In these instructions, various danger levels are employed to draw the
user’s attention to particular information. In so doing, we wish to
safeguard the user’s safety, obviate hazards and guarantee correct
operation of the appliance.
DANGER
Risk of a dangerous situation causing serious physical
injury.
WARNING
Risk of a dangerous situation causing slight physical
injury.
CAUTION
Risk of material damage.
Signals important information.
¼Signals a referral to other instructions or other pages in the
instructions.
1.1.2.Symbols used on the equipment
4
~
Protective earthing
Alternating current
Before installing and commissioning the device, read
carefully the instruction manuals provided.
Dispose of the used products in an appropriate recovery
and recycling structure.
03/12/2013 - 300026082-001-02
This appliance must be connected to the protective earth.
4
12
M002628-A
1. Introduction
1.2Abbreviations
EGC 25
Caution: danger, live parts.
Disconnect the mains power prior to any operations.
4 3CE: Collective conduit for sealed boiler
4 DHW: Domestic hot water
4 Hi: Lower heating value LHV (Nett)
4 Hs: Higher heating value HHV (Gross)
4 PPS: Polypropylene hardly inflammable
4 PCU: Primary Control Unit - PCB for managing burner operation
4 PSU: Parameter Storage Unit - Parameter storage for PCBs
PCU and SU
4 SCU: Secondary Control Unit - control panel PCB
4 SU: Safety Unit - Safety PCB
4 HRU: Heat Recovery Unit
4 3WV: 3-way valve
4 HL: High Load - DHW tank with plate exchanger
4 SL: Standard Load - DHW tank with coil
4 SHL: Solar High Load - Solar DHW tank with plate exchanger
4 SSL: Solar Standard Load - Solar DHW tank with coil
1.3General
1.3.1.Manufacturer’s liability
Our products are manufactured in compliance with the requirements
of the various applicable European Directives. They are therefore
delivered with [ marking and all relevant documentation.
In the interest of customers, we are continuously endeavouring to
make improvements in product quality. All the specifications stated in
this document are therefore subject to change without notice.
Our liability as the manufacturer may not be invoked in the following
cases:
4 Failure to abide by the instructions on using the appliance.
4 Faulty or insufficient maintenance of the appliance.
4 Failure to abide by the instructions on installing the appliance.
5
03/12/2013 - 300026082-001-02
EGC 251. Introduction
1.3.2.Installer’s liability
The installer is responsible for the installation and inital start up of the
appliance. The installer must respect the following instructions:
4 Read and follow the instructions given in the manuals provided
with the appliance.
4 Carry out installation in compliance with the prevailing legislation
and standards.
4 Perform the initial start up and carry out any checks necessary.
4 Explain the installation to the user.
4 If a maintenance is necessary, warn the user of the obligation to
check the appliance and maintain it in good working order.
4 Give all the instruction manuals to the user.
1.3.3.User’s liability
To guarantee optimum operation of the appliance, the user must
respect the following instructions:
1.4Certifications
4 Read and follow the instructions given in the manuals provided
with the appliance.
4 Call on qualified professionals to carry out installation and initial
start up.
4 Get your installer to explain your installation to you.
4 Have the required checks and services done.
4 Keep the instruction manuals in good condition close to the
appliance.
This appliance is not intended to be used by persons (including
children) whose physcial, sensory or mental capacity is impaired or
persons with no experience or knowledge, unless they have the
benefit, through the intermediary of a person responsible for their
safety, of supervision or prior instructions regarding use of the
appliance. Care should be taken to ensure that children do not play
with the appliance.
To prevent hazardous situations from arising, if the mains lead is
damaged it must be replaced by the original manufacturer, the
manufacturer’s dealer or another suitably skilled person.
03/12/2013 - 300026082-001-02
CE identification no
NOx classification
Type of connection Chimney: B23, B
CE-0085CM0178
5 (EN 297 pr A3, EN 483)
Flue gas outlet: C
C
93(x)
33
13(x)
, C
33(x)
, C
43(x)
, C53, C
83(x)
,
6
2. Safety instructions and recommendationsEGC 25
2Safety instructions and
recommendations
2.1Safety instructions
DANGER
If you smell gas:
1.Do not use a naked flame, do not smoke, do not
operate electrical contacts or switches ( doorbell,
light, motor, lift, etc..).
2.Shut off the gas supply.
3.Open the windows.
4.Evacuate the premises.
5.Call your fitter.
DANGER
If you smell flue gases:
1.Switch the appliance off.
2.Open the windows.
3.Evacuate the premises.
4.Call your fitter.
