In three phase systems, when all phases are in correct order and phases are balanced, Normal LED turns on and the relay is energized. Missing Phase : When at least one of phases L1, L2, L3 is missing, phase off LED turns on and relay de-energizes its contact. Phase Sequence : If the phase sequence is correct, Relay On LED turns on and relay energizes its contact. If phase order is changed, Phase Off LED turns on and relay de-energizes its contact. Phase Voltage Unbalance : Phase-phase voltage unbalance is adjusted using the knob located on the front panel of the device. If phase unbalance exceeds the adjusted limit, Phase Off LED turns on, relay de­energises its contact .
Voltage Asymmetry Adjustment (Phase Unbalance)(asym.%)
Phase to phase asymmetry is adjusted using the adjustment knob in the
range of ±%6 .... ±%20
Technical Data:
Rated Voltage, Un : 3 Phases (3 x 380Vac) Operating Range : (0,8-1,1) x Un (Un nominal voltage) Frequency : 60 Hz Energizing and de-energizing difference : +%3 (15-16) : Normally Closed Contact (15-18) : Normally Open Contact Contact Current : max. 5A/250 VAC Power Consumption : < 8 VA Device Protection Class : IP20 Connector Protection Class : IP00
Ambient Temperature : -5 °C.......+50 °C
Humidity : %15.........%95
(without condensation)
Connection Type : Perpendicular to inner panel or to
connection rail
Dimensions : 58 x 90 x 35
PHASE FAILURE and SEQUENCE MONITORING DEVICE (without Neutral)
48mm
15
18
16
L1 L2 L3
L1,L2,L3 : 3 x 380 V ac 3 phase 380 Vac 3P&3W
L3
N
L2
L1
Connection Scheme
M
3 ~
FKR2T-DIN (with PTC)
PTC Protection : If you have a device with PTC protection capability (FKR3T-DIN), additional properties are equal with Thermistor Relay (TKR). If you do not want to use this property, simply short circuit the PTC connections.