DE DIETRICH C 310 ECO, C 610 ECO User Manual

Gas fired condensing boiler
C 310 ECO - C 610 ECO
EN
User Guide
300015183-001-A

Contents

1.1 Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.2 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2 Safety instructions and recommendations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.1 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.2 Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
4 Use of the appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
4.1 Control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
4.2 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
4.3 Changing the settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
4.4 Stopping the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
4.5 Commissioning the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
5 Checking and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
6 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
6.1 Identification plate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
6.2 Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
7 Technical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
8 Energy savings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
2
C 310 ECO - C 610 ECO 02/10/07 - 300015183-001-A

1Introduction

1.1 Symbols used

Caution danger
Risk of injury and damage to equipment. Attention must be paid to the warnings on safety of persons and equipment.
Specific information
Information must be kept in mind to maintain comfort.

1.2 Introduction

Congratulations on your choice of a high quality product. We strongly advise you to read the following instructions in order to guarantee the optimal operation of your appliance. We are sure that it will be entirely to your satisfaction and will meet with all of your expectations.
` Keep these instructions in a safe place close to the appliance.
` For a proper operating of the boiler, follow carefully the
instructions.
` The manufacturer is not liable for any improper use of the
appliance or failure to maintain or install the unit correctly (the user shall take care to ensure that the system is installed by a qualified fitter).
` In the interest of customers, De Dietrich Thermique SAS are
continuously endeavouring to make improvements in product quality. All the specifications stated in this document are therefore subject to change without notice.
Reference
Z
Refer to another manual or other pages in this instruction manual.
DHW: Domestic hot water
SMI: Integrated mixer system
` Get your fitter to explain your installation to you.
02/10/07 - 300015183-001-A C 310 ECO - C 610 ECO
3

2 Safety instructions and recommendations

2.1 Safety instructions

Fire hazard

Do not stock products of an inflammable nature close to
the appliance.
If you smell gas, do not use a naked flame, do not smoke,
do not operate electrical contacts or switches (doorbell, lights, motor, lift, etc.).
1. Cut the gas supply
2. Open the windows
3. Extinguish all flames
4. Evacuate the premises
5. Contact a qualified professional
6. Inform the gas supplier

Risk of intoxication

Do not obstruct the air inlets in the room (even partially).
In the event of flue gas emanation
1. Switch the appliance off
2. Open the windows
3. Evacuate the premises
4. Contact a qualified professional

Risk of being burnt

Avoid direct contact with the flame viewport.
Depending on the settings of the appliance:
- The temperature of the flue gas conduits may exceed 60°C
- The temperature of the radiators may reach 95°C
- The temperature of the domestic hot water may reach 65°C

Risk of damage

Do not stock chloride or fluoride compounds close to the
appliance.
Install the appliance in frost-free premises.
Do not neglect to service the appliance: Contact a qualified professional or take out a maintenance contract for the annual servicing of the appliance.

2.2 Recommendations

Only qualified professionals are authorised to work on the
appliance and the instalation.
Before any work, switch off the mains supply to the
appliance.
Check regularly that the installation contains water and is pressurised.
Keep the appliance accessible at all times.
Avoid draining the installation.
The appliance should be on Summer or Antrifreeze mode rather than switched off to guarantee the following functions:
- Antifreeze protection
- Protection against corrosion on domestic hot water tanks fitted with a titanium anode.
4
C 310 ECO - C 610 ECO 02/10/07 - 300015183-001-A

3 Description

The front of the boiler (with the inspection hatch for the heat exchanger) is the side from which it is serviced.
1. Pressure gauge