WARNING
Depending on the settings of the appliance:
4The temperature of the flue gas conduits may exceed
60°C.
4The temperature of the radiators may reach 85°C.
4The temperature of the domestic hot water may reach
65°C.
CAUTION
Do not neglect to service the appliance:
4For completely safe and optimum operation, you
must have your boiler regularly serviced by an
approved installer.
7
03/12/2013 - 300026082-001-02
EGC 252. Safety instructions and recommendations
2.2Recommendations
WARNING
Only qualified professionals are authorised to work on the
appliance and the installation.
4 Regularly check the water pressure in the installation (minimum
pressure 0.8 bar, recommended pressure between 0.08 and 1.5
bar).
4 Keep the appliance accessible at all times.
4 Never remove or cover labels and rating plates affixed to the
appliance. Labels and rating plates must be legible throughout the
entire lifetime of the appliance.
4 The appliance should be on Summer or Antrifreeze mode rather
than switched off to guarantee the following functions:
- Anti blocking of pumps
- Antifreeze protection
03/12/2013 - 300026082-001-02
8
3. DescriptionEGC 25
3Description
3.1Operating principle
3.1.1.Gas/air setting
Air is sucked in by the fan and the gas injected into the venturi
attached to the fan inlet. The fan rotation speed modulates and adapts
to thermal energy requirements thanks to the temperatures measured
by the various sensors. The gas and air are mixed in the venturi, which
enables operation at a constant ratio. The noise of the venturi is
absorbed by a silencer attached to its inlet. The gas/air mixture is
carried to the burner in the top of the exchanger, guided by the premix channel.
3.1.2.Combustion
The burner heats the heating water circulating in the heat
exchanger. At a return temperature lower than around 55°C, the flue
gases cool down to a temperature lower than the dew point, thus
causing the condensation of the water vapour contained in the flue
gases in the lower section of the heat exchanger. The heat released
during this condensation process (the latent heat or condensing heat)
is also transferred to the heating water. The cooled combustion gases
are evacuated via the combustion gas outlet flue. The condensation
water is evacuated via a siphon.
9
03/12/2013 - 300026082-001-02
C003072-C
18
19
16
17
15
14
13
12
11
1234
10
9
5
6
7
8
EGC 253. Description
3.2Main parts
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Flue gas discharge pipe
Flue gas measuring point
Heat exchanger
Ignition/ionization electrode
Box for the control PCBs
Control panel
Command module
Water pressure sensor
Circulation pump
Hydroblock
3-way valve
Safety valve
Casing
Expansion vessel
Combined venturi and gas valve unit
Fan
Air intake silencer
18
19
Mixer pipe
Automatic air vent
03/12/2013 - 300026082-001-02
10
-
)
L
m
rrr
ddd
T
y
1
2
SERVICE
°C°Fh
barPsi
% rpm
kW uA
x10 l/min
°CSt:
M002715-A
t
h
j
AB
EF
CD
-
)
L
m
r
r
r
d
d
d
T
y
1
2
SERVICE
°C°Fh
barPsi
% rpm
kW uA
x10 l/min
°CSt:
M002716-A
t
h
j
3. DescriptionEGC 25
3.3Control panel
3.3.1.Description of the keys
11
A
B
C
D
E
F
3.3.2.Description of the display
Key functions
n
G
t
d
[-]
Return button j, Escape G or Manual reset t
Heating temperature button d or [-]
DHW temperature button r or [+]S [Enter] Key
) [Chimney-sweeping] keys
Press keys A and B simultaneously
f [Menu] keys
Press keys C and D simultaneously
Back to the previous level without saving the
modifications made
Manual reset
Central heating function:
Access to the max. heating temperature parameter.
To reduce a value
03/12/2013 - 300026082-001-02
-
)
L
m
rrr
d
d
d
T
y
1
2
SERVICE
°C°Fh
barPsi
% rpm
kW uA
x10 l/min
°CSt:
M002717-A
t
h
j
-
)
L
m
rrr
ddd
T
y
1
2
SERVICE
°C°Fh
barPsi
% rpm
kW uA
x10 l/min
°CSt:
M002718-A
t
h
j
-
)
L
m
rrr
ddd
T
y
1
2
SERVICE
°C°Fh
barPsi
% rpm
kW uA
x10 l/min
°CSt:
M002719-A
t
h
j
-
)
L
m
rrr
ddd
T
y
1
2
SERVICE
°C°Fh
barPsi
% rpm
kW uA
x10 l/min
°CSt:
M002720-A
t
h
j
EGC 253. Description
r
[+]
®
Operating modes
n
d
D
r
S
m
DHW function:
Access to sanitary hot water temperature parameter.
