DE DIETRICH TWH 200E, TWH 300E, TWH 300EH User Manual

Export
C003182-B
KALIKO
Thermodynamic water heater
TWH 200E TWH 300E TWH 300EH
EN
300026515-001-03
Declaration of conformity
The device complies with the standard type described in the EG declaration of conformity. It was manufactured and commissioned in accordance with European directives.
The original declaration of conformity is available from the manufacturer.
Contents
1 Introduction ................................................................................................6
1.1 Symbols used .......................................................6
1.2 Abbreviations ........................................................6
1.3 General ..................................................................7
1.3.1 Manufacturer’s liability .............................................7
1.3.2 Installer’s liability .....................................................7
1.4 Homologations ......................................................7
1.4.1 Certifications ...........................................................7
1.4.2 Directive 97/23/EC ..................................................8
1.4.3 Factory test .............................................................8
2 Safety instructions and recommendations ..............................................9
2.1 Safety instructions ...............................................9
2.2 Recommendations ................................................9
2.3 Safety data sheet: R-134a refrigerant ...............10
2.3.1 Product identification .............................................10
2.3.2 Hazard identification ..............................................10
2.3.3 Composition / Information on the ingredients ........10
2.3.4 First aid .................................................................10
2.3.5 Fire prevention measures .....................................10
2.3.6 In the event of accidental spillage .........................11
2.3.7 Handling ................................................................11
2.3.8 Personal protection ...............................................11
2.3.9 Considerations on disposal ...................................12
2.3.10 Regulations ...........................................................12
3 Technical description ..............................................................................13
3.1 General description ............................................13
3.2 Main parts ............................................................14
3.3 Operating principle .............................................14
3.4 Technical specifications ....................................15
03/02/2014 - 300026515-001-03
3.4.1 Characteristics of the appliance ............................15
3.4.2 Heating time of the DHW tank depending on the air
temperature ...........................................................16
3.4.3 Max domestic hot water set point reached by the heat
pump depending on the air temperature ...............16
1
Contents
4 Installation ................................................................................................17
4.1 Regulations governing installation ...................17
4.2 Package list .........................................................17
4.2.1 Standard delivery ..................................................17
4.2.2 Accessories ...........................................................17
4.3 Storage and transport ........................................18
4.3.1 Transport ...............................................................18
4.4 Choice of the location ........................................19
4.4.1 Type plate .............................................................19
4.4.2 Positioning of the appliance ..................................19
4.4.3 Main dimensions ...................................................23
4.5 Positioning the appliance ..................................25
4.5.1 Unpacking the appliance .......................................25
4.5.2 Positioning the appliance ......................................25
4.5.3 Levelling ................................................................26
4.6 Hydraulic connections .......................................26
4.6.1 Connecting the calorifer to the domestic water circuit
(secondary circuit) .................................................26
4.6.2 Connection to a boiler (Version EH) ......................28
4.6.3 Connection to solar collectors (Version EH) .........30
4.7 Condensates discharge .....................................32
4.8 Installing the control system in the living
room .....................................................................32
4.8.1 Choose a location .................................................32
4.8.2 Operations to be carried out on the thermodynamic
DHW tank ..............................................................33
4.8.3 Installing the control system in the living
room ......................................................................34
4.9 Electrical connections ........................................35
4.9.1 Recommendations ................................................35
4.9.2 Connecting the hydraulic back-up (Version
EH) ........................................................................35
4.9.3 Access to the connection terminal HP/HC ............36
4.9.4 Connection with HP/HC signal connected ............37
4.9.5 Connection with timer programming .....................39
4.9.6 Connection with timer programming and photovoltaic
signal .....................................................................40
4.10 Electrical principle diagram ...............................41
4.11 Filling the thermodynamic DHW tank ...............42
5 Commissioning ........................................................................................43
5.1 Control panel .......................................................43
5.1.1 Description of the keys ..........................................43
5.1.2 Description of the display ......................................43
03/02/2014 - 300026515-001-03
2
5.1.3 Browsing in the menus ..........................................45
5.2 Check points before commissioning ................45
5.3 Putting the appliance into operation ................46
5.3.1 Commissioning ......................................................46
5.4 Checks and adjustments after
commissioning ...................................................46
5.5 Choosing the operating mode ...........................46
5.6 Reading out measured values ...........................47
5.6.1 Measurements menu ............................................47
5.6.2 Counters ................................................................47
5.7 Modifying the installer parameters ...................49
5.7.1 Access to parameters ...........................................49
5.7.2 List of the parameters ...........................................50
5.7.3 Control system sequence ......................................51
5.7.4 Return to the factory settings ................................51
6 Switching off the appliance .....................................................................53
6.1 Installation shutdown .........................................53
6.2 Antifreeze protection ..........................................53
7 Checking and maintenance .....................................................................54
7.1 General instructions ...........................................54
7.2 Maintenance operations to be performed ........55
7.2.1 Refrigerant circuit ..................................................55
7.2.2 Hydraulic circuit .....................................................55
7.2.3 Aeraulics ...............................................................55
7.2.4 Impressed current anode ......................................55
7.2.5 Checking the safety valve or unit ..........................55
7.2.6 Descaling ..............................................................56
7.2.7 Cleaning the condensates discharge duct ............56
7.3 Accessing the bottom inspection trap .............57
7.4 Maintenance form ...............................................58
8 Troubleshooting .......................................................................................59
03/02/2014 - 300026515-001-03
8.1 Messages (Code type bxx or Exx) .....................59
8.1.1 Messages (type code bXX) ..............................59
8.1.2 Messages (type code EXX) ..............................61
8.2 Message and error history .................................62
8.2.1 Err error display ....................................................63
8.2.2 bL blockage display ...............................................63
8.2.3 Reset error and blockage history ..........................63
3
Contents
9 Spare parts ................................................................................................64
9.1 General ................................................................64
9.2 Spare parts ..........................................................64
9.2.1 Heat pump .............................................................64
9.2.2 DHW tank ..............................................................66
03/02/2014 - 300026515-001-03
4
03/02/2014 - 300026515-001-03
5
1. Introduction
1 Introduction
1.1 Symbols used
TWH 200E TWH 300E TWH 300EH
In these instructions, various danger levels are employed to draw the user’s attention to particular information. In so doing, we wish to safeguard the user’s safety, obviate hazards and guarantee correct operation of the appliance.
DANGER
Risk of a dangerous situation causing serious physical injury.
WARNING
Risk of a dangerous situation causing slight physical injury.
1.2 Abbreviations
CAUTION
Risk of material damage.
Signals important information.
¼Signals a referral to other instructions or other pages in the instructions.
Before installing and commissioning the device, read carefully the instruction manuals provided.
4 HP: Heat pump
4 DHW: Domestic hot water
4 LP: Low pressure
4 HP: High pressure
4 CFC: Chlorofluorocarbon
4 Qpr: Static losses (Thermal losses from the DHW tank when it is
off for 24 hours)
4 COP: Performance coefficient
4 HP/HC: Peak hours / Off-peak hours
6
03/02/2014 - 300026515-001-03
TWH 200E TWH 300E TWH 300EH
1.3 General
1. Introduction
1.3.1. Manufacturer’s liability
Our products are manufactured in compliance with the requirements of the various applicable European Directives. They are therefore
delivered with [ marking and all relevant documentation.
In the interest of customers, we are continuously endeavouring to make improvements in product quality. All the specifications stated in this document are therefore subject to change without notice.
Our liability as the manufacturer may not be invoked in the following cases:
4 Failure to abide by the instructions on using the appliance.
4 Faulty or insufficient maintenance of the appliance.
4 Failure to abide by the instructions on installing the appliance.
1.4 Homologations
1.3.2. Installer’s liability
The installer is responsible for the installation and inital start up of the appliance. The installer must respect the following instructions:
4 Read and follow the instructions given in the manuals provided
with the appliance.
4 Carry out installation in compliance with the prevailing legislation
and standards.
4 Perform the initial start up and carry out any checks necessary.
4 Explain the installation to the user.
4 If a maintenance is necessary, warn the user of the obligation to
check the appliance and maintain it in good working order.
4 Give all the instruction manuals to the user.
1.4.1. Certifications
03/02/2014 - 300026515-001-03
Electrical compliance / Marking CE
n
This product complies to the requirements to the european directives and following standards:
4 2006/95/EC Low Voltage Directive
Reference Standard: EN 60.335.1.
4 2004/108/EC Electromagnetic Compatibility Directive
7
1. Introduction TWH 200E TWH 300E TWH 300EH
Reference Standard: EN 50.081.1 / EN 50.082.1 / EN 55.014.
1.4.2. Directive 97/23/EC
This product conforms to the requirements of european directive 97 / 23 / EC, article 3, paragraph 3, on pressure equipment.
1.4.3. Factory test
Before leaving the factory, each appliance is tested for the following:
4 Water tightness
4 Air tightness
4 Electrical safety.
8
03/02/2014 - 300026515-001-03
TWH 200E TWH 300E TWH 300EH 2. Safety instructions and recommendations
2 Safety instructions and
recommendations
2.1 Safety instructions
DANGER
If smoke is released or in case of refrigerant leak:
1. Do not use a naked flame, do not smoke, do not operate electrical contacts or switches ( doorbell, light, motor, lift, etc..).
2. Open the windows.
3. Switch the appliance off.
4. Avoid contact with the refrigerant. Danger of frost injuries.
5. Trace possible leaks and seal them immediately.
2.2 Recommendations
WARNING
Depending on the settings of the appliance:
4 Do not touch the refrigeration connection pipes with
your bare hands while the appliance is running. Risk of being burnt.
