DE DIETRICH TWINEO EGC 25 User Manual

Twineo
Gas fired floor-standing condensing boiler
EGC 25
EN
User Guide
300026082-001-02
Contents
1 Introduction ................................................................................................4
1.1.1 Symbols used in the manual ...................................4
1.1.2 Symbols used on the equipment .............................4
1.2 Abbreviations ........................................................5
1.3 General ..................................................................5
1.3.1 Manufacturer’s liability .............................................5
1.3.2 Installer’s liability .....................................................6
1.3.3 User’s liability ..........................................................6
1.4 Certifications .........................................................6
2 Safety instructions and recommendations ..............................................7
2.1 Safety instructions ...............................................7
2.2 Recommendations ................................................8
3 Description ..................................................................................................9
3.1 Operating principle ...............................................9
3.1.1 Gas/air setting .........................................................9
3.1.2 Combustion .............................................................9
3.2 Main parts ............................................................10
3.3 Control panel .......................................................11
3.3.1 Description of the keys ..........................................11
3.3.2 Description of the display ......................................11
4 Operating the appliance ..........................................................................14
4.1 Putting the appliance into operation ................14
4.2 Reading out measured values ...........................14
4.3 Changing the settings ........................................15
4.3.1 Parameter descriptions .........................................15
4.3.2 Modification of the user-level parameters .............16
4.3.3 Setting the manual mode ......................................18
4.3.4 Changing the heating temperature ........................18
4.3.5 Modifying the domestic hot water temperature
setting ....................................................................18
4.3.6 Modifying the domestic hot water set point
temperature ...........................................................19
1
03/12/2013 - 300026082-001-02
Contents
4.4 Installation shutdown .........................................19
4.5 Antifreeze protection ..........................................19
5 Checking and maintenance .....................................................................20
5.1 General instructions ...........................................20
5.2 Periodic checks ..................................................20
6 Troubleshooting .......................................................................................22
6.1 Error messages (Sub-status 9) ........................22
6.2 Faults (type code Exx) ........................................24
7 Technical specifications ..........................................................................28
7.1 Technical specifications ....................................28
8 Energy savings .........................................................................................29
8.1 Energy-saving advice .........................................29
8.2 Recommendations ..............................................29
9 Warranty ....................................................................................................30
9.1 General ................................................................30
9.2 Warranty terms ...................................................30
2
03/12/2013 - 300026082-001-02
3
03/12/2013 - 300026082-001-02
D000241-C
EGC 25
1 Introduction
1.1 Symbols used
1. Introduction
1.1.1. Symbols used in the manual
In these instructions, various danger levels are employed to draw the user’s attention to particular information. In so doing, we wish to safeguard the user’s safety, obviate hazards and guarantee correct operation of the appliance.
DANGER
Risk of a dangerous situation causing serious physical injury.
WARNING
Risk of a dangerous situation causing slight physical injury.
CAUTION
Risk of material damage.
Signals important information.
¼Signals a referral to other instructions or other pages in the instructions.
1.1.2. Symbols used on the equipment
4
~
Protective earthing
Alternating current
Before installing and commissioning the device, read carefully the instruction manuals provided.
Dispose of the used products in an appropriate recovery and recycling structure.
03/12/2013 - 300026082-001-02
This appliance must be connected to the protective earth.
4
1 2
M002628-A
1. Introduction
1.2 Abbreviations
EGC 25
Caution: danger, live parts. Disconnect the mains power prior to any operations.
4 3CE: Collective conduit for sealed boiler
4 DHW: Domestic hot water
4 Hi: Lower heating value LHV (Nett)
4 Hs: Higher heating value HHV (Gross)
4 PPS: Polypropylene hardly inflammable
4 PCU: Primary Control Unit - PCB for managing burner operation
4 PSU: Parameter Storage Unit - Parameter storage for PCBs
PCU and SU
4 SCU: Secondary Control Unit - control panel PCB
4 SU: Safety Unit - Safety PCB
4 HRU: Heat Recovery Unit
4 3WV: 3-way valve
4 HL: High Load - DHW tank with plate exchanger
4 SL: Standard Load - DHW tank with coil
4 SHL: Solar High Load - Solar DHW tank with plate exchanger
4 SSL: Solar Standard Load - Solar DHW tank with coil
1.3 General
1.3.1. Manufacturer’s liability
Our products are manufactured in compliance with the requirements of the various applicable European Directives. They are therefore
delivered with [ marking and all relevant documentation.
In the interest of customers, we are continuously endeavouring to make improvements in product quality. All the specifications stated in this document are therefore subject to change without notice.
Our liability as the manufacturer may not be invoked in the following cases:
4 Failure to abide by the instructions on using the appliance.
4 Faulty or insufficient maintenance of the appliance.
4 Failure to abide by the instructions on installing the appliance.
5
03/12/2013 - 300026082-001-02
EGC 25 1. Introduction
1.3.2. Installer’s liability
The installer is responsible for the installation and inital start up of the appliance. The installer must respect the following instructions:
4 Read and follow the instructions given in the manuals provided
with the appliance.