2. Sensor tube for outlet temperature sensor

3. Flow connection

4. Connection for second return (optional)

5. Return connection

6. Filling and emptying tap

7. Condensates collector

8. Combusted gas temperature sensor

9. Condensates discharge

10. Measurement point O

11. Wheel

12. Setting bolt

13. Condensates evacuation pipe

14. Flue gas discharge duct

15. Inspection hatch

16. Reduction sleeve Ø250/Ø200 (Option)

17. Heat exchanger

18. Output sensor

19. Air intake

22. Gas connection

2
/CO
2

24. Ignition/ionisation electrode

25. Return sensor

26. Heating body sensor

27. Base frame

28. Pivoting castor

29. Fan

30. Venturi

31. Multivalve gas unit

32. Non-return valve

33. Differential air pressure switch

34. Gas filter

35. Air chamber

36. Control panel

37. Adjustment keys

38. Display screen

39. General ON
40. Button

41. Combusted gas flue

42. Combusted gas valve

43. Combusted gas discharge connection with an integrated
condensates collection device
/ OFF 7 switch
8

23. Flame inspection window

02/10/07 - 300015183-001-A C 310 ECO - C 610 ECO
5

4 Use of the appliance

8

4.1 Control panel

1. General ON 8 / OFF 7 switch
The control panel should always be switched on to take advantage of the heating pump anti-sticking function. It is preferable to use the "summer" mode for the period during which the heating is to be cut off. Furthermore, if an interactive remote control (CDI 2) is connected and the 1 switch is in the off on the CDI 2.
position, there will be no display
7

2. Access hatch for the settings and programme keys

4.2 Display

1
2 1
1 Text and numerical display
2 Graphic display bar for the programme in circuit A, B or C
Light area: Reduced temperature heating period or tank load
3
disabled
Dark area: Comfort temperature heating period or tank load
4
enabled
5 Flashing cursor showing the current time
Number display (current time, adjusted values, parameters,
6
etc.)
Active programme display, P1, P2, P3, P4
7
or E : Summer mode activated
The arrows flash when setting values can be modified using
8
the + and - keys
SUNDAY
3 4 5 6 7
bar
024681012141618202224
SUNDAY
bar
A
BC
91011
A
BC
C000142_10
91011
-04

3. On light / Alarm

- The red resetting button lights up when the burner is in the safety condition
- The flashing red light signals a sensor error

4. Reset button

5. Timed circuit breaker (4 A)

A second protective function can be found on the safety control card.
9 Circuit operation symbols
Opening the 3-way valve
>
Closing the 3-way valve
8
=
Displayed circuit pump on
:
A B C Name of the circuit displayed
10 Symbol displayed above the active operating mode
Symbols indicating that the following inputs/outputs are
11
active
D Burner on DHW load pump on # Summer mode T Not available
6
C 310 ECO - C 610 ECO 02/10/07 - 300015183-001-A

4.3 Changing the settings

4.3.1 Keys accessible when the flap is closed

0 2 4 6 8 1012141618202224
SUNDAY
Temperature setting keys
2% 2$ 2
/
Comfort temperature
Reduced temperature
Domestic hot water temperature
Is used to adjust the selected temperature
A
-04
C000142_02
Operating mode selection keys
AUTO Heating according to the time programme
Forced Comfort mode:
%
$
- until midnight if  flashes
- all the time if
Forced Low mode:
- until midnight if
- all the time if
is steady
flashes
is steady

4.3.2 Keys accessible when the flap is open

024681012141618202224
SUNDAY
Manual "Summer" shutdown key
#
STANDARD
K
Key for access to setting and measurements
J I
The heating is switched off and DHW production is ensured. The symbols # and are displayed{E}.
"Standard" programme key Reset of all time programmes.
Fitter settings access key
Page scrolling
Line scrolling
. 
A
A
Programming keys
%O
Antifreeze mode
Tank load enabled mode
STANDARD
C000142_03
$P
S
A.B.C Circuit display selection key
PROG
-04
Enter (per 1/2 hour) the comfort temperature period or tank load enabled (dark area)
Enter (per 1/2 hour) the reduced temperature period or tank load disabled (light area)
Return key
Active heating programme selection key (P1, P2, P3 or P4)
H
02/10/07 - 300015183-001-A C 310 ECO - C 610 ECO
Back to the title or the previous line
7

4.4 Stopping the boiler

1. Deactivate the electricity supply to the boiler. In this way, any
intergrated regulator is switched off.

2. Close the gas valve.

A boiler which is switched off is not protected against
frost.

