Maintenance-Free Sealed Lead Acid Battery.
Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.
Design for Standby Power Applications
Design Life Float Charging Voltage
Up to 5 Years in Standby Service at 25
13.5 ~ 13.8 VDC/Unit at 25℃ (77)
Eurobat (20) : 3-5 YEARS STANDARD COMMERCIAL Equalization Charging Voltage
Self Discharge
Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);
Fully recharging is required before usage, and charged sooner if stored
Storage: -15 ~ 40 (5~104) at higher temperature than 25 (77℉).
Design according with IEC 61056-1/2:2012
Nominal Capacity
260A
--
Length (L) 150.9±2.0 mm 5.94±0.08 inch Width (W) 51.0±1.0 mm 2.01±0.04 inch Container Height (h) 94.3±1.0 mm 3.71±0.04 inch Overall Height (H) 98.6±1.0 mm 3.89±0.04 inch
F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN
1.60V 47.5 33.0 29.0 26.1 22.0 18.9 14.0 11.0 7.95 5.54 4.29 3.43
1.67V 44.1 31.1 27.4 24.7 21.0 18.0 13.5 10.6 7.76 5.42 4.20 3.34
1.70V 42.7 30.3 26.7 24.0 20.5 17.6 13.2 10.5 7.67 5.35 4.15 3.30
1.75V 40.5 28.8 25.4 23.0 19.8 17.0 12.8 10.2 7.56 5.29 4.10 3.26
1.80V 38.4 27.4 24.4 22.2 19.1 16.4 12.5 10.0 7.49 5.23 4.06 3.22
1.85V 36.4 26.0 23.3 21.3 18.5 16.0 12.1 9.84 7.44 5.21 4.04 3.19
F.V/Time 2MIN 4MIN 5MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 45MIN 60MIN 90MIN
1.60V 570 396 348 313 264 228 168 132 95.4 66.5 51.5 41.2
1.67V 529 373 329 297 251 217 162 128 92.9 64.9 50.3 40.2
1.70V 512 363 320 289 246 212 159 126 92.1 64.4 49.9 39.7
1.75V 486 346 306 277 238 204 154 123 90.8 63.5 49.3 39.2
1.80V 461 329 293 266 229 197 149 121 89.9 62.9 48.8 38.8
1.85V 437 314 281 256 219 187 144 119 89.2 62.5 48.5 38.6
Please refer to the official site for the latest rating confirmation. URL: www.csb-battery.com
Issued: 200927
Tel: +31(0)180-418-140 Tel: +886-2-2880-5600
Fax: +31(0)180-418-327
Fax: +866-2-2888-3300
Tel: +86-10-6597-8065/8165/8265
Fax: +86-10-6597-8565
24W @15min-rate to 1.67V per cell @25 (77)
HR series
HR 1224W
Valve Regulated Lead Acid Battery
General
Nominal Operating Temperature : 25(77)
Discharge : -15 ~ 50 (5~122)
Charge: -15 ~ 40 (5~104)
Specification
Nominal Voltage
12V (6 cells per unit)
Terminal tightening torque
Weight
Approx. 1.95 Kg (4.30 lbs)
Maximum Discharge Current
100/130A (5sec)
Internal Resistance
Approx. 20.6 mΩ
Short Circuit Current
Maximum Charge Current
2.4A
Terminal types
F1/F2-Faston Tab187/250
BUSINESS HEADQUARTERS
Container Material
ABS (UL 94-HB) & Flame Retardant (94-V0) available upon request
Dimensions
Constant Power Discharge Characteristics Unit: W (25, 77)
Sales Offices
Constant Current Discharge Characteristics Unit: A (25, 77)
Recognized under UL 1989,
and certified by ISO 9001, 14001, 45001, 50001.
BEIJING OFFICE (CHINA)
Tel: +86-755-8831-6488/6775/6075
Tel: +86-21-5046-1622/0833/0094
Tel: +886-2-2880-5600
Fax: +886-2-2888-3300
USA OFFICE
EUROPE (EMEA) OFFICE
TAIPEI OFFICE
Tel: +1-817-244-7777 / 1-(800)3-CSB-USA (272872)
Fax: +86-755-8831-6548
Fax: +86-21-5046-1046
Fax: +1-817-244-4445
SHENZHEN OFFICE (CHINA)
SHANGHAI OFFICE (CHINA)
Loading...