Datasheet MIC184BMM, MIC184BM Datasheet (MICREL)

Page 1
MIC184 Micrel
MIC184
Local/Remote Thermal Supervisor
Advance Information
General Description
The MIC184 is a versatile digital thermal supervisor capable of measuring temperature using either its own internal sensor or an inexpensive external sensor. A 2-wire serial interface is provided to allow communication with either I2C or SMBus masters. This device is a pin-for-pin and software compatible upgrade for the industry standard LM75.
Additional features include remote temperature measure­ment capability, and interrupt status and mask bits in the chip’s configuration register for software polling. The open­drain interrupt output pin can be used as either an overtem­perature alarm or thermostatic control signal. Three program­mable address pins permit users to multidrop up to 8 devices along the 2-wire bus, allowing simple distributed temperature sensing networks. Superior performance, low power and small size makes the MIC184 an excellent choice for the most demanding thermal management applications.
Features
Measures local and remote temperatures
Pin and software backward compatible to LM75
9-bit sigma-delta ADC
2-wire I2C/SMBus compatible interface
Programmable thermostatic settings for either internal or
external zone
Open-drain comparator/interrupt output pin
Interrupt mask and status bits
Low-power shutdown mode
Fail-safe response to diode faults
2.7V to 5.5V power supply range
Up to 8 devices may share the same bus
8-Lead SOP and MSOP Packages
Applications
Desktop, Server and Notebook Computers
Printers and Copiers
Test and measurement equipment
Consumer electronics
Ordering Information
Part Number Temperature Range Package
MIC184BM –55°C to +125°C 8-lead SOP MIC184BMM –55°C to +125°C 8-lead MSOP
Typical Application
3.0V to 3.6V V
DD
3 ×
10k
Data
Clock
Interrupt
FROM
SERIAL BUS
HOST
2-Channel SMBus Temperature Measurement System
Micrel, Inc. • 1849 Fortune Drive • San Jose, CA 95131 • USA • tel + 1 (408) 944-0800 • fax + 1 (408) 944-0970 • http://www.micrel.com
November 2000 1 MIC184
8 1 2 3
VDD DATA CLK INT
MIC184
A2/T1
A1 A0
GND
5 6 7 4
0.1µF ceramic
2200pF
OPTIONAL REMOTE TEMPERATURE SENSOR
Page 2
MIC184 Micrel
Pin Configuration
CLK
INT
GND
Pin Description
Pin Number Pin Name Pin Function
1 DATA Data (Digital I/O): Open-drain. Serial data input/output. 2 CLK Clock (Digital Input): The host provides the serial bit clock on this input. 3 INT Interrupt (Digital Output): Open-drain. Interrupt or thermostat output. 4 GND Ground: Power and signal return for all IC functions. 5 A2/T1 Address Bit 2 (Digital Input): Slave address selection input. See “Slave
6 A1 Address Bit 1 (Digital Input): Slave address selection input. See “Slave
7 A0 Address Bit 0 (Digital Input): Slave address selection input. See “Slave
8 VDD Supply (Analog Input): Power supply input to the IC.
1DATA 2 3 4
Address Truth Table. Temperature Sensor 1 (Analog Input): Input from remote temperature sensor
(diode junction).
Address Truth Table.
Address Truth Table.
8 VDD
A0
7
A1
6
A2/T1
5
MIC184 2 November 2000
Page 3
MIC184 Micrel
Absolute Maximum Ratings (Note 1)
Power Supply Voltage, V
Voltage on Any Pin................................–0.3V to V
Current Into Any Pin...................................................±6mA
Power Dissipation, T
A
Junction Temperature ............................................. +150°C
................................................... 6.0V
DD
+0.3V
DD
= +125°C ...............................30mW
Operating Ratings (Note 2)
Power Supply Voltage, V Ambient Temperature Range (T Package Thermal Resistance (θ
SOP.................................................................+152°C/W
MSOP..............................................................+206°C/W
.............................. +2.7V to +5.5V
DD
) ............-55°C to +125°C
A
)
JA
Storage Temperature ............................... –65°C to +150°C
ESD Ratings (Note 3)
Human Body Model.................................................. TBD V
Machine Model......................................................... TBD V
Soldering
Vapor Phase (60 sec.) .............................+220°C +5⁄–0°C
Infrared (15 sec.)...................................... +235°C +5⁄–0°C
Electrical Characteristics
2.7V VDD 5.5; TA = +25°C, bold values indicate 55°C TA +125°C, Note 4; unless noted. Symbol Parameter Condition Min Typ Max Units Power Supply
I
DD
t
POR
V
POR
V
HYST
Temperature-to-Digital Converter Characteristics
t
CONV
Remote Temperature Input (T1)
I
F
Address Inputs (A2/T1, A1, A0)
V
IL
V
IH
C
IN
I
LEAK
I
PD
Supply Current INT open, A2, A1, A0 = VDD or GND, 340 TBD µA
CLK = DATA = high, normal mode shutdown mode, CLK = 100kHz 2.5 µA INT open, A2, A1, A0 = V
or GND, 1 TBD µA
DD
CLK = DATA = high, shutdown mode
Power-On Reset Time VDD > V
POR
15 100 µs
Power-On Reset Voltage all registers reset to default values, 2.0 2.7 V
A/D conversions initiated
Power-On Reset Hysteresis Voltage 250 mV
AccuracyLocal Temperature 0°C T Note 5, 6 3V VDD 3.6V
–55°C T
+100°C, INT open, ±1 ±2 °C
A
+125°C, INT open, ±2 ±3 °C
A
3V VDD 3.6V
AccuracyRemote Temperature 0°C T
+100°C, INT open, ±1 ±3 °C
D
Note 5, 6, 7 3V VDD 3.6V, 0°C TA +85°C
–55°C T
+125°C, INT open, ±2 ±5 °C
D
3V VDD 3.6V, 0°C TA +85°C
Conversion Time, Note 5 local temperature 100 160 ms
remote temperature 200 320 ms
Current to External Diode high level 224 400 µA
Note 5
low level 7.5 14 µA
Low Input Voltage 2.7V ≤ VDD 5.5V 0.6 V High Input Voltage 2.7V ≤ VDD 5.5V 2.0 V Input Capacitance 10 pF Input Current ±0.01 ±1 µA Pulldown Current on A2/T1 A2 = VDD, flows for t
at power-up 25 µA
POR
November 2000 3 MIC184
Page 4
MIC184 Micrel
Symbol Parameter Condition Min Typ Max Units Serial Data I/O Pin (DATA)
V
OL
V
IL
V
IH
C
IN
I
LEAK
Serial Clock Input (CLK)
V
IL
V
IH
C
IN
I
LEAK
Status Output (INT)
V
OL
t
INT
t
nINT
T_SET Default T_SET Value t HYST Default HYST Value t
Serial Interface Timing (Note 5)
t
1
t
2
t
3
t
4
t
5
Low Output Voltage IOL = 3mA 0.4 V
IOL = 6mA 0.8 V Low Input Voltage 2.7V ≤ VDD 5.5V 0.3V High Input Voltage 2.7V ≤ VDD 5.5V 0.7V
DD
DD
V V
Input Capacitance 10 pF Input current ±0.01 ±1 µA
Low Input Voltage 2.7V ≤ VDD 5.5V 0.3V High Input Voltage 2.7V ≤ VDD 5.5V 0.7V
DD
DD
V V
Input Capacitance 10 pF Input current ±0.01 ±1 µA
Low Output Voltage, IOL = 3mA 0.4 V
Note 8
Interrupt Propagation Delay, from TEMP > T_SET, FQ = 00 to INT < VOL, Note 5 R
IOL = 6mA 0.8 V
t
+1
= 10kΩ; POL bit = 0
PULLUP
CONV
µs
Interrupt Reset Propagation Delay, from any register read to INT > VOH, 1 µs Note 5 R
POR POR
= 10kΩ; POL bit = 0
PULLUP
after VDD > V after VDD > V
, Note 9 80 80 80 °C
POR
, Note 9 75 75 75 °C
POR
CLK (Clock) Period 2.5 µs Data In Setup Time to CLK High 100 ns Data Out Stable After CLK Low 0 ns DATA Low Setup Time to CLK Low start condition 100 ns DATA High Hold Time stop condition 100 ns
After CLK High
Note 1. Exceeding the absolute maximum rating may damage the device. Note 2. The device is not guaranteed to function outside its operating rating. Note 3. Devices are ESD sensitive. Handling precautions recommended.