4.4.1 Precautions to take if there is a danger of frost

Heating circuit:
Use a correctly dosed antifreeze to prevent the heating water freezing. If this cannot be done, drain the system completely. In all cases, consult the fitter.
Domestic hot water circuit:
Drain the domestic water tank and pipes.

4.4.2 Precautions to take in the event of prolonged shutdown (one year or more)

- Close the gas valve
- The boiler and the chimney must be swept carefully.
- Close the door of the boiler to prevent the internal circulation of air.

4.5 Commissioning the boiler

4.5.1 Commissioning
Before filling it with water for the first time, rinse the installation and eliminate solder pearls, metal shavings, grease, and sludge from the former installation.
Jobs to be done before commissioning for the first time:
1. Ensure that the boiler is switched off
2. Remove the casings on the inspection side
3. Open the main gas valve
4. Check the electrical connections, particularly the earth
5. Fill the boiler and the installation with water (minimum pressure
1.0 bar)
6. Bleed the heating installation
7. Fill the siphon with water
8. Check the connection of the combusted gas evacuation and the
air inlet
9. Empty the gas inlet
10. Open the gas valve on the gas pipe to the boiler
11. Check the admission pressure of the gas PI
12. Check whether the gas connection is leak proof
13. Activate the electricity supply to the boiler
14. Activate the boiler ON switch
15. Operate the circulation pump and check the assembly position
and the rotation direction
16. Set the boiler regulation according to the heating request
17. The boiler starts to operate You can monitor operation in the menu #TEST INPUTS, parameter
SEQ:
a. Check the setting of the gas/air ratio and, if necessary, correct it.
The check is carried out at high and low speed, while setting takes place only on the gas multiblock. For checking and setting, you will need an electronic CO gas manometer.Be sure correctly to close the opening around the sensor when making the measurement. Connect the gas manometer between the measuring point PG under the gas multiblock and the measurement point PL on the venturi.
b. Run the boiler at high speed (forced "high speed" mode) by
pressing keys TEST EMISSION appears on the display with
P%
and
meter on the basis of O2)) and a
2
simultaneously for 2 seconds.
P$
.
c. After reaching minimum output, measure the gas value
measurement point PG under the gas block and the measurement point PL on the venturi and compare the results with the values in the table below. Divergent values must be corrected using the setting screw on the gas multiblock.
d. Then measure the CO
in the table. If the values exceed the limits shown, correct them according to the drawing below. Check the flame via the flame inspection window. It must not go out.
e. Run the boiler at low speed (forced "low speed" mode) by
pressing keys then on -. TEST EMISSION appears on the display with
f. After reaching minimum output, measure the gas value
measurement point PG under the gas block and the measurement point PL on the venturi and compare the results with the values in the table below. Divergent values must be corrected using the setting screw on the gas multiblock.
g. Then measure the CO
in the table. If the values exceed the limits shown, correct them according to the drawing below. Check the flame via the flame inspection window. It must not go out.
Repeat the steps as of step e until the measurements match the values in the table.
If you do not manage to correct the differences, contact our after sales service.
h. Remove the measuring device and close the measurement
points.
18. Check the gas seal control and the minimum gas pressure pressure switch (if need be)
percentage and compare it with the value
2
and
P%
P$
percentage and compare it with the value
2
P at the
simultaneously for 2 seconds
.
P at the
8
C 310 ECO - C 610 ECO 02/10/07 - 300015183-001-A
Table of CO2 - O2 values
Natural gas H/E
(G20)
High speed (100%) Low speed (±20%) High speed (100%) Low speed (±20%)
Indicative CO
Adjust to ±0,5% ±0,5% ±0,5% ±0,5%
Indicative O
Adjust to ±0,5% ±0,5% ±0,5% ±0,5%
value 9,0% 9,0% 9,0% 9,0%
2
Set to 9,0 ± 0,15% 9,0 ± 0,15% 9,0 ± 0,15% 9,0 ± 0,15%
value 4,8% 4,8% 4,8% 4,8%
2
Set to 4,8 ± 0,25% 4,8 ± 0,25% 4,8 ± 0,25% 4,8 ± 0,25%
P C310-280 (Pa) 1300 ± 100 60 ± 10 1150 ± 100 45 ± 10
P C310-350 1020 ± 100 42 ± 10 840 ± 100 32 ± 10P C310-430 900 ± 10 50 ± 10 750 ± 100 40 ± 10P C310-500 1350 ± 100 65 ± 10 1200 ± 100 50 ± 10P C310-570 1650 ± 100 85 ± 10 1500 ± 100 70 ± 10
Set the parameter to a value greater than or equal to 8, depending on the options connected.
Then set the gas seal control pressure switch to a trigger pressure equivalent to 50% of the admission pressure. Do not forget that the admission pressure measured does not affect the closing pressure (higher).
19. Press the Reset key to return the boiler to "user level"
20. Heat the installation to around 80°C and then stop the boiler
21. Bleed the heating installation and Checking the hydraulic
pressure
22. The boiler is now operational
23. Set the boiler regulation to the desired values
24. Switch the boiler on and fill in the label "Set to"
Each individual boiler is delivered with the following fixed
factory settings:
Natural gas L/LL
(G25)
Burner regulation - Modulating, depending on the
outlet temperature
Flow temperature - 90°C
02/10/07 - 300015183-001-A C 310 ECO - C 610 ECO
9

