller as follows:
1. During the cooling mode, compressor and evaporator fan run
2. During the compressor off mode, evaporator fan pulses three
3. During an actual defrost event other than the off-cycle defrost,
simultaneously.
minutes on and three minutes off.
compressor stays off but the evaporator fan runs continuously.
Cooling Cycle Defrost Cycle
Compressor On Compressor Off Compressor Off
Evap Fan OnEvap Fan
Off
X
Evap Fan OnEvap Fan
Off
Cycles On 3-Min, Off
3-Min
Evap Fan OnEvap Fan
X
Off
5
18600 and CTP-NB Series Service and Installation Manual
Operation: 18600PDL Series
Product should be loaded into the unit with care. Failure to heed these recommendations could result in damage to the interior of the cabinet or the blower coil.
This unit is equipped with two ON/OFF switches located behind the louvered machine compartment panel. The unit’s com pres sor and all evaporator fans will begin op er at ing when the main power switch is turned to the ON position. Tem per a ture ranges for the base are 36°F to 40°F (2°C to 4°C).
The switch labeled rail is for the raised rails. The rail switch is accessible through a 1.5” (3.8cm) diameter hole in the louvered panel. Turning this switch to the ON position will activate the refrigeration for the rails. Temperature ranges for the raised rails are 33°F to 41°F (0.5°C to 5°C).
Product located in the rails must be removed at the end of day. This allows you to turn the rails off at night to save energy and the rails will have time to defrost as needed.
A minimum of one hour of off time per day with the pans removed from the rails is required to properly defrost the rails.
The power must be turned to OFF and the unit disconnected from the power source whenever performing service or maintenance functions. Never operate the unit without the louvered panel in place!
All R404A models have a high pressure limiting device. Under severe overloading conditions, or in the event of a condenser fan failure or a plugged or blocked condenser, this device may shut down the refrigeration system. This device will automatically reset, but determining the cause of the high pressure condition should be investigated by a qualified refrigeration technician.
Refrigerator Evaporator Fan Operation
When the refrigerator is initially powered up or immediately following a power outage the unit will begin cooling after a 3-6 minute delay. During normal operation the evaporator fan pulses independently of the compressor as dictated by the controller as follows:
1. During the cooling mode, compressor and evaporator fan run simultaneously.
2. During the compressor off mode, evaporator fan pulses three minutes on and three minutes off.
3. During an actual defrost event other than the off-cycle defrost, compressor stays off but the evaporator fan runs continuously.
Cooling Cycle Defrost Cycle
Compressor On Compressor Off Compressor Off
Evap Fan OnEvap Fan
Off
X
Evap Fan OnEvap Fan
Off
Cycles On 3-Min, Off
3-Min
Evap Fan OnEvap Fan
Off
X
Operation: CTP-NB Series
The unit is equipped with one ON/OFF switch located on the right end of the unit. The unit’s com pres sor will begin op er at ing when this switch is turned to the ON position. Tem per a ture ranges for the rail are 33°F to 41°F.
Product located in the rail must be removed at the end of day. This allows you to turn the rail OFF at night to save energy and the rail will have time to defrost as needed.
6
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
A minimum of one hour of off time per day with the pans removed from the rail is required to properly defrost the rail.
The power switch must be turned to OFF and the unit disconnected from the power source whenever performing service or maintenance functions. Never operate the unit without the louvered panel in place!
Pressure Control Settings
The factory recommended low-pressure control settings for 18600PTBM’s are: 55psi cut-in and 30psi cut-out
to maintain proper temperature for product in the rail. The interior temperature is controlled by the thermostat mounted in the mechanical compartment.
The factory recommended low-pressure control settings for 18600PTL’s are: 20psi (1.38bar) cut-in and 10psi
(0.70bar) cut-out. The base and rail temperatures are controlled by the thermostats mounted in the machine compartment.
A pressure control is located in the machine compartment. An adjustable control has the word COLDER on the knob, with an arrow to indicate the adjustment direction. These controls are field adjustable and do not require a service agent.
In attempting to adjust the pressure control, you can do damage to your unit by accidentally adjusting the differential. Please make small incremental adjustments if a temperature adjustment is necessary, please contact the service department at Delfield (800) 733-8829 or your local service agent. Delfield is not responsible for charges incurred while having the pressure control adjusted.
