Datasheet NCB8-18GM40-N0-10M DataSheet (Pepperl Fuchs)

Page 1
Inductive sensor NCB8-18GM40-N0-10M
Technical Data
General specifications
Switching function Normally closed (NC) Output type NAMUR Rated operating distance sn8 mm Installation flush Assured operating distance sa0 ... 6.48 mm
0102
Model Number
NCB8-18GM40-N0-10M
Features
•8 mm flush
Accessories
EXG-18
Quick mounting bracket with dead stop
BF 18
Mounting flange, 18 mm
Actual operating distance s Reduction factor rAl 0.39 Reduction factor r Reduction factor r Output type 2-wire
Nominal ratings
Nominal voltage Uo8 V Switching frequency f 0 ... 1500 Hz Hysteresis H 1 ... 15 typ. 5 % Reverse polarity protection reverse polarity protected Short-circuit protection yes Current consumption
Measuring plate not detected Measuring plate detected
Switching state indicator all direction LED, yellow
Functional safety related parameters
MTTFd 2660 a Mission Time (TM) 20 a Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F) Storage temperature -40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection type cable PVC , 10 m Core cross-section 0.75 mm Housing material Stainless steel 1.4305 / AISI 303 Sensing face PBT Degree of protection IP67 Cable
Bending radius
General information
Use in the hazardous area see instruction manuals
Category
Compliance with standards and directives
Standard conformity
NAMUR
Electromagnetic compatibility Standards
Approvals and certificates
EAC conformity TR CU 012/2011 FM approval
Control drawing UL approval cULus Listed, General Purpose CSA approval cCSAus Listed, General Purpose CCC approval CCC approval / marking not required for products rated 36 V
0.36
Cu
0.71
304
Dimensions
7.2 ... 8.8 mm typ. 8 mm
r
2.2 mA 1 mA
2
> 10 x cable diameter
1G; 2G; 3G; 1D; 3D
EN 60947-5-6:2000 IEC 60947-5-6:1999 NE 21:2007 EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
116-0165
Release date: 2018-04-19 08:13 Date of issue: 2018-04-19 204725_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
M18x1
4
24
LED
37
40
1
Page 2
Inductive sensor NCB8-18GM40-N0-10M
Electrical Connection
BN
BU
Equipment protection level Ga
CE marking 0102
ATEX marking ¬ II 1G Ex ia IIC T6T1 Ga The Ex-related marking can also be printed on the enclosed label.
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety"
Appropriate type NCB8-18GM...-N0...
Effective internal inductivity C
Effective internal inductance L
Ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
Equipment protection level Gb
CE marking 0102
ATEX marking ¬ II 1G Ex ia IIC T6T1 Ga
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety"
Appropriate type NCB8-18GM...-N0...
Effective internal inductivity C
Effective internal inductance L
Maximum permissible ambient temperature T
Equipment protection level Gc (ic)
Certificate PF 13 CERT 2895 X
CE marking
i
i
i
i
L+
L-
Use is restricted to the following stated conditions
120 nF ; a cable length of 10 m is considered.
50 µH ; a cable length of 10 m is considered.
temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Note:
Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already
been applied to the temperature table for category 1.
The Ex-significant identification is on the enclosed adhesive label
Use is restricted to the following stated conditions
120 nF ; a cable length of 10 m is considered.
50 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
ATEX marking ¬ II 3G Ex ic IIC T6T1 Gc
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection category "ic" Use is restricted to the following
Effective internal inductivity C
Effective internal inductance L
Special conditions
for Pi=34 mW, Ii=25 mA, T6
for Pi=34 mW, Ii=25 mA, T5
for Pi=34 mW, Ii=25 mA, T4-T1
for Pi=64 mW, Ii=25 mA, T6
for Pi=64 mW, Ii=25 mA, T5
for Pi=64 mW, Ii=25 mA, T4-T1
for Pi=169 mW, Ii=52 mA, T6
for Pi=169 mW, Ii=52 mA, T5
for Pi=169 mW, Ii=52 mA, T4-T1
for Pi=242 mW, Ii=76 mA, T6
for Pi=242 mW, Ii=76 mA, T5
for Pi=242 mW, Ii=76 mA, T4-T1
i
i
The Ex-significant identification is on the enclosed adhesive label
stated conditions
120 nF ; a cable length of 10 m is considered.
