3½ DIGIT, LED DISPLAY, 4-20mA LOOP-POWERED METERS
DMS-20PC-4/20
2
DATEL, Inc., Mansfi eld, MA 02048 (USA) • Tel: (508)339-3000, (800)233-2765 Fax: (508)339-6356 • E–mail: sales@datel.com • Internet: www .datel.com
Operating and Setup Instructions
Performance/Functional Specifi cations
Typical at TA = +25°C, unless otherwise noted.
➀ The DMS-20PC-4/20, using any of the DIP-switch settings described above, can
withstand overcurrents, including those resulting from accidental reverse-polarity
connections, up to ±40mA without sustaining any damage.
➁ Because DATEL's DMS-4/20 loop-powered meters employ active circuitry to con-
vert the loop current into a voltage, the meters' effective series impedance varies
in a manner that maintains the loop voltage drop constant over the full 4-to-20mA
current range. Listed impedance specifi cation applies at 20mA.
➂ When looking up DIP-switch settings in the Tables and the desired display readings
can be achieved with either of two different settings, using the higher setting # will
produce less sensitive offset (R3) and span (R7) adjustments. Please keep in mind
that the DMS-20PC standard meter (from which the DMS-20PC-4/20 is derived)
has an accuracy specifi cation of ±2 counts (max.). Thus, it may not always be
possible to obtain the exact desired display reading.
1. Set R7 (full scale span/gain adjust) and R3 (zero/offset adjust) fully
clockwise, roughly 22 turns, and place SW1-SW6 to OFF.
2. Select DIP switch setting #2.
3. Apply a precision 4mA input, with proper polarity, and adjust R3 until
the meter's display reads "000".
4. Apply a precision 20mA input and adjust R7 until the meter's display
reads "1000". Repeat steps 3 and 4 to make sure the adjustments do
not affect one another.
5. Select the appropriate decimal point by setting SW4, SW5 or SW6 to
ON (DP1, DP2 or DP3 respectively).
NOTE: If a display reading other than "000" to "1000" is desired,
refer to DIP–Switch Settings Table 1 for SW1–SW3 settings.
Current Loop Input Min. Typ. Max. Units
Full Scale Input Range ➀ +4 –– +20 mA
Input Impedance ➁ –– 250 –– Ω
Voltage Drop ➁ –– 4.5 5.0 Volts
Overcurrent Protection ➀ –– –– ±40 mA
Performance
Sampling Rate 2.5 readings per second
Accuracy (1 minute warm–up) ±0.05%FS ±1 Count
Temperature Drift (0 to +60°C) –– ±0.15 ±0.3 Cnts/°C
Display
Display Type and Size 3½ digit, red LED, 0.37"/9.4mm
Polarity Indication "–" for negative readings
Overrange Indication "–1_ __ " for negative inputs
"1 _ __ " for positive inputs
Physical/Environmental
Operating Temperature 0 –– +60 °C
Storage Temperature –40 –– +75 °C
Humidity (Non–condensing) 0 –– 95 %
Case Material Polycarbonate
Weight 0.6 ounces (17 grams)
Display Reading SW1 SW2 SW3
4mA 20mA
1. 000 to 1050-1999 Off Off Off
2. 000 to 650-1350 On Off Off
3. 000 to 450-800 Off On Off
4. 000 to 300-500 Off Off On
5. 000 to 200-300 On On On
Table 1. DMS-20PC-4/20S (Unipolar Model) DIP-Switch Settings
DMS-20PC-4/20S Unipolar reading, loop-powered LED meter
DMS-20PC-4/20B Bipolar reading, loop-powered LED meter
DMS-20PC-4/20P Positive reading, loop-powered LED meter
DMS-BZL3 Bezel assembly
DMS-BZL4 Bezel assembly with sealing gasket
DMS-20-CP Panel cutout punch
A panel-mount retaining clip is supplied with each model.
1. Desired display readings are:
4mA ="0.00"
20mA = "6.00"
Use DIP-switch setting #3 in Table 1 and enable decimal point DP2
via SW5. Apply 4mA and adjust R3 so the display reads "0.00". Apply
20mA and adjust R7 so the display reads "6.00".
2. Desired display readings are:
4mA = "000"
20mA = "800"
Use DIP-switch setting #2 in Table 1. Apply 4mA and adjust R3 so the
display reads "000". Apply 20mA and adjust R7 so the display reads
"800". For these display readings, no decimal points are used. Set
SW4, SW5 and SW6 to OFF.
3. Desired display readings are:
4mA = ".000"
12mA = ".250"
This example is not as straightforward as the previous two. Notice that
12mA is exactly halfway between 4mA and 20mA. If we assume that
the input could go up to 20mA, the display reading would then be:
2 x .250 or ".500". From Table 1 we can now select DIP-switch
setting #4 and enable DP1 via SW4. Apply 4mA and adjust R3 so
the display reads ".000". Apply 12mA and adjust R7 so the display
reads ".250".
Examples (DMS-20PC-4/20S-Unipolar Model)
DMS-20PC-4/20S (Unipolar Reading Model)
As shipped, the DMS-20PC-4/20S is factory calibrated to read "000"
for a 4mA input and "1000" for a 20mA input. The following worst-case
procedure assumes the DMS-20PC-4/20S is completely mis-adjusted, i.e.,
both potentiometers and the DIP switches are randomly set. When perform-
ing DIP-switch settings, be sure the DIP switch's small actuators are fi rmly
engaged in their fully-ON or fully-OFF positions.
1
2
3
4
56
ON
123
4
5
6
ON
1234
56
ON
Ordering Information