18600 and CTP-NB Series Service and Installation Manual
Temperature Control Settings
A thermostat controls temperature in the 18600PTBM base, 18600PTL base, 18600PTL rail, BUCM, BSTM, 18600PDL
base and 18600PDL rail. Thermostats are located in the machine compartment. They
are field adjustable and do not require a service agent. The factory setting is 2.5. Set toward 1 for higher temperatures and toward 7 for lower temperatures.
Please make small incremental adjustments if a temperature adjustment is necessary. Contact the service department at Delfield +1 (989) 773­7981 or your local service agent for additional assistance. Delfield is not responsible for charges incurred while adjusting the thermostat.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
7
18600 and CTP-NB Series Service and Installation Manual
Care & Cleaning
Door Gasket Maintenance
Door gaskets require regular cleaning to prevent mold and mildew build up and also to retain the elasticity of the gasket. Gasket cleaning can be done with the use of warm soapy water. Avoid full strength cleaning products on gaskets as this can cause them to become brittle and crack. Never use sharp tools or knives to scrape or clean the gasket. Gaskets can be easily replaced and do not require the use of tools or an authorized service person. The gaskets are “Dart” style and can be pulled out of the groove in the door and new gaskets can
be “pressed” back into place.
Drain Maintenance - Base
Each unit has a drain located inside the unit that removes the condensation from the evaporator coil and routes it to an external condensate evaporator pan. Each drain can become loose or disconnected during normal use. If you notice water accumulation on the inside of the unit be sure the drain tube is connected to the evaporator drain pan. If water is collecting underneath the unit make sure the end of the drain tube is in the condensate evaporator in the machine compartment. The leveling of the unit is important as the units are designed to drain properly when level. Be sure all drain lines are free of obstructions.
Drawer Maintenance
Drawer Assembly Cleaning
The drawer assembly is designed to be cleaned easily. Both drawer and tracks are removable without tools. The drawer tracks are dishwasher safe or can be cleaned in a sink with detergents and a soft bristle brush. Drawers and tracks should be cleaned on a weekly basis.
Remove Drawers
Pull the drawer box out until it stops. Lift up on the drawer front and pull the drawer box completely out. Using a soft bristle brush, clean the track on the bottom of the drawer box. When finished, it should be wiped clean of all food and debris.
Tracks
The drawer box assembly must be removed. Pull the drawer tracks out until they hit a stop. Locate blue safety clips towards the back of each drawer track. Blue safety clips have a tab on the top. Push
the tab back until it clicks. Lift up and pull the drawer tracks all the way out of the drawer cage. The drawer tracks are dishwasher safe
tab on top of
blue safety clip
tracks should be cleaned on a weekly basis. Using a soft bristle brush, wash the track making sure each roller is thoroughly cleaned. The drawer cage should be cleaned with a soft bristle brush, removing any food and debris gathered on the bottom ledge. Once it’s cleaned thoroughly with a soft bristle brush, wipe remaining debris clean with a soft towel.
Reassembly
Push the drawer tracks into the drawer cage. The blue safety clip must remain pushed towards the back. Lift up and slide the drawer track all the way into the drawer cage. The blue safety clip will lock
or can be cleaned in a sink with detergents and a soft bristle brush. Drawers and
in place automatically. Once all tracks are replaced, insert the drawer box. Rest the drawer box bottom track on the front track roller. Then push the drawer back in place SLOWLY. When the drawer box is about half way in you will hit a STOP. You must lift the front of the drawer up approximately ½” (1.3cm) to continue inward. Clean tracks as often as possible. The cleaner the tracks are the better they will operate.
Caster Maintenance
Wipe casters with a damp cloth monthly to prevent corrosion.
The power switch must be turned to OFF and the unit disconnected from the power source whenever performing service, maintenance functions or cleaning
the refrigerated area.
Refrigerators and Freezers
The interior and exterior can be cleaned using soap and warm water. If this isn’t sufficient, try ammonia and water or a nonabrasive liquid cleaner. When cleaning the exterior, always rub with the “grain” of the stainless steel to avoid marring the finish. Do not use an abrasive cleaner because it will scratch the stainless steel and can damage the
breaker strips and gaskets.