To increase a value
Access the selected menu or confirm a value modification
State heating pump
Heating programme deactivated:
The heating function is deactivated
State DHW pump
DHW off
Manual mode
Flame output level
n
e
r
t
y
System pressure
n
bar
Low output level 0 - 25 %
Average output level 25 - 50 %
High output level 50 - 75 %
Output level 75 - 100 %
Pressure indicator:
The symbol is displayed next to the installation’s pressure
value. If no water pressure sensor is connected, -.appears on the display
03/12/2013 - 300026082-001-02
12
-
)
L
m
rrr
ddd
T
y
1
2
SERVICE
°C°Fh
barPsi
% rpm
kW uA
x10 l/min
°CSt:
M002721-A
t
h
j
3. DescriptionEGC 25
Other information
n
"
!
)
-
K
\
a
I
M
a
User menu:
Parameters at user level can be changed
Information menu:
Reading the various current values
Chimney-sweeping position:
Forced full or part load for CO2 measurement
Service menu:
Parameters at installer level can be changed
Display with the symbols:
$ + K + Z (Maintenance message)
Hour counter menu:
Readout of the operating hours, number of successful
starts and hours on mains supply
Blocking:
After 5 resets in under 1 hour, the appliance should be
switched off and switched on again before resetting
Outside temperature sensor present
The symbol is displayed when the boiler pump is
operating
Defect:
Boiler indicates a fault. This is indicated by an E code
and a flashing display
13
03/12/2013 - 300026082-001-02
EGC 25
4Operating the appliance
4.1Putting the appliance into operation
1. Check the water pressure in the installation shown on the control
panel display.
If the water pressure is lower than 0,8 bar, more water
should be added. If necessary, top up the water level in the
heating system (recommended hydraulic pressure
between 1,5 and 2,0 bar).
2. Open the gas valve on the boiler.
3. Switch on the boiler.
4. The start-up cycle begins and cannot be interrupted. During the
start-up cycle, the display shows the following information:
fK[xx
pK[xx
The version numbers are displayed alternately.
5. A vent cycle of a duration of around 3 minutes is carried out
automatically.
6. In standby mode, the screen usually displays 0, plus the water
pressure and the symbols d and r.
: Software version
: Parameter version
4. Operating the appliance
4.2Reading out measured values
The following current values can be read off the information menu
Q:
4 5t = State.
4 5v = Sub-status.
4 t1 = Flow temperature (°C).
4 t" = Return temperature (°C).
4 t3 = DHW tank temperature (°C).
4 t4 = Outside temperature (°C).
4 t5 = Solar boiler temperature (°C).
4 t6 = Solar panel temperature (°C).
4 5p = Internal set point (°C).
4 fl = Ionization current (µA).
4 Mf = Fan speed in rpm.
4 pr = Water pressure (bar (MPa)).
4 p; = Supplied relative heat output (%).
03/12/2013 - 300026082-001-02
14
)
r
d
bar
C003049-A
t
h
j
h
j
4x
2x
4. Operating the appliance
EGC 25
The current values can be read as follows:
1. Press the two f keys simultaneously. The symbol Q flashes.
2. Confirm using key S.
is displayed, alternating with the
5t
current status 3 (for example).
3. Press the [+] key.
sub-status
(for example).
30
4. Press the [+] key.
flow temperature
is displayed, alternating with the current
5v
is displayed, alternating with the current
t1
°C (for example).
60
5. Press the [+] key successively to scroll down the various
parameters.
t", t3, t4, t5, t6
6. Press the [+] key.
set point
°C (for example).
88
7. Press the [+] key.
ionization current
8. Press the [+] key.
fan rotation speed
9. Press the [+] key.
water pressure
#0
is displayed, alternating with the internal
5p
is displayed, alternating with the current
fl
µA (for example).
70
is displayed, alternating with the current
Mf
3000
pr
rpm (for example).
is displayed, alternating with the current
bar (for example). If no water pressure sensor
.
is connected, [-.-] appears on the display.
10.Press the [+] key.
modulation percentage
11.Press the [+] key. The readout cycle starts again with
is displayed, alternating with the current
p;
% (for example).
78
5t
.
12.Press the j key 2 times to return to the current operating mode.