5 Checking and maintenance

The boiler is almost maintenance-free if it is set correctly.
Make the following checks at least 1 time a year:
- Checking the combustion in the boiler
- Checking the heat exchanger
- Checking condensates discharge.
- Checking the ignition electrode
- Checking for leaks (water, combusted gas, gas)
- Checking the hydraulic pressure
- Checking the air inlet circuit
Carry out the following maintenance at least *1 time a year:
- Cleaning the condensates collector
- Cleaning the siphon.
10
C 310 ECO - C 610 ECO 02/10/07 - 300015183-001-A

6 Troubleshooting

6.1 Identification plate

Before informing the fitter of a fault, make a note of the following information:

Type of gas used

Boiler type
Date of manufacture
Year (01 = 2001, 02 = 2002, ...)
Week
Serial no. of the appliance
This information can be found on the rating plate stuck to the
front plate of the boiler.
D
02/10/07 - 300015183-001-A C 310 ECO - C 610 ECO
11

6.2 Error messages

6.2.1 Faults

In the event of a fault, the display may show the following messages. Contact your fitter.
Message Probable causes Solution
24V SHORT-CIRC.
BURNER FAILURE
I-CURRENT FAIL
MCBA FAILURE 5
MCBA FAILURE 8
MCBA FAILURE 11
MCBA FAILURE 12
MCBA FAILURE 30
MCBA FAILURE 61
MCBA FAILURE 89
MCBA FAILURE 90
MCBA FAILURE XX
MCBA.COM.FAULT
ROOM S.A FAIL. ROOM S.B FAIL. ROOM S.C FAIL. EXCHAN.S.FAIL.
OUTL S.B FAIL. OUTL S.C FAIL.
OUTSI. S.FAIL.
SWIM.P. S.FAIL
FAN OFF FAIL
FAN ON FAIL
Short circuit 24V Check the wiring
Igniter fault
Ionisation error
Faulty gas valve Replace the gas valve
No gas or presence of air in the pipe Measure the gas supply pressure. Bleed the gas circuit
Ionisation fault during operation
External influences Check the wiring
Air pressostat open
Internal fault
Bridge open
T maxi exceeded Check the water flow
Air pressostat closed
Detection of gas leak V1
Detection of gas leak V2
Internal safety control box fault Reset the boiler. Replace the command and safety box.
Communication error between DIEMATIC and safety control box
Fault in the corresponding sensor
The fan is not working
The fan is working constantly
Check the ignition electrode (spacing of the electrodes), its connector and its connection cable. Replace if necessary.
Check the earth, Check the ionisation current, If necessary rectify the level of CO
2
Check the earth, Check the ionisation current, If necessary rectify the level of CO
2
Check:
- if the flue gas / combustive air duct is not blocked (i.e. siphon)
- if the air pressure switch and the connection are blocked
- Check that multi-wire connections are undamaged
- Presence of humidity in the control panel