50 µH ; A cable length of 10 m is considered.
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
41 °C (105.8 °F)
41 °C (105.8 °F)
41 °C (105.8 °F)
29 °C (84.2 °F)
29 °C (84.2 °F)
29 °C (84.2 °F)
Release date: 2018-04-19 08:13 Date of issue: 2018-04-19 204725_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2
Page 3
Inductive sensor NCB8-18GM40-N0-10M
Equipment protection level Gc (nL)
Standard conformity EN 60079-15:2005 Ignition protection category "n"
Effective internal capacitance C
Effective internal inductance Li 50 µH ; A cable length of 10 m is considered.
120 nF ; a cable length of 10 m is considered.
i
Use is restricted to the following stated conditions
General The apparatus has to be operated according to the appropriate data in the data sheet and in this instruction manual.
Special conditions
for Pi=34 mW, Ii=25 mA, T6
for Pi=34 mW, Ii=25 mA, T5
for Pi=34 mW, Ii=25 mA, T4-T1
for Pi=64 mW, Ii=25 mA, T6
for Pi=64 mW, Ii=25 mA, T5
for Pi=64 mW, Ii=25 mA, T4-T1
for Pi=169 mW, Ii=52 mA, T6
for Pi=169 mW, Ii=52 mA, T5
for Pi=169 mW, Ii=52 mA, T4-T1
for Pi=242 mW, Ii=76 mA, T6
for Pi=242 mW, Ii=76 mA, T5
for Pi=242 mW, Ii=76 mA, T4-T1
Equipment protection level Da
CE marking 0102
ATEX marking ¬ II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety"
Appropriate type NCB8-18GM...-N0...
Effective internal inductivity C
Effective internal inductance L
Maximum permissible ambient temperature T
Equipment protection level Dc
CE marking 0102
i
i
The data stated in the data sheet are restricted by this operating instruction! The special conditions must be observed! The ATEX Directive applies only to the use of apparatus under atmospheric conditions. If you use the device outside atmospheric conditions, consider that the permissible safety parameters should be reduced.
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
41 °C (105.8 °F)
41 °C (105.8 °F)
41 °C (105.8 °F)
29 °C (84.2 °F)
29 °C (84.2 °F)
29 °C (84.2 °F)
Use is restricted to the following stated conditions
120 nF A cable length of 10 m is considered.
50 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
surface temperature, and the effective internal reactance values can be found on the EC-type-examination certificate.
The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained.
ATEX marking ¬ II 3D IP67 T 111 °C (231.8 °F) X
Standards EN 50281-1-1
Special conditions
Maximum heating (Temperature rise)
at U
using an amplifier in accordance with EN 60947­5-6
Equipment protection level Dc (tc)
CE marking 0102
ATEX marking ¬ II 3D Ex tc IIIC T80°C Dc
Standards EN 60079-0:2012+A11:2013, EN 60079-31:2014
General The corresponding datasheets, declarations of conformity, EC-type examination certificates, certifications, and
Special conditions
Maximum permissible ambient temperature T
at U
using an amplifier in accordance with EN 60947­5-6
=9 V, RV=562
Bmax
=9 V, RV=562
Bmax
The Ex-relevant identification may also be printed on the accompanying adhesive label.
Protection via housing Use is restricted to the following stated conditions
Values can be obtained from the following list, depending on the max. operating voltage Ub max and the minimum series resistance Rv.
11 K
11 K
The Ex-related marking can also be printed on the enclosed label.
Protection by enclosure "tc" Some of the information in this instruction manual is more specific than the information provided in the datasheet.
control draw see datasheets), form an integral part of this document. These documents can be found at The maximum surface temperature of the device was determined without a layer of dust of the information in this instruction manual is more specific than the information provided in the datasheet.
Values can be obtained from the following list, depending on the max. operating voltage Ub max and the minimum
Umax
series resistance Rv.
61 °C (141.8 °F)
61 °C (141.8 °F)
Release date: 2018-04-19 08:13 Date of issue: 2018-04-19 204725_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.