CAUTION
4 Do not neglect to service the appliance.
4 In order to limit the risk of being scalded, the
installation of a thermostatic mixing valve on the domestic hot water flow piping is compulsory.
WARNING
Only certified professionals having received adequate training are permitted to work on the appliance and the installation.
03/02/2014 - 300026515-001-03
WARNING
Before any work, switch off the mains supply to the appliance.
9
2. Safety instructions and recommendations
2.3 Safety data sheet: R-134a refrigerant
2.3.1. Product identification
4 Refrigerant name: R-134a
2.3.2. Hazard identification
4 Effects harmful to health:
- The vapours are heavier than air and may lead to asphyxia owing to reduced oxygen levels.
- Liquefied gas: Contact with the liquid may cause serious frost and eye injuries.
4 Product classification: This product is not classified as a
"hazardous preparation" according to European Union regulations.
TWH 200E TWH 300E TWH 300EH
2.3.3. Composition / Information on the ingredients
4 Chemical nature: 1,1,1,2-Tetrafluoroethane R-134a.
4 Ingredients that may lead to hazardous situations:
Substance name
1,1,1,2-Tetrafluoroethane R-134a 100 % 811-97-2 212-377-0
Concentration CAS number CE number Classification GWP
2.3.4. First aid
4 If inhaled: Evacuate the subject from the contaminated area and
take him into the open air. If feeling unwell: Call a doctor.
4 In the event of contact with the skin: Treat frost injuries as
burns. Rinse in abundant water, do not remove clothing (risk of adhesion to the skin). If skin burns appear, call a doctor immediately.
4 In the event of contact with the eyes: Rinse immediately in
water, holding the eyelids well apart (at least 15 minutes). Consult an ophthalmologist immediately.
1300
10
2.3.5. Fire prevention measures
4 Appropriate extinguishing agents: All extinguishing agents can be
used.
03/02/2014 - 300026515-001-03
TWH 200E TWH 300E TWH 300EH
2. Safety instructions and recommendations
4 Inappropriate extinguishing agents: None to our knowledge. In the
event of fire nearby, use the appropriate extinguishing agents.
4 Specific hazards:
- Rise in pressure. In the presence of air, an inflammable mixture may form under certain temperature and pressure conditions
- Toxic and corrosive vapours may be released by the effect of the heat.
4 Special intervention methods: Cool the volumes exposed to heat
with water spray.
4 Protection of the firemen:
- Full facepiece self-contained breathing apparatus
- Complete body protection.
2.3.6. In the event of accidental spillage
4 Individual precautions:
- Avoid contact with the skin and eyes
- Do not intervene without appropriate protective equipment
- Do not inhale the vapours
- Evacuate the hazardous area
- Stop the leakage
- Eradicate all sources of ignition
- Ventilate the spillage area mechanically (Risk of asphyxia).
4 Cleaning / Decontamination: Allow residual product to evaporate.
2.3.7. Handling
4 Technical measures: Ventilation.
4 Precautions to be taken:
- No smoking
- Prevent the accumulation of electrostatic charges
- Work in a well ventilated place.
2.3.8. Personal protection
4 Respiratory protection:
- If insufficient ventilation: AX type cartridge mask
- In confined spaces: Full facepiece self-contained breathing
apparatus.
4 Hand protection: Protective gloves in leather or nitrile rubber.
4 Eye protection: Safety glasses with side protection.
4 Skin protection: Clothing made mostly of cotton.
4 Industrial hygiene: Do not drink, eat or smoke at the place of work.
03/02/2014 - 300026515-001-03
11
2. Safety instructions and recommendations TWH 200E TWH 300E TWH 300EH
2.3.9. Considerations on disposal
4 Product waste: Consult the manufacturer or the supplier for
information on recovery or recycling.
4 Soiled packaging: Reuse or recycle after decontamination.
Destroy in authorised installations.
WARNING
Disposal must be done in compliance with prevailing local and national regulations.
2.3.10. Regulations
4 EC Regulation 842/2006: Fluorinated greenhouse gases under
the Kyoto Protocol.
12
03/02/2014 - 300026515-001-03
TWH 200E TWH 300E TWH 300EH 3. Technical description
3 Technical description
3.1 General description
The DHW tanks in the TWH range have the following characteristics:
4 Floor-standing thermodynamic storage DHW tank
4 Thermodynamic unit extracting energy from unheated ambient air
or outside air
4 Control panel with display of the volume of water heated and
hourly programming
4 Heat exchanger for connection to a boiler or a solar circuit (Version
EH)
4 Steatite electrical resistor 2.4 kW
4 Enamelled tank protected by impressed current anode
4 Very thick insulation (0% CFCs)
The thermodynamic water heater is a hot water tank that can be heated by:
4 The Heat Pump (up to 65°C)
4 The electric heating resistance (Electrical back-up - AUTO and
Boost mode) (up to 70°C)
4 The additional heat exchanger (Version EH)
03/02/2014 - 300026515-001-03
13
C003185-F
5
6
10
2
1
3 4
15
16
13
12
14
17
11
19
18
8
7
9
3. Technical description
3.2 Main parts
TWH 200E TWH 300E TWH 300EH
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Fan
Evaporator
Expansion valve
Solenoid valve for defrosting
Regulation
temperature sensor
Impressed current anode
Safety thermostat
Steatite electrical resistor
temperature sensor
Air conduits
High pressure (HP) pressure switch
Low pressure (LP) pressure switch
Compressor
Pressure measurement point - High pressure (HP)
Ventilation grid
Domestic hot water outlet
18
19
Condenser
Cold water inlet
3.3 Operating principle
The thermodynamic DHW tank uses unheated ambient air or outside air to prepare DHW.
The refrigerant circuit is a closed circuit in which the R-134a refrigerant plays the role of an energy carrier.
The heat from the intake air is transferred to the refrigerant in the finned heat exchanger at a low evaporation temperature.
The refrigerant is sucked in by a compressor in vapour form, which raises it to a higher pressure and temperature and sends it to the condenser. In the condenser, the heat extracted in the evaporator and some of the energy absorbed by the compressor are released into the water.
14
03/02/2014 - 300026515-001-03
C003625-D
TWH 200E TWH 300E TWH 300EH 3. Technical description
The refrigerant is depressurised in the thermostatic expansion valve and is cooled. The refrigerant can again extract the heat contained in the inlet air into the evaporator.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Compressor
Low pressure (LP) pressure switch
Condenser
Domestic hot water tank
Heat exchanger (Version EH)
Steatite electrical resistor
Impressed current anode
Temperature regulator (HP)
Limiting thermostat
Temperature regulator (Electric heating resistance)
Sensor tube
Filter-drier
Thermostatic expansion valve
Ambient air thermostat
Evaporator
Fan
17
18
19
20
Expansion valve bulb
Sensor tube
Solenoid valve for defrosting
High pressure (HP) pressure switch
3.4 Technical specifications
3.4.1. Characteristics of the appliance
Model
Capacity litres 270 265 215
Output (HP) -Air temperature = 15°C W 1700 1700 1700
Absorbed electrical power (HP) W 500 500 500
(1)
COP
(2)
COP
Air flow rate - maximum
Nominal air flow rate (DP = 25 Pa)
Electrical resistor output W 2400 2400 2400
(1) Value obtained at an air temperature of 15°C and a relative humidity of 70%. Water inlet temperature at 15°C in accordance with EN255-3. (2) Value obtained with an air temperature of 7 and a water inlet at 10 °C, as per EN16147 based on Specification LCIE N°103-15/B:2011 (3) Domestic cold water input at 10°C - Primary inlet temperature at 80°C (4) Output: 34.1 kW (5) The installation of suction and backflow conduits on the heat pump lessens its performance
(2)
m3/h
m3/h
TWH 300 E TWH 300 EH TWH 200 E
3.7 3.6 3.5
2.94 2.75 2.90
385 385 385
320 320 320
03/02/2014 - 300026515-001-03
15
0
2
4
6
8
10
12
14
16
18
20
-5 0 5 10 15 20 25 30 35
Y
X
B
A
C003447-A
C003483-B
51°
-5 0 5 7 10 X
55°
65°
Y
3. Technical description TWH 200E TWH 300E TWH 300EH
Model
TWH 300 E TWH 300 EH TWH 200 E
Operating pressure bar (MPa) 10 10 10
Power supply voltage V 230 230 230
Circuit breaker A 16 16 16
Exchanger surface
Continuous output DT = 35 K
Flow rate over 10 minutes with DT = 30 K
Heating time (15-51 °C)
(1)
Qpr
(1)
V40
(2)
Vmax
(2)
Pes
(3) (4)
(3)
(1)
Maximum length of the air connection Diameter 160 mm
(5)
2
m
- 1.00 -
litres per hour - 955.6 -
l/10 mm - 420 -
Hours 7 7 5
kWh/24h 0.67 0.75 0.73
litres 357 358 240
litres 388 383 281.9
W 34 36 30
m 25 25 25
R134a refrigerant kg 1.45 1.45 1.45
Weight (empty) kg 105 123 92
(1) Value obtained at an air temperature of 15°C and a relative humidity of 70%. Water inlet temperature at 15°C in accordance with EN255-3. (2) Value obtained with an air temperature of 7 and a water inlet at 10 °C, as per EN16147 based on Specification LCIE N°103-15/B:2011 (3) Domestic cold water input at 10°C - Primary inlet temperature at 80°C (4) Output: 34.1 kW (5) The installation of suction and backflow conduits on the heat pump lessens its performance
3.4.2. Heating time of the DHW tank depending on the air temperature
Scenario for complete heating of the DHW tank
A
B
Y
X
Heating time for a set point of 51°C
Heating time for a set point of 62°C
Heating time (Hours)
Air temperature (°C)
3.4.3. Max domestic hot water set point reached by the heat pump depending on the air temperature
Y
Max domestic hot water temperature (°C)
16
X
Air temperature (°C)
03/02/2014 - 300026515-001-03
TWH 200E TWH 300E TWH 300EH 4. Installation
4 Installation
4.1 Regulations governing installation
CAUTION
Installation and maintenance of the appliance must be done by a qualified professional in accordance with prevailing statutory texts and codes of practice.