- Eliminate electro-magnetic influences
- Check the bridge between terminals X4-3 and X4-12 on the MCBA
- Fuse F2 faulty in the control p.c.b
Check:
- If Faulty air pressostat
- If the wiring to the air pressure switch is in order
- If the thermal draught is too great
The gas sealing control (optional) has detected a leak.
Check whether there is a leak in the gas valve; otherwise replace the valve.
The gas sealing control (optional) has detected a leak.
Check whether there is a leak in the gas valve; otherwise replace the valve.
Check the link and the connections between DIEMATIC and safety control box
Check the link and the connectors. Replace the sensor if necessary. To erase the message, briefly cut off the power to the boiler using the On/Off switch. Advise the installer. However, you can operate in manual mode on the part of the installation concerned. See comments below.
- Faulty fan
- Check the fan wiring (corrosion of the connection)
- Command and safety box faulty
- Electrical connections broken
- Faulty fan control (replace the fan)
12
C 310 ECO - C 610 ECO 02/10/07 - 300015183-001-A
Message Probable causes Solution
Check the link and the connectors. Replace the sensor if
BOILER S.FAIL.
Faulty boiler sensor
necessary. Reset the boiler.
DHW S. FAILURE
Faulty domestic hot water sensor
Check the link and the connectors. Replace the sensor if necessary.
Check the link and the connectors. Replace the sensor if
SMOKE S. FAIL.
Faulty flue gas sensor
necessary. Reset the boiler
Check the link and the connectors. Replace the sensor if
BACK S.FAILURE
Faulty return sensor
necessary. Reset the boiler
The safety control box does not signal a gas valve. Check:
- The wiring of the gas valve
VALVE FAIL
Combined gas valve unit faulty
- A possible fault in the gas valve (faulty coil)
- Check the wiring. Check that the fuses are in good working condition.
Check the tightness of the gas circuit. Check the ignition
PARASIT FLAME
Detection of a parasite flame
electrode spacing.
Check that the surface of the burner does not have any fibre residues.
REARM CVI
Control error Reset the boiler
Check the wiring.
STB BOILER
Flow temperature > maximum
Bleed the boiler. Check the boiler pump. Check the hydraulic circuit on the installation.
Check the wiring.
STB EXCHANGE
Exchanger temperature too high
Bleed the boiler. Check the boiler pump. Check the hydraulic circuit on the installation.
STB SMOKE
Flue gas temperature too high Heat exchanger fouled
Check the wiring.
STB BALK
Return temperature too high
Bleed the boiler. Check the boiler pump. Check the hydraulic circuit on the installation.
02/10/07 - 300015183-001-A C 310 ECO - C 610 ECO
13