Note 4. Final test on outgoing product is performed at TA = TBD°C. Note 5. Guaranteed by design over the operating temperature range. Not 100% production tested. Note 6. Accuracy specification does not include quantization noise, which may be as great as ±1⁄2LSB (±1⁄4°C). Note 7. TD is the temperature of the remote diode junction. Testing is performed using a single unit of one of the transistors listed in Table 5. Note 8. Current into the INT pin will result in self-heating of the MIC184. INT pin current should be minimized for best accuracy. Note 9. This is the decimal representation of a binary data value.
Human body model: 1.5k in series with 100pF. Machine model: 200pF, no series resistance.
Timing Diagram
t
1
SCL
t
4
t
2
SDA Input
t
3
SDA Output
Serial Interface Timing
MIC184 4 November 2000
t
5
Page 5
MIC184 Micrel
0
50
100
150
200
250
300
350
400
450
500
-60
-40
-20
0
204060
80
100
120
140
SUPPLY CURRENT (µA)
TEMPERATURE (°C)
Operating I
DD
vs. Temperature
VDD = 3.3V
VDD = 5.0V
f
CLOCK
= 0Hz
0
50
100
150
200
250
300
350
400
0246
QUIESCENT CURRENT (µA)
SUPPLY VOLTAGE (V)
Shutdown Mode IDD
vs. Suply Voltage
-12
-10
-8
-6
-4
-2
0
012345678910
MEASURMENT ERROR (°C)
CAPACITANCE (nF)
Measurment Error vs.
Capcitance on T1
Typical Characteristics
Local Temperature
Measurement Error
3
2
1
0
-1
-2 VDD = 3.3V
MESUREMENT ERROR (°C)
-3
LOCAL DIODE TEMERATURE (°C)
9 8 7 6 5 4 3 2 1
SHUTDOWN CURRENT (µA)
0
0 50 100150 200250 300 350 400
0
204060
-60
-40
-20
Shutdown I
80
DD
vs. Frequency
VDD = 5.0V
VDD = 3.0V
CLOCK FREQUENCY (kHz)
100
120
140
Remote Temperature
Measurement Error
5 4 3 2 1 0
-1
-2
-3 VDD = 3.3V
-4
MESUREMENT ERROR (°C)
-5
REMOTE DIODE TEMERATURE (°C)
3.5 3
2.5 2
1.5 1
0.5
SHUTDOWN CURRENT (µA)
0
0
-40
-20
204060
-60
Shutdown Mode I
vs. Temperature
VDD = 5.0V
f
= 0Hz
CLOCK
VDD = 3.3V
0
-60
204060
-40
-20
TEMPERATURE (°C)
80
100
DD
80
100
120
120
140
140
Response to Immersion in
140
MSOP-8
120 100
80 60 40 20
0
0 5 10 15
MEASURED LOCAL TEMPERATURE (°C)
November 2000 5 MIC184
125°C Fluid Bath
SOIC-8
TIME (Sec)
Measurement Error vs.
PCB Leakage to +5V/+3.3V/GND
-10
-15
-20
-25
MEASUREMENT ERROR (°C)
-30
1x10
5 0
-5
GND
3.3V
5.0V
6
1x1071x1081x10
RESISTANCE FROM T1()
9
Page 6
MIC184 Micrel
Functional Diagram
A2/T1
A1 A0
DATA
CLK
2:1
MUX
Bandgap
Sensor
and
Reference
2-Wire
Serial Bus
Interface
1-Bit DAC
Register
Temperature
Setpoint
Register
Temperature
Hysteresis
Register
Configuration
Register
Result
TEMPERATURE-TO-DIGITAL
CONVERTER
Digital Filter
and
Control
Logic
State
Machine
and
Digital
Comparator
Pointer
Register
MIC184
Functional Description
Pin Descriptions
VDD
Power supply input. See electrical specifications.
GND
Ground return for all MIC184 functions.
CLK
Clock input to the MIC184 from the two-wire serial bus. The clock signal is provided by the bus host and is shared by all devices on the bus.
DATA
Serial data I/O pin that connects to the two-wire serial bus. DATA is bidirectional and has an open-drain output driver. An external pull-up resistor or current source somewhere in the system is necessary on this line. This line is shared by all devices on the bus.
A2/T1, A1, A0
These inputs set the three least significant bits of the MIC184’s 7-bit slave address. Each MIC184 will only respond to its own unique slave address, allowing the use of up to eight MIC184s on a single bus. A match between the MIC184s address and
Thermostat
Output
INT
the address specified in the serial bit stream must be made to initiate communication. A1 and A0 should be connected directly to VDD or ground. When A2/T1 is used as an address bit input, it should also be tied to VDD or ground. A2/T1 can alternatively connect to a remote temperature sensor. When A2/T1 is used for temperature measurements, an off-chip diode junction must be connected between A2/T1 and ground. In this case, internal circuitry will detect A2 as logic low, leaving four possible slave addresses. See “Temperature Measurement and Power On for more information. A2/T1, A1, and A0 determine the slave address as shown in Table 1.