4 Carry out installation in compliance with the prevailing legislation
and standards.
4 Perform the initial start up and carry out any checks necessary.
4 Explain the installation to the user.
4 If a maintenance is necessary, warn the user of the obligation to
check the appliance and maintain it in good working order.
4 Give all the instruction manuals to the user.
1.3.3. User’s liability
To guarantee optimum operation of the appliance, the user must respect the following instructions:
1.4 Certifications
4 Read and follow the instructions given in the manuals provided
with the appliance.
4 Call on qualified professionals to carry out installation and initial
start up.
4 Get your installer to explain your installation to you.
4 Have the required checks and services done.
4 Keep the instruction manuals in good condition close to the
appliance.
This appliance is not intended to be used by persons (including children) whose physcial, sensory or mental capacity is impaired or persons with no experience or knowledge, unless they have the benefit, through the intermediary of a person responsible for their safety, of supervision or prior instructions regarding use of the appliance. Care should be taken to ensure that children do not play with the appliance.
To prevent hazardous situations from arising, if the mains lead is damaged it must be replaced by the original manufacturer, the manufacturer’s dealer or another suitably skilled person.
03/12/2013 - 300026082-001-02
CE identification no
NOx classification
Type of connection Chimney: B23, B
CE-0085CM0178
5 (EN 297 pr A3, EN 483)
Flue gas outlet: C C
93(x)
33
13(x)
, C
33(x)
, C
43(x)
, C53, C
83(x)
,
6
2. Safety instructions and recommendations EGC 25
2 Safety instructions and
recommendations
2.1 Safety instructions
DANGER
If you smell gas:
1. Do not use a naked flame, do not smoke, do not operate electrical contacts or switches ( doorbell, light, motor, lift, etc..).
2. Shut off the gas supply.
3. Open the windows.
4. Evacuate the premises.
5. Call your fitter.
DANGER
If you smell flue gases:
1. Switch the appliance off.
2. Open the windows.
3. Evacuate the premises.
4. Call your fitter.
WARNING
Depending on the settings of the appliance:
4 The temperature of the flue gas conduits may exceed
60°C.
4 The temperature of the radiators may reach 85°C.
4 The temperature of the domestic hot water may reach
65°C.
CAUTION
Do not neglect to service the appliance: 4 For completely safe and optimum operation, you
must have your boiler regularly serviced by an approved installer.
7
03/12/2013 - 300026082-001-02
EGC 25 2. Safety instructions and recommendations
2.2 Recommendations
WARNING
Only qualified professionals are authorised to work on the appliance and the installation.
4 Regularly check the water pressure in the installation (minimum
pressure 0.8 bar, recommended pressure between 0.08 and 1.5 bar).
4 Keep the appliance accessible at all times.
4 Never remove or cover labels and rating plates affixed to the
appliance. Labels and rating plates must be legible throughout the entire lifetime of the appliance.
4 The appliance should be on Summer or Antrifreeze mode rather
than switched off to guarantee the following functions:
- Anti blocking of pumps
- Antifreeze protection
03/12/2013 - 300026082-001-02
8
3. Description EGC 25
3 Description
3.1 Operating principle
3.1.1. Gas/air setting
Air is sucked in by the fan and the gas injected into the venturi attached to the fan inlet. The fan rotation speed modulates and adapts to thermal energy requirements thanks to the temperatures measured by the various sensors. The gas and air are mixed in the venturi, which enables operation at a constant ratio. The noise of the venturi is absorbed by a silencer attached to its inlet. The gas/air mixture is carried to the burner in the top of the exchanger, guided by the pre­mix channel.
3.1.2. Combustion
The burner heats the heating water circulating in the heat exchanger. At a return temperature lower than around 55°C, the flue gases cool down to a temperature lower than the dew point, thus causing the condensation of the water vapour contained in the flue gases in the lower section of the heat exchanger. The heat released during this condensation process (the latent heat or condensing heat) is also transferred to the heating water. The cooled combustion gases are evacuated via the combustion gas outlet flue. The condensation water is evacuated via a siphon.
9
03/12/2013 - 300026082-001-02
C003072-C
18
19
16
17
15
14
13
12
11
1234
10
9
5
6
7
8
EGC 25 3. Description
3.2 Main parts
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Flue gas discharge pipe
Flue gas measuring point
Heat exchanger
Ignition/ionization electrode
Box for the control PCBs
Control panel
Command module
Water pressure sensor
Circulation pump
Hydroblock
3-way valve
Safety valve
Casing
Expansion vessel
Combined venturi and gas valve unit
Fan
Air intake silencer
18
19
Mixer pipe
Automatic air vent
03/12/2013 - 300026082-001-02
10
-
)
L
m
rrr
ddd
T
y
1 2
SERVICE
°C°Fh barPsi % rpm kW uA x10 l/min
°CSt:
M002715-A
t
h
j
A B
E F
C D
-
)
L
m
r
r
r
d
d
d
T
y
1 2
SERVICE
°C°Fh barPsi % rpm kW uA x10 l/min
°CSt:
M002716-A
t
h
j
3. Description EGC 25
3.3 Control panel
3.3.1. Description of the keys
11
A
B
C
D
E
F
3.3.2. Description of the display
Key functions
n
G
t d
[-]
Return button j, Escape G or Manual reset t Heating temperature button d or [-] DHW temperature button r or [+] S [Enter] Key ) [Chimney-sweeping] keys
Press keys A and B simultaneously f [Menu] keys
Press keys C and D simultaneously
Back to the previous level without saving the modifications made
Manual reset
Central heating function: Access to the max. heating temperature parameter.