4.2 Package list
4.2.1. Standard delivery
The delivery includes:
4 The thermodynamic DHW tank x1
4 Dielectric connection (delivered in the instructions bag for the
DHW tank) (2x)
4 Lip gasket (2x)
4 Condensate evacuation hose (1x)
4 Instructions + Kyoto Protocol sticker (1x)
4 Hose holding clip (1x)
4 The user instructions
4 The installation and maintenance instructions
4.2.2. Accessories
Accessories
Galvanised 90° elbow (Diameter 160 mm) EH 77
Adapter sleeve (Diameter 160 mm) EH 205
Insulated flexible duct (Diameter 160 mm - Length 3 m) EH 206
Set of 2 retaining clamps (Diameter 160 mm) EH 207
Passing through walls (Diameter 160 mm) + Closing plate EH 208
Outside grid (Diameter 160 mm) (aluminium) EH 209
PPE duct (Diameter 160 mm - Length 2x1 m) + 2 sleeves EH 272
290° elbows (PPE) (Diameter 160 mm) + 2 sleeves EH 273
2 sleeves PPE (Diameter 160 mm) EH 274
Roof outlet Black (Diameter 160 mm) EH 275
Tightness bed plate for flat roof (Diameter 160 mm) EH 276
package
03/02/2014 - 300026515-001-03
17
C003496-B
4. Installation TWH 200E TWH 300E TWH 300EH
Accessories package
Tightness bed plate for sloping roof 25 to 45° (Diameter 160 mm)
Reduced elbow kit EH 434
Connection kit for safety unit ER 208
EH 277
4.3 Storage and transport
CAUTION
4 Have 2 people available.
4 Use a 3-wheel hand truck.
4 Handle the appliance with gloves.
4 The appliance cover cannot be used for transport
operations. The cover is not capable of withstanding heavy weights.
4 Model 300 : Allow a minimum room height of
approximately 2.15 m Model 200 : Allow a minimum room height of approximately 1.84 m.
4 The thermodynamic DHW tank must be stored and transported in
its packaging and not filled with water.
4 Ambient transport and storage temperatures admissible: from
-20 to +60°C.
4.3.1. Transport
We recommend shipping the appliance vertically.
It is possible to ship the appliance horizontally over short
distances but only on its back.
CAUTION
The appliance must never be stacked or laid on another side; it may otherwise malfunction or break down.
18
03/02/2014 - 300026515-001-03
C003192-D
TWH 200E TWH 300E TWH 300EH
4.4 Choice of the location
4. Installation
4.4.1. Type plate
4 The type plate must be accessible at all times.
4 The type plate identifies the product and provides the following
information:
- Appliance type
- Manufacturing date (Year - Week)
- Serial number.
4.4.2. Positioning of the appliance
CAUTION
When installing the appliance, respect the IP21 environmental rating.
CAUTION
4 Do not install the thermodynamic water heater in
premises exposed to gas, vapours or dust. Do not install the thermodynamic DHW tank in an atmosphere which is chlorinated (swimming pool) or fluorinated (aerosols, detergents, solvents, etc.).
4 The air taken in must in no event be dusty.
4 Adequate thermal insulation in relation to adjacent
living spaces is recommended.
4 Temperature of the ambient air or of the air taken in
by the heat pump for optimum running: from 10 to 35°C.
Install the appliance in a dry, frost-free room at a minimum
4
temperature of 7°C.
4 Install the appliance on a flat, solid surface.
03/02/2014 - 300026515-001-03
19
C004021-A
C004020-A
C004019-A
A
C004022-A
C004023-A
B
4. Installation TWH 200E TWH 300E TWH 300EH
4 Install the appliance on a base frame. The base frame must at all
times present sufficient resistance to the load.
Advised positions
n
Garage:
4 Unheated room.
4 Enables recovery of the free energy released by your vehicle’s
engine when switched off after use or by household appliances in operation.
Laundry room:
4 Unheated room.
4 Enables the dehumidification of the room and recovery of the
energy wasted by washing and drying machines.
Habitable room:
4 Can obtain free heat from the garage.
Via crawl space:
4 Connection to the crawl space is possible if the volume is greater
than 30 m3.
4 The crawl space must be frost-free (temperature > 1°C).
If the crawl space is poorly insulated, thermal losses from the home will be greater.
Via outside air:
4 Connection to the outside air may lead to overconsumption of
electricity if the outside air temperature falls outside the operating range.
4 Minimum distance to be observed for the ducts if intake and
backflow are done on the same façade: 700 mm.
20
Risk of discomfort in the Eco operating mode.
03/02/2014 - 300026515-001-03
C003481-C
690
300
1100
1100 mini
0 160
C004734-A
0 160 / 200
800 mini
800
826
598
C003188-F
V > 30m
3
150
150
min.
400
min.
400
690
A
0 600
TWH 200E TWH 300E TWH 300EH
4. Installation
Cupboard:
4 With EH77 or EH273: 1100 mm x 1100 mm - Ducted version. Be
sure to make the aeraulic connections absolutely leakproof in order to prevent the cupboard from losing heat.
We strongly recommend installing the control system in the living room.
4 With EH434 (Reduced elbow kit): 800 mm x 800 mm - Ducted
version. Be sure to make the aeraulic connections absolutely leakproof in order to prevent the cupboard from losing heat.
We strongly recommend installing the control system in the living room.
A (mm) 1690 2000 2000
TWH 200E TWH 300E TWH 300EH
4 To ensure adequate access and facilitate maintenance, allow
sufficient space around the appliance.
4 Model 200: Allow a minimum distance of 0.4 m at both sides of the
appliance and a minimum room height of around 1.84 m for operation without air ducts.
4 Model 300: Allow a minimum distance of 0.4 m at both sides of the
appliance and a minimum room height of around 2.15 m for operation without air ducts.
03/02/2014 - 300026515-001-03
21
4. Installation TWH 200E TWH 300E TWH 300EH
Pipe length
n
CAUTION
Do not use accessories that may cause considerable pressure drops (extraction grid with mosquito screen, partially extended flexible duct, etc.). Pressure drops from accessories must be lower than or equal to the static pressure of the fan (50 Pa). If the pressure drops are greater, the performance of the appliance will be impaired and the loading times increased.
Maximum length of the air connection m
diameter 160 mm 25
Accessories package Equivalent length in m
Galvanised 90° elbow (Diameter 160 mm) EH77 1.0
Adapter sleeve (Diameter 160 mm) EH205 1.5
Insulated flexible duct (Diameter 160 mm - Length 3 m) EH206 3.0
Passing through walls (Diameter 160 mm) + Closing plate EH208 7.0
Outside grid (Diameter 160 mm) (aluminium) EH209 8.0
PPE duct (Diameter 160 mm - Length 2x1 m) + 2 sleeves EH272 0.2
290° elbows (PPE) (Diameter 160 mm) + 2 sleeves EH273 0.2
Roof outlet Black (Diameter 160 mm) EH275 2.0
Reduced elbow kit EH434 6.0
22
03/02/2014 - 300026515-001-03
C003183-E
50°
A
690
90
B
1025
810
4
(1)
3
1
2
4
TWH 200E TWH 300E TWH 300EH 4. Installation
4.4.3. Main dimensions
TWH 200E - TWH 300E
n
03/02/2014 - 300026515-001-03
A Z E R
(1)
TWH 200E TWH 300E
A 1690 2000
B 974 1287
Impressed current anode
Steatite electrical resistor 2.4 kW
Domestic hot water outlet G 3/4"
Domestic cold water inlet G 3/4"
Adjustable feet ¼See chapter "Positioning the appliance", page
25
23
C003476-B
90
690
810
300
455
658
1375
2000
1025
4
(1)
1
2
3
4
5
6
7
4. Installation TWH 200E TWH 300E TWH 300EH
TWH 300EH
n
24
A Z E R T Y U
(1)
Impressed current anode
Steatite electrical resistor 2.4 kW
Secondary domestic hot water flow G 3/4"
Solar exchanger or boiler inlet G 3/4"
Sensor tube for solar or boiler sensor G 3/4"
Solar exchanger or boiler outlet G 3/4"
Domestic cold water inlet G 3/4"
Adjustable feet ¼See chapter "Positioning the appliance", page
25
03/02/2014 - 300026515-001-03
M003102-A
1
2
3
4
5
6
7
8
TWH 200E TWH 300E TWH 300EH 4. Installation
4.5 Positioning the appliance
4.5.1. Unpacking the appliance
CAUTION
Remove all packaging materials. Check that the contents are intact. If you notice a defect, do not use the appliance and contact the supplier.
1. Remove the retaining screw from the fan grille.
2. Turn the grille anticlockwise.
3. Remove the fan grille.
4. Unscrew the 2 screws from the compressor support part.
5. Remove the compressor support part and discard it.
6. Put the grille back in place.
7. Turn the grille clockwise to fit it back into its housing.
8. Put the retaining screws in place.
4.5.2. Positioning the appliance
¼Refer to the instructions affixed to the packaging of the appliance
CAUTION
After positioning the appliance, wait one hour before starting it up.
03/02/2014 - 300026515-001-03
25
C003187-E
B
21
(1)
19
4. Installation
4.6 Hydraulic connections
TWH 200E TWH 300E TWH 300EH
4.5.3. Levelling
To improve condensates evacuation, we recommend tilting the appliance slightly backwards.