0 = Comfort
1 = Energy-saving mode
2 = Management using a programmable thermostat
0 = No anticipation resistance for the ON/OFF thermostat
1 = Anticipation resistance for the ON/OFF thermostat
0 = Simple
1 = Comprehensive
2 = Automatic switching to simple after 3 minutes
3 = Automatic switching to simple after 3 minutes; Key blocking is
active
1 to 98 minutes
99 minutes = continuous
0 = Low
1 = High
setting
EGC 25
80
55
1
2
0
2
2
1
4.3.2.Modification of the user-level parameters
Parameters p1 to p8 can be modified by the user in order to meet
central heating and DHW comfort needs.
03/12/2013 - 300026082-001-02
16
)
r
d
bar
C003050-A
t
h
j
h
j
1x
2x
4. Operating the applianceEGC 25
CAUTION
Modification of the factory settings may be detrimental to
the functioning of the appliance.
1. Press the two keys f simultaneously and then key [+] until the
symbol W flashes on the menu bar.
2. Select the users menu using the key S.
flashing.
1
is displayed with
p[1
3. Press the S key a second time. The value 80°C appears and
flashes (for example).
4. Change the value by pressing the [-] or [+] key. In this example
using key [-] to
5. Confirm the value with the S key.
60
°C.
is displayed with
p[1
1
flashing.
6. Press the j key 2 times to return to the current operating mode.
4The parameters
same way as
p1
p2
to
are changed in the
p8
. After step 2, use the [+] key to
move to the required parameter.
4The parameters
temperature) and
(the maximum heating water
p1
(the maximum drinking water
p2
temperature) can also be modified using the quick
selection menu.
17
03/12/2013 - 300026082-001-02
)
m
r
d
bar
C003051-A
t
h
j
h
j
2x
2x
bar
d
C003052-A
1x
EGC 25
4. Operating the appliance
4.3.3.Setting the manual mode
In some cases it may be necessary to switch the boiler to manual
operation, For example, if the controller has not yet been
connected. The boiler can be switched to automatic or manual
operation under the symbol m. To do this, proceed as follows:
1. Press the two keys f simultaneously and then key [+] until the
symbol m flashes on the menu bar.
2. Press the S key:
or
The text
sensor is connected). The flow temperature is determined by the
internal heating curve.
or
The value of the minimum flow temperature.
3. Press the [-] or [+] key to increase this value temporarily in manual
operation.
4. Confirm the value with the S key. The boiler is now set to manual
operation.
5. Press the j key 2 times to return to the current operating mode.
with the current water pressure (only if an outside
Zv
4.3.4.Changing the heating temperature
If using an outside temperature sensor, the heating flow
temperature is adjusted automatically.
In summer, it is possible to reduce the heating flow temperature whilst
maintaining comfort. To do this, proceed as follows:
1. Press the d key 1 times.
2. The symbol d and the current temperature are displayed (the
temperature flashes, e.g.
85
°C).
3. Change the value by pressing the [-] or [+] key. In this example
using key [-] to
60
°C.
4. To confirm, press the S key.
It also possible to modify this setting using the parameter
.
p1
4.3.5.Modifying the domestic hot water
temperature setting
03/12/2013 - 300026082-001-02
It may be that a lower domestic hot water temperature will be sufficient
for your needs. Reduce this temperature and save energy. To do this,
proceed as follows:
18
C003053-A
r
1x
C003912-A
r
1x
1x
4. Operating the appliance
EGC 25
1. Press the r key 1 times.
2. The symbol r and the current temperature are displayed (the
temperature flashes, e.g.
60
°C).
3. Change the value by pressing the [-] or [+] key. In this example
using key [-] to
55
°C.
4. To confirm, press the S key.
4.3.6.Modifying the domestic hot water set point
temperature
To modify the set point of the solar tank (if connected), proceed as
follows
1. Press the r key for 3 seconds.
2. Symbols r and
(for example,
S;
3. Change the value by pressing the [-] or [+] key. In this example
using key [-] to
4. To confirm, press the S key.
and the current temperature are displayed
S;
and the temperature 60°C flash).
°C.
55
4.4Installation shutdown
4.5Antifreeze protection
CAUTION
Do not switch off the boiler.
If the central heating system is not used for a long period, we
recommend proceeeding as follows:
4 Press key d until OFF is displayed.
4 Press key r until OFF is displayed.
When the heating water temperature in the boiler is too low, the
integrated boiler protection system starts up. This protection functions
as follows:
4 If the water temperature is lower than 7°C, the heating pump starts
up.
4 If the water temperature is lower than 4°C, the boiler starts up.
4 If the water temperature is higher than 10°C, the boiler shuts down
and the circulation pump continues to run for a short time.
4 If the water temperature in the storage tank is less than 4°C, it is
reheated to its set point.