To reduce a value
03/12/2013 - 300026082-001-02
-
)
L
m
rrr
d
d
d
T
y
1 2
SERVICE
°C°Fh barPsi % rpm kW uA x10 l/min
°CSt:
M002717-A
t
h
j
-
)
L
m
rrr
ddd
T
y
1 2
SERVICE
°C°Fh barPsi % rpm kW uA x10 l/min
°CSt:
M002718-A
t
h
j
-
)
L
m
rrr
ddd
T
y
1 2
SERVICE
°C°Fh barPsi % rpm kW uA x10 l/min
°CSt:
M002719-A
t
h
j
-
)
L
m
rrr
ddd
T
y
1 2
SERVICE
°C°Fh
barPsi
% rpm kW uA x10 l/min
°CSt:
M002720-A
t
h
j
EGC 25 3. Description
r
[+]
®
Operating modes
n
d
D
r
S
m
DHW function: Access to sanitary hot water temperature parameter.
To increase a value
Access the selected menu or confirm a value modification
State heating pump
Heating programme deactivated: The heating function is deactivated
State DHW pump
DHW off
Manual mode
Flame output level
n
e r t y
System pressure
n
bar
Low output level 0 - 25 %
Average output level 25 - 50 %
High output level 50 - 75 %
Output level 75 - 100 %
Pressure indicator: The symbol is displayed next to the installation’s pressure value. If no water pressure sensor is connected, -.­appears on the display
03/12/2013 - 300026082-001-02
12
-
)
L
m
rrr
ddd
T
y
1 2
SERVICE
°C°Fh barPsi % rpm kW uA x10 l/min
°CSt:
M002721-A
t
h
j
3. Description EGC 25
Other information
n
"
!
)
-
K
\
a
I
M
a
User menu: Parameters at user level can be changed
Information menu: Reading the various current values
Chimney-sweeping position: Forced full or part load for CO2 measurement
Service menu: Parameters at installer level can be changed
Display with the symbols: $ + K + Z (Maintenance message)
Hour counter menu: Readout of the operating hours, number of successful starts and hours on mains supply
Blocking: After 5 resets in under 1 hour, the appliance should be switched off and switched on again before resetting
Outside temperature sensor present
The symbol is displayed when the boiler pump is operating
Defect: Boiler indicates a fault. This is indicated by an E code and a flashing display
13
03/12/2013 - 300026082-001-02
EGC 25
4 Operating the appliance
4.1 Putting the appliance into operation
1. Check the water pressure in the installation shown on the control panel display.
If the water pressure is lower than 0,8 bar, more water should be added. If necessary, top up the water level in the heating system (recommended hydraulic pressure between 1,5 and 2,0 bar).
2. Open the gas valve on the boiler.
3. Switch on the boiler.
4. The start-up cycle begins and cannot be interrupted. During the start-up cycle, the display shows the following information:
fK[xx pK[xx
The version numbers are displayed alternately.
5. A vent cycle of a duration of around 3 minutes is carried out automatically.
6. In standby mode, the screen usually displays 0, plus the water
pressure and the symbols d and r.
: Software version
: Parameter version
4. Operating the appliance
4.2 Reading out measured values
The following current values can be read off the information menu Q:
4 5t = State. 4 5v = Sub-status. 4 t1 = Flow temperature (°C). 4 t" = Return temperature (°C). 4 t3 = DHW tank temperature (°C). 4 t4 = Outside temperature (°C). 4 t5 = Solar boiler temperature (°C). 4 t6 = Solar panel temperature (°C). 4 5p = Internal set point (°C). 4 fl = Ionization current (µA). 4 Mf = Fan speed in rpm. 4 pr = Water pressure (bar (MPa)). 4 p; = Supplied relative heat output (%).
03/12/2013 - 300026082-001-02
14
)
r
d
bar
C003049-A
t
h
j
h
j
4x
2x
4. Operating the appliance
EGC 25
The current values can be read as follows:
1. Press the two f keys simultaneously. The symbol Q flashes.
2. Confirm using key S.
is displayed, alternating with the
5t
current status 3 (for example).
3. Press the [+] key.
sub-status
(for example).
30
4. Press the [+] key.
flow temperature
is displayed, alternating with the current
5v
is displayed, alternating with the current
t1
°C (for example).