1. Level the appliance using the adjustable feet.
(1) Adjustable feet, Basic dimension 4 mm Can be adjusted from 4 mm to 21 mm
CAUTION
Before making the hydraulic connections, it is essential to rinse the circuit to get rid of any particles that may damage certain units (safety valve, pumps, valves, etc.). If rinsing has to be done using an aggressive product, neutralise the rinsing water before disposing of it in the waste water network.
Using hoses which are too short or too rigid encourages the transmission of vibrations and the production of noises.
Version EH: Make all the hydraulic connections for the DHW tank using flexible pipes.
4.6.1. Connecting the calorifer to the domestic water circuit (secondary circuit)
When making the connections, it is imperative that the standards and corresponding local directives are respected.
Specific precautions
n
Before making the connection, rinse the drinking water inlet
26
pipes in order not to introduce metal or other particles into the appliance’s tank.
03/02/2014 - 300026515-001-03
TWH 200E TWH 300E TWH 300EH
4. Installation
CAUTION
Do not connect the domestic hot water connection directly to copper pipes in order to prevent galvanic couples in iron/ copper (risk of corrosion). It is compulsory to fit the domestic hot water connection with a dielectric connection (Supplied).
Safety valve or safety unit
n
CAUTION
In accordance with safety rules, a safety unit calibrated to 7 bar must be mounted on the DHW tank’s domestic cold water inlet.
4 Integrate the safety valve in the cold water circuit.
4 Install the safety valve close to the calorifer in a place which is
easy to access.
Size
n
4 The diameter of the safety unit and its connection to the calorifer
must be at least equal to the diameter of the domestic cold water inlet on the calorifer.
4 There must be no cut-off element between the valve or the safety
unit and the domestic hot water calorifer.
4 The outlet pipe in the valve or safety assembly must not be
blocked.
To avoid restricting the flow of water in the event of overpressure:
4 The safety device drain pipe must have a uniform and sufficient
gradient and its diameter must be at least equal to that of the outlet opening of the safety device (to prevent the flow of water being hindered if the pressure is too high).
4 The cross section of the discharge pipe from the safety unit must
be at least equal to the cross section of the opening of the safety unit outlet.
Isolating valves
n
03/02/2014 - 300026515-001-03
Hydraulically isolate the primary and secondary circuits using stop valves to facilitate maintenance operations on the unit. The valves make it possible to carry out maintenance on the calorifer and its components without draining the entire installation.
These valves are also used to isolate the calorifer unit when conducting a pressurised check on the leak tightness of the installation if the test pressure is greater than the admissible operating pressure.
27
4. Installation TWH 200E TWH 300E TWH 300EH
CAUTION
If the mains pipes are made of copper, fit a sleeve made of steel, cast iron or any other insulating material between the tank’s hot water outlet and the pipes to prevent corrosion to the connection.
Connecting the domestic cold water
n
Make the connection to the cold water supply according to the hydraulic installation diagram. Install a water drain in the boiler room and a funnel-siphon for the safety unit.
The components used for the connection to the cold water supply must comply with the prevailing standards and regulations in the country concerned. Fit a one-way valve to the domestic cold water circuit.
Pressure reducer
n
If the mains pressure exceeds 80% of the calibration of the valve or safety unit (e.g. 5,5 bar (0,55 MPa) for a safety unit calibrated to 7 bar (0,7 MPa)), a pressure reducer must be installed upstream of the appliance. Install the pressure reducer downstream the water meter in such a way as to ensure the same pressure in all of the installation pipes.
Measures to take to prevent hot water flow return
n
Fit a one-way valve to the domestic cold water circuit.
4.6.2. Connection to a boiler (Version EH)
CAUTION
Before making the water connections of the heating circuit and domestic hot water tank heat exchanger, it is imperative to rinse the circuits to remove any particles which might damage the components (safety valve, pumps, valves, ...).
28
03/02/2014 - 300026515-001-03
C003613-B
TWH 200E TWH 300E TWH 300EH 4. Installation
A
1
2
3
4
7
9
11
16
17
18
21
22
24
25
26
27
Boiler
Heating flow
Heating return
Safety valve
Pressure gauge
Automatic air vent
Isolating valve
Heating pump
Expansion vessel
Drain cock
Filling the heating circuit
Outside sensor
Boiler sensor
DHW calorifier exchanger primary inlet
DHW calorifier heat exchanger primary outlet
DHW pump
Non-return valve
03/02/2014 - 300026515-001-03
28
Domestic cold water inlet
29
C003612-A
4. Installation TWH 200E TWH 300E TWH 300EH
29
30
33
50
51
52
Pressure reducer
Safety unit
DHW sensor
Disconnector
Thermostatic valve
Differential valve (only with module fitted with a 3-speed pump)
57
90
Domestic hot water outlet
Anti-thermosiphon loop
4.6.3. Connection to solar collectors (Version EH)
CAUTION
Limit the domestic hot water temperature to 60°C.
30
4
Pressure gauge
03/02/2014 - 300026515-001-03
TWH 200E TWH 300E TWH 300EH 4. Installation
27
28
29
30
57
61
79
80
84
85
87
88
89
90
109
112a
112b
Non-return valve
Domestic cold water inlet
Pressure reducer
Safety unit
Domestic hot water outlet
Thermometer
Primary solar exchanger outlet on the DHW calorifier
Primary solar exchanger inlet on the DHW calorifier
Stop valve with releasable non-return valve
Primary solar circuit pump
Safety valve calibrated at 6 bar
Solar expansion vessel
Heat transfer fluid container
Anti-thermosiphon loop (= 10 x Pipe diameter)
Domestic hot water thermostatic mixing valve
Solar sensor probe
Solar DHW sensor
114
126
129
130
131
132
Primary solar circuit filling and draining device
Solar regulator
Insulation
Manual bleed degasser
Solar collectors
Complete solar station with solar regulator
03/02/2014 - 300026515-001-03
31
1
C003656-B
min. 200
4. Installation
4.7 Condensates discharge
TWH 200E TWH 300E TWH 300EH
1. Mount a siphon in the condensates discharge pipe.
CAUTION
If there is no siphon, problems with condensates discharge may arise when the compressor is running.
2. Mount the flow collector.
3. Fit the clamp to the flow header.
4.8 Installing the control system in the living room
The control system is mounted as standard on the heat pump. It is possible to install the control system in the living room for greater comfort.
4 The user can remotely control programming of DHW production.
4 The user is informed directly if the installation malfunctions in any
way.
4.8.1. Choose a location
Install the control system against an internal wall around 1.5 metres from the floor in the carefully chosen pilot room.
Locations in the room that are not recommanded:
4 Encased
4 Exposed to solar radiation.
32
03/02/2014 - 300026515-001-03
C003254-C
1
1
2
6
4
3
5
C003329-D
7
C003408-D
TWH 200E TWH 300E TWH 300EH 4. Installation
4.8.2. Operations to be carried out on the thermodynamic DHW tank
1. Unscrew the 2 screws.
2. Remove the front cover.
3. Separate the control system command module from its base.
4. Disconnect the command module (2 wires).
5. Unscrew the 2 fastening wires on the base.
6. Remove the wire and discard it.
7. Unscrew the 2 fastening screws on the base of the control panel
and remove the base.
03/02/2014 - 300026515-001-03
33
C003330-D
8
C003334-G
10
13
9
10
1
2
3
6
C003331-A
4. Installation TWH 200E TWH 300E TWH 300EH
8. Connect the 2 wires for connecting the command module at the
appliance end (not supplied).
9. Replace the front cover.
10.Tighten the 2 screws.
4.8.3. Installing the control system in the living room
1. Drill 2 holes with a Ø of 6 mm.
2. Put the plugs in place.
3. Attach the wall support.
34
03/02/2014 - 300026515-001-03
4
5
C003407-D
TWH 200E TWH 300E TWH 300EH
4.9 Electrical connections
4. Installation
4. Connect the 2 wires on the command module.
5. Put the control system module in place.
4.9.1. Recommendations
WARNING
4 Only qualified professionals may carry out electrical
connections, always with the power off.
4 Do not connect the power supply directly to the HP/
HC contact.
The earthing shall comply with local standards.
Power the appliance with a circuit that includes a 16 A omnipolar circuit breaker, D curve type, with a gap of more than 3 mm.
The DHW tank is delivered with a 3G cable. If the power cable is damaged, it must be replaced by the manufacturer, its after sales service or persons with similar qualifications in order to obviate any danger. The electricity supply is connected to the mains by connection cable (~230 V, 50 Hz) and electrical plug.
The HP/HC connection is made on the terminal block.
4.9.2. Connecting the hydraulic back-up (Version EH)
1. Remove the front cover.
See chapter "Installing the control system in the living
¼
room", page 32
03/02/2014 - 300026515-001-03
35
C003618-B
Backup
C003254-C
1
1
2
4. Installation TWH 200E TWH 300E TWH 300EH
2. Access to the PCB.
3. Connect the boiler back-up connector (boiler back-up). To set the
boiler inlet, refer to the boiler instruction manual.
4.9.3. Access to the connection terminal HP/HC
1. Unscrew the 2 screws.
2. Remove the front cover.
36
03/02/2014 - 300026515-001-03
C003335-A
HP/HC 230V
C003335-B
C003617-E
A
A
B
C1 C2
538 kW/h
1
1
A1
A2
0
Auto
0
15 / 45 A 500 mA
TEST
16 A40 A 2 A
30
mA
L N
X11-2 HP/H
X11-1 LINE
C
1 2
3 4 4
TWH 200E TWH 300E TWH 300EH 4. Installation
3. Access to the PCB.
4. Make the electrical connection using cable with a cross section of
1,5 mm2.