INT
Temperature events are indicated to external circuitry via this output. INT may be configured as active-low or active-high by the host. Operation of the INT output is controlled by the MODE and POL bits in the MIC184s configuration register. See Comparator and Interrupt Modes below. This output is open-drain and may be wire-ORed with other open-drain signals. Most systems will require a pull-up resistor or current source on this pin. If the IM bit in the configuration register is set, it prevents the INT output from sinking current. In I2C and SMBus systems, the IM bit is therefore an interrupt mask bit.
MIC184 6 November 2000
Page 7
MIC184 Micrel
stupnIsserddAevalS481CIM
1T/2A1A0AyraniBxeH
000 0001001 001 1001001 010 0101001 011 1101001 100 0011001 101 1011001 110 0111001 111 1111001
edoid00 0001001 edoid01 1001001 edoid10 0101001 edoid11 1101001
b b b b b b b b b b b b
84
h
94
h
A4
h
B4
h
C4
h
D4
h
E4
h
F4
h
84
h
94
h
A4
h
B4
h
Table 1. MIC184 Slave Address Settings
Temperature Measurement
The temperature-to-digital converter for both internal and external temperature data is built around a switched current source and a 9-bit analog-to-digital converter. The tempera­ture is calculated by measuring the forward voltage of a diode junction at two different bias current levels. An internal multiplexer directs the current sources output to either an internal or external diode junction.
The MIC184 uses twos-complement data to represent tem­peratures. If the MSB of a temperature value is 0, the temperature is ≥ 0°C. If the MSB is 1, the temperature is < 0°. More detail on this is given in Temperature Data Format below. A
temperature event
results if the value in the tem­perature result register (TEMP) is greater than the value in the overtemperature setpoint register (T_SET), or if it is less than the value in the temperature hysteresis register (T_HYST).
The value of the ZONE bit in the configuration register determines whether readings are taken from the on-chip sensor or from the A2/T1 input. At power-up, the ZONE bit of the configuration register is set to zero. The MIC184 therefore monitors its internal temperature and compares the result
against the contents of T_SET and T_HYST. Setting the ZONE bit in CONFIG will result in the MIC184 acquiring temperature data from an external diode connected to the A2/T1 pin. This diode may be embedded in an integrated circuit (such as a CPU, ASIC, or graphics processor), or it may be a diode-connected discrete transistor. Once the new value is written to CONFIG, the A/D converter will begin a new conversion and return temperature data from the external zone. This data will be compared against T_SET, T_HYST, and the state of the Fault_Queue (described below). The internal status bit (STS) and the INT output will then be updated accordingly. See Applications Information for more details on switching between zones.
Diode Faults
The MIC184 is designed to respond in a fail-safe manner to hardware faults in the external sensing circuitry. If the con­nection to the external diode is lost, or the sense line (A2/T1) is shorted to VDD or ground, the temperature data reported by the A/D converter will be forced to its full-scale value (+127.5°C). This will cause an overtemperature event to occur whenever T_SET +127.0°C (0 1111 1110b). An interrupt will be generated if so enabled. The temperature reported for the external zone will remain 0 1111 1111b = +127.5°C until the fault condition is cleared. This fault detec­tion requires that the MIC184 complete the number of conver­sion cycles specified by Fault_Queue. The MIC184 may therefore require one or more conversion cycles following power-on or a transition from shutdown to normal operation before reporting an external diode fault.
Serial Port Operation
The MIC184 uses standard SMBus WRITE_BYTE, READ_BYTE, WRITE_WORD, and READ_WORD opera­tions for communication with its host. The SMBus WRITE_BYTE and WRITE_WORD operations involve send­ing the devices slave address (with the R/W bit low to signal a write operation), followed by a command byte and one or two data bytes. The SMBus READ_BYTE operation is simi­lar, but is a composite write and read operation: the host first sends the devices slave address followed by the command byte, as in a write operation. A new “start” bit must then be sent to the MIC184, followed by a repeat of the slave address with the R/W bit (LSB) set to the high (read) state. The data
etyB_dnammoCretsigeRtegraT
yraniBxeHlebaLnoitpircseD
00000000
b
10000000
b
01000000
b
11000000
b
00100000
b
·
·
·
11111111
b
00
h
10
h
20
h
30
h
40
h
·
·
·
FF
h
PMETtlusererutarepmetderusaem
GIFNOCretsigernoitarugifnoc
TSYH_Tsiseretsyherutarepmet
TES_Ttniopteserutarepmetrevo
devreseresutonod
Table 2. MIC184 Register Addresses
November 2000 7 MIC184
Page 8
MIC184 Micrel
S1001
A2 A1 A0
0A000000XXA
D4D5D6 D3 D2 D1 D0D7
/A P
MIC184 Slave Address
DATA
CLK
Command Byte
Data Byte to MIC184
START
STOP
R/W = WRITE
ACKNOWLEDGE ACKNOWLEDGE
NOT ACKNOWLEDGE
S1001
A2 A1 A0 A2 A1 A0
0A000000XXAS1 1 100
D4D5D6 D3 D2 D1 D0
A
D7
/A P
MIC184 Slave Address
DATA
CLK
Command Byte
MIC184 Slave Address
Data Read From MIC184
START
START
STOP
R/W = WRITE
R/W = READ
ACKNOWLEDGE ACKNOWLEDGE ACKNOWLEDGE
NOT ACKNOWLEDGE
S1001
A2 A1 A0
0A000000XXA
D8 D7 D6 D5 D4 D3 D0 D1
A
D0
XXXXXXX/AP
MIC184 Slave Address
DATA
CLK
Command Byte
High-Order Byte to MIC184
Low-Order Byte to MIC184
START
STOP
R/W = WRITE
ACKNOWLEDGE ACKNOWLEDGE
ACKNOWLEDGE
NOT ACKNOWLEDGE
S1001
A2 A1 A0
0A000000XXA
MIC184 Slave Address
DATA
CLK
Command Byte
START
R/W = WRITE
ACKNOWLEDGE ACKNOWLEDGE
S1001
A2 A1 A0
1A A
D4D5D6 D3 D2 D1 D0D7D8
/A PXXXXXXX
MIC184 Slave Address
High-Order Byte from MIC184
Low-Order Byte from MIC184
START
STOP
R/W = READ
ACKNOWLEDGE ACKNOWLEDGE
NOT ACKNOWLEDGE
S1001
A2 A1 A0
1A A
D4D5D6 D3 D2 D1 D0D7D8
/A PXXXXXXX
MIC184 Slave Address
DATA
CLK
High-Order Byte from MIC184
Low-Order Byte from MIC184
START
STOP
R/W = READ
ACKNOWLEDGE ACKNOWLEDGE
NOT ACKNOWLEDGE
Master-to-slave transmission Slave-to-master response
Figure 1. WRITE_BYTE Protocol
Figure 2. READ_BYTE Protocol
Figure 3. WRITE_WORD Protocol
Figure 4. READ_WORD Protocol
Figure 5. RECEIVE_DATA from a 16-Bit Register
MIC184 8 November 2000
Page 9
MIC184 Micrel
S1001
A2 A1 A0
AX1 XXXXXXXA
MIC184 Slave Address
First Byte of Transaction
START
ACKNOWLEDGE ACKNOWLEDGE
R/W = WRITE
/A PXX XXXXXX
Last Byte of Transaction
A/D Converter
in Standby
Conversion
in Progress
New Conversion
in Progress
New Conversion
Begins
Conversion Interrupted
By MIC184 Acknowledge
Result
Ready
t
CONV
STOP
NOT ACKNOWLEDGE
A
SS1000
A2 A1 A0 A2 A1 A0
0A00000001A 10 100 XX XXXXXX/AP
MIC184 Slave Address
TEMP exceeds T_SET or falls below T_HYST
MIC184 Slave Address
DATA
INT*
Command Byte = 01
h
= CONFIG
CONFIG Value**
START
START
STOP
R/W = WRITE
ACKNOWLEDGE
ACKNOWLEDGE
ACKNOWLEDGE
R/W = READ
NOT ACKNOWLEDGE
Master-to-slave transmission Slave-to-master response
t
n/INT
t
/INT
* Assumes INT Polarity is active low.