60
5. Press the [+] key successively to scroll down the various parameters.
t", t3, t4, t5, t6
6. Press the [+] key.
set point
°C (for example).
88
7. Press the [+] key.
ionization current
8. Press the [+] key.
fan rotation speed
9. Press the [+] key.
water pressure
#0
is displayed, alternating with the internal
5p
is displayed, alternating with the current
fl
µA (for example).
70
is displayed, alternating with the current
Mf
3000
pr
rpm (for example).
is displayed, alternating with the current
bar (for example). If no water pressure sensor
.
is connected, [-.-] appears on the display.
10.Press the [+] key.
modulation percentage
11.Press the [+] key. The readout cycle starts again with
is displayed, alternating with the current
p;
% (for example).
78
5t
.
12.Press the j key 2 times to return to the current operating mode.
4.3 Changing the settings
15
4.3.1. Parameter descriptions
03/12/2013 - 300026082-001-02
EGC 25 4. Operating the appliance
Factory
Parameter Description Adjustment range
p1
p2
p3
p4
p5
p6
p7
p8
Flow temperature: T
Domestic hot water temperature: T
Heating / DHW mode
ECO mode
Anticipation resistance
Display screen
Post-circulation of the pump
Brightness of display lighting
SET
SET
20 to 90 °C
40 to 65 °C
0 = Heating deactivated / DHW deactivated 1 = Heating activated / DHW activated 2 = Heating activated / DHW deactivated 3 = Heating deactivated / DHW activated
0 = Comfort 1 = Energy-saving mode 2 = Management using a programmable thermostat
0 = No anticipation resistance for the ON/OFF thermostat 1 = Anticipation resistance for the ON/OFF thermostat
0 = Simple 1 = Comprehensive 2 = Automatic switching to simple after 3 minutes 3 = Automatic switching to simple after 3 minutes; Key blocking is
active
1 to 98 minutes 99 minutes = continuous
0 = Low 1 = High
setting
EGC 25
80
55
1
2
0
2
2
1
4.3.2. Modification of the user-level parameters
Parameters p1 to p8 can be modified by the user in order to meet central heating and DHW comfort needs.
03/12/2013 - 300026082-001-02
16
)
r
d
bar
C003050-A
t
h
j
h
j
1x
2x
4. Operating the appliance EGC 25
CAUTION
Modification of the factory settings may be detrimental to the functioning of the appliance.
1. Press the two keys f simultaneously and then key [+] until the symbol W flashes on the menu bar.
2. Select the users menu using the key S.
flashing.
1
is displayed with
p[1
3. Press the S key a second time. The value 80°C appears and flashes (for example).
4. Change the value by pressing the [-] or [+] key. In this example using key [-] to
5. Confirm the value with the S key.
60
°C.
is displayed with
p[1
1
flashing.
6. Press the j key 2 times to return to the current operating mode.
4 The parameters
same way as
p1
p2
to
are changed in the
p8
. After step 2, use the [+] key to
move to the required parameter.
4 The parameters
temperature) and
(the maximum heating water
p1
(the maximum drinking water
p2
temperature) can also be modified using the quick selection menu.
17
03/12/2013 - 300026082-001-02
)
m
r
d
bar
C003051-A
t
h
j
h
j
2x
2x
bar
d
C003052-A
1x
EGC 25
4. Operating the appliance
4.3.3. Setting the manual mode
In some cases it may be necessary to switch the boiler to manual operation, For example, if the controller has not yet been connected. The boiler can be switched to automatic or manual operation under the symbol m. To do this, proceed as follows:
1. Press the two keys f simultaneously and then key [+] until the symbol m flashes on the menu bar.
2. Press the S key:
or
The text
sensor is connected). The flow temperature is determined by the internal heating curve.
or
The value of the minimum flow temperature.
3. Press the [-] or [+] key to increase this value temporarily in manual operation.
4. Confirm the value with the S key. The boiler is now set to manual operation.
5. Press the j key 2 times to return to the current operating mode.
with the current water pressure (only if an outside
Zv
4.3.4. Changing the heating temperature
If using an outside temperature sensor, the heating flow temperature is adjusted automatically.
In summer, it is possible to reduce the heating flow temperature whilst maintaining comfort. To do this, proceed as follows:
1. Press the d key 1 times.
2. The symbol d and the current temperature are displayed (the temperature flashes, e.g.
85
°C).
3. Change the value by pressing the [-] or [+] key. In this example using key [-] to
60
°C.
4. To confirm, press the S key.
It also possible to modify this setting using the parameter
.
p1
4.3.5. Modifying the domestic hot water
temperature setting
03/12/2013 - 300026082-001-02
It may be that a lower domestic hot water temperature will be sufficient for your needs. Reduce this temperature and save energy. To do this, proceed as follows:
18
C003053-A
r
1x
C003912-A
r
1x
1x
4. Operating the appliance
EGC 25
1. Press the r key 1 times.
2. The symbol r and the current temperature are displayed (the temperature flashes, e.g.
60
°C).