For other codes not listed here

- Cut the power supply to the boiler.
- Reset the boiler.
- Change the safety control box if the message persists.
ROOM S.A FAIL., ROOM S.B FAIL., ROOM S.C FAIL.
Automatic operating without room temperature influence.
OUTL S.B FAIL., OUTL S.C FAIL.
The circuit concerned goes from automatic to manual mode. The pump turns and the valve is no longer supplied. It may be manually operated if necessary.
DHW S. FAILURE
Heating of domestic hot water is no longer ensured. The load temperature of the dhw tank is the same as the boiler.
OUTSI. S.FAIL.
The boiler operates on BOILER MAX temperature. The regulation of the 3-way valve on circuits B or C (if present) is no longer handled. Nonetheless, the limitation of the maximum temperature is guaranteed and the valve can be operated manually if necessary.
Reheating the domestic hot water remains ensured.
The 10 latest faults appearing on the display are memorised in
the paragraph #HISTORY D..
14
C 310 ECO - C 610 ECO 02/10/07 - 300015183-001-A
6.2.2 (Temporary) blockage
Message Probable causes Solution
BL. AIR
BL.RET.HIGH.BOI
BL.SPEED
BLOCKING b26
BL.DT BOI BACK
BL.INT.MCBA
BL.SMOKE
BL.CS OPEN
BL.DT BOI.EXC.
BLOCKING bXX The control box is off.
Air supply insufficient during pre-ventilation.
A safety lockdown occurs after 5 starts.
Return temperature > Flow temperature for 10 minutes minimum, after boiler operating at lower stage
The maximum temperature increase speed tolerated in the exchanger has been exceeded. The boiler is blocked for 10 minutes.
After 5 successive attempts during a single heating request, the repeated cut-offs will be saved (the blockage code and the boiler situation at the time of the blockage).
he maximum difference tolerated between the outlet and return temperatures has been exceeded. The boiler is blocked for 150 seconds. After 20 successive attempts during a single heating request, the repeated cut-offs will be saved (the blockage code and the boiler situation at the time of the blockage). However, the boiler does not break down and continues to operate.
The setting of the parameters is incorrect or the memory is faulty.
Flue gas temperature > Flue gas temperature maximum. Trigger 150 seconds.
Blockage input on the CS bridge terminals, is open, or absence of a bridge.
If T between boiler temperature and exchanger temperature > 5°C
Trigger 10 Min. seconds. After 5 successive attempts during a single heating request, the repeated cut-offs will be saved (the blockage code and the boiler situation at the time of the blockage). The boiler will not be locked down.
- if the flue gas / combustive air duct is not blocked (i.e. siphon)
- if the air pressure switch and the connection are blocked
Connection or outlet and return sensor reversed
-Pump
- Water flow
- Hydraulic pressure
Check the bridge between terminals X4-8 and X4-3 in the box
-Pump
- Water flow
- Hydraulic pressure
- Configuration of the communication robot
- Boiler setting
- Fouling
- External safety and bridge
-Pump
- Water flow
Check the wiring Reset the boiler
The blockage mode is a normal operating mode and therefore
does not indicate a breakdown but a normal boiler operating status. A blockage code is likely to signal a technical problem in the installation or an incorrect setting.
02/10/07 - 300015183-001-A C 310 ECO - C 610 ECO
15

7 Technical characteristics

7.1 C 310 ECO

C 310-... ECO Unit 280 350 430 500 570
Introduction
Number of sections 56789
Regulating the output Modulating
Output (80/60°C) PN
Output (50/30°C) PN
Power input
Combustion gas and by-products
Gas supply pressure mbar 17 - 25
Gas flow rate Gas H/E (15°C - 1013 mbar)
Gas flow rate Gas L/LL(15°C - 1013 mbar)
Average nitrogen oxide emission (NOx) mg/kWh < 60
Maximum pressure at the flue gas nozzle
Combusted gas flow
Temperatures of the combusted gases at 80/60°C
Boiler types: B23, C33, C53, C63, C83
Heating
Safety temperature °C 110
Water setting range °C 20 - 90
Water pressure minimum bar 0,8
Water pressure maximum bar 6
Water content l 4960718293
Water resistance at
Water resistance at
Electricity characteristics
Power supply voltage V/Hz 230 / 50
Power consumption
Insulation class IP 21
Miscellaneous
Weight without water kg 360 410 460 510 560
Acoustic level at 1 meter dBA 60
T = 10°C mmCE 4520 4400 4800 4400 5000T = 20°C mmCE 1130 1100 1200 1100 1250
minimumkW51657992106
maximum kW 261 327 395 462 531
minimumkW56718498113
maximum kW 282 353 427 499 573
minimumkW54688295109
maximum kW 269 336 404 471 539
minimum m
maximum m
minimum m
maximum m
minimum Kg/h 91 114 138 160 183
maximum Kg/h 453 565 680 793 907
minimum °C 57
maximum °C 65
minimum W 12 12 12 12 12
maximum W 303 340 470 600 858
3
/h 5,7 7,2 8,7 10,1 11,5
3
/h 28,5 35,5 42,7 49,8 57,0
3
/h 6,6 8,4 10,1 11,7 13,4
3
/h 33,1 41,3 49,7 57,9 66,3
Pa 150 150 150 150 150
16
C 310 ECO - C 610 ECO 02/10/07 - 300015183-001-A