19
03/12/2013 - 300026082-001-02
T001507-B
EGC 25
5Checking and maintenance
5.1General instructions
The boiler does not require a lot of maintenance. Nevertheless, we
recommend having the boiler inspected and serviced at regular
intervals.
4 Maintenance and cleaning of the boiler must be carried out at least
once a year by a qualified technician.
4 Have the flues swept at least once a year or more, depending on
the regulations in force in your country.
CAUTION
4Maintenance operations must be done by a qualified
engineer.
4We recommend taking out a maintenance contract.
4Only original spare parts must be used.
4Make certain that the flues and chimneys are
connected, in good condition and not blocked.
4Do not modify nor block the condensate outlet(s).
4If a neutralisation system is installed, follow the
instructions delivered with the neutralisation system
for cleaning and servicing of this system.
5. Checking and maintenance
5.2Periodic checks
4 Check the water pressure in the installation (Menu
INFORMATION).
If the water pressure is lower than 0,8 bar, more water
should be added. If necessary, top up the water level in the
heating system (recommended hydraulic pressure
between 1,5 and 2,0 bar).
4 Carry out a visual check for the presence of any water leaks.
03/12/2013 - 300026082-001-02
20
1
2
3
4
T000181-B
5. Checking and maintenanceEGC 25
4 Open and close the radiator valves several times a year (this
prevents the valves from seizing up).
4 Clean the outside of the boiler using a damp cloth and a light
detergent.
CAUTION
Only a qualified professional is authorised to clean the
inside of the boiler.
21
03/12/2013 - 300026082-001-02
M002722-A
EGC 256. Troubleshooting
6Troubleshooting
6.1Error messages (Sub-status 9)
To display the current error code, proceed as follows:
1. Press the two f keys simultaneously. The symbol Q flashes.
2. Confirm using key S.
current status 3 (for example).
is displayed, alternating with the
5t
3. Press the [+] key. The display shows
value (
Code
Su:00 The PSU PCB is incorrectly configured Parameter error on the PSU PCB
Su:01 Maximum flow temperature exceededThe water flow in the installation is insufficient
Su:02 The increase in flow temperature has
Su:07 Maximum difference between the flow
Su:08 The RL inlet on the PCU PCB terminal
DescriptionChecking / solution
4Contact the professional who takes care of maintenance of the
appliance
4Check the circulation (direction, pump, valves)
The water flow in the installation is insufficient
exceeded its maximum limit
and return temperature exceeded
block is open
4Check the circulation (direction, pump, valves)
4Check the water pressure
Sensor error
4Contact the professional who takes care of maintenance of the
appliance
The water flow in the installation is insufficient
4Check the circulation (direction, pump, valves)
4Check the water pressure
Sensor error
4Contact the professional who takes care of maintenance of the
appliance
Parameter error
4Contact the professional who takes care of maintenance of the
appliance
Bad connection
, for example) alternately.
30
and the current error
5v
4Contact the professional who takes care of maintenance of the
appliance
Su:09 Live/neutral inversionParameter error
4Contact the professional who takes care of maintenance of the
appliance
03/12/2013 - 300026082-001-02
22
6. TroubleshootingEGC 25
CodeDescriptionChecking / solution
Su:10
Su:11
The BL inlet on the PCU PCB terminal
block is open
The contact connected to the BL inlet is open
4Contact the professional who takes care of maintenance of the
appliance
Parameter error
4Contact the professional who takes care of maintenance of the
appliance
Bad connection
4Contact the professional who takes care of maintenance of the
appliance
Su:13 Communication error with the SCU
PCB
Bad connection
4Contact the professional who takes care of maintenance of the
appliance
SCU PCB not installed in the boiler
4Contact the professional who takes care of maintenance of the
appliance
Su:14 The water pressure is lower than 0,8
bar
Not enough water in the circuit
4Top up the installation with water
Su:15 Gas pressure too lowIncorrect setting of the gas pressure switch on the SCU PCB
4Check that the gas valve is fully opened
4Contact the professional who takes care of maintenance of the
appliance
Su:16 The SU PCB is not recognisedWrong SU PCB for this boiler
4Contact the professional who takes care of maintenance of the
appliance
Su:17 The parameters saved on the PCU
PCB are impaired
Parameter error on the PCU PCB
4Contact the professional who takes care of maintenance of the
appliance
Su:18 The PSU PCB is not recognisedWrong PSU PCB for this boiler
4Contact the professional who takes care of maintenance of the
appliance
Su:19 The boiler has not been configuredThe PSU PCB has been changed
4Contact the professional who takes care of maintenance of the
appliance
Su:21 Communication error between the
PCU and SU PCBs
Bad connection
4Contact the professional who takes care of maintenance of the
appliance
Su:22 No flame during operationNo ionization current
4Check that the gas valve is fully opened
4Contact the professional who takes care of maintenance of the
appliance
Su:25 Internal error on the SU PCB
4Contact the professional who takes care of maintenance of the
appliance
Su:28 An HL tank is detected whilst the boiler
cannot control it.