3. Change the value by pressing the [-] or [+] key. In this example using key [-] to
55
°C.
4. To confirm, press the S key.
4.3.6. Modifying the domestic hot water set point
temperature
To modify the set point of the solar tank (if connected), proceed as follows
1. Press the r key for 3 seconds.
2. Symbols r and
(for example,
S;
3. Change the value by pressing the [-] or [+] key. In this example using key [-] to
4. To confirm, press the S key.
and the current temperature are displayed
S;
and the temperature 60°C flash).
°C.
55
4.4 Installation shutdown
4.5 Antifreeze protection
CAUTION
Do not switch off the boiler.
If the central heating system is not used for a long period, we recommend proceeeding as follows:
4 Press key d until OFF is displayed. 4 Press key r until OFF is displayed.
When the heating water temperature in the boiler is too low, the integrated boiler protection system starts up. This protection functions as follows:
4 If the water temperature is lower than 7°C, the heating pump starts
up.
4 If the water temperature is lower than 4°C, the boiler starts up.
4 If the water temperature is higher than 10°C, the boiler shuts down
and the circulation pump continues to run for a short time.
4 If the water temperature in the storage tank is less than 4°C, it is
reheated to its set point.
19
03/12/2013 - 300026082-001-02
T001507-B
EGC 25
5 Checking and maintenance
5.1 General instructions
The boiler does not require a lot of maintenance. Nevertheless, we recommend having the boiler inspected and serviced at regular intervals.
4 Maintenance and cleaning of the boiler must be carried out at least
once a year by a qualified technician.
4 Have the flues swept at least once a year or more, depending on
the regulations in force in your country.
CAUTION
4 Maintenance operations must be done by a qualified
engineer.
4 We recommend taking out a maintenance contract.
4 Only original spare parts must be used.
4 Make certain that the flues and chimneys are
connected, in good condition and not blocked.
4 Do not modify nor block the condensate outlet(s).
4 If a neutralisation system is installed, follow the
instructions delivered with the neutralisation system for cleaning and servicing of this system.
5. Checking and maintenance
5.2 Periodic checks
4 Check the water pressure in the installation (Menu
INFORMATION).
If the water pressure is lower than 0,8 bar, more water should be added. If necessary, top up the water level in the heating system (recommended hydraulic pressure between 1,5 and 2,0 bar).
4 Carry out a visual check for the presence of any water leaks.
03/12/2013 - 300026082-001-02
20
1
2
3
4
T000181-B
5. Checking and maintenance EGC 25
4 Open and close the radiator valves several times a year (this
prevents the valves from seizing up).
4 Clean the outside of the boiler using a damp cloth and a light
detergent.
CAUTION
Only a qualified professional is authorised to clean the inside of the boiler.
21
03/12/2013 - 300026082-001-02
M002722-A
EGC 25 6. Troubleshooting
6 Troubleshooting
6.1 Error messages (Sub-status 9)
To display the current error code, proceed as follows:
1. Press the two f keys simultaneously. The symbol Q flashes.
2. Confirm using key S.
current status 3 (for example).
is displayed, alternating with the
5t
3. Press the [+] key. The display shows
value (
Code
Su:00 The PSU PCB is incorrectly configured Parameter error on the PSU PCB
Su:01 Maximum flow temperature exceeded The water flow in the installation is insufficient
Su:02 The increase in flow temperature has
Su:07 Maximum difference between the flow
Su:08 The RL inlet on the PCU PCB terminal
Description Checking / solution
4 Contact the professional who takes care of maintenance of the
appliance
4 Check the circulation (direction, pump, valves)
The water flow in the installation is insufficient
exceeded its maximum limit
and return temperature exceeded
block is open
4 Check the circulation (direction, pump, valves)
4 Check the water pressure
Sensor error
4 Contact the professional who takes care of maintenance of the
appliance
The water flow in the installation is insufficient
4 Check the circulation (direction, pump, valves)
4 Check the water pressure
Sensor error
4 Contact the professional who takes care of maintenance of the
appliance
Parameter error
4 Contact the professional who takes care of maintenance of the
appliance
Bad connection
, for example) alternately.