7.2 C 610 ECO

C 610-... ECO Unit 700 860 1000 1140
Introduction
Number of sections 2 x 6 2 x 7 2 x 8 2 x 9
Regulating the output Modulating
Output (80/60°C) PN
Output (50/30°C) PN
Nominal output (Hi)
Combustion gas and by-products
Gas category (see table in "General Description" chapter)
Gas supply pressure mbar 17 - 25
Gas flow rate Gas H/E (15°C - 1013 mbar)
Gas flow rate Gas L/LL(15°C - 1013 mbar)
Average nitrogen oxide emission (NOx) mg/kWh < 60
Maximum pressure at the flue gas nozzle Pa 130
Combusted gas flow
Temperatures of the combusted gases at 80/ 60°C
Boiler types: B23, C33, C53, C63, C83
Heating
Safety temperature °C 110
Water setting range °C 20 - 90
Water pressure minimum bar 0,8
Water pressure maximum bar 6
Water content l 120 142 164 186
Water resistance at
Water resistance at
T = 10°C mmCE 4400 4800 4400 5000T = 20°C mmCE 1100 1200 1100 1250
Electricity characteristics
Power supply voltage V/Hz 230 / 50
Power consumption
Insulation class IP 21
Miscellaneous
Weight without water kg 820 920 1020 1120
Acoustic level at 1 meter dBA 63
minimum kW 87 123 122 148
maximum kW 654 790 924 1062
minimum kW 94 131 130 156
maximum kW 706 854 998 1146
minimum kW 91 128 127 153
maximum kW 672 808 942 1078
minimum m
maximum m
minimum m
maximum m
3
/h 9.6 13.5 13.4 16.2
3
/h 70 85.4 99.6 114
3
/h 11.2 15.8 15.6 18.8
3
/h 82.6 99.4 115.8 132.6
minimum kg/h 153 215 214 257
maximum kg/h 1130 1360 1586 1814
minimum °C 57
maximum °C 65
minimum W 12
maximum W 694 980 1240 1684
02/10/07 - 300015183-001-A C 310 ECO - C 610 ECO
17