** Status bits in CONFIG are cleared to zero following this operation.
Figure 6. A/D Converter Timing
Figure 7. Responding to Interrupts
November 2000 9 MIC184
Page 10
MIC184 Micrel
to be read from the MIC184 may then be clocked out. There is one exception to this rule: If the location latched in the pointer register from the last write operation is known to be correct (i.e., points to the desired register), then the RECEIVE_DATA procedure may be used. To perform a RECEIVE_DATA, the host sends an address byte to select the slave MIC184, and then retrieves the appropriate number (one or two) of data bytes. Figures 1 through 5 show the formats for these data read and data write procedures.
The command byte is 8 bits (1 byte) wide. This byte carries the address of the MIC184 register to be operated upon, and is stored in the MIC184s pointer register. The pointer register is a write-only register, which is implemented for backward compatibility to the National Semiconductor LM75 and similar devices. The command byte (pointer register) values corre­sponding to the various MIC184 register addresses are shown in Table 2. Command byte values other than 0000 00XX
= 00h through 03h are reserved, and should not
b
be used. The CONFIG register is 8 bits (1 byte) wide. Therefore,
communications with the CONFIG register will at a minimum require a READ_BYTE, WRITE_BYTE, or a RECEIVE_BYTE.
The TEMP, T_HYST, and T_SET registers are logically nine bits wide. Note, though, that these registers are physically two bytes (one SMBus word) wide within the MIC184. Prop­erly communicating with the MIC184 involves a 16-bit READ_WORD or RECEIVE_WORD from, or WRITE_WORD to, these registers. This is a requirement of the I2C/SMBus serial data protocols, which only allow data transfers to occur in multiples of eight bits.
Temperature Data Format
The LSB of each 9-bit logical register represents 0.5°C. The values are in a twos complement format, wherein the most significant bit (D8) represents the sign: “0” for positive tem­peratures and “1” for negative temperatures. The seven least significant bits of each 16-bit physical register are undefined. Therefore, physical bits D6 through D0 of the data read from these registers must be masked off, and the resulting binary value right justified before using the data received. It is also possible to read only the first byte of any of these three registers, sacrificing 0.5°C of resolution in exchange for somewhat simpler data handling. However, all writes to the T_SET and T_HYST registers must be in the 16-bit
WRITE_WORD format. Table 3 shows examples of the data format used by the MIC184 for temperatures.
A/D Converter Timing
Whenever the MIC184 is not in its low power shutdown mode, the internal A/D converter (ADC) attempts to make continu­ous conversions unless interrupted by a bus transaction accessing the MIC184. When the MIC184 is accessed, the conversion in progress will be halted, and the partial result discarded. When the access of the MIC184 is complete the ADC will begin a new conversion cycle, with results valid t
after that. Figure 6 shows this behavior. t
CONV
CONV
is twice as long for external conversions as it is for internal conver­sions. This allows the use of a filter capacitor on the A2/T1 input without a loss of accuracy due to the resulting longer settling times.
Power-On
When power is initially applied, the MIC184s internal regis­ters are set to default states which make the MIC184 com­pletely backward compatible with the LM75. Also at this time, the levels on the address inputs A2, A1, and A0 are read to establish the devices slave address. The MIC184s power­up default state can be summarized as follows:
Normal-mode operation (MIC184 not in shutdown)
ZONE is set to internal (on-chip temperature sensing)
INT function is set to comparator mode
INT output is set to active-low operation
Fault_Queue depth = 1
Interrupts are enabled (IM = 0)
T_SET = +80°C; T_HYST = +75°C
In order to accommodate the use of A2/T1 as a dual-purpose input, there is a weak pulldown on A2/T1 that will attempt to sink 25µA from the pin to ground for t
following power-
POR
up of the MIC184. This allows the MIC184 to pull A2/T1 to a low state when a diode junction is connected from that pin to ground, and latch a zero as the A2 address value. If A2 is not to be used as a diode connection, it should be connected to VDD or ground. Note that a fault in the external temperature sensor (if used) may not be reported until one or more conversion cycles have been completed following power-on. See DIODE FAULTS.
erutarepmeTyraniBwaRyraniBdeksaMxeHdeksaM
C°521+XXXXXXX010111110010111110
C°52+XXXXXXX010011000010011000
C°5.0+XXXXXXX100000000100000000
C°0XXXXXXX000000000000000000
C°5.0 XXXXXXX111111111111111111 C°52 XXXXXXX011100111011100111 C°04 XXXXXXX000011011000011011 C°55 XXXXXXX010010011010010011
b b b b b b b b
AF0
h
230
h
100
h
000
h
FF1
h
EC1
h
0B1
h
291
h
Table 3. Digital Temperature Format
MIC184 10 November 2000
Page 11
MIC184 Micrel
Shutdown Mode
Setting the SHDN bit in the configuration register halts the otherwise continuous conversions by the A/D converter. The MIC184s power consumption drops to 1µA typical in shut­down mode. All registers may be read from, or written to, while in shutdown mode. Serial bus activity will slightly increase the MIC184s power consumption.