This message disappears after 10
seconds if the boiler can control the
4Wait for 10 seconds to see whether the error persists
4Contact the professional who takes care of maintenance of the
appliance
HL tank
Su:29 Communication error between the
PCU and SCU-s191 PCBs
Bad connection
4Contact the professional who takes care of maintenance of the
appliance
Su:30 Communication error between the
SCU-s191 PCBs and the solar control
system
Bad connection
4Contact the professional who takes care of maintenance of the
appliance
23
03/12/2013 - 300026082-001-02
EGC 256. Troubleshooting
CodeDescriptionChecking / solution
Su:31 The TAS is in open circuitThe Titan Active System® is on an open circuit
4Contact the professional who takes care of maintenance of the
appliance
Remarks:
Domestic hot water production is stopped but may nevertheless be
restarted for 72 hours after the boiler is switched off.
The tank is no longer protected.
If a tank without Titan Active System® is connected to the boiler, check that
the TAS simulation connector is fitted to the SCU-s191 PCB.
Su:32 The TAS is short circuitedThe Titan Active System® is short-circuited
4Contact the professional who takes care of maintenance of the
appliance
Remarks:
Domestic hot water production is stopped but may nevertheless be
restarted for 72 hours after the boiler is switched off.
The tank is no longer protected.
If a tank without Titan Active System® is connected to the boiler, check that
the TAS simulation connector is fitted to the SCU-s191 PCB.
Su:33 The header sensor in the solar control
system is defective
Su:34 The sensor in the solar tank is defective Bad connection
Bad connection
Sensor fault
4Contact the professional who takes care of maintenance of the
appliance
Sensor fault
6.2Faults (type code Exx)
Code
e00
e01
Cause of
the fault
PCUPSU PCB not connectedBad connection
PCUThe safety parameters are
DescriptionChecking / solution
incorrect
4Contact the professional who takes care of maintenance of the
appliance
In the event of an operating fault, the control panel flashes and
displays a code.
1. Make a note of the code displayed.
The code is important for the correct and rapid diagnosis of the
type of failure and for any technical assistance that may be
needed.
2. Press the t key. If the code is displayed again, switch off the boiler
and then switch it back on.
PSU PCB faulty
4Contact the professional who takes care of maintenance of the
appliance
Bad connection
PSU PCB faulty
e02
03/12/2013 - 300026082-001-02
PCUThe boiler flow sensor has short-
circuited
4Contact the professional who takes care of maintenance of the
appliance
Bad connection
Sensor fault
4Contact the professional who takes care of maintenance of the
appliance
24
6. TroubleshootingEGC 25
CodeCause of
the fault
e03
e04
e05
e06
PCUThe boiler flow sensor is on an
PCUBoiler temp too lowBad connection
PCUBoiler temperature too highBad connection
PCUThe return temperature sensor has
DescriptionChecking / solution
Bad connection
open circuit
Sensor fault
4Contact the professional who takes care of maintenance of the
appliance
Sensor fault
4Contact the professional who takes care of maintenance of the
appliance
No water circulation
4Vent the air in the heating system
4Check the circulation (direction, pump, valves)
4Check the water pressure
Sensor fault
4Contact the professional who takes care of maintenance of the
appliance
No water circulation
4Vent the air in the heating system
4Check the circulation (direction, pump, valves)
4Check the water pressure
Bad connection
short-circuited
Sensor fault
e07
e08
e09
e10
4Contact the professional who takes care of maintenance of the
appliance
PCUThe return temperature sensor is
on an open circuit
Bad connection
Sensor fault
4Contact the professional who takes care of maintenance of the
appliance
PCUReturn temperature too lowBad connection
Sensor fault
4Contact the professional who takes care of maintenance of the
appliance
No water circulation
4Vent the air in the heating system
4Check the circulation (direction, pump, valves)
4Check the water pressure
PCUReturn temperature too highBad connection
Sensor fault
4Contact the professional who takes care of maintenance of the
appliance
No water circulation
4Vent the air in the heating system
4Check the circulation (direction, pump, valves)
4Check the water pressure
PCUDifference between the flow and
return temperatures insufficient
Bad connection
Sensor fault
25
4Contact the professional who takes care of maintenance of the
appliance
No water circulation