8 Energy savings

Here are a few tips for saving energy:
- Install reflector panels behind the radiators.
- Do not cover the radiators. Do not hang curtains in front of the radiators.
- Insulate pipes to prevent thermal losses and condensation.
- Do not obstruct aeration grates (even partially). They help to reduce humidity in the home. The more humid a home, the more heating it consumes.
- Turn heating off when airing a room (5 minutes a day is sufficient) Avoid deregulating the thermostat. Place the start/stop switch on Off.
- Do not shut down heating completely if you are absent. Lower the thermostat by 3-4°C.
- Use the sun's heat as much as possible.
- Take showers rather than baths. Use a water-saving shower head.
18
C 310 ECO - C 610 ECO 02/10/07 - 300015183-001-A
Warranty
You have just purchased one of our appliances and we thank you for the trust you have placed in our products.
Please note that your appliance will provide good service for a longer period of time if it is regularly checked and maintained.
Your fitter and our customer support network are at your disposal at all times.
Warranty terms
Starting from the purchase date shown on the original fitter's invoice, your appliance has a contractual guarantee against any manufacturing defect.
The length of the guarantee is mentioned in the price catalogue.
The manufacturer is not liable for any improper use of the appliance or failure to maintain or install the unit correctly (the user shall take care to ensure that the system is installed by a qualified fitter).
In particular, the manufacturer shall not be held responsible for any damage, loss or injury caused by installations which do not comply with the following:
- applicable local laws and regulations
- specific requirements relating to the installation, such as national and/or local regulations
- the manufacturer's instructions, in particular those relating to the regular maintenance of the unit
- the rules of the profession
France
The preceding dispositions are not exclusive of benefits for the purchaser of the legal guarantee as stated in Civil Code articles 1641 to 1648.
Belgium
The preceding dispositions about the contractual guarantee are not exclusive of profit if the need arises for the purchaser in Belgium of the applicable legal dispositions on hidden defects.
Switzerland
The application of the warranty is subject to the terms and conditions of sale, delivery and warranty of the company marketing our products.
Other countries
The above provisions do not restrict the benefit of the legal laws regarding hidden defects applicable in the buyer's country.
The warranty is limited to the exchange or repair of such parts as have been recognised to be faulty by our technical department and does not cover labour, travel and carriage costs.
The warranty shall not apply to the replacement or repair of parts damaged by normal wear and tear, negligence, repairs by unqualified parties, faulty or insufficient monitoring and maintenance, faulty power supply or the use of unsuitable fuel.
Sub-assemblies such as motors, pumps, electric valves etc. are guaranteed only if they have never been dismantled.
02/10/07 - 300015183-001-A C 310 ECO - C 610 ECO
19
FR
DE DIETRICH THERMIQUE S.A.S.
www.dedietrich-thermique.fr
Direction des Ventes France
57, rue de la Gare
F- 67580 MERTZWILLER
+33 (0)3 88 80 27 00 +33 (0)3 88 80 27 99
DE
BE
CH
AT
DE DIETRICH HEIZTECHNIK
www.dedietrich-heiztechnik.de
Rheiner Strasse 151
D- 48282 EMSDETTEN
+49 (0)25 72 / 23-5
+49 (0)25 72 / 23-102
info@dedietrich.de
VAN MARCKE
www.vanmarcke.be
Weggevoerdenlaan 5
B- 8500 KORTRIJK +32 (0)56/23 75 11
VESCAL S.A.
www.chauffer.ch / www.heizen.ch
Z.I de la Veyre, St-Légier
1800 VEVEY 1 +41 (0)21 943 02 22 +41 (0)21 943 02 33
DE DIETRICH HEIZTECHNIK
www.dedietrich-heiztechnik.de
Am Concorde Park1-B4/28
A-2320 SCHWECHAT / WIEN
+43 (0)1 / 706 40 60-0
+43 (0)1 / 706 40 60-99
office@dedietrich.at
LU
RU
CN
NEUBERG S.A.
www.dedietrich-heating.com
39 rue Jacques Stas
L- 2010 LUXEMBOURG
+352 (0)2 401 401
DE DIETRICH
www.dedietrich-otoplenie.ru
8 Gilyarovskogo Str. 7 R- 129090 MOSCOW
+7 495.974.16.03 +7 495.974.66.08 dedietrich@nnt.ru
DE DIETRICH
www.dedietrich-heating.com
Room 512, Tower A, Kelun Building 12A Guanghua Rd, Chaoyang District
C-100020 BEIJING +86 (0)106.581.4017 +86 (0)106.581.4018 +86 (0)106.581.7056 +86 (0)106.581.4019
contactBJ@dedietrich.com.cn
© Copyright
All technical and technological information contained in these technical instructions, as well as any drawings and technical descriptions supplied, remain our property and shall not be multiplied without our prior consent in writing..
Subject to alterations.
02 october 2007
DE DIETRICH THERMIQUE 57, rue de la Gare F- 67580 MERTZWILLER - BP 30
Loading...