4.9.4. Connection with HP/HC signal connected
Shunt connection with HP/HC relay (Dry contact in the
n
heat pump)
03/02/2014 - 300026515-001-03
1
Meter
37
C1 C2
538 kW/h
1
0
15 / 45 A 500 mA
TEST
16 A40
C003616-D
A 2 A
30
mA
L N
X11-2 HP/H
X11-1 LINE
C
L N
X11-2 HP/HC
X11-1 LINE
A
1 2
3 4 4
4. Installation
TWH 200E TWH 300E TWH 300EH
2
3
4
A
B
Connection circuit breaker
AC type differential switch
Circuit breaker
Power cable 1,5 mm
Shunt 1,5 mm
2
2
4 Set parameter P04 to 2.
4 The heat pump and additional heating are not permitted to operate
in Peak Hours
4 Rapid Boost heating at one touch
4 The 2 signal wires must be routed as far as the appliance’s box
Connection to the meter with direct HP/HC contact (Dry
n
contact or voltage in the heat pump)
38
1
2
3
4
A
Meter
Connection circuit breaker
AC type differential switch
Circuit breaker
Power cable 1,5 mm
2
4 Set parameter P04 to 2.
4 The heat pump and additional heating are not permitted to operate
in Peak Hours
4 Rapid Boost heating at one touch
03/02/2014 - 300026515-001-03
C1 C2
538 kW/h
1
0
15 / 45 A 500 mA
TEST
16 A40
C003615-D
A 2 A
30
mA
L N
1 2
3 4 4
TWH 200E TWH 300E TWH 300EH 4. Installation
4 The 2 signal wires must be routed as far as the appliance’s box
4.9.5. Connection with timer programming
1
2
3
4
Meter
Connection circuit breaker
AC type differential switch
Circuit breaker
4 Easy to install
4 Opt for hourly programming to take advantage of the HP/HC tariff
03/02/2014 - 300026515-001-03
39
C004218-B
A
TEST
16 A40 A 2 A
30
mA
L N
X11-2 HP/H
PV-S
DC AC
X11-1 LINE
C
3
5
6
4 4
4. Installation TWH 200E TWH 300E TWH 300EH
4.9.6. Connection with timer programming and photovoltaic signal
3
AC type differential switch
4
Circuit breaker
5
Photovoltaic panel
6
Inverter
A
Power cable 1,5 mm
4The heat pump and electrical backup are allowed to operate depending on the time program.
4The heat pump will start to heat at the temperature of 62 °C (parameter P07) when the photovoltaic signal is actif.
4If the photovoltaic signal is actif when the contact is open, set the parameter P04 on 3.
4If the photovoltaic signal is actif when the contact is closed, set the parameter P04 on 4.
2
40
03/02/2014 - 300026515-001-03
3
3
4
PCU-195
2
θ
°C
1
2
1
2
X8
1
5 4
4
1
2
6
1
2
3
1 2
2
1
2
3
X-HC
1
2
1
X7
2
θ
°C
2
2
1
1
1
2
X3
1
X1
1
2
θ
°C
2
1
2
X4
1
θ
°C
2
1
2
X2
1
3
X5
5
6
2
θ
°C
1
2
1
1
2
4
P
COM
NC NO
L
SPL1
N
1
2
3
4
1
X-B1
1
2
R5R4R3R1R2
S1 S2 S3 TA
S4 S5
P
TS
X6
1
2
2 4
R6
2
5
1 23
KLIXON
HP
ALIMENTATION 230 V
SPC003402-B
TWH 200E TWH 300E TWH 300EH 4. Installation
4.10 Electrical principle diagram
03/02/2014 - 300026515-001-03
Control panel
Fan
Solenoid valve for defrosting
Compressor
Condenser
Electric heating resistance
41
A Z E R T Y
C003409-A
4. Installation TWH 200E TWH 300E TWH 300EH
*
L
N
P
R1 - R6
S4
S5
SPL1
TA
TS
X1
X2-S3
X3-S2
X4-S1
X5
X6
X7
Earth
Live
Neutral
Pressure switch
Relay
Evaporator sensor
Room sensor
Splice
Impressed current anode
Safety thermostat
Connecting the impressed current anode
Bottom DHW temperature sensor
Middle DHW temperature sensor
Top DHW temperature sensor
Room sensor, Evaporator, Pressure switch
Control panel connection
Hydraulic back-up command terminal board
X8
X-B1
X-HC
Command terminal board
Electrical back-up command terminal board
Pricing information input (HP-HC). Allows authorisation of domestic hot water production depending on the setting of the HP/HC input
4.11 Filling the thermodynamic DHW tank
1. Open a hot water tap.
2. Open the cold water tap located on the safety unit. Ensure that the
drainage valve on the unit is closed.
3. When the water overflows through the hot water tap, the appliance
is full. Close the hot water tap.
42
03/02/2014 - 300026515-001-03
C003197-B
MENUMODE
C003186-H
1 2 3 4 5 6 7
1
4
3
4
1
2
MENUMODE
TWH 200E TWH 300E TWH 300EH 5. Commissioning
5 Commissioning
5.1 Control panel
5.1.1. Description of the keys
( - )
MODE
MENU
Browse keys
Operating mode selection key
Key to access the various menus
5.1.2. Description of the display
!
J
!
K
88[8 8
Quantity of domestic hot water available (depending on the set point input)
Parameter settings
Alarm
Comfort period active or Clock programming
Display of the date (day:month) or the time (hour:minutes) depending on the selected menu
03/02/2014 - 300026515-001-03
1 2 3 4 5 6 7
888
L X ( ) B V M % W > C
Display of the day of the week (1=Monday, 2=Tuesday, etc.)
Digital display
Number of baths available (40 °C)
Quantity of water (litres)
Reduces set values
Increases set values
Confirm key
Reset the control system after a breakdown
Automatic mode or Comfort mode
Eco mode
Boost mode
Holiday mode
43
C003487-B
C003484-B
C003485-B
C003486-A
C003493-A
1
4
3
4
1
2
5. Commissioning
TWH 200E TWH 300E TWH 300EH
Display Domestic hot water
production
Heat pump The 2 segments of the tank flash simultaneously when domestic hot water production
Electrical back-up The right-hand segment of the tank flashes when domestic hot water production is
Hydraulic additional heating The left-hand segment of the tank flashes when domestic hot water production is
Heat pump + Electrical back­up + Hydraulic additional heating
M + W
% + W
> C
Boost function active via the HP/HC inlet
Boost function active via the HP/HC inlet
Boost function active via the HP/HC inlet
+ W
DHW production mode indicator
n
The main display indicates the domestic hot water production mode.
Description
is handled by the heat pump
handled by electrical back-up
handled by hydraulic back-up (Version EH)
The 2 segments of the tank flash alternately when domestic hot water production is handled by the heat pump, by electrical back-up and by hydraulic backup (EH version)
Indicator of the water volume available
n
When producing domestic hot water, the display indicates the number of baths available and the level to which the tank is filled (quantity of hot water available).
4 The number of baths is calcuated based on a domestic hot water
temperature of 40°C.
4 The level to which the tank is filled is calculated according to the
set point temperature.
4 Set the 2 parameters, P18 and P19, according to the
appliance model. ¼See chapter: "Modifying the installer parameters", page
49
44
03/02/2014 - 300026515-001-03
C003203-D
1x
3
1
4
3
4
1
2
MENUMODE
C003204-B
1x 2x 3x
. . .
1
4
3
4
1
2
MENUMODE
TWH 200E TWH 300E TWH 300EH
5. Commissioning
5.1.3. Browsing in the menus
1. Press the MENU key. The SE nS 1 menu is displayed
(Temperature measurement).
2. Use the ( and ) keys to scroll through the menus (See table
below).
3. To access the selected menu, press the MODE key (B).
4. To go back to the previous display, press the key MENU.
5. To go back ty the main display, press once key MENU.
Accessing the menu
1x MENU SE nS
1x )
2x )
3x )
4x )
5x )
6x )
Menu Description See chapter
1
CL OC 2
Pr oG 3
Co un 4
PA rA 5
Er bL 6
Co dE 7
Measurements menu
Setting the time and the date
Modify an hourly programme
Meters
Setting parameters
Failure history
Installer parameters
¼ "Reading out measured values", page 47
¼Refer to the user instructions
¼Refer to the user instructions
¼ "Counters", page 47
¼ "Reading out measured values", page 47
¼ "Message and error history", page 62
¼ "Modifying the installer parameters", page 49
5.2 Check points before commissioning
4 Check that the thermodynamic DHW tank is full of water.
4 Check the seals.
4 Check that the safety devices are operating correctly.
4 Check the operating mode.
03/02/2014 - 300026515-001-03
45
C003493-A
1
4
3
4
1
2
5. Commissioning
5.3 Putting the appliance into operation
5.3.1. Commissioning
CAUTION
Initial commissioning must be done by a qualified professional.
Carry out the commissioning operations in the following order:
1. Connect to the mains.
2. Check that no error codes or messages are shown on the display.
The domestic hot water set point temperature is set to 55°C in comfort mode.
3. Select the Boost operating mode.
See chapter: "Choosing the operating mode", page 46
¼
4. The compressor starts up after 120 seconds if DHW production is
required.
TWH 200E TWH 300E TWH 300EH
5.4 Checks and adjustments after commissioning
4 Check the leak tightness of the connections.
4 Check the temperature of the 3 DHW temperature sensors to
ensure that the appliance operates correctly. If the readout values are incorrect, check the positioning of the sensors in the sensor tube.