Entering shutdown mode will not affect the state of INT when the device is in comparator mode (MODE = 0). However, If the device is shut down while in interrupt mode, the INT pin will be deasserted and the internal latch (STS) holding the interrupt status will be cleared. Therefore, no interrupts will be generated while the MIC184 is in shutdown mode, and the interrupt status will not be retained. It is important to note, however, that the
cause
of the last temperature event
will
be retained in the MIC184. This is described further in “Com- parator and Interrupt Modes below. The diode fault detection mechanism (see Diode Faults) requires one or more A/D conversion cycles to detect external sensor faults. Hence, no diode faults will be detected while the device is in shutdown.
Comparator and Interrupt Modes
Depending on the setting of the MODE bit in the configuration register, the INT output will behave either as an interrupt request signal or a thermostatic control signal. Thermostatic operation is known as
comparator mode
. The INT output is asserted whenever the measured temperature, as reported in the TEMP register, exceeds the threshold programmed in the T_SET register for the number of conversions specified by Fault_Queue (described below). In comparator mode, INT will remain asserted unless and until the measured tempera­ture falls below the value in the T_HYST register for Fault_Queue conversions. No action on the part of the host is required for operation in comparator mode. Note that entering shutdown mode will not affect the state of INT when the device is in comparator mode.
In
interrupt mode
, once a temperature event has caused STS to be set, and the INT output to be asserted, they will not be automatically deasserted when the measured temperature falls below T_HYST. They can only be deasserted by reading any of the MIC184's internal registers or by putting the device into SHUTDOWN mode. If the most recent temperature event was an overtemperature condition, STS will not be set again, and INT cannot be reasserted, until the device has detected that TEMP < T_HYST. Similarly, if the most recent temperature event was an undertemperature condition, STS will in be set again, and INT cannot be reasserted, until the device has detected that TEMP > T_SET. This keeps the internal logic of the MIC184 backward compatible with that of
]3:4[GIFNOChtpeDeueuQ_tluaF
00*noisrevnoc1 10snoisrevnoc2 01snoisrevnoc4 11snoisrevnoc6
gnittestluafeD*
Table 4. Fault_Queue Depth Settings
the LM75 and similar devices.
this:
while the MIC184 is operating in interrupt mode, the part
There is a software override for
can be unconditionally set to monitor for an overtemperature condition, regardless of what caused the last temperature event. This is done by clearing the MODE bit, and then immediately resetting it to 1. Following this sequence the next temperature event detected will be an overtemperature con­dition, regardless of whether the last temperature event was the result of an overtemperature or undertemperature condi­tion.
In both modes, the MIC184 will be responsive to overtem­perature events upon power up.
Fault_Queue
A Fault_Queue (programmable digital filter) is provided in the MIC184 to prevent false tripping due to thermal or electrical noise. Two bits, CONFIG[4:3], set the depth of Fault_Queue. Fault_Queue then determines the number of consecutive temperature events (TEMP > T_SET or TEMP < T_HYST) which must occur in order for the condition to be considered valid. As an example, assume the MIC184 is in comparator mode, and CONFIG[4:3] is programmed with 10
. Then the
b
measured temperature would have to exceed T_SET for four consecutive A/D conversions before INT would be asserted or the status bit set. Similarly, TEMP would have to be less than T_HYST for four consecutive conversions before INT would be reset.
Like any filter, the Fault_Queue function also has the effect of delaying the detection of temperature events. In this ex­ample, it would take 4 × t
to detect a temperature event.
CONV
The depth of Fault_Queue vs. D[4:3] of the configuration register is shown in Table 4.
Handling Interrupts
The MIC184 may be either polled by the host, or request the hosts attention via the INT pin. In the case of polled opera­tion, the host periodically reads the contents of CONFIG to check the state of the status bit. The act of reading CONFIG clears the status bit, STS. If more than one event that sets the status bit occurs before the host polls the MIC184, only the fact that at least one such event has occurred will be apparent to the host.
If TEMP < T_HYST or TEMP > T_SET for Fault_Queue conversions, the status bit STS will be set in the CONFIG register. This action cannot be masked. However, a tempera­ture event will only generate an interrupt signal on INT if interrupts from the MIC184 are enabled (IM = 0 and MODE = 1 in the configuration register). Reading any register following an interrupt will cause INT to be deasserted, and will clear STS. The host should read the contents of the configuration register after receiving an interrupt to confirm that the MIC184 was the source of the interrupt. This is shown in Figure 7. As noted above, putting the device into shutdown mode will also deassert INT and clear STS. Therefore, this usually should not be done before completing the appropriate interrupt service routine(s).
Since temperature-to-digital conversions continue while INT is asserted, it is possible that temperature could change between the MIC184s assertion of its INT output and the hosts response to the interrupt. It is good practice when
November 2000 11 MIC184
Page 12
MIC184 Micrel
servicing interrupts for the host to read the current tempera­ture to confirm that the condition that caused the interrupt still exists.
Interrupt Polarity Selection
The INT output can be programmed to behave as an active­low signal or an active-high signal. The default is active-low. INT polarity is selected by programming the appropriate value into the polarity bit (POL) in the CONFIG register. Clearing POL selects active-low interrupts; setting POL se­lects active-high interrupts. INT is an open-drain digital output and may be wire-ORed with other open-drain logic signals. Most applications will require a pull-up resistor on this pin.
Whether the CONFIG registers POL bit is set to provide a current-sinking (low) or high-Z (high) state at the INT pin when STS is high, writing a one to IM will put the INT pin into a high-Z state. This meets the requirement of an active-low interrupt for the SMBus, while making IM available as an INT­forcing bit for those applications which employ an active-high INT output (for example, software fan-control routines).
LM75 Compatibility
The MIC184 can be used interchangeably with the LM75 in existing applications. The MIC184 offers several advantages over the LM75:
Ability to monitor a second, remote temperature
Interrupt masking capability
Status bit for software polling routines
Lower quiescent current
Supports single-byte reads from 16-bit registers
No inadvertent 8-bit read bus lock-up issues
The three MSBs of the configuration register (which power up as zeroes) are used to access the MIC184s additional functions. These are reserved bits according to the LM75 specification and, for the LM75, must always be written as zeroes. The MSB of the MIC184s status register is a status flag that does not exist in the LM75. This bit will be set to one whenever an overtemperature event occurs. This bit would never be set by an LM75. Software should not depend on this bit being zero when using the MIC184 as an LM75 upgrade. If at power-up the measured temperature is higher than T_SET, the status bit will be set following the first conversion by the A/D. See Applications Information for a method by which host software can use this fact to differentiate between an MIC184 and an LM75.
