3. Set the boiler to full load:
Continue
pressing for around 3 seconds on the B key. The status
signal for the B button is orange and always flashes green
briefly; The low speed mode is parameterised.
Press the B button again 2 times. The status signal for the
B
button is orange and always goes off briefly 2 times; Full load is
set.
The full load status can only be reached via the part load
status.
4. Measure the percentage of O2 or CO2 in the flue gases (Front
panel removed
).
The boiler is supplied with two types of gas blocks. See
drawing for the position of control screw A for a full load.
5. If this rate does not match the required value, correct the gas/air
ratio using the adjustment screw A on the gas valve unit:
If the level is too high, turn the screw A clockwise to reduce the
gas flow rate.
If the level is too low, turn the screw A anti-clockwise to increase
the gas flow rate.
O2/ CO2 control and setting values at full load for
G20 (Gas H)
Boiler type Setting value Checking value
O2 (%) CO2 (%) O2 (%) CO2 (%)
EMC-M 24 4,3 ± 0,3 9,3 ± 0,1 4,3 ± 0,5 9,3 ± 0,3
EMC-M 24/28 MI 4,3 ± 0,3 9,3 ± 0,1 4,3 ± 0,5 9,3 ± 0,3
EMC-M 30/35 MI 4,3 ± 0,3 9,3 ± 0,1 4,3 ± 0,5 9,3 ± 0,3
EMC-M 34/39 MI 4,3 ± 0,3 9,3 ± 0,1 4,3 ± 0,5 9,3 ± 0,3
O2/ CO2 control and setting values at full load for
G25 (Gas L)
Boiler type Setting value Checking value
O2 (%) CO2 (%) O2 (%) CO2 (%)
EMC-M 24 4,0 ± 0,3 9,3 ± 0,1 4,0 ± 0,5 9,3 ± 0,3
EMC-M 24/28 MI 4,0 ± 0,3 9,3 ± 0,1 4,0 ± 0,5 9,3 ± 0,3
EMC-M 30/35 MI 4,0 ± 0,3 9,3 ± 0,1 4,0 ± 0,5 9,3 ± 0,3
EMC-M 34/39 MI 4,0 ± 0,3 9,3 ± 0,1 4,0 ± 0,5 9,3 ± 0,3
O2/ CO2 control and setting values at full load for
G31 (Propane)
Boiler type Setting value Checking value
O2 (%) CO2 (%) O2 (%) CO2 (%)
EMC-M 24 5,2 ± 0,3 10,3 ± 0,1 5,2 ± 0,5 10,3 ± 0,3
EMC-M 24/28 MI 5,2 ± 0,3 10,3 ± 0,1 5,2 ± 0,5 10,3 ± 0,3
EMC-M 30/35 MI 5,2 ± 0,3 10,3 ± 0,1 5,2 ± 0,5 10,3 ± 0,3
EMC-M 34/39 MI 5,2 ± 0,3 10,3 ± 0,1 5,2 ± 0,5 10,3 ± 0,3