4 A few days after start up of the appliance, a visual inspection must
be made to check for any leaks in the water system or any blockages in the condensates runoff.
5.5 Choosing the operating mode
The operating mode is shown on the main display.
1. To change the operating mode, press the MODE key several times
until the symbol corresponding to the desired operating mode appears on the display.
46
03/02/2014 - 300026515-001-03
C003206-D
1x 2x 3x
. . .
1
4
3
4
1
2
MENUMODE
TWH 200E TWH 300E TWH 300EH
5. Commissioning
Display Operating
Description
mode
M
Automatic or Comfort
Comfort programme activated
Domestic hot water production is handled by the heat pump and by electrical back-up if necessary (+ Hydraulic back-up for EH version). If domestic hot water production is not satisfied by the compressor after a modifiable time delay (factory setting: 5 hours - Parameter P23), the back-ups start up.
%
Eco Reduced programme activated.
Domestic hot water production is handled by the heat pump alone. After the compressor stops, the displayed quantity of domestic hot water available may not be
complete (!).
W
Boost
Forced operating activated
Domestic hot water production is handled simultaneously by the heat pump and the electrical back­up for a modifiable period (factory setting: 6 hours).
> days
Vacation
Holiday period
Shutting down domestic hot water production. The domestic hot water temperature is kept at 10°C.
5.6 Reading out measured values
5.6.1. Measurements menu
1. Press once the MENU key. The SE nS 1 menu is displayed.
2. Press the MODEB key to go to the Measurements menu. The SE
01 menu is displayed.
3. Use the ( and ) keys to switch from one measurement to
another.
Parameters
SE 01 SE 02 SE 03 SE 04 SE 05 SE 06
St Su
SP 1 SP 2
5.6.2. Counters
Displaying the counters
n
Description Unit
Top DHW temperature sensor °C
Middle DHW temperature sensor °C
Bottom DHW temperature sensor °C
Room sensor °C
Evaporator temperature sensor °C
Electricity tariff:
4 HP1: Peak hours
4 HC0: Off-peak hours
Operating status / sub-status of the control system sequence
Back-up setpoint °C
Compressor setpoint °C
03/02/2014 - 300026515-001-03
1. Press once the MENU key. The SE nS 1 menu is displayed.
47
C004186-A
1
4
3
4
1
2
MENUMODE
C003210-C
1
1
4
3
4
1
2
MENUMODE
C004186-A
1
4
3
4
1
2
MENUMODE
C003210-C
1
1
4
3
4
1
2
MENUMODE
5. Commissioning
TWH 200E TWH 300E TWH 300EH
2. Press the ) key 3 times. The Co un 4 menu is displayed.
3. Press the MODE B key to go to the Counters menu. The number
of the counter is shown to the right of the display.
4. Use the ( and ) keys to switch from one counter to another (See
table below).
5. To exit this menu, press the MODE B key.
6. To go back to the main display, press the MENU button.
Meter
Description Unit
1 Total electric energy input for DHW production kWh
2 Electric energy input by the compressor in the last 24 hours
kWh
The counter is reset at 00:00 hours every day
3 Electric energy input by the electrical back-up in the last 24 hours
kWh
The counter is reset at 00:00 hours every day
4 Number of hours operation of the hydraulic backup h
5 Number of hours powered up h
6 Instantaneous output W
Resetting the counters
n
1. Press once the MENU key. The SE nS 1 menu is displayed.
2. Press the ) key 3 times. The Co un 4 menu is displayed.
3. Press the MODE B key to go to the Counters menu. The number
of the counter is shown to the right of the display.
48
4. Use the ( and ) keys to switch from one counter to another.
5. Press the
key to reset the meter displayed to zero.
V
03/02/2014 - 300026515-001-03
C004187-A
1
4
3
4
1
2
MENUMODE
C003203-D
1x
3
1
4
3
4
1
2
MENUMODE
C004192-A
1
4
3
4
1
2
MENUMODE
C003307-A
1
4
3
4
1
2
MENUMODE
TWH 200E TWH 300E TWH 300EH
6. Confirm using key MODE B.
7. To exit this menu, press the MODE B key.
8. To go back to the main display, press the MENU button.
5.7 Modifying the installer parameters
CAUTION
Modification of the factory settings may be detrimental to the functioning of the appliance.
5.7.1. Access to parameters
To prevent input errors, access to this menu requires the use of the access code 012.
5. Commissioning
1. Press once the MENU key. The SE nS 1 menu is displayed.
2. Press the ) key 6 times. The Co dE menu is displayed.
3. Enter the access code
012
4. Press the MODE B-key for the menu. The parameter
using the ( or ) keys.
P1
displays.
5. Scroll through the parameters using the ( or ) key.
6. To modify a parameter, press the MODE B key. The parameter
value flashes.
7. Set the desired value using the ( or ) key.
8. Confirm using key MODE B.
03/02/2014 - 300026515-001-03
49
5. Commissioning TWH 200E TWH 300E TWH 300EH
5.7.2. List of the parameters
Parameters Description Adjustment range Factory
setting
P 01 P 02 P 04
P 06
DHW setpoint in Auto mode 40 to 70 °C 55 °C
DHW set point in Eco mode 40 to 65 °C 55 °C
Choice of mode for the DHW Comfort period:
4 0 = Use the time programs.
4 1 = Use the electricity tariff information input. Tells you whether or not
domestic hot water production is permitted (HP1 = not permitted => Contact closed, HC0 = permitted => Contact open).
4 2 = Use the electricity tariff information input. Tells you whether or not
domestic hot water production is permitted (HP1 = not permitted => Contact open, HC0 = permitted => Contact closed).
4 3 = Use the time programs. The status of the electricity tariff information
input is used to activate the Boost function with compressor only (HP1 = Boost deactivated => Contact closed, HC0 = Boost activated => Contact open).
4 4 = The status of the electricity tariff information input is used to activate
the Boost function with compressor only (HP1 = Boost activated => Contact open, HC0 = Boost deactivated => Contact closed).
4 5 = The status of the electricity tariff information input is used to activate
the Boost function with compressor and back-up (HP1 = Boost deactivated => Contact closed, HC0 = Boost activated => Contact open).
4 6 = The status of the electricity tariff information input is used to activate
the Boost function with compressor and back-up (HP1 = Boost activated => Contact open, HC0 = Boost deactivated => Contact closed).
Automatic switch to summer time (last Sunday in March) and winter time (last Sunday in October):
0 - 6 0
0 - 1 1
P 07 P 17
P 18 P 19 P 20 P 21
P 22
P 23
P 24 P 25
4 0 = Function not active (for countries where the time change is done on
other dates or is not in use)
4 1 = Function active
DHW setpoint in Boost mode 40 to 70 °C 62 °C
Protection by impressed current anode
4 0 = Deactivation
4 1 = Activation
Water volume contained in the DHW tank (x 10 l) 6 - 255 27
Water volume for one bath (l) 10 - 255 120
Maximum duration of the Boost mode (h) 1 - 10 6
Measurement unit
4 0 = °C
4 1 = °F
Back-up type
4 0 = None
4 1 = Electrical back-up
4 2 = Hydraulic additional heating
Time delay for starting the electrical or hydraulic back-up in Automatic mode (Hours)
Compressor start-up time (seconds) 60 - 255 120
Management of the fans in domestic hot water production mode
0 - 1 1
0 - 1 0
0 - 2 1
0 - 10 5
0 - 2 0
50
4 0 = Automatic
4 1 = Average speed of fan rotation
4 2 = Maximum speed of fan rotation
03/02/2014 - 300026515-001-03
C003495-B
3
1
4
3
4
1
2
MENUMODE
TWH 200E TWH 300E TWH 300EH
5. Commissioning
Parameters Description Adjustment range Factory
setting
P 26
Antilegionella function. The tank is overheated every Saturday from 1 o’clock to
0 - 1 0
6 o’clock (65 °C).
4 0 = Off
4 1 = Activated outside holiday periods
4 2 = Always activated
P 27
Compressor cut-off hysteresis in relation to the set point for the bottom domestic
5 - 15 10
hot water temperature sensor (only in Auto or Boost mode)
P 28
Maximum DHW temperature (bottom sensor) for compressor cut-off (°C) (only
35 - 50 45
in Auto or Boost mode)
P 29 P 30 P 31
Minimum duration of compressor operation (minutes) 3 - 10 3
Anti-short-cycle period between 2 compressor start-ups (minutes) 5 - 10 5
Hydraulic additional heating
0 - 1 0
4 0 = contact R6 closed if there is an additional hydraulic heating request
4 1 = contact R6 opened if there is an additional hydraulic heating request
P 32
DHW setpoint used for the antilegionella function 55 to 70 °C 65 °C
5.7.3. Control system sequence
Control system sequence
Status Sub-status Operation
0 0 Appliance off
7 Compressor post-operation
1 1 Anti-short cycle activated
2 Wait for the start-up condition for domestic hot water production
3 Start-up of the fan and the defrosting valve
2 5 Compressor starts
6 Defrosting
3 1 Anti-short cycle activated
4 Additional heating starts
7 Compressor post-operation
4 5 Compressor starts
6 Defrosting
9 -- Blockage state
5.7.4. Return to the factory settings
1. Press the ( and ) keys simultaneously for 5 seconds. The
rSt menu is displayed.
03/02/2014 - 300026515-001-03
51
C004193-A
1
4
3
4
1
2
MENUMODE
5. Commissioning TWH 200E TWH 300E TWH 300EH
2. Press the MODE B key to carry out a TOTAL RESET of all
parameters.
52
03/02/2014 - 300026515-001-03
TWH 200E TWH 300E TWH 300EH 6. Switching off the appliance
6 Switching off the appliance
6.1 Installation shutdown
CAUTION
Try to avoid switching off the appliance in order to maintain protection against corrosion. The appliance’s frost protection continues to be activated.