MIC184 12 November 2000
Page 13
MIC184 Micrel
Register Set and Programmers Model
Internal Register Set
emaNnoitpircseDetyBdnammoCnoitarepOtluafeDpU-rewoP
PMETerutarepmetderusaem00
GIFNOCretsigernoitarugifnoc10
TSYH_Tsiseretsyh20
TES_Ttniopteserutarepmet30
Detailed Register Descriptions
]7[D]6[D]5[D]4[D]3[D]2[D]1[D]0[D
ylnodaeretirw/daeretirw/daeretirw/daeretirw/daeretirw/daeretirw/daer tpurretni
sutats
)STS(
stiBnoitcnuFnoitarepO
STS)ylnodaer(sutatstpurretni enon=0,deruccotpurretni=1
MIksamtpurretnidelbasid=1,delbane=0
ENOZnoitceleserutarepmetetomer/lanretnilanretni=0,etomer=1
Q_FhtpedeueuQ_tluaF
LOPnoitcelesytiraloptuptuoTNI wolevitca=0,hgihevitca=1
EDOM
NDHS
h h h h
ylnodaertib-9000000000 etirw/daertib-800000000 etirw/daertib-9011010010 etirw/daertib-9000001010
b
b
b b
)etirW/daeRtiB-8(GIFNOC
tpurretni
)3(
ksam
)MI(
pmet
tceles
)ENOZ(
eueuqtluaf
htped
)Q_F(
tni
ytiralop
)LOP(
TNI/PMC
edom
)EDOM(
nwodtuhS
)NDHS(
,snoisrevnoc2=10,noisrevnoc1=00 snoisrevnoc6=11,snoisrevnoc4=01
tpurretni/rotarapmoc
nipTNIrofnoitcelesedom
nwodtuhs/lamron
noitcelesedomgnitarepo
lamron=0
,edomtpurretni=1
edomrotarapmoc=0
,nwodtuhs=1
)1(
C°0
)2(
C°57+ C°08+
Power-Up Default Value: 0000 0000b = 00
(4)
h
not in shutdown mode
comparator mode
INT = active low
Fault_Queue depth = 1
local temperature zone
interrupts enabled.
CONFIG Command Byte Address: 0000 0001b = 01
h
(1)
TEMP will contain measured temperature data for the selected zone after the completion of one conversion.
(2)
After the first Fault_Queue conversions are complete, the status bit will be set if TEMP < T_HYST or TEMP > T_SET.
(3)
Setting IM forces the open-drain INT output into its high-Z state. See INT Polarity Selection.
(4)
After the first Fault_Queue conversions are completed, the status bit will be set if TEMP < T_HYST or TEMP > T_SET.
November 2000 13 MIC184
Page 14
MIC184 Micrel
Temperature Result Register
)ylnOdaeRtiB-9(PMET
]51[D]41[D]31[D]21[D]11[D]01[D]9[D]8[D]7[D]6[D]5[D]4[D]3[D]2[D]1[D]0[D
BSM7tib6tib5tib4tib3tib2tib1tibBSL XXXXXXX
CDAmorfataderutarepmet
stiBnoitcnuFnoitarepO
]7:51[D
Power-Up Default Value: 0 0000 0000b = 0°C
enozdetcelesrof
TEMP Command Byte Address: 0000 0000b = 00
ataderutarepmetderusaem
* The value in TEMP is 9 logical bits in width, but due to the
h
conventions of I System software should ignore undefined bits D[6:0]. See Serial Port Operation" and "Temperature Data Format for more details.
TEMP will contain measured temperature data for the selected zone after the completion of one conversion.
*ylnodaer
2
C/SMBus, it is represented by 16 serial bits.
Hysteresis Register
)etirW/daeRtiB-9(TSYH_T
]51[D]41[D]31[D]21[D]11[D]01[D]9[D]8[D]7[D]6[D]5[D]4[D]3[D]2[D]1[D]0[D
BSM7tib6tib5tib4tib3tib2tib1tibBSL XXXXXXX
gnittessiseretsyherutarepmet
stiBnoitcnuFnoitarepO
]7:51[Dgnittessiseretsyherutarepmet*etirw/daer
T_HYST Power-Up Default Value: 0 1001 0110b (+75°C) T_HYST Command Byte Address: 0000 0010b = 02
h
Temperature Setpoint Register
]51[D]41[D]31[D]21[D]11[D]01[D]9[D]8[D]7[D]6[D]5[D]4[D]3[D]2[D]1[D]0[D
BSM7tib6tib5tib4tib3tib2tib1tibBSL XXXXXXX
stiBnoitcnuFnoitarepO
]7:51[Dtnioptesrotarapmocerutarepmetrevo*etirw/daer
T_SET Power-Up Default Value: 0 1010 0000b (+80°C) T_SET Command Byte Address: 0000 0011b = 03
h
* The value in T_HYST is 9 logical bits in width, but due to the
conventions of I2C/SMBus, it is represented by 16 serial bits. System software should ignore undefined bits D[6:0] during register reads. Bits [6:0] should be set to zero during register writes. See "Serial Port Operation" and Temperature Data Format for more details.
)etirW/daeRtiB-9(TES_T
tniopteserutarepmetrevo
* The value in T_SET is 9 logical bits in width, but due to the
conventions of I2C/SMBus, it is represented by 16 serial bits. System software should ignore undefined bits D[6:0] during register reads. Bits [6:0] should be set to zero during register writes. See Serial Port Operation" and Temperature Data Format for more details.
MIC184 14 November 2000
Page 15
MIC184 Micrel
Applications Information
Switching Zones
The recommended procedure for switching between the internal and external zones is as follows:
1. Disable interrupts (if used) by setting the IM bit in CONFIG.
2. Read the CONFIG register to: a) Verify no masked interrupt was pending
(D[7] = 0) b) Clear STS prior to switching zones c) Hold the settings of CONFIG register for the
current zone
3. Write the appropriate values to T_SET and T_HYST for the new zone.
4. Write to CONFIG as follows: a) To toggle the ZONE bit (1 = remote, 0 =
internal)
b) If interrupts are being used, step 4 should
also clear MODE
5. If interrupts are being used, MODE must then be set to 1 and IM reset to 0
At the conclusion of the serial bus transaction for step 4, the A/D converter will begin a conversion cycle using the new zone setting. The next conversion cycle completed serial bus transaction for step 5 will result in the state of the INT output being updated (if enabled) for the new zone. Generally the MIC184s A/D converter operates continu­ously, but it will be halted and reset each time the part recognizes its slave address on the serial bus. Interrupted conversions will remain halted until the end of the host’s communication with the MIC184. After the completion of step 5 and a delay of contain the results for the new zone. The above routine is extremely unlikely to miss a temperature event, as even one A/D conversion is typically much slower than the I2C/SMBus transactions that control the MIC184. See Figure 6: A/D Converter Timing.