30
and the current error
5v
4 Contact the professional who takes care of maintenance of the
appliance
Su:09 Live/neutral inversion Parameter error
4 Contact the professional who takes care of maintenance of the
appliance
03/12/2013 - 300026082-001-02
22
6. Troubleshooting EGC 25
Code Description Checking / solution
Su:10 Su:11
The BL inlet on the PCU PCB terminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care of maintenance of the
appliance
Parameter error
4 Contact the professional who takes care of maintenance of the
appliance
Bad connection
4 Contact the professional who takes care of maintenance of the
appliance
Su:13 Communication error with the SCU
PCB
Bad connection
4 Contact the professional who takes care of maintenance of the
appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care of maintenance of the
appliance
Su:14 The water pressure is lower than 0,8
bar
Not enough water in the circuit
4 Top up the installation with water
Su:15 Gas pressure too low Incorrect setting of the gas pressure switch on the SCU PCB
4 Check that the gas valve is fully opened
4 Contact the professional who takes care of maintenance of the
appliance
Su:16 The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care of maintenance of the
appliance
Su:17 The parameters saved on the PCU
PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care of maintenance of the
appliance
Su:18 The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care of maintenance of the
appliance
Su:19 The boiler has not been configured The PSU PCB has been changed
4 Contact the professional who takes care of maintenance of the
appliance
Su:21 Communication error between the
PCU and SU PCBs
Bad connection
4 Contact the professional who takes care of maintenance of the
appliance
Su:22 No flame during operation No ionization current
4 Check that the gas valve is fully opened
4 Contact the professional who takes care of maintenance of the
appliance
Su:25 Internal error on the SU PCB
4 Contact the professional who takes care of maintenance of the
appliance
Su:28 An HL tank is detected whilst the boiler
cannot control it. This message disappears after 10 seconds if the boiler can control the
4 Wait for 10 seconds to see whether the error persists
4 Contact the professional who takes care of maintenance of the
appliance
HL tank
Su:29 Communication error between the
PCU and SCU-s191 PCBs
Bad connection
4 Contact the professional who takes care of maintenance of the
appliance
Su:30 Communication error between the
SCU-s191 PCBs and the solar control system
Bad connection
4 Contact the professional who takes care of maintenance of the
appliance
23
03/12/2013 - 300026082-001-02
EGC 25 6. Troubleshooting
Code Description Checking / solution Su:31 The TAS is in open circuit The Titan Active System® is on an open circuit
4 Contact the professional who takes care of maintenance of the
appliance
Remarks: Domestic hot water production is stopped but may nevertheless be restarted for 72 hours after the boiler is switched off. The tank is no longer protected. If a tank without Titan Active System® is connected to the boiler, check that the TAS simulation connector is fitted to the SCU-s191 PCB.
Su:32 The TAS is short circuited The Titan Active System® is short-circuited
4 Contact the professional who takes care of maintenance of the
appliance
Remarks: Domestic hot water production is stopped but may nevertheless be restarted for 72 hours after the boiler is switched off. The tank is no longer protected. If a tank without Titan Active System® is connected to the boiler, check that the TAS simulation connector is fitted to the SCU-s191 PCB.
Su:33 The header sensor in the solar control
system is defective
Su:34 The sensor in the solar tank is defective Bad connection
Bad connection Sensor fault
4 Contact the professional who takes care of maintenance of the
appliance
Sensor fault
6.2 Faults (type code Exx)
Code
e00
e01
Cause of the fault
PCU PSU PCB not connected Bad connection
PCU The safety parameters are
Description Checking / solution
incorrect
4 Contact the professional who takes care of maintenance of the
appliance
In the event of an operating fault, the control panel flashes and displays a code.
1. Make a note of the code displayed. The code is important for the correct and rapid diagnosis of the type of failure and for any technical assistance that may be needed.
2. Press the t key. If the code is displayed again, switch off the boiler and then switch it back on.
PSU PCB faulty
4 Contact the professional who takes care of maintenance of the
appliance
Bad connection PSU PCB faulty
e02
03/12/2013 - 300026082-001-02
PCU The boiler flow sensor has short-
circuited
4 Contact the professional who takes care of maintenance of the
appliance
Bad connection Sensor fault
4 Contact the professional who takes care of maintenance of the
appliance
24
6. Troubleshooting EGC 25
Code Cause of
the fault
e03
e04
e05
e06
PCU The boiler flow sensor is on an
PCU Boiler temp too low Bad connection
PCU Boiler temperature too high Bad connection
PCU The return temperature sensor has
Description Checking / solution
Bad connection
open circuit
Sensor fault
4 Contact the professional who takes care of maintenance of the
appliance
Sensor fault
4 Contact the professional who takes care of maintenance of the
appliance
No water circulation
4 Vent the air in the heating system
4 Check the circulation (direction, pump, valves)
4 Check the water pressure
Sensor fault
4 Contact the professional who takes care of maintenance of the
appliance
No water circulation
4 Vent the air in the heating system
4 Check the circulation (direction, pump, valves)
4 Check the water pressure
Bad connection
short-circuited
Sensor fault
e07
e08
e09
e10
4 Contact the professional who takes care of maintenance of the
appliance
PCU The return temperature sensor is
on an open circuit
Bad connection Sensor fault
4 Contact the professional who takes care of maintenance of the