6.2 Antifreeze protection
In the event of extended absence (holiday), programme the corresponding number of days. The temperature of the water in the tank is maintained at 10°C.
¼Refer to the user instructions.
03/02/2014 - 300026515-001-03
53
7. Checking and maintenance TWH 200E TWH 300E TWH 300EH
7 Checking and maintenance
7.1 General instructions
CAUTION
Installation and maintenance of the appliance must be done by a qualified professional in accordance with prevailing statutory texts and codes of practice.
CAUTION
Before working on the appliance, ensure that it is switched off and safe.
CAUTION
Check the discharge on the compressor condenser for single phase voltages.
CAUTION
Before working on the cooling circuit, switch off the appliance and wait a few minutes. Some equipment such as the compressor and the pipes can reach temperatures higher than 100°C and high pressures, which may cause serious burns.
When the appliance is switched off, the fan continues to run by inertia for around one minute.
Maintenance operations are important for the following reasons:
4 To guarantee optimum performance
4 To extend the life of the equipment
4 To provide an installation which offers the customer optimum
comfort over time.
CAUTION
At no time allow water to get into the control components. Before starting cleaning, disconnect the mains power plug or switch off the appliance.
54
03/02/2014 - 300026515-001-03
TWH 200E TWH 300E TWH 300EH
7.2 Maintenance operations to be performed
7.2.1. Refrigerant circuit
No maintenance is required on the refrigerant circuit in the thermodynamic water heater.
7.2.2. Hydraulic circuit
Check the watertightness of the water connections.
7.2.3. Aeraulics
Cleaning the evaporator
n
7. Checking and maintenance
DANGER
Risk of injury on the sharp-edged fins.
CAUTION
Do not distort or damage the fins.
4 Clean the evaporator at regular intervals using a soft-haired brush.
4 Carefully realign the fins using a suitable comb if they are bent.
Cleaning the fan
n
Check the cleanliness of the fan 1 time per year. Clogging by dust and other particles impairs the heat pump’s performance.
7.2.4. Impressed current anode
No maintenance operations are required on an impressed current anode.
The appliance’s control panel must be switched on to ensure operation of the impressed current anode.
03/02/2014 - 300026515-001-03
7.2.5. Checking the safety valve or unit
Operate the safety valve or unit at least 1 time per month to check that it is running correctly. This check provides forewarning of any occurrences of excess pressure that may damage the domestic hot water calorifier.
55
C003214-E
7. Checking and maintenance TWH 200E TWH 300E TWH 300EH
WARNING
Failure to comply with this maintenance rule may cause deterioration of the DHW tank and the cancellation of the guarantee.
7.2.6. Descaling
Use a new leak tight seal on the inspection trap.
In hard water regions, it is advisable to ask the fitter to descale the DHW tank exchanger once a year in order to maintain its level of performance.
1. Turn off the domestic cold water inlet.
2. Drain the calorifier.
3. Open a hot water tap.
4. Open the valve on the safety unit.
5. Remove the insulation from the inspection hatch.
6. Pull out the DHW sensor.
7. Remove the inspection trap (13 mm spanner).
8. Remove the 2 bulbs from the safety thermostat.
9. Remove the limescale deposited in the tank in the form of sludge
or strips. Keep the limescale on the wall of the tank: it provides effective protection against corrosion and enhances the insulation of the DHW tank.
10.Then replace all the parts in reverse order.
Each time it is opened, the lip gasket must be replaced to guarantee tightness. Place the positioning lug on the gasket toward the outside of the tank.
11.After each intervention, ensure that the installation is watertight.
The screws retaining the visit trap must be tightened to 6 N·m +1/-0. Use a torque wrench.
7.2.7. Cleaning the condensates discharge duct
Check the cleanliness of the condensates discharge pipe. An obstruction by dust may cause poor condensates flow or even a risk of excessive accumulation of water.
DANGER
Risk of the heat pump malfunctioning.
56
03/02/2014 - 300026515-001-03
85°
1
C003190-B
TWH 200E TWH 300E TWH 300EH 7. Checking and maintenance
7.3 Accessing the bottom inspection trap
Have a lip gasket and a retainer ring on hand for the inspection hatch.
1. Disconnect the mains supply.
2. Drain the calorifier.
3. Open a hot water tap.
4. Open the valve on the safety unit.
5. Set the appliance to repair position
6. Check the extent of scaling in the tank and on the exchanger.
Keep the limescale on the wall of the tank: it provides effective protection against corrosion and enhances the insulation of the DHW tank. Remove limescale deposits from the bottom of the tank. Remove limescale deposits from the exchanger to guarantee its performance.
7. Fit the unit together.
1
.
CAUTION
Each time it is opened, the lip gasket + retainer ring unit must be replaced to guarantee tightness. Place the positioning lug on the gasket toward the outside of the tank.
8. After reassembly, check the tightness of the lower flange.
The screws retaining the visit trap must be tightened to 6 N·m +1/-0. Use a torque wrench.
03/02/2014 - 300026515-001-03
57
7. Checking and maintenance TWH 200E TWH 300E TWH 300EH
7.4 Maintenance form
No. _____
Date _________
Checks made ______________________________
Remarks _____________________By_______________
Signature ____________
58
03/02/2014 - 300026515-001-03
TWH 200E TWH 300E TWH 300EH 8. Troubleshooting
8 Troubleshooting
8.1 Messages (Code type bxx or Exx)
8.1.1. Messages (type code bXX)
In the case of failure, the control panel displays a message and a corresponding code.
1. Make a note of the code displayed.
The code is important for the correct and rapid diagnosis of the type of failure and for any technical assistance that may be needed.
2. Disconnect and reconnect the mains cable.
The appliance will restart only when the malfunction has been corrected.
3. If the code is displayed again, correct the problem by following the
instructions in the table below:
Code no.
B00 B01
B02
B03
B04
B25
Description Checking / solution
Parameter error on the PCU PCB Reset the parameters
Pressure switch alarm Note: DHW production is handled by back­up if back-up enabled
Maximum DHW temperature exceeded Note: DHW production is not covered (by the compressor or the back-up)
The room temperature is higher than 35°C. The compressor is outside its operating range. Note: DHW production is handled by back­up if back-up enabled.
The room temperature is less than -5°C. Note: DHW production is handled by back­up if back-up enabled.
The bottom DHW temperature sensor is short circuited
4 Check the power supply to the compressor
4 Check the pressure switch connection
4 Check the connection on the top DHW sensor
4 Check that the back-up is not running permanently
4 Modify the parameters according to the instructions in the manual.
4 The compressor will handle DHW production once the room
temperature is less than 35°C.
4 Modify the parameters according to the instructions in the manual.
4 The compressor will handle DHW production once the room
temperature is higher than -5°C.
Bad connection
4 Check whether the sensor is connected
4 Check the link and the connectors
4 Check that the sensor has been correctly fitted
Sensor fault
4 Check the Ohmic value of the sensor
4 Replace the sensor if necessary
03/02/2014 - 300026515-001-03
59
8. Troubleshooting
Code no. Description Checking / solution
B26
B27
B28
The bottom DHW temperature sensor is open
The top DHW temperature sensor is short circuited
The top DHW temperature sensor is open
Bad connection
4 Check whether the sensor is connected
4 Check the link and the connectors
4 Check that the sensor has been correctly fitted
Sensor fault
4 Check the Ohmic value of the sensor
4 Replace the sensor if necessary
Bad connection
4 Check whether the sensor is connected
4 Check the link and the connectors
4 Check that the sensor has been correctly fitted
Sensor fault
4 Check the Ohmic value of the sensor
4 Replace the sensor if necessary
Bad connection
4 Check whether the sensor is connected
4 Check the link and the connectors
4 Check that the sensor has been correctly fitted
Sensor fault
TWH 200E TWH 300E TWH 300EH
B32
B33
B40
The impressed current anode is in open circuit.
The impressed current anode is short­circuited.
Measurement error on the domestic hot water temperature sensors.
Remarks:
4 This message is only displayed on initial
commissioning.
4 This message disappears after 10
minutes or when you press the B key.
4 Check the Ohmic value of the sensor
4 Replace the sensor if necessary 4 Check that the connection cable between the SCU PCB and the
anode is not severed
4 Check that the anode is not broken
4 Check that the DHW tank is correctly filled with water
Remarks:
4 Domestic hot water production has stopped but can nonetheless
be restarted using key V (For 72 hours)
4 Protection against corrosion is not ensured 4 Check that the connection cable between the PCU PCB and the
anode is not short-circuited
4 Check that the anode is not short-circuited
Remarks:
4 Domestic hot water production has stopped but can nonetheless
be restarted using key V (For 72 hours)
4 Protection against corrosion is not ensured
The 3 sensors do not measure the same value
4 Check the location of the sensors.
60
If the causes of the problem are still present after several attempts at automatic start-up, the appliance goes into lockdown mode (also called failure).
¼see chapter: "Messages (type code EXX)", page 61
03/02/2014 - 300026515-001-03
C003212-B
2"
1
4
3
4
1
2
MENUMODE
TWH 200E TWH 300E TWH 300EH 8. Troubleshooting
8.1.2. Messages (type code EXX)
1. The display shows :
- The symbol (!)
- The symbol
- The fault code (for example
2. After correcting the failure, press the
the error code continues to display, search for the cause in the error table and apply the solution.