Step 2(c) is recommended because the MIC184 has only one CONFIG register, corresponding to the active zone. In order to preserve data integrity for both zones, 2(c) allows the host to create a virtual CONFIG register for the inactive zone by dedicating one byte of memory to that purpose. Additional virtual registers may be created as needed by inserting additional reads as steps 2(d), 2(e), etc. These could for example correspond to the values in T_SET and T_HYST immediately prior to switching zones. Steps 4(b) and 5 ensure that the MIC184 will enter the new zone searching for an overtemperature event.
t
x Fault_Queue
CONV
, STS and INT will
after
the
Identifying an MIC184 by Software Test
The MIC184 and the LM75 each have an eight-bit CONFIG register. In LM75-type parts, no more than seven of the eight bits of this register are used, and at least one bit (the MSB) will always return a zero. The MIC184 uses all eight bits of the CONFIG register: the MSB is the part’s status bit (STS). A simple test by which the host can determine whether a system has an MIC184 installed, or is using a legacy LM75-type device, is to create a situation which will set the MSB in the MIC184’s CONFIG register and then determine if the MSB is in fact set. Two examples of how this can be done are outlined below. The first is interrupt-driven, the second uses software polling. Note that both procedures generate one or more spurious interrupts. The code for these tests should therefore temporarily disable any affected interrupt routines.
{START Interrupt-Driven Test and Initialization
Routine}
1. Disable the host’s overtemperature and undertemperature interrupt handling routine. Redirect interrupts from the part under test to a handler for the interrupt that will be generated in steps (4) and (7) of this routine.
2. Write 0000 0010b (02h) to the CONFIG register. (The assumption is made that the host is an I2C or SMBus part, and therefore responds to an active-low interrupt request.)
3. Write 1100 1000 1000 0000b = C880h to T_SET and T_HYST. This corresponds to -55.5°C.
4. When the part has finished its first A/D conver­sion, INT will be asserted.
5. Read out the contents of the CONFIG register: a) If the part is an MIC184, the MSB will be set
to one (CONFIG = 1000 0010b = 82h).
b) If the part is a conventional LM75-type part,
the MSB will be zero (CONFIG = 0000 0010b = 02h).
6.Write 0111 1111 1000 0000b = 7F80h to T_SET and T_HYST. This corresponds to +127.5°C.
7.When the part has finished its next A/D conver­sion, INT will be asserted a second time.
8.Read CONFIG again, to clear the interrupt request from step (7). This will also clear STS, if the part under test is an MIC184.
9.Based on the results of the test in step (4), do the following within 50ms total:
a) Set the CONFIG register as required. b) Load T_HYST with its operational value. c) Load T_SET with its operational value. d) Set the host’s interrupt handling routine back
to overtemperature and undertemperature mode.
{END}
November 2000 15 MIC184
Page 16
MIC184 Micrel
{START Polling-Based Test and Initialization
Routine}
1. Temporarily disable the host’s interrupt input from the device under test.
2. Write 0000 0010b (02h) to the CONFIG register.
3. Write 1100 1000 1000 0000b = C880h to T_SET and T_HYST. This corresponds to -55.5°C.
4. Wait t
(160ms max.) for the part to finish at
conv
least one A/D conversion.
5. Read the contents of the CONFIG register: a) If the part is an MIC184, the MSB will be set
to one (CONFIG = 82h).
b) If the part is a conventional LM75-type part,
the MSB will be zero (CONFIG = 02h).
6. Write 0111 1111 1000 0000b = 7F80h to T_SET and T_HYST. This corresponds to +127.5°C.
7. Wait an additional t
for the part to finish a
conv
second conversion.
8. Read CONFIG again, to clear the interrupt request from step (7). This will also clear STS, if the part under test is an MIC184.
9. Based on the results of the test in step (4), do the following four steps within 50ms total:
a) Set the CONFIG register as required. b) Load T_HYST with its operational value. c) Load T_SET with its operational value. d) Re-enable the host’s interrupt handling input
from the part under test.
{END}
These routines force the device under test to generate an overtemperature fault (steps 3 and 4), followed by an undertemperature fault (steps 6 through 8). This sequence causes the device under test to exit the routine prepared to respond to an overtemperature condition. If being immedi­ately prepared to detect an undertemperature condition upon exit is desired, swap steps 3 and 6 in each routine.
Remote Diode Selection
Most small-signal PNP transistors with characteristics similar to the JEDEC 2N3906 will perform well as remote tempera­ture sensors. Table 3 lists several examples of such parts. Micrel has tested those marked with a bullet for use with the MIC184.
Minimizing Errors
Self-Heating
One concern when using a part with the temperature accu­racy and resolution of the MIC184 is to avoid errors induced by self-heating (VDD × IDD). In order to understand what level of error this might represent, and how to reduce that error, the dissipation in the MIC184 must be calculated, and its effects examined as a temperature error.
In most applications, the INT output will be low for at most a few milliseconds before the host sets it back to the high state, making its duty cycle low enough that its contribution to self­heating of the MIC184 is negligible. Similarly, the DATA pin will in all likelihood have a duty cycle of substantially below 25% in the low state. These considerations, combined with more typical device and application parameters, allow the following calculation of typical device self-heating in interrupt­mode:
PD = (I
1% I
DD(typ.)
OL(int)
3.3V + 25% I
0.3V)
OL(data)
0.3V +
PD = (0.3mA × 3.3V + 25% × 1.5mA × 0.3V +
1% × 1.5mA × 0.3V)
TJ = 1.11mW × 206°C/W
T
relative to TA is 0.23°C
J
If the part is to be used in comparator mode, calculations similar to those shown above (accounting for the expected value and duty cycle of I
) will give a good estimate of the
OL(int)
devices self-heating error. In any application, the best test is to verify performance
against calculation in the final application environment. This is especially true when dealing with systems for which some of the thermal data, (for example, PC board thermal conduc­tivity and/or ambient temperature), may be poorly defined or unavailable except by empirical means.
Series Resistance
The operation of the MIC184 depends upon sensing the V
of a diode-connected PNP transistor ("diode") at two
CB-E
different current levels. For remote temperature measure­ments, this is done using an external diode connected be­tween A2/T1 and ground.