appliance
PCU Return temperature too low Bad connection
Sensor fault
4 Contact the professional who takes care of maintenance of the
appliance
No water circulation
4 Vent the air in the heating system
4 Check the circulation (direction, pump, valves)
4 Check the water pressure
PCU Return temperature too high Bad connection
Sensor fault
4 Contact the professional who takes care of maintenance of the
appliance
No water circulation
4 Vent the air in the heating system
4 Check the circulation (direction, pump, valves)
4 Check the water pressure
PCU Difference between the flow and
return temperatures insufficient
Bad connection Sensor fault
25
4 Contact the professional who takes care of maintenance of the
appliance
No water circulation
4 Vent the air in the heating system
4 Check the circulation (direction, pump, valves)
4 Check the water pressure
03/12/2013 - 300026082-001-02
EGC 25 6. Troubleshooting
Code Cause of
the fault
e11
e12
e14
PCU Difference between the flow and
PCU Maximum boiler temperature
PCU 5 burner start-up failures No ignition
Description Checking / solution
Bad connection
return temperatures too great
Sensor fault
4 Contact the professional who takes care of maintenance of the
appliance
No water circulation
4 Vent the air in the heating system
4 Check the circulation (direction, pump, valves)
4 Check the water pressure
Bad connection exceeded (STB thermostat maximum)
Sensor fault
4 Contact the professional who takes care of maintenance of the
appliance
No water circulation
4 Vent the air in the heating system
4 Check the circulation (direction, pump, valves)
4 Check the water pressure
4 Contact the professional who takes care of maintenance of the
appliance
Ignition arc, but no flame formation
e16
e17
e34
e35
4 Check that the gas valve is fully opened
4 Contact the professional who takes care of maintenance of the
appliance
Presence of the flame but insufficient ionization (<3 µA)
4 Check that the gas valve is fully opened
4 Contact the professional who takes care of maintenance of the
appliance
PCU Detection of a parasite flame Ionization current present even though there is no flame
Ignition transformer defective
Gas valve defect
The burner remains very hot: CO2 too high
4 Contact the professional who takes care of maintenance of the
appliance
PCU Internal error on the SU board Bad connection
SU PCB faulty
4 Contact the professional who takes care of maintenance of the
appliance
PCU The fan is not running at the right
speed
Bad connection
Fan defective
4 Contact the professional who takes care of maintenance of the
appliance
PCU Flow and return reversed Bad connection
Sensor fault
e36
PCU The flame went out more than 5
times in 24 hours while the burner was operating
03/12/2013 - 300026082-001-02
4 Contact the professional who takes care of maintenance of the
appliance
Water circulation direction reversed
4 Check the circulation (direction, pump, valves)
No ionization current
4 Check that the gas valve is fully opened
4 Contact the professional who takes care of maintenance of the
appliance
26
6. Troubleshooting EGC 25
Code Cause of
the fault
e37
e38
e39
e40
PCU Communication failure with the
PCU Communication failure between
PCU The BL inlet is open Parameter incorrectly set
PCU HRU/URC unit test error Bad connection
Description Checking / solution
Bad connection SU PCB
4 Contact the professional who takes care of maintenance of the
appliance
Bad connection the PCU and SCU PCBs
SCU PCB not connected or faulty
4 Contact the professional who takes care of maintenance of the
appliance
Bad connection
External cause
4 Contact the professional who takes care of maintenance of the
appliance
External cause
4 Contact the professional who takes care of maintenance of the
appliance
27
03/12/2013 - 300026082-001-02
EGC 25 7. Technical specifications
7 Technical specifications
7.1 Technical specifications
Boiler type EGC 25
General
Nominal output (Pn) Heating System (80/60 °C)
Nominal output (Pn) Heating System (50/30 °C)
Nominal output (Pn) Heating System (40/30 °C)
Nominal input (Qn) Heating System (Hi)
Nominal input (Qn) Heating System (Hs)
Nominal input (Qnw) DHW System (Hi)
Nominal input (Qnw) DHW System (Hs)
Heating efficiency under full load (Hi) (80/60 °C) - % 96,3
Heating efficiency under full load (Hi) (50/30 °C) - % 102,0
Heating efficiency under partial load (Hi) (Return temperature 60°C) - % 96,1
Heating efficiency under partial load (EN 92/42) (Return temperature 30°C)
Data on the gases and combustion gases
Gas consumption - Natural gas H (G20) minimum-maximum
Gas consumption - Natural gas L (G25) minimum-maximum
Gas consumption - Propane G31 minimum-maximum
NOx-Emission (Scrolls forward EN297A3)
Mass flue gas flow rate minimum-maximum kg/h 8,9 - 49,3
Flue gas temperature minimum-maximum °C 30 - 80
Maximum counter pressure
Characteristics of the heating circuit
Water content (ex expansion vessel)
Water operating pressure minimum kPa (bar (MPa)) 80 (0,8)
Water operating pressure (PMS) maximum kPa (bar (MPa)) 300 (3,0)
Water temperature maximum °C 110
Operating temperature maximum °C 90
Electrical characteristics
Power supply voltage
Power consumption - Pump position high - Fastest maximum W 141
Power consumption - Pump position low - Slowest maximum W 78
Power consumption - Standby maximum W 4
Electrical protection index
Other characteristics
Weight (empty)
minimum-maximum kW 5,0 - 24,1
minimum-maximum kW 5,6 - 25,5
minimum-maximum kW 5,6 - 25,9
minimum-maximum kW 5,2 - 25,0
minimum-maximum kW 5,8 - 27,8
minimum-maximum kW 5,2 - 29,3
minimum-maximum kW 5,8 - 32,6
- % 108,0
0,55 - 3,10
0,64 - 3,61
0,21 - 1,20
IP21
m3/h
m3/h
m3/h
mg/kWh 38
Pa 120
l 1,9
VAC 230
kg 50
03/12/2013 - 300026082-001-02
28
8. Energy savings
8 Energy savings
8.1 Energy-saving advice
EGC 25
4 Keep the room in which the boiler is installed well ventilated.
4 Do not block ventilation outlets.
4 Do not cover the radiators. Do not hang curtains in front of the
radiators.