Code no. Description Checking / solution
E00
E01
The parameter storage unit on the PCU electronic board is defective
The middle DHW temperature sensor is short circuited Note: DHW production is not covered
Replace the PCU PCB
Bad connection
4 Check whether the sensor is connected
4 Check the link and the connectors
4 Check that the sensor has been correctly fitted
Sensor fault
V
E02
).
key for 2 seconds. If
V
E02
E04
E05
The middle DHW temperature sensor is open Note: DHW production is not covered
The room temperature sensor is short circuited Note: DHW production is handled by back-up if back-up enabled
The room temperature sensor is open Note: DHW production is handled by back-up if back-up enabled
4 Check the Ohmic value of the sensor
4 Replace the sensor if necessary
Bad connection
4 Check whether the sensor is connected
4 Check the link and the connectors
4 Check that the sensor has been correctly fitted
Sensor fault
4 Check the Ohmic value of the sensor
4 Replace the sensor if necessary
Bad connection
4 Check whether the sensor is connected
4 Check the link and the connectors
4 Check that the sensor has been correctly fitted
Sensor fault
4 Check the Ohmic value of the sensor
4 Replace the sensor if necessary
Bad connection
4 Check whether the sensor is connected
4 Check the link and the connectors
4 Check that the sensor has been correctly fitted
Sensor fault
03/02/2014 - 300026515-001-03
4 Check the Ohmic value of the sensor
4 Replace the sensor if necessary
61
C003203-D
1x
3
1
4
3
4
1
2
MENUMODE
C004189-A
1
4
3
4
1
2
MENUMODE
8. Troubleshooting TWH 200E TWH 300E TWH 300EH
Code no. Description Checking / solution
E06
The evaporator temperature sensor is short circuited Note: DHW production is handled by back-up if back-up enabled
Bad connection
4 Check whether the sensor is connected
4 Check the link and the connectors
4 Check that the sensor has been correctly fitted
Sensor fault
4 Check the Ohmic value of the sensor
4 Replace the sensor if necessary
E07
The evaporator temperature sensor is open Note: DHW production is handled by back-up if back-up enabled
Bad connection
4 Check whether the sensor is connected
4 Check the link and the connectors
4 Check that the sensor has been correctly fitted
Sensor fault
4 Check the Ohmic value of the sensor
4 Replace the sensor if necessary
E08
Malfunction on the defrosting function Note: DHW production is handled by back-up if back-up enabled
4 Check activation of the defrosting solenoid valve
4 Check the position of the temperature sensor in the evaporator
4 Check that the fan is working correctly
4 Check that the condensates can flow freely
E09
E10
The low pressure pressure switch alarm sounds for more than 120 seconds Note: DHW production is handled by back-up if back-up enabled
The low pressure pressure switch alarm has been tripped more than 3 times during the last 24 hours Note: DHW production is handled by back-up if back-up enabled
4 Check the position of the temperature sensor in the evaporator
4 Check that the fan is working correctly
4 Check that the condensates can flow freely
4 Check the position of the temperature sensor in the evaporator
4 Check that the fan is working correctly
4 Check that the condensates can flow freely
4 Check the refrigerant load
8.2 Message and error history
62
The Er bL 6 menu is used to consult the last 16 messages and the last 16 errors displayed by the control panel.
1. Press once the MENU key. The SE nS 1 menu is displayed.
2. Press the ) key 5 times. The Er bL 6 menu is displayed.
3. Press the MODE B key to go to this menu.
Accessing the menu
1x
)
2x
)
3x
)
Menu Description
Err
bL
CLr
Error history
Blockage history
Reset error and blockage history
03/02/2014 - 300026515-001-03
C004190-A
1
4
3
4
1
2
MENUMODE
C004191-A
1
4
3
4
1
2
MENUMODE
TWH 200E TWH 300E TWH 300EH 8. Troubleshooting
4. The Er r menu is displayed with the number of errors that have
occurred.
5. To go back to the previous display, press the key MENU.
8.2.1. Err error display
1. When the Err menu is dislayed, press the MODE B key.
2. The code
EXX
are its time and date alternately.
3. - Press the MODE (B) key to access details of the error.
- Use the ( and ) keys to browse the error list.
- Use the MENU key to go back to the error list.
for the last error that occurred is displayed as
8.2.2. bL blockage display
1. When the bL menu is dislayed, press the MODE B key.
2. The code
bXX
for the last blockage that occurred is displayed
as are its time and date alternately.
3. - Press the MODE (B) key to display the details of the error.
- Use the ( and ) keys to scroll through the blockage list.
- Use the MENU key to go back to the blockage list.
8.2.3. Reset error and blockage history
1. When the Er bL menu is dislayed, press the MODE B key.
2. The error and blockage history are reset.
03/02/2014 - 300026515-001-03
63
C003489-B
8
29
21
16
24
22
19
13
1
18
5
15
28
14
6
2
3
12
17
11
4
7
10
4
20
23
25
26
27
9. Spare parts TWH 200E TWH 300E TWH 300EH
9 Spare parts
9.1 General
When it is observed subsequent to inspection or maintenance work that a component in the appliance needs to be replaced, use only original spare parts or recommended spare parts and equipment.
To order a spare part, give the reference number shown on the list.
9.2 Spare parts
Spare parts list reference: 300026515-002-01
9.2.1. Heat pump
64
03/02/2014 - 300026515-001-03
TWH 200E TWH 300E TWH 300EH 9. Spare parts
Markers Reference Description
1 SFH41000 Base frame
2 SFH22038 Air sensor
3 SFH22039 Evaporator sensor
4 SFH32178 Electrical harness
5 SFH24053 Coil
6 SFH40173 Sensor bracket
7 SFH31034 Command module
8 SFH20050 Compressor
10 SFH33170 Earthing connector
11 SFH37008 Motorised fan
12 SFH31306 Control system board
13 SFH23108 Expansion valve
14 SFH24052 Solenoid valve
15 SFH22234 LP pressure switch
16 SFH21038 Filter drier
17 SFH40172 Fan bracket
18 SFH41001 Control panel bracket
19 SFH41002 Air duct
20 SFH51172 Foam gasket
21 SFH40171 Compressor bracket
22 SFH25298 Heat exchanger
23 SFH12102 Valve plug
24 SFH22056 Tank sensor 0.5 m + Connector
25 SFH22057 Tank sensor 1.5 m + Connector
26 SFH22058 Tank sensor 2 m + Connector
27 200020513 Screw bag Heat pump
28 7611992 Wired high pressure (HP) pressure switch
29 7610320 Compressor insulation
03/02/2014 - 300026515-001-03
65
C003477-G
17
20
28
29
21
20
15
23
22
25
24
9
10b
12
10a
12
1
4
3
2
5
6
30
31
18
8
26
7
31
32
19
11
9. Spare parts TWH 200E TWH 300E TWH 300EH
9.2.2. DHW tank
66
Markers Reference Description
1 300019082 Heating element
2 97862390 Housing for heating element
3 97866635 Fastening plate
4 95363327 Thermostat
5 200011080 Connection cable - Black (x3)
6 300019070 Connection bridge
7 89534902 Earth wire
8 300025717 Power supply cable
9 95013133 Lip gasket diameter 82 mm
10a 200021118 Connection G 3/4" ACI complet
As of serial number 193
10b 200019797 Connection G1" 1/2 ACI complet
From serial number 101 to serial number 192
03/02/2014 - 300026515-001-03
TWH 200E TWH 300E TWH 300EH 9. Spare parts
Markers Reference Description
11 300014305 O-ring 14x4 EPDM
12 200011550 Titanium anode
15 300025716 ACI anode cable
17 95365613 Contact spring for pocket
18 89525501 Complete top mounting
19 89705511 Gasket 7 mm + Retainer ring 5 mm
20 300025193 Nozzle
21 300025194 Grill
22 300025192 Top cover
23 200020278 Back cover + Spacers + Screw
24 200020279 Front cover + Spacers + Screw
25 300025216 Panel strap
26 300025930 Front cover 200E
26 300025931 Front cover 300E / 300EH
28 94994712 Pipe PVC diameter 16x12
29 S101017 Pipe clamp 135
30 97860646 Adjustable foot M10x35 (3x)
31 300025648 Dielectric connection 3/4"
32 200020217 Screws for casing
03/02/2014 - 300026515-001-03
67
9. Spare parts TWH 200E TWH 300E TWH 300EH
68
03/02/2014 - 300026515-001-03
AD001-AI
DUEDI S.r.l.
DE DIETRICH SERVICE
BDR Thermea (Czech republic) s.r.o
www.duediclima.it
www.dedietrich.cz
Distributore Ufficiale Esclusivo
De Dietrich-Thermique Italia
www.dedietrich-heiztechnik.com
Freecall 0800 / 201608
Jeseniova 2770/56
130 00 Praha 3
+49 (0)25 72 / 9161-0
+49 (0)25 72 / 9161-102
info@remeha.de
Via Passatore, 12 - 12010 San Defendente di Cervasca CUNEO
+39 0171 857170 +39 0171 687875 info@duediclima.it
+420 271 001 627 info@dedietrich.cz
IT
DE DIETRICH THERMIQUE S.A.S
DE DIETRICH THERMIQUE Iberia S.L.U.
www.dedietrich-calefaccion.es
C/Salvador Espriu, 11
08908 L’HOSPITALET de LLOBREGAT
+34 935 475 850 info@dedietrich-calefaccion.es
ES
129164, Россия, г. Москва
Зубарев переулок, д. 15/1
Бизнес-центр «Чайка Плаза»,
офис 309
+7 (495) 221-31-51
CZ
300026515- 001-03
DEDIETRICH THERMIQUE 57,ruedelaGareF-67580MERTZWILLER-BP 30
© Copyright All technical and technological information contained in these technical instructions, as well as any drawings and technical descriptions supplied, remain our property and shall not be multiplied without our prior consent in writing.
03/02/2014
Loading...