4Vent the air in the heating system
4Check the circulation (direction, pump, valves)
4Check the water pressure
03/12/2013 - 300026082-001-02
EGC 256. Troubleshooting
CodeCause of
the fault
e11
e12
e14
PCUDifference between the flow and
PCUMaximum boiler temperature
PCU5 burner start-up failuresNo ignition
DescriptionChecking / solution
Bad connection
return temperatures too great
Sensor fault
4Contact the professional who takes care of maintenance of the
appliance
No water circulation
4Vent the air in the heating system
4Check the circulation (direction, pump, valves)
4Check the water pressure
Bad connection
exceeded (STB thermostat
maximum)
Sensor fault
4Contact the professional who takes care of maintenance of the
appliance
No water circulation
4Vent the air in the heating system
4Check the circulation (direction, pump, valves)
4Check the water pressure
4Contact the professional who takes care of maintenance of the
appliance
Ignition arc, but no flame formation
e16
e17
e34
e35
4Check that the gas valve is fully opened
4Contact the professional who takes care of maintenance of the
appliance
Presence of the flame but insufficient ionization (<3 µA)
4Check that the gas valve is fully opened
4Contact the professional who takes care of maintenance of the
appliance
PCUDetection of a parasite flameIonization current present even though there is no flame
Ignition transformer defective
Gas valve defect
The burner remains very hot: CO2 too high
4Contact the professional who takes care of maintenance of the
appliance
PCUInternal error on the SU boardBad connection
SU PCB faulty
4Contact the professional who takes care of maintenance of the
appliance
PCUThe fan is not running at the right
speed
Bad connection
Fan defective
4Contact the professional who takes care of maintenance of the
appliance
PCUFlow and return reversedBad connection
Sensor fault
e36
PCUThe flame went out more than 5
times in 24 hours while the burner
was operating
03/12/2013 - 300026082-001-02
4Contact the professional who takes care of maintenance of the
appliance
Water circulation direction reversed
4Check the circulation (direction, pump, valves)
No ionization current
4Check that the gas valve is fully opened
4Contact the professional who takes care of maintenance of the
appliance
26
6. TroubleshootingEGC 25
CodeCause of
the fault
e37
e38
e39
e40
PCUCommunication failure with the
PCUCommunication failure between
PCUThe BL inlet is openParameter incorrectly set
PCUHRU/URC unit test errorBad connection
DescriptionChecking / solution
Bad connection
SU PCB
4Contact the professional who takes care of maintenance of the
appliance
Bad connection
the PCU and SCU PCBs
SCU PCB not connected or faulty
4Contact the professional who takes care of maintenance of the
appliance
Bad connection
External cause
4Contact the professional who takes care of maintenance of the
appliance
External cause
4Contact the professional who takes care of maintenance of the
appliance
27
03/12/2013 - 300026082-001-02
EGC 257. Technical specifications
7Technical specifications
7.1Technical specifications
Boiler typeEGC 25
General
Nominal output (Pn)
Heating System (80/60 °C)
Nominal output (Pn)
Heating System (50/30 °C)
Nominal output (Pn)
Heating System (40/30 °C)
Nominal input (Qn)
Heating System (Hi)
Nominal input (Qn)
Heating System (Hs)
Nominal input (Qnw)
DHW System (Hi)
Nominal input (Qnw)
DHW System (Hs)
Heating efficiency under full load (Hi) (80/60 °C)-%96,3
Heating efficiency under full load (Hi) (50/30 °C)-%102,0
Heating efficiency under partial load (Hi) (Return temperature 60°C)-%96,1
Heating efficiency under partial load (EN 92/42) (Return temperature
30°C)
Data on the gases and combustion gases
Gas consumption - Natural gas H (G20)minimum-maximum
Gas consumption - Natural gas L (G25)minimum-maximum
Gas consumption - Propane G31minimum-maximum
NOx-Emission (Scrolls forward EN297A3)
Mass flue gas flow rateminimum-maximum kg/h8,9 - 49,3
Flue gas temperatureminimum-maximum °C30 - 80
Maximum counter pressure
Characteristics of the heating circuit
Water content (ex expansion vessel)
Water operating pressureminimumkPa (bar (MPa)) 80 (0,8)
Water operating pressure (PMS)maximumkPa (bar (MPa)) 300 (3,0)
Water temperaturemaximum°C110
Operating temperaturemaximum°C90
Electrical characteristics
Power supply voltage
Power consumption - Pump position high - FastestmaximumW141
Power consumption - Pump position low - SlowestmaximumW78
Power consumption - StandbymaximumW4
Electrical protection index
Other characteristics
Weight (empty)