Stainless Steel Care and Cleaning
To prevent discoloration of rust on stainless steel several important steps need to be taken. First, we need to understand the properties of stainless steel. Stainless steel contains 70- 80% iron, which will rust. It also contains 12-30% chromium, which forms an invisible passive film over the steels surface, which acts as a shield against corrosion. As long as the protective layer is intact, the metal is still stainless. If the film is broken or contaminated, outside elements can begin to breakdown the steel and begin to form discoloration of rust. Proper cleaning of stainless steel requires soft cloths or plastic
scouring pads.
NEVER USE STEEL PADS, WIRE BRUSHES OR SCRAPERS!
Cleaning solutions need to be alkaline based or non-chloride cleaners. Any cleaner containing chlorides will damage the protective film of the stainless steel. Chlorides are also commonly found in hard water, salts, and household and industrial cleaners. If cleaners containing chlorides are used be sure to rinse repeatedly and dry thoroughly. Routine cleaning of stainless steel can be done with soap and water. Extreme stains or grease should be cleaned with a non-abrasive cleaner and plastic scrub pad. Always rub with the grain of the steel. There are stainless steel cleaners available which can restore and preserve the finish of the steels protective layer. Early signs of stainless steel breakdown are small pits and cracks. If this has begun, clean thoroughly and start to apply stainless steel cleaners in attempt
to restore the passivity of the steel.
Never use an acid based cleaning solution! Many food products have an acidic content, which can deteriorate the finish. Be sure to clean the stainless steel surfaces of ALL food products. Common items include, tomatoes,
peppers and other vegetables.
Cleaning the Condenser Coil
In order to maintain proper refrigeration performance, the condenser fins must be cleaned of dust, dirt and grease regularly. It is recommended that this be done at least every three months.
8
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Care & Cleaning, continued
If conditions are such that the condenser is totally blocked in three months, the frequency of cleaning should be increased. Clean the condenser with a vacuum cleaner or stiff brush. If extremely dirty, a commercially available condenser cleaner may be required.
Failure to maintain a clean condenser coil can initially cause high temperatures and excessive run times. Continuous operation with a dirty or clogged condenser coil can result in compressor failure. Neglecting the condenser coil cleaning procedures will void any warranties associated with the compressor and cost to replace the compressor.
Never use a high-pressure water wash for this cleaning procedure as water can damage the electrical
components located near or at the condenser coil.
Doors/Hinges
Over time and with heavy use doors the hinges may become loose. If this happens tighten the screws that mount the hinge brackets to the frame of the unit. Loose or sagging doors can cause the hinges to pull out of the frame, which may damage both the doors and the hinges. In some cases this may require qualified service agents or maintenance
personnel to perform repairs.
Do not place hot pans on/against the blue ABS liner. Do not throw items into the storage area. Failure to follow these recommendations could result in damage to the interior of the cabinet or to the blower coil. Overloading the storage area, restricting the airflow, and continuous opening and closing of the doors and drawers will hamper the units ability to maintain
operational temperature.
18600 and CTP-NB Series Service and Installation Manual
Continuous opening and closing of the doors will hamper the unit’s ability to maintain optimum refrigeration temperature. Top section is not intended for overnight storage. Product should be removed from pans. Pans can remain in unit while empty.
Refrigerated rail units
Product in the rail should be removed to the refrigerated base at the end of the day. This allows you to turn the rail off at night to save energy and to defrost the rail. It also helps maintain product quality. The standard wrapped refrigerated rail units are controlled by a low­pressure control that is set to maintain the proper rail temperature. An on/off switch is also provided for the rail and is required to be shut off at night. With a LiquiTec rail a thermostat is provided to maintain rail temperature as well as the rail on/off switch. The LiquiTec rail is required to be shut off at night as well to allow for defrosting. To ensure product quality in the rail it is recommended that product be
rotated every four hours.
If adding any item to the unit, be sure to keep in mind the location of the refrigeration lines on wrapped rail units. A refrigeration leak in a rail is extremely difficult and costly to repair. In some cases it cannot be repaired
at all.
Preventing blower coil corrosion
To help prevent corrosion of the blower coil, store all acidic items, such as pickles and tomatoes, in sealable containers. Immediately
wipe up all spills.
Units with pans should be operated with pans in place. Operating the unit without all pans in place will lower
efficiency and may damage the unit.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
9
Loading...
+ 19 hidden pages