Since this technique relies upon measuring the relatively small voltage difference resulting from two levels of current through the external diode, any resistance in series with the external diode will cause an error in the temperature reading
Vendor Part Number Package Tested
Fairchild MMBT3906 SOT-23 On Semiconductor MMBT3906L SOT-23 Phillips Semiconductor PMBT3906 SOT-23 Rohm Semiconductor SST3906 SOT-23 Samsung KST3906-TF SOT-23 Zetex FMMT3906 SOT-23
Table 5. Transistors Suitable for Remote Temperature Sensing Use
MIC184 16 November 2000
Page 17
MIC184 Micrel
from the MIC184. A good rule of thumb is this: for each ohm in series with the external transistor, there will be a 0.9°C error in the MIC184's temperature measurement. It is not difficult to keep the series resistance well below an ohm (typically
0.1), so in most systems this will not be an issue.
Filter Capacitor Selection
When using a remote diode for temperature sensing, it is sometimes desirable to use a filter capacitor between the A2/ T1 and GND pins of the MIC184. The use of this capacitor is recommended in environments with a significant high fre­quency noise (such as digital switching noise), or if long wires are used to connect to the remote diode. The maximum recommended total capacitance from the A2/T1 pin to GND is 2700pF. This usually suggests the use of a 2200pF NP0 or C0G ceramic capacitor with a 10% tolerance.
If the remote diode is to be at a distance of more than 6" ~ 12" from the MIC184, using a shielded cable (solid foil shield microphone cable is a good choice) for the connections to the diode can significantly help reduce noise pickup. Remember to subtract the cable's conductor-to-shield capacitance from the 2700pF maximum total capacitance.
Layout Considerations
Local Mode Only Applications:
If the MIC184 is not going to be used with an external diode, the best layout is one which keeps it thermally coupled to the subsystem(s) whose temperature it must monitor, while avoiding any strong sources of EMI, RFI, or electrostatically coupled noise. Two of the most common examples of such sources are switching power supply transformers and CRTs.
Remote Mode Applications:
1. If the remote sensing capability of the MIC184 will be used in an application, place the MIC184 as close to the remote diode as possible, while taking care to avoid severe noise sources (high frequency power transformers, CRTs, memory and data busses, and the like).
2. Since any conductance from the various volt­ages on the PC Board and the A2/T1 pin can induce serious errors, it is good practice to guard the remote diodes emitter trace with a pair of ground traces. These ground traces should be returned to the MIC184s own ground pin. They should
not
be grounded at any other
part of their run. However, it is highly desirable
to use these guard traces to carry the diode’s own ground return back to the ground pin of the MIC184, thereby providing a Kelvin connection for the base of the diode. See Figure 8.
3. When using the MIC184 to sense the tempera­ture of a processor or other device which has an integral on-board “diode” (e.g., Intels Pentium
®
III), connect the emitter and base of the remote sensor to the MIC184 using the guard traces and Kelvin return shown in Figure 8. The collector of the remote “diode” is inaccessible to the user on these types of chips. To allow for this, the MIC184 has superb rejection of noise appearing from collector to GND, as long as the base to ground connection is relatively quiet.
4. Due to the small currents involved in the mea­surement of the remote diode’s V
BE
, it is important to adequately clean the PC board after soldering. This is most likely to show up as an issue in some situations where water-soluble soldering fluxes are used.
5. In general, wider traces for the ground and A2/ T1 pins will help reduce susceptibility to radiated noise (wider traces are less inductive). Use trace widths and spacing of 10 mils wherever possible. Wherever possible, place a ground plane under the MIC184, and under the connec­tions from the MIC184 to the remote diode. This will help guard against stray noise pickup.
6. Always place a good quality VDD bypass capaci­tor directly adjacent to, or underneath, the MIC184. This part should be a 0.1µF ceramic capacitor. Surface-mount parts provide the best bypassing because of their low inductance.
7. When the MIC184 is being powered from particularly noisy power supplies, or from supplies which may have sudden high-amplitude spikes appearing on them, it can be helpful to add additional power supply filtering. This should be implemented as a 100 resistor in series with the parts VDD pin, and a 4.7µF, 6.3V electrolytic capacitor from VDD to GND. See Figure 9.
November 2000 17 MIC184
Page 18
MIC184 Micrel
10k Pull-ups
FROM
SERIAL BUS
HOST
DATA
1
CLK
2
INT
3
GND
VDD
A0 A1
A2/T1
8 7 6 54
GUARD/RETURN
REMOTE DIODE (A2/T1)
GUARD/RETURN
Figure 8. Guard Traces/Kelvin Ground Returns
3.0V to 3.6V
100
4.7µF0.1µF
MIC184
8 1 2 3
VDD DATA CLK INT
A2/T1
A1 A0
GND
5 6 7 4
2200pF
Figure 9. VDD Decoupling for Very Noisy Supplies
2N3906
MIC184 18 November 2000
Page 19
MIC184 Micrel
Package Information
0.026 (0.65) MAX)
PIN 1
0.157 (3.99)
0.150 (3.81)
0.064 (1.63)
0.045 (1.14)
0.122 (3.10)
0.112 (2.84)
0.036 (0.90)
0.032 (0.81)
0.050 (1.27) TYP
0.197 (5.0)
0.189 (4.8)
0.020 (0.51)
0.013 (0.33)
0.0098 (0.249)
0.0040 (0.102)
SEATING
PLANE
8-Lead SOP (M)
0.199 (5.05)
0.187 (4.74)
0.120 (3.05)
0.116 (2.95)
0.043 (1.09)
0.038 (0.97)
DIMENSIONS:
INCHES (MM)
0°–8°
0.012 (0.30) R
45°
0.050 (1.27)
0.016 (0.40)
0.244 (6.20)
0.228 (5.79)
DIMENSIONS:
INCH (MM)
0.010 (0.25)
0.007 (0.18)
0.007 (0.18)
0.005 (0.13)
0.012 (0.03)
0.0256 (0.65) TYP
0.008 (0.20)
0.004 (0.10)
8-Lead MSOP (MM)
5° MAX
0° MIN
0.012 (0.03) R
0.039 (0.99)
0.035 (0.89)
0.021 (0.53)
November 2000 19 MIC184
Page 20
MIC184 Micrel
MIC184 20 November 2000
Page 21
MIC184 Micrel
MICREL INC. 1849 FORTUNE DRIVE SAN JOSE, CA 95131 USA
TEL + 1 (408) 944-0800 FAX + 1 (408) 944-0970 WEB http://www.micrel.com
This information is believed to be accurate and reliable, however no responsibility is assumed by Micrel for its use nor for any infringement of patents or
other rights of third parties resulting from its use. No license is granted by implication or otherwise under any patent or patent right of Micrel Inc.
© 2000 Micrel Incorporated
November 2000 21 MIC184
Loading...