minimum-maximum kW5,0 - 24,1
minimum-maximum kW5,6 - 25,5
minimum-maximum kW5,6 - 25,9
minimum-maximum kW5,2 - 25,0
minimum-maximum kW5,8 - 27,8
minimum-maximum kW5,2 - 29,3
minimum-maximum kW5,8 - 32,6
-%108,0
0,55 - 3,10
0,64 - 3,61
0,21 - 1,20
IP21
m3/h
m3/h
m3/h
mg/kWh38
Pa120
l1,9
VAC230
kg50
03/12/2013 - 300026082-001-02
28
8. Energy savings
8Energy savings
8.1Energy-saving advice
EGC 25
4 Keep the room in which the boiler is installed well ventilated.
4 Do not block ventilation outlets.
4 Do not cover the radiators. Do not hang curtains in front of the
radiators.
4 Install reflective panels behind the radiators to prevent heat
losses.
4 Insulate the pipes in rooms that are not heated (cellars and lofts).
4 Close the radiators in rooms not in use.
4 Do not run hot (or cold) water pointlessly.
4 Install a water-saving shower head to save up to 40 % energy.
4 Take showers rather than baths. A bath consumes twice as much
water and energy.
8.2Recommendations
The remote control is available in the following versions:
4 Wire
4 Radio
The setting of the control panel and/or of the remote control has a
considerable influence on energy consumption.
A few tips:
4 In the room in which the room thermostat is installed, it’s advised
not to use thermostatic valve radiators. If a thermostatic valve is
used the valve must be fully opened.
4 Completely closing and opening thermostatic valve radiators
causes undesirable temperature fluctuations. Open and close
thermostatic valves in small steps.
4 Lower the temperature to around 20°C. This reduces heating costs
and energy consumption.
4 Lower the temperature when you air the rooms.
4 When setting a time schedule , bear days when you are absent
and holidays in mind.
29
03/12/2013 - 300026082-001-02
EGC 25
9Warranty
9.1General
9.2Warranty terms
9. Warranty
You have just purchased one of our appliances and we thank you for
the trust you have placed in our products.
Please note that your appliance will provide good service for a longer
period of time if it is regularly checked and maintained.
Your installer and our customer support network are at your disposal
at all times.
The following provisions are not exclusive of the buyer being able
benefit from the legal provisions applicable regarding hidden defects
in the buyer’s country.
Starting from the purchase date shown on the original installer’s
invoice, your appliance has a contractual guarantee against any
manufacturing defect.
The length of the guarantee is mentioned in the price catalogue.
The manufacturer is not liable for any improper use of the appliance
or failure to maintain or install the unit correctly (the user shall take
care to ensure that the system is installed by a qualified engineer).
In particular, the manufacturer shall not be held responsible for any
damage, loss or injury caused by installations which do not comply
with the following:
4 applicable local laws and regulations,
4 specific requirements relating to the installation, such as national
and/or local regulations,
4 the manufacturer’s instructions, in particular those relating to the
regular maintenance of the unit,
4 the rules of the profession.
The warranty is limited to the exchange or repair of such parts as have
been recognised to be faulty by our technical department and does
not cover labour, travel and carriage costs.
The warranty shall not apply to the replacement or repair of parts
damaged by normal wear and tear, negligence, repairs by unqualified
parties, faulty or insufficient monitoring and maintenance, faulty
power supply or the use of unsuitable fuel.
03/12/2013 - 300026082-001-02
Sub-assemblies such as motors, pumps, electric valves etc. are
guaranteed only if they have never been dismantled.
The legislation laid down by european directive 99/44/EEC,
transposed by legislative decree No. 24 of 2 February 2002 published
in O.J. No. 57 of 8 March 2002, continues to apply.
30
AD001NU-AJ
DUEDI S.r.l.
DE DIETRICH SERVICE
BDR Thermea (Czech republic) s.r.o
www.duediclima.it
www.dedietrich.cz
Distributore Ufficiale Esclusivo
De Dietrich-Thermique Italia
www.dedietrich-heiztechnik.com
Freecall 0800 / 201608
Jeseniova 2770/56
130 00 Praha 3
+49 (0)25 72 / 9161-0
+49 (0)25 72 / 9161-102
info@remeha.de
Via Passatore, 12 - 12010
San Defendente di Cervasca
CUNEO