4 Install reflective panels behind the radiators to prevent heat
losses.
4 Insulate the pipes in rooms that are not heated (cellars and lofts).
4 Close the radiators in rooms not in use.
4 Do not run hot (or cold) water pointlessly.
4 Install a water-saving shower head to save up to 40 % energy.
4 Take showers rather than baths. A bath consumes twice as much
water and energy.
8.2 Recommendations
The remote control is available in the following versions:
4 Wire
4 Radio
The setting of the control panel and/or of the remote control has a considerable influence on energy consumption.
A few tips:
4 In the room in which the room thermostat is installed, it’s advised
not to use thermostatic valve radiators. If a thermostatic valve is used the valve must be fully opened.
4 Completely closing and opening thermostatic valve radiators
causes undesirable temperature fluctuations. Open and close thermostatic valves in small steps.
4 Lower the temperature to around 20°C. This reduces heating costs
and energy consumption.
4 Lower the temperature when you air the rooms.
4 When setting a time schedule , bear days when you are absent
and holidays in mind.
29
03/12/2013 - 300026082-001-02
EGC 25
9 Warranty
9.1 General
9.2 Warranty terms
9. Warranty
You have just purchased one of our appliances and we thank you for the trust you have placed in our products.
Please note that your appliance will provide good service for a longer period of time if it is regularly checked and maintained.
Your installer and our customer support network are at your disposal at all times.
The following provisions are not exclusive of the buyer being able benefit from the legal provisions applicable regarding hidden defects in the buyer’s country.
Starting from the purchase date shown on the original installer’s invoice, your appliance has a contractual guarantee against any manufacturing defect.
The length of the guarantee is mentioned in the price catalogue. The manufacturer is not liable for any improper use of the appliance or failure to maintain or install the unit correctly (the user shall take care to ensure that the system is installed by a qualified engineer).
In particular, the manufacturer shall not be held responsible for any damage, loss or injury caused by installations which do not comply with the following:
4 applicable local laws and regulations,
4 specific requirements relating to the installation, such as national
and/or local regulations,
4 the manufacturer’s instructions, in particular those relating to the
regular maintenance of the unit,
4 the rules of the profession.
The warranty is limited to the exchange or repair of such parts as have been recognised to be faulty by our technical department and does not cover labour, travel and carriage costs.
The warranty shall not apply to the replacement or repair of parts damaged by normal wear and tear, negligence, repairs by unqualified parties, faulty or insufficient monitoring and maintenance, faulty power supply or the use of unsuitable fuel.
03/12/2013 - 300026082-001-02
Sub-assemblies such as motors, pumps, electric valves etc. are guaranteed only if they have never been dismantled.
The legislation laid down by european directive 99/44/EEC, transposed by legislative decree No. 24 of 2 February 2002 published in O.J. No. 57 of 8 March 2002, continues to apply.
30
AD001NU-AJ
DUEDI S.r.l.
DE DIETRICH SERVICE
BDR Thermea (Czech republic) s.r.o
www.duediclima.it
www.dedietrich.cz
Distributore Ufficiale Esclusivo
De Dietrich-Thermique Italia
www.dedietrich-heiztechnik.com
Freecall 0800 / 201608
Jeseniova 2770/56
130 00 Praha 3
+49 (0)25 72 / 9161-0
+49 (0)25 72 / 9161-102
info@remeha.de
Via Passatore, 12 - 12010 San Defendente di Cervasca CUNEO
+39 0171 857170 +39 0171 687875 info@duediclima.it
+420 271 001 627 info@dedietrich.cz
IT
DE DIETRICH THERMIQUE Iberia S.L.U.
www.dedietrich-calefaccion.es
C/Salvador Espriu, 11
08908 L’HOSPITALET de LLOBREGAT
+34 935 475 850 info@dedietrich-calefaccion.es
ES
129164, Россия, г. Москва
Зубарев переулок, д. 15/1
Бизнес-центр «Чайка Плаза»,
офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE S.A.S
7605610-001-017605636-001-01
300026081-001-04
7605633-001-017605646-001-01
300026082-001-02
DEDIETRICH THERMIQUE 57,ruedelaGareF-67580MERTZWILLER-BP 30
© Copyright All technical and technological information contained in these technical instructions, as well as any drawings and technical descriptions supplied, remain our property and shall not be multiplied without our prior consent in writing.
03/12/2013
Loading...